You are on page 1of 24

Generator Set

Installation Recommendations

4/05

MN2400

WARNING:
CALIFORNIA PROPOSITION 65 WARNING:
Engine exhaust from this product contains chemicals known
to the state of California to cause cancer, birth defects and
other reproductive harm.

WARNING:
CALIFORNIA PROPOSITION 65 WARNING:
Battery posts, terminals and related accessories are known to
the state of California to cause cancer, birth defects and other
reproductive harm.

Table of Contents
Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Site Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Room Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Room Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Utility Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Foundation Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exhaust System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Level Of Attenuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MultiEngine Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exhaust Manifold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exhaust Gas Restriction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exhaust Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wind Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rain Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Engine Mounted Radiator Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote Mounted Radiator Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heat Exchanger Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hot Well Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cooling System Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Air Flow System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fuel System (Diesel only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fuel System Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fuel Type and Grade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Multi Engine Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Other Fuel System Considerations & Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transfer Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery Starting System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Formulas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

MN2400

Page 2
Page 3
Page 3
Page 3
Page 4
Page 4
Page 8
Page 8
Page 8
Page 8
Page 9
Page 9
Page 10
Page 10
Page 10
Page 10
Page 11
Page 12
Page 12
Page 12
Page 14
Page 15
Page 15
Page 16
Page 16
Page 17
Page 17
Page 18
Page 18
Page 19
Page 19
Page 19
Page 20

Installation Recommendations Page 1

Installation Guidelines 30kW to 2000kW


Large generator sets have requirements that smaller generator sets do not. Vibration, noise,
heat, air flow, fuel supply issues become more critical for very large power generation systems.
The purpose of this document is to assist the consultant in the design and installation of this land
based generator set. Closely following these recommendations will assure that the generator is
properly installed and will provide many years of trouble free dependable service. These are
general guidelines and if your installation requires some detail that is not described in this
document, please contact your Baldor representative before you proceed.

Important

Intended Use
This document describes techniques that should be followed to properly install Baldor 30kW to
2000kW Generators for stationary land based applications.
Be sure you are completely familiar with all Safety Instructions detailed in product service
manual. Do not proceed if you are unsure of any detail. Contact your Baldor Distributor, they are
experienced and are happy to assist you and to answer your questions.
The procedures presented in this manual are suggestions and it is the responsibility of the
Owner/Operator to arrange for these procedures to be performed by licensed contractors
according to all applicable codes including local codes for your Municipality/City/County and
State. In addition to these suggestions, before installing your generator you should obtain the
most up to date copies of the following documents from the National Electrical Code and other
authorities:
S
National Electric Code, Articles 230, 250, 445, 517, 700.
S
National Fire Protection Association
No. 30 Storage, Handling and Use of Flammable Liquids.
No. 37 Stationary Combustion Engines and Gas Turbines.
No. 99 Essential Electrical Systems for Health Care Facilities.
No. 101 Life Safety Code No. Systems.
No. 110 1985 Emergency and Standby Power Systems.
S
NEMA MG1
S
Local Codes applicable to Genset Installation. See your local building inspector.
NFPA (National Fire Protection Association (617) 7703000 (includes NEC)
1 Batterymarch Park, Quincy, MA 021697471 USA
NEMA (National Electrical Manufacturers Association) (703) 8413200
1300 N. 17th Street, Suite 1847, Rosslyn, VA, 22209 USA

Page 2 Installation Recommendations

MN2400

Site Planning
Room Size

Open frame generators must be protected from the environment while having good ventilation
and cooling. Here are some considerations for planning a generator room or enclosure:
S
Never use the Genset room for storage.
S
The room must be large enough to contain the Genset and all the accessories, such as
batteries and their charging system, transfer switch and other controls, and elements of
the cooling and fuel systems.
S
2 feet minimum (preferably 4 feet), must be allowed on the two sides and the front of
the engine for service access. Allow clearance between hot parts of the system
(exhaust) and structural members of the building.
S
On the generator end of the engine, allow a space equal to the length of the generator
(generator length only, not the entire Genset).
S
Certain safety and building codes may require the Genset room not to be used to
house any other mechanical or electrical equipment.

Room Location Often a separate building located on the site away from the main building is the most simple and
cost effective. Major considerations when housing the Genset in a separate building are:
S
Maintain the building at a satisfactory temperature year round (to meet applicable
codes).
S
Assure the Genset is not located so far from the emergency loads that reliability is
compromised.
S
The floors load carrying capacity must be checked and must exceed the weight of the
Genset and its associated equipment.
S
Engine Cooling System
A Genset with an engine mounted radiator is the least costly to install; however, the
room must be located in a place where sufficient radiator cooling air can be brought
into and exhausted from the room.
S
Exhaust System
The exhaust system must minimize exhaust restriction. Exhaust restriction must be
correct to ensure proper engine operation. Refer to product specifications for correct
exhaust pressure (inches Hg). The exhaust system should be as short and have as
few bends as possible. Engine exhaust must be directed away from occupied
buildings, windows and doorways.
For aesthetic reasons, consider exhaust placement in relation to the building. Over a
period of time, exhaust gas carbon deposits will tend to accumulate on any nearby wall
or structure. Attention must also be given to exhaust noise in selecting placement of
the exhaust system.
S
Room Air
If the Genset is cooled with an engine mounted radiator, and sufficient air is brought
into and exhausted from the room to satisfy the radiator cooling requirements and the
combustion air requirements, the room will not overheat when the Genset is running.
If a remote mounted radiator or a heat exchanger is used, and adequate air is
circulated through the room to keep it at a reasonable temperature, there will be
adequate air for combustion.
S
Fuel Tanks (Diesel Only)
Locate the fuel storage tank as near the Genset as possible. This will minimize the cost
of fuel system installation and will maximize fuel system reliability.
S
Controls and Transfer Switch
Locate the control switch gear as close to the emergency loads and the Genset as
practical. This will minimize the chances that a failure of the power line to the
emergency load will go undetected. In locating the switchgear, accessibility for service
and maintenance must be considered.

MN2400

Installation Recommendations Page 3

Room Location Continued


S
Genset Noise
Internal combustion engines produce noise, so the room should be located away from
occupied buildings. In addition the Genset room can be treated to reduce noise
transmission. In locating the Genset room, both engine, fan and exhaust noise must be
considered.
If noise within the Genset room, or noise transmitted to the surrounding parts of the
building are a concern, then the room must be made large enough to allow for
installation of noise attenuating walls and noise absorbing walls.
Light weight concrete blocks filled with sand or special sound block concrete blocks
are commonly used. Noise attenuating, tight fitting windows and doors also help reduce
noise transmission to the rest of the building.
A doublewalled room should be considered. Vibration isolators under the Genset rails
will also reduce the transmission of noise through the floor.
S
Code Requirements
Building and safety codes deal with engine location. These requirements are
concerned with fire rated walls, a location that minimizes the possibility of damage to
the Genset and interruption of the emergency system due to storms, foods, fire,
vandalism, etc.
Codes often deal with the need to maintain certain temperatures in the Genset room
and with fuel system location. The most important codes in the USA are the National
Fire Protection Association Code Numbers 99 and 110, but local codes must also be
observed.
Utility Power During periods when the generator is not running, utility power must be provided to power critical
components. Battery chargers, block heaters, space heaters and other devices must have
power to maintain the generator set components and allow fast easy starting.
Foundation Design
WARNING: An open bottom stationary engine Generator Set must be installed over noncombustible
materials and shall be located such that it prevents combustible materials from accumulating
under the Generator Set.
Foundation Checklist
A. Evaluate if a separate, isolated foundation is required for the application.
B. Observe local codes on soil bearing capacity freezing and thawing.
C. Design the separate foundation for the Genset and specify the appropriate concrete mix.
D. Determine if the application requires vibration isolators and if so, order as a factory option.
The foundation must be strong enough to support the weight of the Genset and its associated
equipment, must prevent any deflection of the Genset base and absorb vibration produced by the
rotating and reciprocating masses.
Setting The Genset On An Existing Concrete Floor Slab
S
If an existing floor is used, the floor slab must be strong enough to carry 1.50 times the
Genset wet weight (including coolant and oil) to accommodate dynamic loads.
S
The actual mounting arrangement (ie., surface area in contact with the floor) will
determine the compressive strength required.
S
The Genset should be securely fastened to the floor slab with expansion anchors that
fit the mounting holes shown on the Genset installation diagram.
S
For installations not expected to be permanent, elastomer pad with nonslip surface
placed between the base and the floor will also prevent movement.
S
Any floor/slab surface should be as flat as possible to prevent subbase deflection.

Page 4 Installation Recommendations

MN2400

Vibration Isolators
S
Vibration isolators are commonly used to mount the Genset to a concrete pad, Figure
2-1. The purpose of vibration isolators is to reduce the noise and vibration which would
be transmitted from the Genset to the foundation or supporting structure.
S
A simple and effective method of mounting and applying pad type isolators is to place
nonskidding type isolation pads directly between the subbase and floor. The number
of pads required is determined by the rating of the pads and the Gensets weight.
Figure 2-1 Typical Installation of JBolt or Spring Type Isolator
Generator Base

Spring Type Isolator


Generator Base

J-Bolt
Fill with Grout

3 (76mm) Pipe
Use of expansion
bolts also acceptable

Foundation
J or L Bolt

J or L Bolt

Steel spring isolators are a very effective and commonly used. Steel spring isolators
are typically 9598% efficient (reduces the transmitted vibration 9598%) while a pad
type can be 7588% efficient. Spring isolators also level the Genset subbase in the
event the foundation pad is not perfectly level. The base should be mounted to the
foundation pad as shown in Figure 2-1 or as recommended by the isolator
manufacturer.
A common practice is to pour a concrete pad directly on top of the floor slab and to
mount the Genset on this pad. The purpose of the pad is for cleaning around the
Genset and to provide a more level base. When using this method, floor strength must
support the pad and the Genset. The pad should be at least 6in (150mm) thick and
extend beyond the Genset in all directions 12in (300mm).

Weight of the Genset


The dry weight of the entire Genset is shown on the Generator Set Specification Sheet. The wet
weight includes the fluids (coolant and oil).
Designing an Isolated Foundation
If the Genset cannot be mounted directly on a floor slab, or if it is desirable to isolate it from the
floor slab, then a separate foundation slab must be designed.
A massive concrete foundation is not required. Outside dimensions of the foundation should
exceed the outside Genset dimensions by 12in (300mm).
For single Genset installation, the foundation weight should be a minimum of 1.50 times the
Genset wet weight.
For multiple Genset installation, the foundation weight should be a minimum of 2.0 times the
Genset wet weight.
Figure 2-2 shows a method to calculate foundation thickness and the soil bearing load of the
foundation and Generator Set. The soil load bearing capacity under the foundation must equal
or exceed the load from the foundation and Genset. If it does not, then a footing must be added
to spread the load over a larger area.

MN2400

Installation Recommendations Page 5

Caution:
Caution:

Check the local building codes for load bearing capacity requirements.
If the soil is subject to freezing and thawing, the foundation must be extended below the frost
line. Check the local building codes.
Figure 2-2 Calculate Soil Bearing Load (SBL) Capacity

T +

WT
145 x L x W

Where:
T = Foundation depth in feet (m)
WT = Wet weight of Geneset in lbs (kg)
145 = Density of concrete in lbs/ft3 (kg/m3)
L = Foundation length in feet (m)
W = Foundation width in feet (m)

Foundation

SBL +

TW
WxL

Where:
SBL = Soil bearing load in lbs/ft2 (kPa)
TW = Total weight (foundation load)
Genset (wet) and all other
equipment to be supported
in lbs (kg)
L = Foundation length in feet (m)
W = Foundation width in feet (m)

Table 2-1 shows approximate load bearing capacities for various types of soil if the actual load
bearing capacity of the soil under the foundation is not known.
Table 2-1 Approximate Load Bearing Capacities of Various Soil Types
Soil Type
Hard Rock Granite etc.
Medium Rock Shale etc.
Hardpan
Soft Rock
Compacted Sand and Gravel
Hard Clay
Gravel and Coarse Sand
Loose, Medium and Coarse Sand
Compacted Fine Sand
Medium Clay
Loose Fine Sand
Soft Clay

S
S
S
S
S

Safe Bearing Capacity


lb per ft2
kilo Pascals
50,000 200,000
2,395 9,576
20,000 30,000
958 1,436
16,000 20,000
766 958
10,000 20,000
479 958
10,000 12,000
479 575
8,000 10,000
383 479
8,000 10,000
383 479
8,000 10,000
383 479
6,000 8,000
287 383
4,000 8,000
192 383
2,000 4,000
96 192
2,000
96

Reinforce the foundation with No. 8 gauge steel wire mesh placed horizontally on
6in (150mm) centers. As an alternative, use No. 6 rebars on 12in (300mm) centers
horizontally. Minimum cover over the bars should be 3in (76mm).
Suggested concrete mixture by volume is 1 part cement, 2 parts sand, and 3 parts
aggregate. Maximum slump of 4in (100mm) and a 28day compressive strength of
3000 psi (20,600 kPa).
The size of the bolts holding the subbase to the foundation should be sized to fit the
mounting holes shown on the installation diagram.
Threeinch (76mm) iron pipe sleeves should be placed around the bolts in the
foundation to allow for any mislocation of the bolts after the foundation hardens.
J or L type bolts are recommended for the foundation bolts.
After the foundation is cured and the Genset is located, the sleeves are filled with
grout.

Page 6 Installation Recommendations

MN2400

Exhaust System

Exhaust Checklist
A. Exhaust outlets are not located upwind or near any building air intakes.
B. Flexible piping section is used at engine exhaust outlet.
C. Exhaust piping material is adequate for expected service.
D. Exhaust piping sizing is adequate to prevent back pressure.
E. Exhaust piping components are insulated as necessary to prevent operator burns and
reduce pipe radiant heat losses.
F. Pipe sleeves or fire proof materials are used where exhaust pipe passes through building
materials as per local and state codes.
G. Exhaust pipe includes rain cap or is horizontal.

The purpose of the exhaust system is to safely discharge the engine combustion products into
the atmosphere outside the building. A silencer should be installed in the exhaust system to
reduce noise levels. Compliance with local noise codes is always required.
WARNING: Never allow the exhaust outlet to be positioned so that the exhaust gases are directed
towards any openings or air entry routes (doors, windows, vents, etc...) of an occupied
building. When discharging the hot exhaust gases out of the building do not direct them
towards anything that could catch fire or explode.
For aesthetic reasons, consider exhaust placement in relation to the building. Over a period of
time, exhaust gas carbon deposits will tend to accumulate on any nearby wall or structure.
Attention must also be given to exhaust noise in selecting placement of the exhaust system.
Level Of Attenuation
In general, manufacturers offer three grades of silencers: industrial, residential, and critical.
Check the attenuation curves for the silencer to assure the desired level of silencing is met.
MultiEngine Installations
Caution: Do not connect multiengine exhaust systems together. Each engine must have its own
exhaust system for proper operation.
Exhaust gases from an operating engine will migrate back through a nonoperating engine and
cause a hydraulic lock. This may interfere with starting of the second engine. The migrating
gases will also tend to turn the turbos which are not being provided lubrication if the engine is not
running. Do not use check valves in the exhaust system because they can stick.
Exhaust Manifold
There are two exhaust manifold types. Dry type which is standard and the optional water cooled.
The dry type is simply exposed to the surrounding air and becomes very hot. Shields, insulating
wraps, or other types of guards can be used to limit operator contact with the hot surfaces. This
practice is common where engine room size is small, creating cramped conditions.
Water cooled exhaust manifolds are not available on all engine models. This type manifold has
passages through which engine coolant is circulated to remove heat from the manifold surface. It
also will help protect the operator from contact with the hot manifold surface. This will reduce the
amount of heat that is radiated by the engine to the surrounding air by approximately 20%. In
addition, this type manifold significantly increases the amount of heat the cooling system must
dissipate. Marine and Mining Safety Administration (MSA) codes may require water cooled
manifolds in all Genset installations. If you are in doubt on your particular application, consult
your Baldor Distributor.
Note: If you are using a remote muffler a flexible coupling of 12 or more must be installed between the
exhaust line and the manifold to absorb the engines vibration. However, a short, solid section of pipe
between 6 and 8 long should be placed between the connection of the manifold and the flexible
coupling. This nipple will reduce the possibility of the hot gases burning up the flexible coupling.

MN2400

Installation Recommendations Page 7

Exhaust Gas Restriction


The maximum allowable back pressure, or system restriction, is stated in the product
specifications data (inches Hg). If this back pressure is exceeded, the airfuel ratio is reduced
due to incomplete scavenging of the cylinders, fuel economy and power output is reduced,
engine life is reduced and exhaust temperatures and smoke levels increase. Any restriction of
the exhaust gas reduces horsepower. Take every precaution to reduce restriction. Proper design
and installation will provide safe Genset operation.
It is essential that engine exhaust systems have the least possible restriction to exhaust gas flow.
This can be calculated as shown in Figure 2-3.
Figure 2-3 Exhaust System Calculations

352.05
S (kg/m ) +
Exhaust Temperature ) 273.16 oC
3

To obtain equivalent length of straight pipe for each


long radius 90 bend:

Q (cfm or ft3/min)
10000
9000
8000
7000
6000
5000
4500
4000
3500

Note:

L (m) + 15 x D
15 x D
L (mm) +
1000

For 90 bends, radii of 1.5 times pipe diameter


helps reduce resistance and backpressure.

1.0
0.5

0.1
0.05

2500
2000

1000
900
800

3000

1500

L (ft) + 15 x D
15 x D
L (in) +
12

P (in Hg per ft)

D (in) x 25.4 = D (mm)

Where:
P = Backpressure in psi (kPa)
psi = 0.4912 x in Hg
kPa = 0.1333 x in Hg
L = Length of pipe in ft (m)
Q = Exhaust gas flow ft3/min (m3/min)
D = Inside diameter of pipe in (mm)
S = Specific weight of gas lb/ft3 (kg/m3)
39.6
S (lb/ft 3) +
Exhaust Temperature ) 460 oF

D (in)

P (in Hg) x 25.4 = P (mm Hg)

L x SL x Q 2
5,184 x D 5

cfm (ft3/min) x 0.472 = l/s

P (psi) +

0.01
0.005

0.001
0.0005

7
8
9
10

0.0001
0.00005
0.00001

13

Exhaust Piping
Caution: The weight of the exhaust system must never be imposed on the turbocharger outlet.
Damage to the turbocharger and other components may result.
An exhaust system must withstand the vibration and thermal expansion that they are subjected
to, yet supported well enough to remain independent of the engine.
The most common method of providing flexibility is with the use of bellows type flexible piping.
This piping component allows lateral and linear movement of the piping system without
subjecting fixed components to excessive stress. A minimum of 12 inches of flexible connection
must be provided at the engine exhaust manifold to allow for thermal expansion and vibration. If
the engine is to be mounted on spring type vibration isolators, increase the length to 24 inches.
This component can be specified to be provided by your Baldor distributor. Flexible pipe should
never be used for pipe bends or to cure misalignment problems.
Exhaust piping systems may be supported by a wide variety of methods to long as the system
remains flexible, and capable of withstanding thermal expansion.
The material most commonly used for straight runs and elbows in exhaust systems is Schedule
40 black iron. If hanging weight is a problem, other materials may be used. Galvanized piping
should never be used in exhaust system. Where exhaust piping passes through combustible
material, exhaust thimbles must be used. See Figure 2-4.
Note: Water is one of the byproducts of combustion. This water must be kept from draining back into the
engine. Slanting the horizontal section of the exhaust system piping downward slightly, away from the
engine can do this. A water trap (tee extension with a drain cock) should also be used. The water
trap should be located between the flex coupling and the muffler, but as close to the engine as
possible on a horizontal section of the exhaust piping.

Page 8 Installation Recommendations

MN2400

Figure 2-4 Exhaust Pipe Thimble Installation

(Noise Barrier shown in Figure 2-5)


Wind blowing against air exhaust or intake openings of the Genset room must be considered,
especially where the radiator and fan are located on the engine. Wind blowing against an
exhaust opening creates restriction to the fan. Wind blowing against intake openings can blow
open gravity louvers causing low temperature and moisture problems in bad weather. A turning
vane may be required to prevent exhaust air recirculation between the exhaust louvers and the
barrier surface. This will route the exhaust upward into the atmosphere.
Rain Protection
Moisture entering the engine through an exhaust system can cause extensive damage. Exhaust
outlets must have a rain cap or be horizontal to prevent such damage, see Figure 2-4.
Cooling System Cooling System Checklist
A. Has noise been considered?
B. Has system piping been properly sized?
C. Has system been properly protected from freeze up and corrosion?
D. Have standby equipment heaters been specified?
E. Have all electrically driven devices been connected to load side of EPS connection points?
F. Have system drain valves and air eliminators been installed?
The system consists of the cooling medium which is generally a solution of water and ethylene
glycol, a method of rejecting engine produced heat, and a means to transport cooling medium
between the engine and heat rejection system. The first determination is the type of cooling
system to use radiator cooling or heat exchanger cooling.
Engine Mounted Radiator Cooling
The most simple is the engine mounted radiator shown in Figure 2-5. The radiator, water
circulating pump, fan and fan drive are mounted to the Generator Set base rails by the factory.
This method of engine cooling is the most economical, but may require large ventilation vents
and ducts. An added advantage of this arrangement is that the cooling air removes radiated heat
from the engine, generator, and other equipment located in the emergency power system room.
The only remaining design work with the engine mounted radiator is arranging a method of
providing air to the room, and exhausting it from the radiator. See Air Systems.
Figure 2-5 Engine Mounted Radiator Cooled System With Wind/Noise Barrier
Wind Barrier

Prevailing Wind Direction

Rain Cap
Muffler

Rain Hood

Cool Air
Intake

Automatic
Louvers

Air Flow

Exhaust
Thimble

Engine Driven
Cooling Fan

Air Flow
Flexible Duct

MN2400

Hot Air
Exhaust
Hot Air
Automatic
Louvers

Noise
Barrier

Installation Recommendations Page 9

The ideal setup for cooling air would be to arrange the inlet or inlets such that relatively clean,
cool, dry air is drawn across the electrical switchgear, generator, and engine. The air is then
drawn into the radiator fan, and is blown through the radiator and exhausted by duct work outside
the building. Air inlets must be sized to minimize air restriction and provide the quantity of air
required by the radiator fan, engine combustion air, and any other air exhausts which might be
used in the room. On engine mounted radiator cooled systems, the engine mounted fan will
handle 0.25 of water column. This is combined intake and exhaust restriction.
The room air intakes must be located so as to minimize drawing exhaust fumes and other
outside contaminants into the room. Be very cautious about the location of the engine exhausts
in relation to room air intakes. Also, when locating the inlet and outlet, the consultant should
consider prevailing winds and noise. Motor operated louvers or properly designed and sized
gravity louvers should be used on the air intake and exhaust to minimize static pressure drop.
Caution: In cold climates, the high volume of outside air drawn into the Genset room can quickly
reduce temperatures in the room to freezing. Any water piping or other equipment susceptible
to freeze damage should be properly insulated or located elsewhere.
Remote Mounted Radiator Cooling
The radiator can be mounted remotely (not mounted directly at the engine). The remote/close
system uses the same radiator type except it is mounted in another room or outside the building,
but within close proximity to the Genset. See Figure 2-6.
The remote radiator may be mounted either vertically or horizontally. In general, the radiator will
have an electric fan to provide cooling air and may be able to utilize the engine mounted coolant
pump to provide coolant flow.
Figure 2-6 Remote Radiator Cooled System
Radiator
Electric Motor
and Fan

Vent Line
Supply Line

Prevailing Wind Direction

Return Line

Hot Air
Exhaust
Rain Cap
Muffler

Rain Hood

Cool Air
Intake

Automatic
Louvers

Air Flow

Power
Exhaust

Air Flow

Exhaust
Thimble
Hot Air
Exhaust

Automatic
Louvers

Noise
Barrier

The piping system friction and head loss between engine and radiator must be calculated and
not exceed the capacity of the engine pump. If the maximum coolant friction head loss external to
the engine is exceeded, a hot well system must be used. Before designing the piping system
using an auxiliary pump and hot well, the consultant should look very closely at increasing the
systems pipe size.
Electric motorized Power Exhaust louvers should be connected to the standby Genset and
controlled to open whenever the Genset is running. Operable outlet louvers should be
temperature actuated on remote radiator or heat exchanger cooled units. Louvers have
resistance to air flow. Openings with louvers should be twice the area of an unobstructed opening
to provide proper air flow. At times duct work is necessary to provide cooling air for the room.
Duct work must be sized and installed according to SMACNA Standards.
The electric fan and auxiliary pump, if used, must be connected to the emergency power system.
Radiator and cooling fan must be sized to provide the cooling capacity required at an acceptable
sound level.

Page 10 Installation Recommendations

MN2400

Remote radiator and heat exchanger cooled engine cooling systems will not have an engine
driven fan. As a result, the consultant must provide a means of supplying air to the room, and
exhausting it. The air movement must be provided by an electrically driven fan. This fan may be
located in the air inlet or exhaust opening. If the fan is located on the exhaust side, care must be
taken to not create a high negative pressure in the room and starve the engine of combustion air.
Heat Exchanger Cooling
In the heat exchanger system, engine coolant is circulated through the shell side of a heat
exchanger, while city water, well water, or some other cooling medium, is circulated through the
tube side. The primary consideration in this type cooling system is to remember that during
certain types of disasters, these cooling mediums may not be available, especially city water. The
system is relatively inexpensive to install and maintenance is low. Similar to Figure 2-6 except
the heat exchanger mounts between the engine and hot air exhaust (no radiator).
The heat exchanger cooling system can be used with a cooling tower. These systems are
complex, and consists of circulating pumps, heat exchanger for engine coolant, and cooling
tower for heat rejection. The system design requires that several pieces of equipment be sized
and installed. Overall, this system is more expensive than other methods of engine cooling.
Hot Well Installations
One final consideration on the water side is the Maximum Static Head. This is the maximum
height allowable from the engine crank center line to the highest point in the coolant system. The
maximum static head is specified on generator specification sheets. If this number must be
exceeded, a hot well tank system must be used.
The design of hot well tanks and piping systems is somewhat complex. Your authorized Baldor
Distributor has experience in the design and installation of hot well systems. Consult your Baldor
Distributor if the static head of the coolant system in your Genset application exceeds this criteria
and requires a hot well system.
Cooling System Design
Remote Radiator Cooling
Remote Radiator Airflow generally assumed there will be no external restrictions to airflow. If this
is not true, restriction must be considered in sizing and selection of a cooling fan and drive motor.
Typical examples of restrictions include landscaping, nearby buildings, air turbulence created by
buildings or other structures, and sight or noise screens. See Figure 2-6.
Remote Radiator Fan Motor. Remote radiator cooling systems require the use of an electrically
driven fan. This fan must be connected to the emergency power source. Size of the motor is
determined by the fan size and fan speed.
1. To specify a radiator to cool the coolant you will need to determine the amount of heat
rejected to the coolant. This is listed on the Engine Data Sheet as Heat Rejected to
Coolant in BTU/min. for engines using dry or water cooled type exhaust manifolds, as
applicable.
2. Determine the minimum water flow required at the engine, and the maximum top tank
temperature. Using this information, determine the heat rejection capacity required of
the radiator. Radiator systems should be sized with approximately 15% greater
capacity than the engines maximum full load heat rejection to allow for overload and
cooling system deterioration. Whether water flow is produced by an engine mounted or
auxiliary pump, total piping system friction loss must be calculated. To do this, Genset
location, remote radiator location and friction loss within the radiator, and piping system
must be estimated.
3. Pressure drop through the radiator must be obtained from radiator manufacturer.
4. If total piping system pressure exceeds the allowable Maximum Coolant Friction Head
External to the engine as listed on the Engine Data Sheet, the coolant piping size
should be increased and/or a radiator with less restriction must be used.
5. Pressure drop in pipelines and friction of water tables may be found in most
mechanical handbooks such as Cameron Hydraulic Data handbook.

MN2400

Installation Recommendations Page 11

Table 2-2
Fitting Size
90 Elbow
45 Elbow
Long Sweep Elbow
Close Return Bend
TeeStraight Run
TeeSide Inlet or Outlet
Globe Valve Open
Angle Valve Open
Gate Valve Fully Open
Gate Valve Half Open
Check Valve

Flow Restriction of Fittings Expressed as Equivalent of Straight Pipe (in inches)


1.5
2
2.5
3
4
5
6
8
10
12
14
16
4.4
5.5
6.5
8
11
14
16
21
26
32
37
42
2.5
3
3.8
5
6.3
7.5
10
13
15
17
19
2.8
3.5
4.2
5.2
7
9
11
14
17
20
24
27
13
15
18
24
31
37
51
61
74
85
100
3.5
4.2
5.2
7
9
11
14
17
20
24
27
9.3
12
14
17
22
27
33
43
53
68
78
88
55
67
82
110
140
27
33
41
53
70
1.2
1.4
1.7
2.3
2.9
3.5
4.5
5.8
6.8
8
9
27
33
41
53
70
100
130
160
200
230
260
19
23
32
43
53

Other Considerations
General:
1. Deaeration of the coolant. This can be accomplished through the use of the system
deaerators in very large systems, or simply ensuring the radiator top tank or surge tank
is at the highest point in the piping system. Unvented piping systems can create air
pockets which reduce coolant flow and can lead to engine overheating. Baldor
furnished radiators are equipped with deaerating top tanks.
2. Flexible hoses must be installed at all engine connections and to the radiator to isolate
vibration and allow for thermal expansion.
3. Drain valves must be installed at the lowest point of the cooling system to facilitate
system cleaning and flushing.
4. Water treatment and antifreeze must be added to system coolant. Baldor recommends
50/50 ethylene glycol and coolant treatment for all engines.
5. Thermostatically controlled engine coolant heaters are required to be installed on all
standby Gensets. These will increase starting reliability under cold conditions, and
improve the startup load handling ability.
6. According the NFPA 110, priority level 1 equipment jacket water heaters shall maintain
coolant at a minimum of 90 F (32 C). In outdoor installations where temperatures will
be expected to drop below 32 F (0 C), a battery heater should be employed to keep
the batteries at a minimum of 50 F (10 C), and will shut off at 90 F (32 C).
All heaters will shut off when the engine is operating. Adequate antifreeze protection
will be provided and ether starting aids will not be permitted.
7. The consultant should also consider oil sump heaters if conditions warrant.
Heat Exchanger Cooling:
1. If the engine is to be heat exchanger cooled, the system will require a reliable raw
cooling water source and controls to regulate water flow during Genset operation.
2. The system will also need a reliable method of starting and stopping water flow
automatically. The heat exchanger cooled system may be used with a cooling tower.
3. Baldor Gensets are available with heat exchangers factory mounted on the engine. If a
heat exchanger cooled system is required, specify with order.
4. Shell and tube type heat exchangers are connected such that raw cooling water flows
through the tube side of the heat exchanger, and engine coolant through the shell side.
Tubes are more easily cleaned and the potential for fouling is much greater on the raw
water side.
5. For economic reasons, the raw water flow can be regulated by varying the flow of raw
cooling water through the heat exchanger. This control can be accomplished with a
temperature actuated control valve. The thermostatic bulb for this control must be in
the engine jacket water discharge line. The control valve should be a fully modulated
type with a minimum flow setting. NEVER attempt to regulate engine water flow.
6. Water flow regulators are used only if raw water is from a city or well water source. Do
not attempt to regulate flow if a cooling tower is used. Maintain at least 2 ft/second of
water flow through the tube side of the heat exchanger.
Page 12 Installation Recommendations

MN2400

7.

Heat exchanger cooled systems using city or well water, and cooling, tower heat
rejection, however, will not be protected on the tube side of the heat exchanger, nor
interconnecting piping and cooling tower as engine coolant is not circulated through
these components. These systems must be heat traced, and have sump heaters
installed to protect the various components when the Genset is on standby.

It must also be noted that if an antifreeze solution is used in the shell side of the engine
cooling system heat exchanger, local codes may restrict the discharge of the tube side
cooling water after flowing through the heat exchanger.
Coolant Treatment:
1. Engine coolant should be treated with a Diesel Coolant Additive (DCA) to minimize
corrosion of the engine and cooling system components. A 50/50 ethylene glycol
antifreeze solution is recommended for all Genset engines. This will provide freeze
protection and increase the boiling point of the engine coolant. A solution can be
increased to 65% but freeze protection is reduced after 65%.
2. It is recommended that the consultant specify Baldor supplied DCA and water filters,
and Baldor antifreeze.
3. When the proper solution concentration of antifreeze is used with radiators (engine
mounted as well as remote mounted), and hot well systems, the system will be
adequately protected from freezeup.
Air Flow System

Air System Checklist


A. Air inlet faces the direction of prevailing winds.
B. Air outlet does not face noise sensitive areas without noise attenuating devices.
C. All heat loads have been taken into consideration in sizing air flow.
D. Gravity louvers face inward for air intake and outward for discharge.
E. Where electrically operated ventilation devices are used, power must be present under all
operating situations. Be certain these devices are on the emergency circuit.
The room in which the Generator Set is to be installed must have adequate air flow through it to
provide combustion air, and remove heat radiated from the engine, exhaust system and
generator. See Figure 2-7 for air flow calculations.
Figure 2-7 Air Flow Calculations

BTU/minute
BTU/Hour

QM
0.0181 x DT Fo
QH
V (cfm) +
1.085 x DT Fo
V (cfm) +

Where:
V
= Ventialting air flow ft3/min (m3/min)
QM = Heat disipated by the engine, generator and
other equipment BTU/min
= Heat disipated by the engine, generator and
QH
other equipment BTU/hr
kWSh = Heat disipated by the engine, generator and
other equipment Kilowatt Hours
T
= Premissible temperature rise in the room in F or C
D
= Inside diameter of pipe in (mm)
S
= Specific weight of gas lb/ft3 (kg/m3)

MN2400

KilowattSHours

V (m 3/min) +

kW hr
0.02015 x DT Co

Notes:
1 These calculations assume room ambient of 100F (38C)
2 Increae V by 10% for each 2,500 ft (762m) above sea level
3 Increae V by 10% if uninsulated mufflers are inside room
4. Engine data sheet specifies Radiated heat to ambient in
BTU/min. This value is dry type ad water cooled exhaust
manifolds.
5. Generator efficiency is 88 to 95% for Gensets 50kW to
1200kW. 1kW loss = 56.88 BTU/min.

Installation Recommendations Page 13

Fuel System (Diesel Only)


The fuel system must provide adequate and continuous quantities of clean fuel to the Generator
Set. Bulk fuel is stored in large tanks, usually outside the building, and fuel is transferred to a
smaller tank (day tank) located near the engine.
Day Tank
The quantity of the fuel to be stored by the day tank may be regulated by local or state agencies,
and should be given consideration. If not, NFPA and the NEC require that enough fuel be stored
to operate the Genset for a minimum of 2 hours depending on the type of facility. For practicality,
the day tank should be sized to operate the Genset for two to four hours minimum depending on
how critical the availability of standby power is to your client. Engine fuel consumption can be
calculated based on Net Generator Output by using the engine performance curve.
High fuel level in the day tank should never be higher than the engine injector level unless the
engine is equipped with factory installed check valves. If this condition is encountered, consult
your Baldor Distributor. Lateral distance and the number of pipe fittings from the day tank to the
engine injector pup should be minimized.
Baldor engines use a fuel bypass type injector. The unused fuel is bypassed and drained away
from the engine. This fuel should be returned to the day tank and not the bulk tank. If fuel is
returned to the bulk tank, be sure to size the day tank based on fuel flow to the fuel pump and not
fuel consumption.
Fuel System Placement
The first decision to be made in this section is where to place the bulk storage tank, the day tank,
and how to route the interconnecting piping. Routing of the piping should be as direct as
possible, and with few bends as possible. The bulk storage tank placement should receive
careful consideration. For aesthetic reasons, the tank should be in an area that will not detract
from the building. For practicality, the tank should be located as close as possible to the Genset.
To provide the quickest starting time, and to meet the 10 second starting code requirement
imposed by the National Fire Protection Association (NFPA) 110, it is suggested that a day tank
be used. This tank should be mounted adjacent to the engine. The quantity of the fuel to be
stored may be regulated by local or state agencies, and should be given consideration. The U.S.
National Electric Code, Article 700 calls for onsite fuel supplies to be capable of operating the
Genset at full demand load for at least two hours. Consult NFPA 37 for additional information on
fuel storage methods and quantities. NFPA 110 Level 1 lists Genset fuel quantities required by
class of installation.
Pipe sizes must be determined and installed so as to not exceed injector pump inlet and injector
return line restriction listed on the Engine Data Sheets. The head loss in the pipe system may be
calculated. The graph and friction of viscous fluids tables may be found in most mechanical
handbooks such as Cameron Hydraulic Data handbooks. Refer to product specifications for lift
limits and fuel flow data.

Page 14 Installation Recommendations

MN2400

Large capacity bulk storage tanks allow delivery of fuel in quantity, and minimize dirt and
condensation contamination. Bulk tanks should be kept full to minimize condensation. Bulk tanks
may be located above or below ground. For an above ground tank, consider insulating the tank
to minimize condensation. Whether the tank is to be above or below ground, the consultant must
keep EPA and NFPA, as well as the owners insurance underwriters requirements in mind.
The bulk tank should be sized to provide several days of standby power. The quantity of the fuel
to be stored must be determined based on the length of expected power outages, availability of
fuel deliveries, and how critical the availability of long term standby power is to your client.
Engine fuel consumption can be calculated based on Net Generator Output by using the engine
performance curve.
High fuel level in the main bulk tank may be above the engine injector level if a day tank is used,
and a solenoid valve controlled by a float switch in the day tank is installed in the line to the day
tank. The solenoid valve should be operated electrically from battery voltage and have a means
for a manual bypass. The manual bypass should be of a deadman type to prevent day tank
overfill. For safety, a manual shutoff valve should also be installed ahead of the solenoid valve,
but should remain open under normal circumstances.
Lateral distances and the number of pipe fittings from the bulk tank to the day tank should be
minimized. Piping sizes must be determined and installed so as to not exceed fuel lift pump head
as listed on the day tank manufacturers data sheet. The head loss in the piping system may be
calculated using head loss calculation procedures. The consultant should never plan to use any
line size smaller than 1 inch nominal between the bulk tank and day tank.
General Considerations
In the design and layout of the fuel piping from the bulk tank to the day tank, it is advisable to
either run the piping underground or insulate the line to minimize jelling problems during cold
weather. In cold climates, provisions for heat tracing or preheating the fuel in outside enclosures
may be necessary. Exposed fuel lines inside the Genset building should meet fire resistance
qualifications.
Do not use flexible nonmetallic piping unless it meets these requirements. Galvanized, zinc
bearing alloy, solid copper, or brass should never be used for fuel piping or storage tanks. These
materials can catalyze fuel decomposition and cause fuel filters to plug prematurely. Black steel
is recommended.
Fuel tanks should be epoxy resin coated to minimize metal contact and corrosion. Provision
should be made in the design of the bulk and day tanks to allow access for checking stored fuel,
the addition of additives, and full filtration of stored fuel every 6 to 12 months. If at all possible,
the bulk tank(s) should have gravity fill. Every two years, the owner should have the fuel checked
and changed out as necessary to remove water, scale, and bacteria.
Fuel Type and Grade
The recommended fuel grade for standby Genset operation is No. 2D as specified in ASTMD
975. No. 1D may be used, or a blend of 1D and 2D if climatic conditions warrant. The use of
common bulk storage tank for a diesel standby Genset and No. 2 burning boilers is generally not
recommended. If it is being considered, a careful review of fuel type, expected operating
temperatures, and code requirements is necessary.
The Cetane rating of No. 2 boiler oil is usually lower than that required by a diesel engine to
provide quick starts. This will reduce Genset start up reliability, especially in cold weather.
NFPA 110 does not allow the fuel supply for standby Gensets to be shared by other equipment
on Level 1 type installations. The use of other fuels, including JetA and JP4, in the operation of
Gensets is not recommended, as they will result in loss of engine power, and reduction in the life
of fuel system components.
Multi Engine Considerations
In a multiengine installations, fuel piping should not be manifold connections to each engine.
Provide a day tank and fuel pump system for each Genset. Also, each day tank should be
supplied from the bulk tank individually. If it is desired to operate more than one Genset from a
common day tank, please consult your Baldor Distributor.
Bulk Tank

MN2400

Installation Recommendations Page 15

Other Fuel System Considerations & Recommendations


1. Specify that a flexible section be used at all fuel system connections at the engine.
2. Tanks must be provided with drain connections or a means to allow condensate and
other impurities to be removed periodically from the bottom of tanks.
3. Never allow unions to be installed at the high point in the fuel piping system as they
allow air to enter the system.
4. Low fuel level alarm for main and day tanks.
5. Critical low fuel alarm and engine shutdown on day tank.
6. Fuel heater with thermostat in day tank should be used if temperatures around the day
tank will be less than 20 F (7 C).
7. High fuel level alarm on day tank.
Transfer Switch

Transfer Switch Checklist


A. Locate transfer switch in a clean, dry place, near the emergency load.
B. Provide a circuit breaker between the Genset and the transfer switch.
C. Put a flexible connection between the conduit and Genset.
D. Observe applicable codes in wiringin the transfer switch and Genset.

The transfer switch connects the Genset to the emergency power system. The emergency power
system may include several Gensets and several transfer switches. Typically, the Genset is
wired to the emergency power system through a transfer switch as shown in Figure 2-8.
Figure 2-8 Typical Emergency Power System Installations
Utility
Utility
G
G Gensets
Main
Disconnect

Genset

Branch
Protection

Main
Disconnect
Branch
Protection

Generator Paralleling Control Panel Priority Control


Branch
Protection

Transfer
Switch

TS-2
Transfer
Switch1

Non-Emergency
Loads

TS-1

Transfer
Switch2

Emergency
Loads
Non-Emergency
Loads

Level -1
Loads

Level -2
Loads

Multiple Gensets can be arranged either in parallel or separately connected to dedicated


emergency loads. Figure 2-8 also shows a typical arrangement of two Gensets in parallel with
transfer switches for loads that have different levels of priority. A typical multiple Genset
installation is shown for NFPA 110 Level 1 and Level 2 emergency power circuits and a priority
control to select the appropriate transfer switch.
Wattmeters should be installed on each Genset so load sharing can be checked. The control
system should include an automatic paralleling control. Paralleling identical Gensets is not
difficult, but paralleling dissimilar sets can cause load sharing problems. When designing an
installation that includes the paralleling of dissimilar generators, contract your nearby Baldor
Distributor.

Page 16 Installation Recommendations

MN2400

Transfer Switch Location


The transfer switch location is important and key considerations are:
1. Locate the transfer switch as close to the emergency load as practical to avoid
interruptions of the emergency power system due to natural or manmade disasters, or
to equipment failures. Consider several small transfer switches instead of one large
one to increase reliability.
2. Locate the transfer switch in a clean, dry, well ventilated location, away from excessive
heat. When the ambient air is above 104 F (40 C), fuses and circuit breakers must be
derated. Allow adequate working space around the transfer switch.
3. A circuit breaker (or fuses) should be installed in the line between the generator and
the transfer switch. Baldor Gensets are available with properly sized circuit breaker
built into the generator control. The circuit breaker can be separately mounted. In the
case of very large circuit breakers, a separate floor mounted circuit breaker is easier to
wire up than a wall mounted breaker.
4. Install power and control wires in separate solid conduit with flexible sections at the
Genset. The flexible sections prevent vibration from damaging the conduit. All power
conduits from the Genset must contain all three phases.
5. Never install control wires in the same conduit as power conductors.
6. Conduit, wire, circuit protective device sizes, insulation etc. must conform to applicable
local and national codes and regulations.
7. Be certain to seal around conduits that penetrate the walls of the Genset room to
reduce the amount of noise that is transmitted to the surrounding areas of the building
and maintain site fire code rating.
Battery Starting System
This section describes the battery starting system (nominal 12 volt rating of the battery supply)
for the engine, battery charger, and precautions to take if the ambient temperature is expected to
be below 70 F (20C).
WARNING: If batteries are not mounted in the battery rack supplied with the Genset, protect batteries
from vibration and do not locate them near a source of flame or spark. A battery presents a
risk of fire and explosion because they generate hydrogen gas. Hydrogen gas is extremely
explosive. Never jump start a battery, smoke in the area around the battery or cause any
spark to occur in the area around the battery.
Battery Location
Locate batteries as close as possible to the Genset to minimize starting circuit resistance, see
Figure 2-9. High starting circuit resistance substantially reduces starting cranking ability. The
Genset data sheet lists the maximum allowable cranking system resistance. Mount batteries on a
level rack away from dirt and liquids. Allow space for servicing (checking water level and level of
charge). Baldor Gensets can be ordered with battery racks already installed. Cold ambient
temperature at the battery location substantially reduces the battery output.
Figure 2-9 Battery Starting System

MN2400

Installation Recommendations Page 17

The ability to start the engine depends upon battery capacity, ambient temperature and coolant
and oil temperatures. The Engine/Generator Set Data Sheet lists minimum recommended battery
capacity at various ambient temperatures. The recommended battery capacities are listed in the
Electric Systems section of the Engine Data Sheet, cold cranking amps (CCA) at 0 F (18 C).
Battery capacities decrease as ambient temperatures decrease so it is important to specify
batteries with the appropriate CCA rating at a temperature no higher than the minimum ambient
temperature for the application. Baldor requires thermostatically controlled coolant heaters on all
after cooled standby Gensets. After cooling is called out on the Engine Data Sheet under
General Engine Data section as aspiration.
Oil pan immersion heaters are recommended for standby Gensets housed outside where
ambient temperatures may drop below 0 F (18 C). Coolant heaters and oil pan immersion
heaters are available from Baldor as factory installed options.
Battery Charger An engine mounted alternator to charge the batteries during operation is an available option.
Standby Gensets require a solid state battery charger that is connected to utility power so the
battery is charged continuously while the Genset is not running. The battery charger should be
connected to the emergency circuit. The batteries on prime power Gensets are charged by the
engine mounted alternator, if equipped.
Harmonic wave forms from solid state battery charges and belt driven alternators can cause the
electronic governor on the engine to act erratically. To avoid this, the output of the battery charger
or the belt driven alternator must be connected directly to the battery or to the battery terminals
on the starter. Make control connections to the Genset control using a conduit with a flexible
section at the Genset to avoid damage due to Genset vibrations.
Battery Cables The wire size (wire gauge) of the cables connecting the starter to the batteries must be large
enough to ensure the resistance of the cranking circuit is less than the Maximum Allowable
Resistance of the Cranking Circuit as shown on the EngineGenerator Set Data Sheet. The total
cranking circuit resistance includes the resistance of the cables from the starting motor to the
battery and the resistance of all relays, solenoids, switches, and connections. The resistance of
various sizes of cables is shown in Figure 2-10. For purposes of calculating cranking circuit
resistance to select cable size, the resistance of each connection can be taken as .00001 ohms
and the resistance of each relay, solenoid, and switch can be taken as .0002 ohms. Figure 2-10
illustrates an example of a typical cranking circuit resistance calculation.

Battery Size

Figure 2-10 Typical Battery Cable Calculations


#4

0.00400

#3

#2

#1

#0

#00
#000

Resistance in Ohms at 77F (25C)

0.00380
0.00360
0.00340
0.00320
0.00300
0.00280

2-#0

0.00260
0.00240
0.00220

2-#00

0.00200
0.00180

Maximum allowable resistance of . . . . . . . 0.002 Ohms (24V Systems)


the cranking circuit . . . . . . . . . . . . . . . . 0.0012 Ohms (12V Systems)

0.00160
0.00140

System Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24V


Resistance of 6 connections . . . . . . . . . . . . . . . . . . . . 0.00006 Ohms
Resistance of 100' of #1 Cable . . . . . . . . . . . . . . . . . . 0.00100 Ohms
Total resistance of cranking circuit
0.00106 Ohms

0.00120
0.00100
0.00080
0.00060
0.00040
0.00020
0

100
(2.54)

200
(5.08)

300
(7.62)

400
(10.16)

500
(12.70)

600
(15.24)

700
(17.78)

Cable Length inches(meters)

Page 18 Installation Recommendations

MN2400

Formulas
Single Phase Electric

Single Phase Power Factor is typically 1.0


1 kW = 1 kilo Watt = 1,000 Watts
Watts + Volts x Amps x Power Factor
Amps +

Three Phase Electric

Watts
Volts x Power Factor

Three Phase Power Factor is typically 0.8


1 kW = 1 kilo Watt = 1,000 Watts
Watts + (Volts x Amps x Power Factor) x 1.732
Amps +

Watts
Volts x Power Factor x 1.732

Length

inches x 25.40 = mm
feet x 0.305 = m
yard x 0.914 = m

mm x 0.03937 = inches
m x 3.280 = feet
m x 1.094 = yard

Area

inches2 x 6.451 = cm2


feet2 x 0.0929 = m2

cm2 x 0.394 = inches2


m2 x 10.764 = feet2

Pressure

pounds/ft2 x 0.006944 = pounds/in2


psi x 6.8948 = kPa
psi = 0.4912 inches Hg

pounds/in2 x 144 = pounds/ft2


kPa x 0.1450 = psi
kPa = 0.1333 x inches Hg

Temperature

C = (F32) x 0.55555

F = (C x 1.8) + 32

Torque

ozin x 0.007062 = Nm
lbin x 0.11296 = Nm
lbft x 1.356 = Nm

Nm x 141.6029 = ozin
Nm x 8.8495 = lbin
Nm x 0.7376 = lbft

Velocity

ft/sec x 0.3048 = m/sec


miles/hr x 1.6093 = km/hr
miles/hr x 0.44704 = m/sec

m/sec x 3.2808 = ft/sec


km/hr x 0.6214 = miles/hr
m/sec x 3.2808 = ft/sec
m/sec x 2.2369 = miles/hr

Volume

inches3 x 16.388 = mm3


feet3 x 0.0283 = m3
gallons x 3.785 = liter
gallons x 0.13337 = ft3

cm3 x 0.06102 = inches3


m3 x 35.315 = feet3
liter x 0.2642 = gallon

Miscellaneous

MN2400

Watt x 0.00134 = hp or 746 watts = hp


BTU/hr x 0.293 = Watts
Watts x 3.4122 = BTU/hr
BTU/hr x 0.0003929 = hp
hp x 2,545 = BTU/hr
Approximate fuel Higher Heating Values (HHV):
Natural Gas = 1015 BTU/ ft3, Liquid Propane = 2650 BTU/ ft3
Effect of engine efficiency on fuel consumption:
hp x 2545 BTU/hr per hp
+ 10, 180BTUhr
0.25 efficiency

Installation Recommendations Page 19

Page 20 Installation Recommendations

MN2400

Baldor District Offices


UNITED STATES
ARIZONA
PHOENIX
4211 S 43RD PLACE
PHOENIX, AZ 85040
PHONE: 602-470-0407
FAX: 602-470-0464
CALIFORNIA
LOS ANGELES
6480 FLOTILLA
COMMERCE, CA 90040
PHONE: 323-724-6771
FAX: 323-721-5859
HAYWARD
21056 FORBES STREET
HAYWARD, CA 94545
PHONE: 510-785-9900
FAX: 510-785-9910
COLORADO
DENVER
2520 W BARBERRY PLACE
DENVER, CO 80204
PHONE: 303-623-0127
FAX: 303-595-3772

FAX: 586-978-9969
MICHIGAN Continued
GAND RAPIDS
668 3 MILE ROAD NW
GRAND RAPIDS, MI 49504
PHONE: 616-785-1784
FAX: 616-785-1788

TEXAS
HOUSTON
4647 PINE TIMBERS
SUITE # 135
HOUSTON, TX 77041
PHONE: 713-895-7062
FAX: 713-690-4540

MINNESOTA
MINNEAPOLIS
21080 134TH AVE. NORTH
ROGERS, MN 55374
PHONE: 763-428-3633
FAX: 763-428-4551

DALLAS
3040 QUEBEC
DALLAS, TX 75247
PHONE: 214-634-7271
FAX: 214-634-8874

MISSOURI
ST LOUIS
422 INDUSTRIAL DRIVE
MARYLAND HEIGHTS, MO 63043
PHONE: 314-298-1800
FAX: 314-298-7660
KANSAS CITY
915 N W PLATTE VALLEY DR
RIVERSIDE, MO 64150
PHONE: 816-587-0272
FAX: 816-587-3735

UTAH
SALT LAKE CITY
2230 SOUTH MAIN STREET
SALT LAKE CITY, UT 84115
PHONE: 801-832-0127
FAX: 801-832-8911
WISCONSIN
MILWAUKEE
2725 SOUTH 163RD STREET
NEW BERLIN, WI 53151
PHONE: 262-784-5940
FAX: 262-784-1215

NEW YORK
AUBURN
ONE ELLIS DRIVE
AUBURN, NY 13021
PHONE: 315-255-3403
FAX: 315-253-9923

INTERNATIONAL SALES
FORT SMITH, AR
P.O. BOX 2400
FORT SMITH, AR 72902
PHONE: 479-646-4711
FAX: 479-648-5895

FLORIDA
TAMPA/PUERTO RICO/
VIRGIN ISLANDS
3906 EAST 11TH AVENUE
TAMPA, FL 33605
PHONE: 813-248-5078
FAX: 813-247-2984

NORTH CAROLINA
GREENSBORO
1220 ROTHERWOOD ROAD
GREENSBORO, NC 27406
P O BOX 16500
GREENSBORO, NC 27416
PHONE: 336-272-6104
FAX: 336-273-6628

CANADA
EDMONTON, ALBERTA
4053-92 STREET
EDMONTON, ALBERTA T6E 6R8
PHONE: 780-434-4900
FAX: 780-438-2600

GEORGIA
ATLANTA
62 TECHNOLOGY DR.
ALPHARETTA, GA 30005
PHONE: 770-772-7000
FAX: 770-772-7200

OHIO
CINCINNATI
2929 CRESCENTVILLE ROAD
WEST CHESTER, OH 45069
PHONE: 513-771-2600
FAX: 513-772-2219

CONNECTICUT
WALLINGFORD
65 SOUTH TURNPIKE ROAD
WALLINGFORD, CT 06492
PHONE: 203-269-1354
FAX: 203-269-5485

ILLINOIS
CHICAGO
1601 FRONTENAC ROAD
NAPERVILLE, IL 60563
PHONE: 630-848-5100
FAX: 630-848-5110
INDIANA
INDIANAPOLIS
5525 W. MINNESOTA STREET
INDIANAPOLIS, IN 46241
PHONE: 317-246-5100
FAX: 317-246-5110
800-428-4141
IOWA
DES MOINES
1800 DIXON STREET, SUITE C
DES MOINES, IA 50316
PHONE: 515-263-6929
FAX: 515-263-6515
MARYLAND
BALTIMORE
6660 SANTA BARBARA RD.
SUITE 22-24
ELKRIDGE, MD 21075
PHONE: 410-579-2135
FAX: 410-579-2677
MASSACHUSETTS
BOSTON
6 PULLMAN STREET
WORCESTER, MA 01606
PHONE: 508-854-0708
FAX: 508-854-0291
MICHIGAN
DETROIT
33782 STERLING PONDS BLVD.
STERLING HEIGHTS, MI 48312
PHONE: 586-978-9800

CLEVELAND
8929 FREEWAY DRIVE
MACEDONIA, OH 44056
PHONE: 330-468-4777
FAX: 330-468-4778
OKLAHOMA
TULSA
2 EAST DAWES
BIXBY, OK 74008
PHONE: 918-366-9320
FAX: 918-366-9338
OREGON
PORTLAND
20393 SW AVERY COURT
TUALATIN, OR 97062
PHONE: 503-691-9010
FAX: 503-691-9012
PENNSYLVANIA
PHILADELPHIA
1035 THOMAS BUSCH
MEMORIAL HIGHWAY
PENNSAUKEN, NJ 08110
PHONE: 856-661-1442
FAX: 856-663-6363
PITTSBURGH
616H BEATTY ROAD
MONROEVILLE, PA 15146
PHONE: 412-380-7244
FAX: 412-380-7250
TENNESSEE
MEMPHIS
4000 WINCHESTER ROAD
MEMPHIS, TN 38118
PHONE: 901-365-2020
FAX: 901-365-3914

OAKVILLE, ONTARIO
2750 COVENTRY ROAD
OAKVILLE, ONTARIO L6H 6R1
PHONE: 905-829-3301
FAX: 905-829-3302
MONTREAL, QUEBEC
1844 WILLIAM STREET
MONTREAL, QUEBEC H3J 1R5
PHONE: 514-933-2711
FAX: 514-933-8639
VANCOUVER,
BRITISH COLUMBIA
1538 KEBET WAY
PORT COQUITLAM, BC V3C 5M5
PHONE 604-421-2822
FAX: 604-421-3113
WINNIPEG, MANITOBA
54 PRINCESS STREET
WINNIPEG, MANITOBA R3B 1K2
PHONE: 204-942-5205
FAX: 204-956-4251
AUSTRALIA
UNIT 3, 6 STANTON ROAD
SEVEN HILLS, NSW 2147,
AUSTRALIA
PHONE: (61) (2) 9674 5455
FAX: (61) (2) 9674 2495
UNIT 8, 5 KELLETTS ROAD
ROWVILLE, VICTORIA, 3178
AUSTRALIA
PHONE: (61) (3) 9753 4355
FAX: (61) (3) 9753 4366
BALDOR CENTROAMERICA
RESIDENCIAL PINARES DE SUIZA
POL. 15 #44, NVA. SAN SALVADOR
EL SALVADOR, CENTRO AMERICA
PHONE: (503) 288-1519
FAX: (503) 288-1518
BALDOR SUDAMERICA
CALLE F, EL CANGREJO
CONDOMINIO P.H. CONDADO PLAZA
APT. 11D, BELLA VISTA
PANAM CITY, REP. DE PANAM
PHONE: (507) 265-6041

CHINA
SHANGHAI JIAHUA BUSINESS CENTER
ROOM NO. A-8421
808 HONG QIAO ROAD
SHANGHAI 200030
PHONE: 86-21-64473060
FAX: 86-21-64078620
GERMANY
DIESELSTRASSE 22
D-85551 KIRCHHEIM
MUNICH, GERMANY
PHONE: (49) (89) 90508 - 0
FAX: (49) (89) 90508 - 492
INDIA
14, COMMERCE AVENUE
MAHAGANESH COLONY
PAUD ROAD
PUNE - 411 038
MAHARASHTRA, INDIA
PHONE: 91 20 25 45 95 31/32
FAX: 91 20 24 55 95 30
ITALY
BALDOR ASR AG
SUCCURSALE DI MENDRISIO
VIA BORROMINI, 20A
CH-6850 MENDRISIO
SWITZERLAND
PHONE: 41 91 640 9952
FAX: 41 91 630 2633
JAPAN
DIA BLDG 802,
2-21-1 TSURUYA-CHO,
KANAGAWA-KU
YOKOHAMA, 221-0835, JAPAN
PHONE: 81-45-412-4506
FAX: 81-45-412-4507
KOREA
ROOM 210
BUPYEONG INDUSTRIAL
COMMERCIAL COOPERATIVE
396-16 CHEONGCHEON 2-DONG,
BUPYEONG-GU
INCHEON, KOREA, 403-858
PHONE: 82 32 508 3252
FAX: 82 32 508 3253
MXICO
KM. 2.0 BLVD. AL AEROPUERTO
LEN 37545, GUANAJUATO, MXICO
PHONE: 52 477 761 2030
FAX: 52 477 761 2010
MIDDLE EAST & NORTH AFRICA
VSE INTERNATIONAL CORP.
3233 NORTH ARLINGTON HEIGHTS
SUITE 100W
ARLINGTON HEIGHTS, IL 60004
PHONE: 847 590 5547
SINGAPORE
51 KAKI BUKIT ROAD 2
K B WAREHOUSE COMPLEX
SINGAPORE 417863
PHONE: (65) 6 744 2572
FAX: (65) 6 747 1708
SWITZERLAND
POSTFACH 73
SCHUTZENSTRASSE 59
CH-8245 FEUERTHALEN
SWITZERLAND
PHONE: (41) (52) 6474700
FAX: (41) (52) 6592394
TAIWAN
4F, NO. 25, SEC. 1,
TUNHUA S ROAD,
TAIPEI 10557, TAIWAN, R.O.C.
PHONE: (886-2) 2577-4352
FAX: (886-2) 2577-4157
UNITED KINGDOM
6 BRISTOL DISTRIBUTION PARK
HAWKLEY DRIVE
BRISTOL BS32 0BF U.K.
PHONE: 44 1454 850000
FAX: 44 1454 859001

WARNING:
CALIFORNIA PROPOSITION 65 WARNING:
Engine exhaust from this product contains chemicals known
to the state of California to cause cancer, birth defects and
other reproductive harm.

WARNING:
CALIFORNIA PROPOSITION 65 WARNING:
Battery posts, terminals and related accessories are known to
the state of California to cause cancer, birth defects and other
reproductive harm.

BALDOR GENERATORS
3815 Oregon Street
Oshkosh, WI 54902
(920) 2364200 or (800) 8727697
Fax (920) 2364219
www.baldor.com

Baldor Electric Company


MN2400

Printed in USA
4/05

You might also like