Professional Documents
Culture Documents
LIMITER OVERVOLTAGE
C: \ Documents and Settings \ Owner \ Desktop \ Limiteur_de_surtension_2.doc Pag
e 4/4
The surge arrester comprises two electrodes, one is generally connected to the o
ther neutral to the
earth ground. If the neutral point is not available, the surge arrester is conne
cted between a
phase and earth.
Summary Operating principle
When an overvoltage occurs between the electrodes exceeds a threshold:
Either a simple corona involving no release for direct land.
Either Booting welding active parts of the surge arrester. In this case the limi
ter
Surge must be replaced.
Note 1: The replacement of the surge protector must be preceded by documenting t
he post
transformation.
Note 2: If your installation has been performed with suitable equipment (CPI mus
t monitor
Also the isolation of the neutral conductor), the location of the boot is easy,
the ICC is in alarm
BTA all circuits are open. We need the general cut is possible, otherwise the lo
cation
is difficult to perform.
Choice of surge
NFC 63-150 defines three types of surge protectors, whose characteristics are
following:
(TABLE IS GIVEN)
Rated voltage
ignition voltage to 0% to
f r e q u e n c e i n d u s t r i a l l e
Ignition voltage to 100%
Power frequency
Ignition voltage to 100%
Voltage pulse wave
If the installation is fed by several transformers in parallel, one must install
a limiter
overvoltage on each of them. And of course one ICC is required.
Obviously it must be considered when choosing the surge of dielectric strength
low-voltage switchgear (reinforced equipment: 3000Volts in the case of a main sw
itchboard or in the 10000Volts
For high poles posts). You understand that the surge protector is a weak point i
n
installation, do not just low-voltage equipment is a dielectric strength such as
fault current priority choose this quipement4
Imagine the human consequences in such a situation.
other remarks
The failure to replace the surge limiter following his breakdown has the effect
of changing the regime
Neutral installation is to lose all the benefits of this neutral regime.
4 This may occur when used in an industrial installation type equipment
Domestic whose dielectric strength is less than the breakdown voltage to 100% po
wer frequency.
LIMITER OVERVOLTAGE
JUSTIFICATION SET CURRENT GENERAL BREAKER
EARTH CONNECTION BETWEEN THE TRANSFORMER HTA / BTA and THE TGBT
If a transformer 1000kVA Calculating the double default short-circuit current
FIGURE
Double fault current will not illimit5
Indeed it is a function of the internal impedance of the
source and BTA bonds. The coupling of the transformer is important. In the above
case the current
default will be:
In the case above, this current is equal to 18kA. This value allows the breaker
setting
as recommended by standard NFC 15-100.
Static electricity has nothing to do with types of defects described above.
Protection against surtensions6
required
Protection against any danger that can result:
- A power frequency overvoltage: Overvoltage due to an insulation fault with
higher voltage installation.
- In a surge: overvoltage atmospheric transmitted by the network
distribution or overvoltage due to electrical equipment maneuvers.
Power frequency overvoltage
5 In response to the statement of Mr. Christian CHOCRAUX "We must respond quickl
y because when a fault occurs
it will no longer be limited and it is the protector (of the offending device) w
hich acts with a current
corresponding to the switch setting.
6 Document Normelec
required
Implementation of protection against power frequency overvoltage:
- By limiting the value of the resistance of the earth connection of the power s
et point directly to the
Earth (Rn), where such point exists and that this ground is distinct from the ma
sses
the installation7
, Such that the following relation is verified
Ut withstand voltage at power frequency masses
the installation (this voltage is conventionally taken equal to
2U 1000)
U0 voltage between phase and neutral installation m
t
I
U U R + 0 =
Im maximum current of the first ground fault installation HT8
- Implementing, at the origin of the installation, when no part of the power sou
rce is not connected
directly to the terre9
A surge protector device, such a device must be provided for each
transformer when the installation is fed by several transformers operating in pa
rallel.
prohibited
Coexistence in the same duct or in the same gutter electrical conduits or very l
ow
low voltage and high voltage power lines, unless simultaneously:
- The pipes at very low or low-voltage and high-voltage lines are arranged
on separate supports.
- Grounding resistance media does not exceed the quotient of the voltage
frequency withstand these lines by the intensity of the maximum current top
ground fault of high voltage lines.
required
Choice of surge, if used as its nominal voltage boot 100%
power frequency (Ua) satisfies the relation:
Ut voltage frequency withstand the masses of the installation (this
voltage is conventionally taken equal to 2U 1000)
UUU has <t - U 'phase to neutral voltage if the surge protector is connected bet
ween the
q neutral and earth; line voltage if it is connected between a
phase and earth.
Implementation of the surge protector used if necessary so that
- Its input terminal is connected to the selected active conductor (neutral or p
hase) between the output terminal
transformer and the first switching device.
- Its ground terminal is connected:
Inserting a valeur11 low impedance between the ground terminal of the limiter an
d the earth when the
short-circuit current may pass through this device may be higher than it can
bear this impedance may interest many surge protectors.
important note
The comments above are not exhaustive. I draw your attention indicating that the
y
apply only to industrial, commercial and similar installations subject to regula
tion
subject of this note. Other facilities, especially those concerning the faciliti
es
public distribution are regarding them are subject to a different regulation.
====================
function
Allow mounting on the front of the devices in modular housing 99 mm
or 108 mm in length
function
Mandatory IT system (isolated or impedance) for any HV / LV transformer, it is
connected to the secondary and ensures the flow to ground surges from
high voltage.
The voltage limiter ensures the safety of people and property by limiting the
Current 1st fault after reopening.
Compliant Standards
NF C 63-150
NF C 15-100
Decree No. 88-1056 of 14-11-88:
protection of workers
Main Features
The boot after current limiting inductors is recommended
to limit breakages on the main switchboard busbars and reduces
section of the connecting conductors.
Choice to perform according to the mains voltage, the isolation level
installation and connection point side transformer (phase or the point
middle). Refer to our technical notes.
While the limiter is left from that in case of serious damage (thus visible), th
e
detecting operation by a torus associated with a locator can DLD
be interesting.
SPECIFICATIONS
Keeping short-circuit current 40 kA for 0.2 sec.
400 A permanently
Operating temperature - 5 ... + 40 C
Storage temperature - 25 ... + 70 C