System :

Engine & Machinery Room

Spec.

xxx

By :

xxx

Client :

DMCR

Dwg. No.

xxx

Revision :

xxx

Design for Main Engines at Full Power


Reference to the ISO standard, ISO 8861:1998(E) Engine room ventilation in diesel engine ships
Site Data
Elevaltion:
Max. Outdoor Ambient Air (db):
Engine Room Max. Temperature:
Design Temperature Rise:
References :
Equipment Data
Propulsion Engine
Maker:
Model:
Rated Power:
Engine Speed:
Combusion Air Flow Rate (Max. Power):
Combustion Air Flow Rate (Idle):
Heat Rejected to Ambient (Max Power): ( 0)
ISO Heat Rejection to Ambient:
Quantity Operating:
Total Combustion Air Flow Rate for Operating Engines (Max Power):
Total Combustion Air Flow Rate for Operating Engines (Idle):
Total Heat Rejected for Operating Engines** (Max Power):

0
40
50
10

MTU
10V2000 M93
1120
2450
1.982
0.198
26.00
53.97
1
1.98
0.20
26.00

**NOTE: lower value between ISO and Manufacturer is selected in view of generally overstated
heat radiated values provided by engine manufacture
Generator Engine
Maker:
COELMO
Model:
4.4TW2GM
Rated Power:
103
Engine Speed:
1500
Combusion Air Flow Rate:
0.182
Heat Rejected to Ambient:
( 0)
0.00
ISO Heat Rejection to Ambient (see note 4):
10.16
Quantity Operating:
1
Total Combustion Air Flow Rate for Operating Engines:
0.182
Total Heat Rejected for Operating Engines**:
10.16

m
C
C
C

kW
rpm
m/s
m/s
kW
kW
m/s
m/s
kW

Generator
Generator
Generator
Generator
Generator

Engine
Engine
Engine
Engine
Engine

Pipe Diameter:
Pipe Length:
Pipe Heat Coeff.:
Exhaust Temp.:
Exhaust Heat:

Total Heat Rejected for all Exhaust Pipes:


Other
HPU
Switchgear
Gearbox
Transformers
Pumps
Total Miscellaneous Heat Rejected:

Total Heat Rejected

ft
F
F
F

4200.50
420.05
88790.00
184305.59

CFM
CFM
BTU/hr
BTU/hr

m/s
kW

386.30 CFM
34679.43 BTU/hr

mm
m
kW/m
C
kW

102.00
10.00
0.19
309.00
1.90

mm
m
kW/m
C
kW

138.12 HP

124.31 HP
18994.23 BTU/hr

1.16 ft
13.12 ft
932.00 F
3961.40 BTU/hr
0.33 ft
32.80 ft

10449.90 BTU/hr

0.00
0.00
0.00
3.00
4.00
7.00

kW
kW
kW
kW
kW
kW

0.00
0.00
0.00
10245.00
13660.00
23905.00

page 1 of 2

see note 5

total combined length


note 7
Maker data

total combined length


note 7

588.20 F
6488.50 BTU/hr

kW

kW

Maker data
Maker data

18994.23 BTU/hr

3.06

51.78

note 3
10% of full power
(Guess) / Maker data
see note 4

4200.50 CFM
420.05 CFM
88790.00 BTU/hr

386.30 CFM
0.00 BTU/hr
34679.43 BTU/hr

355.00
4.00
0.29
500.00
1.16

note 1
Engine can start to derate at 45C

1501.92 HP

kW
rpm
m/s
kW
kW

**NOTE: lower value between ISO and Manufacturer is selected in view of generally overstated
heat radiated values provided by engine manufacture
Generator
Maker:
COELMO
Model:
ECP34-1L4
Rated Power:
92.70
kW
Heat Rejected to Ambient:
5.56
kW
Quantity Operating:
1
Total Heat Rejected for Operating Generators
5.56
kW
Engine Exhaust Pipes
Propulsion Engine Pipe Diameter:
Propulsion Engine Pipe Length:
Propulsion Engine Pipe Heat Coeff.:
Propulsion Engine Exhaust Temp.:
Propulsion Engine Exhaust Heat:

0
104
122
50

176818.56

BTU/hr
BTU/hr
BTU/hr
BTU/hr
BTU/hr
BTU/hr

BTU/hr

note 6
note 6
note 6

Project:

80ft Aluminium Catamaran

Date:

xxx

Project #:

01-0171

Printed:

xxx

System :

Engine & Machinery Room

Spec.

xxx

By :

xxx

Client :

DMCR

Dwg. No.

xxx

Revision :

xxx

Cooling Air Required


Larger value to be selected:
ISO 8861:1998 (E) 5.1a_air flow required
ISO 8861:1998 (E) 5.1b_air flow required

4.58
4.93

m/s
m/s

9701.13 CFM
10442.64 CFM

Total Combustion Air Required (ME & MDG at Full Power):


Total Combustion Air Required (ME & MDG at Idle):

2.16
0.38

m/s
m/s

4586.79 CFM
806.35 CFM

Relief Air Required at Full Power:

2.76

m/s

5855.85 CFM

Relief Air Required at Idle:

4.55

m/s

9636.29 CFM

m/s

10442.64 CFM

Relief Air

Supply Fan Capacity


Quantity of Supply Fans:

Flow Rate of Each Supply Fan:

4.93

Open Area (minimum)


Supply air
No. of Open area

Supply air ( approx. 6 - 8 m/s)

0.82

m2

2
8.84 ft

Selected 6 m/s

m2

2
5.44 ft

Selected 9 m/s

Exhaust air
No. of Open area

Exhaust air ( approx. 8 - 12 m/s)

0.51

note 1

ISO 8861:1998(E) 4 - Design outdoor temperature 35C.

note 2

ISO 8861:1998(E) 4 - Maximum temperature rise 12.5C.

note 3

ISO 8861:1998(E) 5.2.2 - Estimate Q = P x mad/p

note 4

ISO 8861:1998(E) 7.1 - Estimate q = 0.396xP0.70

note 5

ISO 8861:1998(E) 6.5 - Estimate q = 6% of generator rated output.

note 6

ISO 8861:1998(E) 6.6 - Estimate q = 20% of total equipment rated power in space.

note 7

ISO 8861:1998(E) See Section 6.7

(reading graph: 4 stoke engine used T = 320 K, 2 stoke engine used T = 250 K)

Conversion Factors Used:


air density @ 35C, 70%rh, 101.3 kPa

P=

1.13 kg/m

ISO 8861:1998(E) 5.3

air specific heat

cp =

1.01 kJ/kg*K

ISO 8861:1998(E) 5.3

specific fuel consumption

mad =

0.0020 kg/kW*s

ISO 8861:1998(E) 5.2.2

boiler fuel consumption

mfs =

0.11 kg/kW*s

ISO 8861:1998(E) 5.2.4

boiler air consumption

maf =

15.70 kg/kg

convert kW to HP

1.34 HP/kW

convert kW to BTU/hr

3415 BTU/hr/kW

convert m/s to cfm

2119 m/s/cfm

convert m to ft

3.28 ft/m

convert Pa to "wg

0.004 "wg/Pa

page 2 of 2

ISO 8861:1998(E) 5.2.4