Professional Documents
Culture Documents
Sankara Subramanian
GRID
End X
I Y(+)
Mark
Space
Terminal currents
Modulated signals
Space
I X (+)
Mark
Mark Mark
Composite - (usually no PLC signal transmission for load)
ON-OFF
channel
End X
I Y(+)
I X (+)
Mark
Space
Terminal currents
Modulated signals
Mark Mark
Composite modulated signal
ON-OFF
channel
Mark
Space
I Y(+)
I X (+)
IF
Mark
Space
Terminal currents
Modulated signals
Mark
End Y
Space
Mark
Space
Composite modulated signal
ON-OFF
channel
180
180
GAP = TRIP
Channel Equipment
Phase-segregated channel
Phase A
Phase B
Phase C
IA
IB
IC
Channel Equipment
Single-phase channel
Phase B typically
I A , I B , I C ???
3-Ph
Ph-Ph
PhGround
Ph-PhGround
Positive (1)
Negative (2)
Zero (0)
Sequence
Modulating quantity
HISTORY
I1 k I 0
I2
k I0
Phase-segregated (3 channels)
A.J. McConnel,
General Electric (1947)
France
MODERN APPROACH
Russian manufacturers
Alstom
General Electric
3-Ph
Ph-Ph
PhGround
Ph-PhGround
Positive (1)
Negative (2)
Zero (0)
Sequence
Measurement errors
Charging currents
Internal faults
x - y =180
BLOCK
x - y = 0
TRIP
s compensates for general tolerances in PLC, relay, CT nonlinearity and changes in atmospheric conditions since the last
propagation delay measurement.
UX
End Y
IX
Y
2
IX, cap.
IY, cap.
IY
I Y, cap.
U
IY
Id
I Y
Y
2
180
IX
IX
I X, cap.
UY
Starters
PLC cannot be activated permanently
Voltage-dependent
Starters:
- current
- voltage
- distance
- complex
modulation
Voltage-dependent Phase
Comparison is universal, but
prone to VT failure.
Ia
Charging
current
Compensation Yc
setting
Ib
Ic
I2
I1
Phase
comparison
High set
Starter
Gap
Detectio
n
Sequencer
I2
RX
Mixer
Angle
shift
Trip
Decision
Trip /
Block
Low set
Starter
TX
Mark / Space
Va
Vb
Vc
Voltage
Input
Sequencer
Compensating
V2 Zneg
Distance
Starter
Input
V2_comp
Working
Starters & Modulator
Phase comparison protection utilizes sequence components based starters
for sensitivity.
Current Modulator to do the mixing of the positive sequence and negative
sequence currents to enable the phase angle detection.
The calculated modulated current positive half cycle is communicated to
the remote end and is compared with the received remote Modulated
current to do the phase angle measurement.
Phase angle Gap measurement starts only when the High set starter pick
up.
Starters
Application -Setting Tips(1)
As continuous transmission is not permitted Starter units are provided
(sensitive-to provide high speed operation) such that Low set initiates
transmission of carrier signal while high set initiates Gap measurements &
trip in phase comparison protection.
Positive(I1) and negative sequence (I2)starters are provided to cover for
balanced and unbalanced fault conditions.
Low set and high set starters are provided to cater for the differences in
the magnitude between the currents at 2 ends and also to account for the
magnitude errors in the CT, hence 2 levels are required.
Impulse (Delta ) starters and Non-Impulse (threshold) starters are
provided.
While generally, Impulse starters finds its application for most system
fault conditions, Non- impulse starters can be set for system conditions
like evolving fault scenarios from external to internal with out much rise in
the fault currents.
Starters
Application -Setting Tips(2)
Impulse Positive sequence starters (I1):
High set Impulse must be set above total line charging current (2 x Ich) to avoid
tripping for closing CB.
High set should be set < 3 phase fault level, typically 50% of If min 3 .
In order to make protection stable during through fault conditions, ensure the
difference between the minimum effective high set setting and maximum effective
low set setting is > than the Positive sequence capacitive current. To meet this
requirement set the ratio of HSS / LSS to a factor of 2.
I1 low set must be set above peak power swing current, to prevent continuous
transmission Alarm being raised for slow swings .Typical swing = 2 In ; set to 2.5
or 3 In
I1 high set needs to be 125% to 200% of I1 low set to give adequate margin
Starters
Application -Setting Tips(3)
Impulse Negative sequence starters (I2):
Impulse negative starters should be set to provide sensitivity for high resistance faults less
than 10% of the rated current.
(3 x Impulse I2 High Set) = Effective earth fault sensitivity of the scheme.
Ensure the following for long transmission line. (same can be adopted for medium lines):
Starters
Application -Setting Tips(4)
Non-Impulse (Threshold) Negative sequence starters (I2):
Non impulse I2 starters are set less sensitive than the impulse I2
starters.
Non-Impulse starters are set above the standing I2 in the system.
Example: Transmission system feeding 1-phase traction feeders.
Typically LOW and HIGH starters are active at both line ends as line
mode is non-symmetrical (though that depends on load current and
usage of voltage starters). Phase Comparison protection awaits only for
GAPs.
IMPORTANT:
PLC transmission should be active at both line ends
during 1-ph AR dead time
!!!ONE-SIDED PLC TRANSMISSION = FALSE TRIP!!!
Teed-off transformers
Phase comparison can be applied to teed-off transformer application
Internal Fault
IF
R
IL
LOAD
IF DIRECTION
LOAD
- In many applications, there can be a step-down transformer teed-off the protected line. This
transformer is not part of the protected unit, but is teed-off to out feed local load. The difficulty is
this tee-line is NOT treated as the third-end of the phase comparison protection.
- Hence the 2 end Phase comparison protection must function correctly for such scenario. The
protection must refrain for internal load and also operate for internal fault scenarios.
Z2
DISTANCE permission
R
LOAD
IF DIRECTION
LOAD
IF
Permissive Scheme
If teed-off transformer is extremely weak, it could be possible to select High Starters higher
then external fault currents (still sensitive for internal faults)
Otherwise we must use Distance permissive scheme. This scheme doesnt require any
additional equipment
PC
Block
Block
PLC
Phase
Comparison
Power
Direction
PLC
Transfo
prot.
Blocking Kit
Direction
PC
LOAD
PLC
Distance
IF DIRECTION
PC
LOAD
IF
3-ended Lines
Phase comparison can be applied to 3-ended lines
I1
I2
PC
PC
IF DIRECTION
PC
LOAD
I3
IF
LOAD
I1
I2
I3
SUM
NO GAPS = BLOCK
Weak Infeed
Phase comparison should be considered with great care in case of weak infeed.
Weak Source
IF
Strong Source
PC
PC
LOAD
IF DIRECTION
LOAD DIRECTION
If fault current is comparable with load current, this could lead to protection inaction
(the angle of modulating quantity [I1+K*I2] is hard to predict)
Coupling Scheme
Behind
Front
To remote
Line Trap
substation
Coupling
Capacitor
Line
Matching
Unit
Transformer(s)
BusBar
Coaxial
Local substation
PLC terminal
The PLC
signal is
routed to HV
Line
The PLC
signal is not
absorbed by
the substation
Substation
Signal
AM
FM
33
RF Noise
RF noise in HV line two mains effects
Impulsive Noise = Caused by atmospheric discharges, breakers and
isolator close/open operation
35
Hi_F
180
OFF
Lo_F
ON
Hi_F
FSK channel
180
OFF
Lo_F
ON
Hi_F
Phase
Comparison
DEF
protection
Negative Sequence
Protection
Charging Current
Compensation
Broken
Conductor
Detection
Single End
Tripping
Unstabilising
Facility
1 &3 Pole
Tripping
Breaker
Failure
Overcurrent
& SEF
Thermal
Protection
End Y
Line Trap
Third Party
PLC,
Coupling
Equipment
Line Trap
Coupling
Coupling
PLC
PLC
PLC
Interface
MiCOM
P547 80TE
PLC
Interface
Third Party
PLC,
Coupling
Equipment
PLC
Out
+
Opto
Out
P547
Modulating Quantity
Unbalanced faults will have negative sequence component
-I1 + KI2
30
25
K
20
15
10
5
0
10
Load, IFLC
LOAD
Fault
Prefault
Current :-
i rly
i mem
ir
Propagation Delay
Where is the Propagation delay introduced?
Delay in supplying i/p pulse to PLC equipment, PLC
equipment processing time (rising edge and lag at switch
off burst on falling edge).
Delay at receiving end - PLC processing time and delay by
the relay in measuring the time period of the input pulse.
Propagation delay of the HF carrier along the power line
(negligible = 3 s per km).
Propagation Delay
Why does the propagation delay need to be considered ?
If it is not considered the effective stability
angle s has to be set much higher
This would limit the maximum line length
150 km
200 km
250 km
300 km
350 km
400 km
90 mi
125 mi
155 mi
185 mi
215 mi
250 mi
30
35
40
45
50
55
For lines longer than 150 km, a 5 degree increase in s is recommended for
each additional 50 km.
Capacitive charging current constraints limit phase comparison application to
a practical maximum of 400 km line length (250 miles).
End X
UX
IX
Y
2
IX, cap.
IY, cap.
IY
I Y, cap.
U
Y
2
IY
Id
I Y
End Y
180
IX
IX
I X, cap.
measured
UY
Icap 1
x - y =180
BLOCK
x - y = 0
TRIP
End X
UX
IX
Y
2
IX, cap.
End Y
IY, cap.
Y
2
IY
UY
= 2*arcsin(I./Iod)
Iod = - I1 + K*I2
Icap
Mode-2
x - y =180
BLOCK
x - y = 0
TRIP
GRID