USERS MANUAL FOR 3 IN ONE CLEAN ROOM MONITOR

MODEL NO. AI-PRHT

TABLE OF CONTENTS

SR .NO

SUBJECTS

PAGE NO

1.

INTRODUCTION

2.

APPLICATION

3.

CLASSIC FEATURES

4.

TECHNICAL SPECIFICATIONS

5.

FRONT PANEL DESCRIPTION

6.

WIRING DIAGRAM

7.

FLOW CHART

Quality is not an act, it is a habit.

1. INTRODUCTION:The 3 in one clean room indicator is microcontroller based Transmitter and control instrument
for indicating process parameters like Humidity, Temperature & Differential Pressure. The
family includes besides the microcontroller based products as following :

MODEL

TYPE

OUTPUT

DIGI MAG-T

mm.W C

4-20 mA

DIGI MAG-T

mm.H g

4-20 mA

% RH/OC

4-20 mA,RS485

2 in 0ne

This instrument has been designed mainly to monitor very important process
parameters using integrated sensors for humidity, temperature & differential pressure.
Our instrument measuring ranges from 0 to 100% R.H. & 0 to 50 Deg. C customizable as
per customer & application requirements, where it is having 3 independent 4-20mA Outputs
one each for all 3 parameters of humidity, temperature, differential pressure.
The front panel operation has been specially designed for user friendly operations.
There are commands for directing mode settings, alarm settings and output settings.
The documentation presented here describes the front panel operation in detail. The
user is requested to go through this manual and simultaneously give commands on the panel of
the indicator. After initial difficulties the user will find that the front panel operations are quite
simple and easy.

Quality is not an act, it is a habit.

2. APPLICATION :1. HVAC System,


2. Cold Storehouse,
3. Factory,
4. Clean Room,
5. Warehouse,
6. Library,
7. Museum,
8. Office,
9. Machine Room And Labs.

3. CLASSIC FEATURES :1.


2.
3.
4.
5.
6.
7.

Measuring Range Humidity


Measuring Range Temperature
Measuring Range Differential Pressure
Accuracy Humidity
Accuracy Temperature
Accuracy Differential Pressure
Output

8. Resolution

:
:
:
:
:
:
:

0.0 to 99.9% R.H.


0.0 to 50.0 Deg. C
0 to 100 Pascals (or as per label)
+/- 1.8% R.H.
+/- 0.5 Deg. C
+/-0.5 % F.S.
Individual 4-20mA Output for all 3 Parameters of
Temperature, Humidity & Differential Pressure
: 0.1Deg.C for Temperature
0.1% R.H. for Humidity
1 Pascals for Differential Pressure.

Quality is not an act, it is a habit.

4. Technical Specifications :
1. Power Supply
2. Signal Output
3. Consumption
4. Electrical Connection

5.
6.
7.
8.

Working Temperature
Environment
Differential Pressure Connection
Cable Entry

: 12 V.D.C., Max. Load 500 Ohms


: 3 x 4-20mA Individual Output for Each Temperature,
Humidity & Differential Pressure
: 22mA
: 4 Pin Screw Terminal Block (Male/Female) for
Cables Dia 1.5 sq.mm. max. for Output 2 Pin Screw
Terminal Block for Power Supply 12 V.D.C.
: 0 to +50 Deg. C
: Air & Neutral Gases.
: 2 Nos. 4 mm. Hose Nipples at top
: 2 Nos. PG7 Rated Plastic Cable Gland.

5. FRONT PANEL DESCRIPTION :

Quality is not an act, it is a habit.

The front panel of the instruments consists of:


Display windows: - 3 Nos.
LEDs

: - 2 Nos.

Keys

: - 4 Nos.

a) DISPLAY WINDOW :
I.

DIFFERENTIAL PRESSURE WINDOW: It consists of 4 displays which indicate the


differential pressure value.

II.

HUMIDITY WINDOW: It consists of 3 displays which indicate the humidity value.

III.

TEMPERATURE WINDOW: It consists of 3 displays which indicate the temperature value.

b) L.E.DS:
This includes 2nos ON status of alarm 1 & alarm 2,indicates by L.E.Ds. steady indication
for low mode &and blinking indication for high mode.

6) WIRING DIAGRAM:
Output connection

1 2

Input connection factory fixed

dc supply

G- ground
T- temperature
RH- humidity
DP- differential pressure

Quality is not an act, it is a habit.

input signals

7) FLOW CHART:
1) FLOW CHART FOR INPUT TYPE ADJUSTMENT:-

Restart the device using RST switch


Continuously press
buttons combinedly.

Press SET key


Press
input

to select type of

Press SET key


Now it display ZERO
Press
input range

to adjust ZERO

Press SET key


Now it display SPAN
Press
input range

Quality is not an act, it is a habit.

to adjust SPAN

A
Press SET key
Now it display Dec 1
Press
to adjust decimal
point of input range.
Press SET key
Now it temp oc display will blink
Press
to adjust
TEMPERATURE value.
Press SET key
Now it humidity % R.H display will blink
Press
to adjust
HUMIDITY value.

Press SET key


Now it will go to NORMAL RUNNING MODE

Quality is not an act, it is a habit.

2) FLOW CHART FOR OUTPUT SETTINGS:-

Press SET key


continuously for 5 sec

Now it displays ALARM

Press
to adjust DIFFERENTIAL
PRESSURE OUTPUT SETTING value, it
displays ZERO.
Press
value.

to adjust ZERO

Press SET key


Now it display SPAN.
Press
value.

Quality is not an act, it is a habit.

to adjust SPAN

A
Press SET key
Now it display ZERO for HUMIDITY
Press
value.

to adjust ZERO

Press SET key


Now it display SPAN for HUMIDITY
Press
value.

to adjust SPAN

Press SET key


Now it display ZERO for TEMPERATURE
TEMPERATUREHUMIDITY
Press
value.

to adjust ZERO

Press SET key


Now it display SPAN for TEMPERATURE
Press
value.

to adjust SPAN

Press SET key , Now it display rt-t for output type


adjustment (4-20mA,0-20).
Press
type selection.

Quality is not an act, it is a habit.

to adjust OUTPUT

10

B
Press SET key , Now it display SCAL for UP & DOWN
adjustment.

Press
to adjust UP &
DOWN type selection.

Press SET key


Now it will go to NORMAL RUNNING MODE

3) FLOW CHART FOR CALIBRATION MODE FOR DIFFERENTIAL PRESSURE:-

Press

key

continuously for 5 sec


Now it displays SCAL
Press SET key
Now it display OFFSET for offset adjustment
TEMPERATUREHUMIDITY
Press
value.

Quality is not an act, it is a habit.

to adjust OFFSET

11

A
Press SET key
Now it display 0v for D.P zero range.
Feed in ovs open condition
(+) port open
Press SET key
Now it display 10v for D.P 10 v range.
Feed in 1ovs connecting pressure at
(+) port of the device (range) as required.
Press SET key
Now it display SCAL .
Press

key

Now it will go to NORMAL WORKING


MODE.

Quality is not an act, it is a habit.

12

4) FLOW CHART FOR ALARM SETTINGS:-

Press SET key


Continuously for 5 sec

Now it displays ALARM

Press SET key ,Now it display AL-1 ALARM 1


settings and second display pv will blink.

Press
to select pressure (pv),
humidity (Rh), temperature (tnp) type
of parameter for alarm indication.
Press SET key ,Now it display typH for ALARM
1 type HIGH or LOW selection.

Press
to select HIGH or
LOW Ttype of alarm indication.

Quality is not an act, it is a habit.

13

Press SET key ,Now it display -0.1 process


value.
Press
value.

to adjust ALARM

Press SET key ,Now it display HYST hystereisis


value.
Press
to adjust
HYSTERESIS value.
Press SET key ,Now it display LAT Y FOR LED
LATCHING SETUP.
Press
to ON and OFF the
led latch operation.
Press SET key ,Now it display AL-2 ALARM 2
settings and second display pv will blink.

Press
to select pressure (pv),
humidity (Rh), temperature (tnp) type
of parameter for alarm indication.

Quality is not an act, it is a habit.

14

C
Press SET key ,Now it display typH for ALARM
2 type HIGH or LOW selection.

Press
to select HIGH or
LOW Ttype of alarm indication.
Press SET key ,Now it display -0.1 process
value.
Press
value.

to adjust ALARM

Press SET key ,Now it display HYST hystereisis


value.
Press
to adjust
HYSTERESIS value.
Press SET key ,Now it display LAT Y FOR LED
LATCHING SETUP.
Press
to ON and OFF the
led latch operation.

Press

key

Now it will go to NORMAL WORKING


MODE.

Quality is not an act, it is a habit.

15

5) FLOW CHART FOR COMMUNICATION SETTINGS:Press SET key


Continuously for 5 sec

Now it displays ALARM

Press
for communication settings ,now it
displays Anbt ambient adjustment.
Press
value.

to adjust ambient

Press SET key ,Now it display SErL scroll mode.

Press SET key ,Now it display baud for


adjusting baud rate value.
Press
value.

Quality is not an act, it is a habit.

to adjust baud rate

16

A
Press SET key ,Now it display s Id for station id
adjusting .
Press
to adjust station id
value for communication.

Press

key

Now it will go to NORMAL WORKING


MODE.

For any technical assistance, please feel free to contact factory at the below
address

Manufactured By :

ACE INSTRUMENTS
(An ISO 9001-2008 Certified Company )
Plot No.77, Shaktipuram, Industrial Estate Kukatpally, Prashantinagar,
Hyderbad 500072 .Phones: +91-40-23078848, 32901226
Email: info@aceinstrumentshyd.com
Website: www.aceinstrumentshyd.com

Quality is not an act, it is a habit.