Professional Documents
Culture Documents
TRANSFORM Partner
Speaker
Andreas Dobler (M1972)
- born in Ludwigshafen/Rhein
- graduated from the University Kaiserslautern holding a degree of
electrical Engineering
- 1998-2004: ABB Energiekabel GmbH: Research & Development, later in
Product Management MV cable accessories
- since 2004: PFISTERER Kontaktsysteme GmbH
Product Management of pluggable cable accessories (CONNEX)
Product Manager of MV-CONNEX (since 2006)
07.06.2012
Page 2
Agenda
Connecting Principle
Medium Voltage
High Voltage
Function
Current Carrying Capability
Dielectric Strength
Mechanical Properties
Testing
Trends
07.06.2013
Page 3
Polymer Housing
Low cost
Higher costs
Low cost
07.06.2013
Page 4
Medium flexibility
Low flexibility
Highest flexibility
07.06.2013
Page 5
Dielectric Strength
Mechanical Properties
Nominal
Short Circuit
Forces / Pressure
Fixation of cable
07.06.2013
Page 6
Conductor
Semi- conductive layer over conductor
Insulation XLPE or EPR
Semi- conductive layer over insulation
Semi- conductive crepe paper
Cable Shield
Metallic foil
Crepe Paper
Armouring
Outer Sheath
07.06.2013
Page 7
Size 0
Size 1
Size 2
Size 3 / 3S
Um
24kV
36kV
42kV
42 / 52kV
IN
250A
630A
800A
1250A
Cross Section *
70mm
240mm
400mm
800mm
11,9mm / 23,5mm
20,1mm / 31,5mm
22,3mm / 36,0mm
34,6mm / 46,0mm
(36,0**)mm
(44,0**) mm
(55,0**) mm
conductor /
insulation
*valid only, if values comply to max. diameter over insulation / max. diameter over conductor
**diameter applicable only without capacitive voltage tap
Andreas Dobler, Pfisterer
07.06.2013
Page 8
Size 4
Size 5-S
Size 6
Size 6-S
Um
72,5kV
145kV
170kV
245kV
IN
2500A
2500A
2500A
2500A
Cross Section *
1600mm
1600mm
2500mm
2500mm
50.4mm / 75mm
50.4mm / 76mm
64.9mm / 113.5mm
64.9mm / 113.5mm
conductor /
insulation
*valid only, if values comply to max. diameter over insulation / max. diameter over conductor
07.06.2013
Page 9
Solutions
- Lamellas
- Spring Contact
- Al- Elast
Source: MultiContact
Source: Pfisterer
Source: BalSeal
- Tulip Contact
Current Carrying Capability
- others
07.06.2013
Page 10
- Tension Cone
- Line contact via grooves
- Contact between Cone and Conductor
- Thrust Piece
- Mechanical fixation
- base component to allow disassembly
07.06.2013
Page 11
2. Geometrical grading
3. Capacitive grading
4. Refractive Grading
-
5. Resistive Grading
-
07.06.2013
Page 12
Description
Costs for
moulds
Usage
Main Disadvantage
Main Advantage
RTV
Room
Temperature
Vulcanizing
Low
Cable Accessories
- High level of
workmanship
- deflector has to be coated
LSR
Liquid Silicone
Rubber
High
Cable Accessories
Material of choice
HTV
High
Temperature
Vulcanizing
High
Insulators
highly automated
EPDM
Ethylene
Propylene Dien
Monomer
(rubber)
High
Cable Accessories
Dielectric Strength
07.06.2013
Page 13
FV
FF
spring force
FS
plug-in force
Dielectric Strength
07.06.2013
Page 14
07.06.2013
Page 15
Transformer
Testing: IEC 60137
Dimensions: EN 50299
Cable Termination
Testing: IEC 60840 bzw. IEC 62067
GIS
Testing: IEC 62271-203
Dimensions: IEC 62271-209
07.06.2013
Page 16
Visual Examination
Dimensional Examination
Material Test
X-Ray Test
Visual Examination
Sample Test
07.06.2013
Page 17
IEC 60137
07.06.2013
Page 18
07.06.2013
Page 19
07.06.2013
Page 20
connecting elements
Andreas Dobler, Pfisterer
07.06.2013
Page 21
Pluggable Bushing
only for
testing
07.06.2013
Page 22
Conventional type
Conventional
Dry Type
Very compact
Maintenance free
Page 23
07.06.2013
Page 24
07.06.2013
Page 25
Lightning Overvoltages
-
Cause:
Atmospheric discharge
Duration:
Magnitude:
> 5 Um
xs =
xs
BIL
1.15
Ures
s
vtw
vtw
Protective zone
m
Basic insulation level
kV
Safety factor
Protection level of the arrester
kV
Front steepness of the overvoltage
kV/s
(usually about 1000 kV/s)
Speed of travelling wave:
300 m/s on overhead line (speed of light c")
200 m/s in cables
07.06.2013
Page 26
GIS
Pluggable
AIS, Porcelain
AIS
Polymer Tube
AIS
Polymer Cage
07.06.2013
Page 27
Pluggable solid state insulated surge arresters for high voltage combine the advantages of
GIS arresters
(maximum electrical protection)
Pluggable technology
(easy connection/disconnnection)
07.06.2013
Page 28
07.06.2013
Page 29
Family owned
Overhead Lines
07.06.2013
Page 30
Thank You!
Contact details
Andreas Dobler
Produktmanager MV CONNEX
PFISTERER Kontaktsysteme GmbH
Rosenstr. 44
73650 Winterbach
Phone: +49 (0)7181 / 7005-340
mailto:andreas.dobler@pfisterer.de
http://www.pfisterer.de
07.06.2013