Teck 90 Armoured Power

OUTER JACKET

INSULATION

INNER JACKET

CONDUCTOR
SHIELD

Shielded One Conductor


90 MIL 100%/133% 5kV
TR-XLPE/PVC/AIA/PVC

TAPE

CONDUCTOR

CONCENTRIC COPPER
BOND CONDUCTOR

ARMOUR

SPECIFIC ATIONS

CONSTRUC T ION

CSA FT1 & FT4

Conductor: Bare copper Class B compact or compressed stranded

CSA C22.2 No. 131 & 174

Conductor Shield: Extruded thermoset semi-conducting shield

CSA C68.3

Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)

IEEE 383 & 1202 (70,000


BTU/hr) Flame Test

Insulation Shield: Extruded thermosetting semi-conducting shield

ICEA T-29-520 (210,000


BTU/hr) Vertical Flame Test

Ground (Bonding/Shield) Conductor: Stranded bare copper conductor

ICEA T-30-520 (70,000


BTU/hr) Vertical Flame Test

Armour: Aluminum Interlocked Armour (AIA)


Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), orange

*Refer to CE Code for details

Options: Other coloured outer jacket and constructions available upon request

HL
AWG Size
Part
Number

Insulation
Thickness
(in.)

Approximate
Diameter (Over)

Copper
Content

Net Weight
w/ Armour

Insul.
(in.)

Inner
Outer
Jacket Armour
Jacket
(in.)
(in.)
(in.)

LB/
MFT

KG/
KM

LB/
MFT

KG/
KM

0.090

0.390

0.680

0.900

0.990

144

214

510

770

0.090

0.430

0.720

0.940

1.030

224

333

590

0.090

0.490

0.780

1.030

1.120

302

449

750

0.090

0.520

0.810

1.000

1.150

406

604

870

19002-06-060

1/0

0.090

0.560

0.880

1.130

1.220

475

707

19002-07-060

2/0

0.090

0.600

0.920

1.170

1.260

562

19002-08-060

3/0

0.090

0.640

0.970

1.220

1.310

19002-09-060

4/0

0.090

0.700

1.020

1.270

1.360

19002-10-060

250

0.090

0.750

1.100

1.380

19002-12-060

350

0.090

0.850

1.240

19002-14-060

500

1/0

0.090

0.970

1.340

Cond.

Bond
Wire

19002-02-060

19002-03-060

19002-04-060

19002-05-060

Amp.
(40C
Ambient)

Recommended
Connector*
TMC2

TMC2X

112

3/3A

3/3A

880

148

3/3A

3/3A

1120

195

3/3A

3/3A

1300

225

4/4A

4/4A

1010

1500

260

4/4A

4/4A

836

1120

1670

299

4/4A

4/4A

709

1055

1300

1930

345

4/4A

4/4A

843

1255

1470

2180

400

5/5A

5/5A

1.480

1013

1508

1680

2500

444

5/5A

5/5A

1.520

1.620

1389

2067

2120

3150

549

6/6A

6/6A

1.620

1.720

1928

2869

2770

4130

688

6/6A

6/6A

19002-16-060

750

2/0

0.090

1.150

1.540

1.830

1.930

2820

4197

3780

5760

889

7/7A

7/7A

19002-17-060

1000

2/0

0.090

1.300

1.760

2.050

2.150

3607

5368

5010

7460

1061

8A

8A/8B

Note: A
 ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.

* See pages 30 & 31 for corresponding connector.


Non-ferrous connectors only.

| 15

CO N TR O L

Universal Toll Free Phone: 1.877.777.5776

MED IU M VOLTAGE
SH IEL D ED

Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)

Teck 90 Armoured Power


OUTER JACKET

INSULATION

INNER JACKET
TAPE

FILLERS

BOND
CONDUCTOR

Shielded Three Conductor


90 MIL 100%/133% 5kV
TR-XLPE/PVC/AIA/PVC

COPPER
TAPE

SPECIFIC ATIONS

CONSTRUC TION

CSA FT1 & FT4

Conductor: Bare copper Class B compact or compressed stranded

CSA C22.2 No. 131 & 174

Conductor Shield: Extruded thermoset semi-conducting shield

CSA C68.3

Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)

IEEE 383 & 1202 (70,000


BTU/hr) Flame Test

Insulation Shield: Extruded thermosetting semi-conducting shield

ICEA T-29-520 (210,000


BTU/hr) Vertical Flame Test

Ground (Bonding) Conductor: Stranded bare copper conductor

ICEA T-30-520 (70,000


BTU/hr) Vertical Flame Test

Armour: Aluminum Interlocked Armour (AIA)

Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)


Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), orange
Options: Galvanized Steel Interlocked Armour (GSIA)
Other coloured outer jacket and constructions available upon request
Helically applied 20% overlapped copper tape shield

HL
AWG Size
Part
Number
Cond.

Bond
Wire

Insulation
Thickness
(in.)

Approximate
Diameter (Over)

Copper
Content

Net Weight
w/ Armour

Insul.
(in.)

Inner
Outer
Jacket Armour
Jacket
(in.)
(in.)
(in.)

LB/
MFT

KG/
KM

LB/
MFT

KG/
KM

0.900

1.170

349

519

1120

1670

0.090

1.450

1.540

Amp.
(40C
Ambient)

93

Recommended
Connector*
TMC2

TMC2X

5/5A

5/5A

19008-03-060

0.090

0.430

1.260

1.540

1.630

503

749

1350

2010

122

6/6A

6/6A

19008-04-060

0.090

0.490

1.390

1.670

1.770

771

1147

1740

2590

159

6A/7

6A/7

19008-05-060

0.090

0.520

1.450

1.730

1.830

939

1397

1960

2920

184

7/7A

7/7A

19008-06-060

1/0

0.090

0.560

1.530

1.810

1.910

1148

1708

2290

3410

211

7/7A

7/7A

19008-07-060

2/0

0.090

0.600

1.620

1.910

2.010

141

2104

2620

3900

243

8A

8A/8B

19008-08-060

3/0

0.090

0.640

1.780

2.070

2.170

1798

2668

3210

4780

279

8A

8A/8B

19008-09-060

4/0

0.090

0.700

1.900

2.190

2.290

2212

3292

3720

5530

321

8A

8A/8B

19008-10-060

250

0.090

0.750

2.010

2.300

2.430

2583

3844

4300

6400

355

9/9A

9/9A/9B

19008-11-060

300

0.090

0.890

2.115

2.355

2.495

3058

4551

4980

7411

372

9/9A

9/9A/9B

19008-12-060

350

0.090

0.906

2.210

2.450

2.590

3569

5311

5638

8390

435

9/9A

9/9A/9B

19008-13-060

400

0.090

0.960

2.315

2.555

2.695

4054

6033

6202

9230

429

10/10A

10/10A

19008-14-060

500

0.090

0.970

2.480

2.770

2.900

4998

7438

7130

10610

536

10/10A

10/10A

19008-16-060

600

0.090

1.115

2.645

2.885

3.025

5991

8916

8471

12606

534

10/10A

10/10A

19008-20-060

750

0.090

1.150

2.980

3.270

3.420

7440

11072

10330

15370

668

11/11A

11/11A

19008-25-060

1000

0.090

1.300

3.310

3.600

3.750

9860

14674

13080

19460

768

12/12A

12/12A

Note: A
 ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.

CO N TR O L

MED IU M VOLTAGE
SH IEL D ED

CONDUCTOR

Metallic Shield: Helically applied 15% gapped copper tape

*Refer to CE Code for details

19008-02-060

CONDUCTOR
SHIELD

INSULATION
SHIELD

ARMOUR

16 |

Universal Toll Free Phone: 1.877.777.5776

* See pages 30 & 31 for corresponding connector.

Teck 90 Armoured Power


OUTER JACKET

INSULATION

INNER JACKET

CONDUCTOR
SHIELD

Shielded One Conductor


115 MIL 133% 5kV (aka 100% 8kV)
(Per AEIC)

TR-XLPE/PVC/AIA/PVC

TAPE

CONDUCTOR

CONCENTRIC COPPER
BOND CONDUCTOR

ARMOUR

SPECIFIC ATIONS

CONSTRUC TION

CSA FT1 & FT4

Conductor: Bare copper Class B compact or compressed stranded

CSA C22.2 No. 131 & 174

Conductor Shield: Extruded thermoset semi-conducting shield

CSA C68.3

Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)

IEEE 383 & 1202 (70,000


BTU/hr) Flame Test

Insulation Shield: Extruded thermosetting semi-conducting shield

ICEA T-29-520 (210,000


BTU/hr) Vertical Flame Test

Ground (Bonding/Shield) Conductor: Stranded bare copper conductor

ICEA T-30-520 (70,000


BTU/hr) Vertical Flame Test

Armour: Aluminum Interlocked Armour (AIA)


Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), orange

*Refer to CE Code for details

Options: Other coloured outer jacket and constructions available upon request

HL
AWG Size
Part
Number

Insulation
Thickness
(in.)

Approximate
Diameter (Over)

Copper
Content

Net Weight
w/ Armour

Insul.
(in.)

Inner
Outer
Jacket Armour
Jacket
(in.)
(in.)
(in.)

LB/
MFT

KG/
KM

LB/
MFT

KG/
KM

0.115

0.440

0.730

0.950

1.040

145

216

550

820

0.115

0.480

0.770

0.990

1.080

225

335

680

0.115

0.540

0.830

1.080

1.170

303

451

840

0.115

0.570

0.910

1.160

1.250

407

606

19012-06-060

1/0

0.115

0.610

0.940

1.190

1.280

453

19012-07-060

2/0

0.115

0.650

0.980

1.230

1.320

476

19012-08-060

3/0

0.115

0.700

1.030

1.310

1.400

19012-09-060

4/0

0.115

0.750

1.080

1.360

1.450

19012-10-060

250

0.115

0.800

1.160

1.440

19012-12-060

350

0.115

0.940

1.290

19012-14-060

500

1/0

0.115

1.020

1.410

Cond.

Bond
Wire

19012-02-060

19012-03-060

19012-04-060

19012-05-060

Amp.
(40C
Ambient)

Recommended
Connector*
TMC2

TMC2X

112

3/3A

3/3A

1010

148

3/3A

3/3A

1250

195

4/4A

4/4A

960

1430

225

4/4A

4/4A

674

1060

1570

260

4/4A

4/4A

708

1170

1740

299

4/4A

4/4A

563

838

1350

2000

345

5/5A

5/5A

710

1057

1520

2260

400

5/5A

5/5A

1.530

849

1263

1730

2580

444

5/5A

5/5A

1.570

1.670

1169

1740

2170

3230

549

6/6A

6/6A

1.690

1.790

1390

2069

2860

4260

688

6A/7

6A/7

19012-16-060

750

2/0

0.115

1.200

1.600

1.890

1.990

2821

4198

3940

5860

889

8/8A

8/8A/8B

19012-17-060

1000

2/0

0.115

1.350

1.810

2.100

2.200

3608

5369

5090

7570

1061

8A

8A/8B

Note: A
 ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.

* See pages 30 & 31 for corresponding connector.


Non-ferrous connectors only.

| 17

CO N TR O L

Universal Toll Free Phone: 1.877.777.5776

MED IU M VOLTAGE
SH IEL D ED

Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)

Teck 90 Armoured Power


OUTER JACKET

INSULATION

INNER JACKET
TAPE

FILLERS

BOND
CONDUCTOR

Shielded Three Conductor


115 MIL 133% 5kV (aka 100% 8kV)
(Per AEIC)

TR-XLPE/PVC/AIA/PVC

COPPER
TAPE

SPECIFIC ATIONS

CONSTRUC TION

CSA FT1 & FT4

Conductor: Bare copper Class B compact or compressed stranded

CSA C22.2 No. 131 & 174

Conductor Shield: Extruded thermoset semi-conducting shield

CSA C68.3

Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)

IEEE 383 & 1202 (70,000


BTU/hr) Flame Test

Insulation Shield: Extruded thermosetting semi-conducting shield

ICEA T-29-520 (210,000


BTU/hr) Vertical Flame Test

Ground (Bonding) Conductor: Stranded bare copper conductor

ICEA T-30-520 (70,000


BTU/hr) Vertical Flame Test

Armour: Aluminum Interlocked Armour (AIA)

CONDUCTOR

Metallic Shield: Helically applied 15% gapped copper tape


Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), orange

*Refer to CE Code for details

Options: G
 alvanized Steel Interlocked Armour (GSIA)
Other coloured outer jacket and constructions available upon request
Helically applied 20% overlapped copper tape shield

HL
AWG Size
Part
Number

Insulation
Thickness
(in.)

Approximate
Diameter (Over)

Copper
Content

Net Weight
w/ Armour

Amp.
(40C
Ambient)

Recommended
Connector*

Insul.
(in.)

Inner
Outer
Jacket Armour
Jacket
(in.)
(in.)
(in.)

LB/
MFT

KG/
KM

LB/
MFT

KG/
KM

0.115

0.480

1.370

1.650

1.750

505

752

1500

2230

122

0.115

0.540

1.500

1.780

1.880

744

1152

1930

2870

159

7/7A

7/7A

0.115

0.570

1.570

1.860

1.960

943

1403

2150

3200

184

7/7A

7/7A

0.115

0.610

1.650

1.940

2.040

1151

1713

2430

3620

211

8/8A

8/8A/8B

Cond.

Bond
Wire

19018-03-060

19018-04-060

19018-05-060

19018-06-060

1/0

TMC2

TMC2X

6/6A

6/6A

19018-07-060

2/0

0.115

0.650

1.800

2.090

2.190

1417

2109

2890

4300

243

8A

8A/8B

19018-08-060

3/0

0.115

0.700

1.900

2.190

2.290

1796

2673

3360

5000

279

8A

8A/8B

19018-09-060

4/0

0.115

0.750

2.010

2.300

2.430

2215

3296

3940

5860

321

9/9A

9/9A/9B

19018-10-060

250

0.115

0.800

2.130

2.420

2.550

2583

3844

4470

6650

355

9/9A

9/9A/9B

19018-11-060

300

0.115

0.920

2.225

2.465

2.605

3064

4560

5155

7671

372

9/9A

9/9A/9B

19018-12-060

350

0.115

0.940

2.430

2.720

2.850

3572

5316

5650

8400

435

10/10A

10/10A

19018-14-060

500

0.115

1.020

2.640

2.930

3.060

5004

7447

7440

11070

536

10/10A

10/10A

Note: A
 ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.

CO N TR O L

MED IU M VOLTAGE
SH IEL D ED

CONDUCTOR
SHIELD

INSULATION
SHIELD

ARMOUR

18 |

Universal Toll Free Phone: 1.877.777.5776

* See pages 30 & 31 for corresponding connector.

Teck 90 Armoured Power


OUTER JACKET

INSULATION

INNER JACKET
TAPE

FILLERS

BOND
CONDUCTOR

Shielded Three Conductor


140 MIL 133% 8kV
TR-XLPE/PVC/AIA/PVC

COPPER
TAPE

SPECIFIC ATIONS

CONSTRUC TION

CSA FT1 & FT4

Conductor: Bare copper Class B compact or compressed stranded

CSA C22.2 No. 131 & 174

Conductor Shield: Extruded thermoset semi-conducting shield

CSA C68.3

Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)

IEEE 383 & 1202 (70,000


BTU/hr) Flame Test

Insulation Shield: Extruded thermosetting semi-conducting shield

ICEA T-29-520 (210,000


BTU/hr) Vertical Flame Test

Ground (Bonding) Conductor: Stranded bare copper conductor

ICEA T-30-520 (70,000


BTU/hr) Vertical Flame Test

Armour: Aluminum Interlocked Armour (AIA)

Metallic Shield: Helically applied 15% gapped copper tape


Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black

*Refer to CE Code for details

Options: G
 alvanized Steel Interlocked Armour (GSIA)
Other coloured outer jacket and constructions available upon request
Helically applied 20% overlapped copper tape shield

HL
AWG Size
Part
Number

19014-01-012

CONDUCTOR

Cond.

Bond
Wire

Insulation
Thickness
(in.)

0.140

Approximate
Diameter (Over)

Copper
Content

Net Weight
w/ Armour

Insul.
(in.)

Inner
Outer
Jacket Armour
Jacket
(in.)
(in.)
(in.)

LB/
MFT

KG/
KM

LB/
MFT

KG/
KM

0.495

1.405

403

600

1434

2134

1.645

1.755

Amp.
(40C
Ambient)

93

Recommended
Connector*
TMC2

TMC2X

6A/7

6A/7

19014-04-012

0.140

0.535

1.490

1.730

1.840

513

763

1619

2409

122

6A/7

6A/7

19014-02-012

0.140

0.590

1.610

1.850

1.960

783

1165

2127

3165

159

7/7A

7/7A

19014-05-012

0.140

0.621

1.735

1.975

2.085

951

1415

2482

3694

184

8A

8A/8B

19014-06-012

1/0

0.140

0.658

1.815

2.055

2.165

1160

1726

2769

4121

211

8A

8A/8B

19014-07-012

2/0

0.140

0.702

1.910

2.150

2.260

1426

2122

3137

4668

243

8A

8A/8B

19014-08-012

3/0

0.140

0.749

2.010

2.250

2.390

1759

2618

3679

5475

279

9/9A

9/9A/9B

19014-09-012

4/0

0.140

0.801

2.125

2.365

2.505

2226

3313

4258

6337

321

9/9A

9/9A/9B

19014-10-012

250

0.140

0.643

2.215

2.455

2.595

2595

3862

4716

7018

355

9A

9A/9B

19014-13-012

300

0.140

0.896

2.325

2.570

2.710

3069

4567

5330

7932

372

10/10A

10/10A

19014-11-012

350

0.140

0.940

2.425

2.665

2.810

3583

5332

5977

8895

435

10/10A

10/10A

19014-14-012

400

0.140

0.985

2.520

2.760

2.900

4065

6049

6551

9749

429

10/10A

10/10A

19014-12-012

500

0.140

1.065

2.685

2.925

3.065

4935

7344

7590

11295

536

10/10A

10/10A

19014-15-012

600

0.140

1.140

2.920

3.160

3.330

6001

8390

9143

13606

534

11/11A

11/11A

19014-16-012

750

0.140

1.235

3.125

3.365

3.535

7438

11069

10891

16208

668

11/11A

11/11A

19014-17-012

1000

0.140

1.385

3.455

3.695

3.865

9868

14685

13765

20485

768

12/12A

12/12A

Note: A
 ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.

* See pages 30 & 31 for corresponding connector.

| 19

CO N TR O L

Universal Toll Free Phone: 1.877.777.5776

MED IU M VOLTAGE
SH IEL D ED

CONDUCTOR
SHIELD

INSULATION
SHIELD

ARMOUR

Teck 90 Armoured Power


OUTER JACKET

INSULATION
SHIELD

INNER JACKET

CONDUCTOR
SHIELD

Shielded One Conductor


220 MIL 133% 15kV
TR-XLPE/PVC/AIA/PVC

TAPE

SPECIFIC ATIONS

CONSTRUC TION

CSA FT1 & FT4

Conductor: Bare copper Class B compact or compressed stranded

CSA C22.2 No. 131 & 174

Conductor Shield: Extruded thermoset semi-conducting shield

CSA C68.3

Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)

IEEE 383 & 1202 (70,000


BTU/hr) Flame Test

Insulation Shield: Extruded thermosetting semi-conducting shield

ICEA T-29-520 (210,000


BTU/hr) Vertical Flame Test

Ground (Bonding/Shield) Conductor: Stranded bare copper conductor

ICEA T-30-520 (70,000


BTU/hr) Vertical Flame Test

Armour: Aluminum Interlocked Armour (AIA)

Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), red

*Refer to CE Code for details

Options: Other coloured outer jacket and constructions available upon request

AWG Size
Part
Number

19020-04-032

CONDUCTOR

Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)

HL

Cond.

Bond
Wire

Insulation
Thickness
(in.)

0.220

Approximate
Diameter (Over)

Copper
Content

Net Weight
w/ Armour

Insul.
(in.)

Inner
Outer
Jacket Armour
Jacket
(in.)
(in.)
(in.)

LB/
MFT

KG/
KM

LB/
MFT

KG/
KM

0.760

1.090

286

426

1028

1530

1.340

1.430

Amp.
(40C
Ambient)

195

Recommended
Connector*
TMC2

TMC2X

5/5A

5/5A

19020-05-032

0.220

0.790

1.120

1.370

1.460

391

582

1170

1740

225

5/5A

5/5A

19020-06-032

1/0

0.220

0.830

1.160

1.410

1.500

459

683

1270

1890

259

5/5A

5/5A

19020-07-032

2/0

0.220

0.860

1.200

1.450

1.540

546

813

1390

2060

298

5/5A

5/5A

19020-08-032

3/0

0.220

0.910

1.250

1.500

1.590

693

1031

1570

2340

343

5/5A

5/5A

19020-09-032

4/0

0.220

0.960

1.300

1.580

1.680

830

1235

1780

2650

397

6/6A

6/6A

19020-10-032

250

0.220

1.020

1.380

1.660

1.760

989

1472

2010

2990

440

6A/7

6A/7

19020-11-032

350

0.220

1.120

1.500

1.780

1.880

1228

1827

2490

3700

543

7/7A

7/7A

19020-12-032

500

1/0

0.220

1.240

1.650

1.940

2.040

1896

2821

3220

4790

678

8/8A

8/8A/8B

19022-12-032

750

2/0

0.220

1.420

1.890

2.180

2.280

2766

4116

4390

6530

872

8A

8A/8B

19022-25-032

1000

2/0

0.220

1.570

2.050

2.340

2.480

3552

5286

5550

8260

1040

9/9A

9/9A/9B

Note: A
 ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.

CO N TR O L

MED IU M VOLTAGE
SH IEL D ED

INSULATION

CONCENTRIC COPPER
BOND CONDUCTOR

ARMOUR

20 |

Universal Toll Free Phone: 1.877.777.5776

* See pages 30 & 31 for corresponding connector.


Non-ferrous connectors only.

Teck 90 Armoured Power


OUTER JACKET

INSULATION

INNER JACKET
TAPE

FILLERS

BOND
CONDUCTOR

Shielded Three Conductor


220 MIL 133% 15kV
TR-XLPE/PVC/AIA/PVC

COPPER
TAPE

SPECIFIC ATIONS

CONSTRUC TION

CSA FT1 & FT4

Conductor: Bare copper Class B compact or compressed stranded

CSA C22.2 No. 131 & 174

Conductor Shield: Extruded thermoset semi-conducting shield

CSA C68.3

Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)

IEEE 383 & 1202 (70,000


BTU/hr) Flame Test

Insulation Shield: Extruded thermosetting semi-conducting shield

ICEA T-29-520 (210,000


BTU/hr) Vertical Flame Test

Ground (Bonding) Conductor: Stranded bare copper conductor

ICEA T-30-520 (70,000


BTU/hr) Vertical Flame Test

Armour: Aluminum Interlocked Armour (AIA)

Metallic Shield: Helically applied 15% gapped copper tape


Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), red

*Refer to CE Code for details

Options: G
 alvanized Steel Interlocked Armour (GSIA)
Other coloured outer jacket and constructions available upon request
Helically applied 20% overlapped copper tape shield

HL
AWG Size
Part
Number

19022-01-032

CONDUCTOR

Cond.

Bond
Wire

Insulation
Thickness
(in.)

0.220

Approximate
Diameter (Over)

Copper
Content

Net Weight
w/ Armour

Insul.
(in.)

Inner
Outer
Jacket Armour
Jacket
(in.)
(in.)
(in.)

LB/
MFT

KG/
KM

LB/
MFT

KG/
KM

0.760

2.020

793

1180

2665

3966

2.310

2.430

Amp.
(40C
Ambient)

164

Recommended
Connector*
TMC2

TMC2X

9/9A

9/9A/9B

19022-02-032

0.220

0.790

2.100

2.370

2.490

964

1435

3089

4597

187

9/9A

9/9A/9B

19022-03-032

1/0

0.220

0.830

2.170

2.460

2.580

1175

1749

3300

4900

215

9/9A

9/9A/9B

19022-04-032

2/0

0.220

0.860

2.260

2.550

2.670

1438

2140

3650

5430

246

9/9A

9/9A/9B

19022-05-032

3/0

0.220

0.910

2.360

2.650

2.770

1821

2710

4140

6160

283

10/10A

10/10A

19022-06-032

4/0

0.220

0.960

2.470

2.760

2.880

2248

3345

4680

6960

325

10/10A

10/10A

19022-07-032

250

0.220

1.020

2.590

2.880

3.000

2607

3880

5275

7850

359

10/10A

10/10A

19022-08-032

350

0.220

1.120

2.900

3.190

3.330

3597

5353

6842

10181

438

11/11A

11/11A

19022-11-032

500

0.220

1.240

3.160

3.450

3.590

5022

7474

8513

12668

536

11/11A

11/11A

19022-16-032

750

0.220

1.420

3.570

3.850

4.000

7452

11090

11507

17122

669

12/12A

12/12A

Note: A
 ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.

* See pages 30 & 31 for corresponding connector.

| 21

CO N TR O L

Universal Toll Free Phone: 1.877.777.5776

MED IU M VOLTAGE
SH IEL D ED

CONDUCTOR
SHIELD

INSULATION
SHIELD

ARMOUR

Teck 90 Armoured Power


OUTER JACKET

INNER JACKET

INSULATION
SHIELD
CONDUCTOR
SHIELD

Shielded Single Conductor


320 MIL 133% 25kV
TR-XLPE/PVC/AIA/PVC

TAPE

SPECIFIC ATIONS

CONSTRUC TION

CSA FT1 & FT4

Conductor: Bare copper Class B compact or compressed stranded

CSA C22.2 No. 131 & 174

Conductor Shield: Extruded thermoset semi-conducting shield

CSA C68.3

Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)

IEEE 383 & 1202 (70,000


BTU/hr) Flame Test

Insulation Shield: Extruded thermosetting semi-conducting shield

ICEA T-29-520 (210,000


BTU/hr) Vertical Flame Test

Ground (Bonding/Shield) Conductor: Stranded bare copper conductor

ICEA T-30-520 (70,000


BTU/hr) Vertical Flame Test

Armour: Aluminum Interlocked Armour (AIA)

Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black

*Refer to CE Code for details

Options: Other coloured outer jacket and constructions available upon request

AWG Size
Part
Number

19023-02-012

CONDUCTOR

Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)

HL

Cond.

Bond
Wire

Insulation
Thickness
(in.)

0.320

Approximate
Diameter (Over)

Copper
Content

Net Weight
w/ Armour

Insul.
(in.)

Inner
Outer
Jacket Armour
Jacket
(in.)
(in.)
(in.)

LB/
MFT

KG/
KM

LB/
MFT

KG/
KM

0.990

1.365

385

573

1386

2063

1.605

1.715

Amp.
(40C
Ambient)

164

Recommended
Connector*
TMC2

TMC2X

6/6A

6/6A

19023-03-012

1/0

0.320

1.026

1.415

1.655

1.765

453

674

1568

2333

187

6A/7

6A/7

19023-04-012

2/0

0.320

1.066

1.455

1.695

1.805

538

801

1634

2432

215

7/7A

7/7A

19023-05-012

3/0

0.320

1.113

1.490

1.730

1.840

685

1019

1970

2932

246

7/7A

7/7A

19023-06-012

4/0

0.320

1.185

1.560

1.800

1.910

818

1217

2136

3179

283

7/7A

7/7A

19023-08-012

250

0.320

1.218

1.640

1.880

1.990

974

1449

2366

3521

325

8/8A

8/8A/8B

19023-10-012

350

0.320

1.315

1.800

2.040

2.150

1343

1999

2966

4414

359

8A

8A/8B

19023-12-012

500

1/0

0.320

1.454

1.940

2.180

2.290

1866

2777

3654

5438

438

8A

8A/8B

19023-14-012

750

2/0

0.320

1.620

2.105

2.350

2.485

2642

3932

4677

6960

536

9/9A

9/9A/9B

19023-15-012

1000

3/0

0.320

1.770

2.235

2.475

2.615

3491

5195

5665

8430

669

9/9A

9/9A/9B

Note: A
 ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.

CO N TR O L

MED IU M VOLTAGE
SH IEL D ED

INSULATION

CONCENTRIC COPPER
BOND CONDUCTOR

ARMOUR

22 |

Universal Toll Free Phone: 1.877.777.5776

* See pages 30 & 31 for corresponding connector.


Non-ferrous connectors only.

Teck 90 Armoured Power


OUTER JACKET

INSULATION

INNER JACKET
TAPE

FILLERS

BOND
CONDUCTOR

Shielded Three Conductor


320 MIL 133% 25kV
TR-XLPE/PVC/AIA/PVC

COPPER
TAPE

SPECIFIC ATIONS

CONSTRUC TION

CSA FT1 & FT4

Conductor: Bare copper Class B compact or compressed stranded

CSA C22.2 No. 131 & 174

Conductor Shield: Extruded thermoset semi-conducting shield

CSA C68.3

Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)

IEEE 383 & 1202 (70,000


BTU/hr) Flame Test

Insulation Shield: Extruded thermosetting semi-conducting shield

ICEA T-29-520 (210,000


BTU/hr) Vertical Flame Test

Ground (Bonding) Conductor: Stranded bare copper conductor

ICEA T-30-520 (70,000


BTU/hr) Vertical Flame Test

Armour: Aluminum Interlocked Armour (AIA)

Metallic Shield: Helically applied 15% gapped copper tape


Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black

*Refer to CE Code for details

Options: Galvanized Steel Interlocked Armour (GSIA)


Other coloured outer jacket and constructions available upon request
Helically applied 20% overlapped copper tape shield

HL
AWG Size
Part
Number

19026-02-012

CONDUCTOR

Cond.

Bond
Wire

Insulation
Thickness
(in.)

0.320

Approximate
Diameter (Over)

Copper
Content

Net Weight
w/ Armour

Insul.
(in.)

Inner
Outer
Jacket Armour
Jacket
(in.)
(in.)
(in.)

LB/
MFT

KG/
KM

LB/
MFT

KG/
KM

0.990

2.530

985

1466

3690

5490

2.820

2.940

Amp.
(40C
Ambient)

187

Recommended
Connector*
TMC2

TMC2X

10/10A

10/10A

19026-03-012

1/0

0.320

1.030

2.650

2.940

3.060

1193

1775

4110

6120

215

10/10A

10/10A

19026-06-012

2/0

0.320

1.070

2.740

3.030

3.150

1460

2173

4490

6680

246

10/10A

10/10A

19026-04-012

3/0

0.320

1.120

2.910

3.190

3.330

1842

2741

5270

7840

283

11/11A

11/11A

19026-05-012

4/0

0.320

1.170

3.020

3.310

3.440

2261

3365

5840

8700

325

11/11A

11/11A

19026-08-012

250

0.320

1.220

3.150

3.430

3.580

2629

3912

6440

9590

359

11/11A

11/11A

19026-11-012

350

0.320

1.370

3.440

3.730

3.880

3615

5380

7720

11490

438

12/12A

12/12A

19026-12-012

500

0.320

1.454

3.625

3.865

4.035

5096

7584

9943

14797

536

12/12A

12/12A

Note: A
 ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.

* See pages 30 & 31 for corresponding connector.

| 23

CO N TR O L

Universal Toll Free Phone: 1.877.777.5776

MED IU M VOLTAGE
SH IEL D ED

CONDUCTOR
SHIELD

INSULATION
SHIELD

ARMOUR

Teck 90 Armoured Power


OUTER JACKET

INNER JACKET

INSULATION
SHIELD
CONDUCTOR
SHIELD

Shielded Single Conductor


345 MIL 133% 28kV
TR-XLPE/PVC/AIA/PVC

TAPE

SPECIFIC ATIONS

CONSTRUC TION

CSA FT1 & FT4

Conductor: Bare copper Class B compact or compressed stranded

CSA C22.2 No. 131 & 174

Conductor Shield: Extruded thermoset semi-conducting shield

CSA C68.3

Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)

IEEE 383 & 1202 (70,000


BTU/hr) Flame Test

Insulation Shield: Extruded thermosetting semi-conducting shield

ICEA T-29-520 (210,000


BTU/hr) Vertical Flame Test

Ground (Bonding/Shield) Conductor: Stranded bare copper conductor

ICEA T-30-520 (70,000


BTU/hr) Vertical Flame Test

Armour: Aluminum Interlocked Armour (AIA)

Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black

*Refer to CE Code for details

Options: Other coloured outer jacket and constructions available upon request

AWG Size
Part
Number

19031-02-012

CONDUCTOR

Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)

HL

Cond.

Bond
Wire

Insulation
Thickness
(in.)

0.345

Approximate
Diameter (Over)

Copper
Content

Net Weight
w/ Armour

Insul.
(in.)

Inner
Outer
Jacket Armour
Jacket
(in.)
(in.)
(in.)

LB/
MFT

KG/
KM

LB/
MFT

KG/
KM

1.035

1.385

387

576

2477

3686

1.625

1.735

Amp.
(40C
Ambient)

140

Recommended
Connector*
TMC2
6A/7

TMC2X
6A/7

19031-03-012

1/0

0.345

1.076

1.465

1.705

1.815

453

674

1565

2329

159

6A/7

6A/7

19031-04-012

2/0

0.345

1.116

1.505

1.745

1.855

538

801

1841

2740

181

7/7A

7/7A

19031-05-012

3/0

0.345

1.160

1.525

1.765

1.875

678

1009

1982

2950

205

7/7A

7/7A

19031-06-012

4/0

0.345

1.215

1.605

1.845

1.955

818

1217

2204

3280

232

7/7A

7/7A

19031-08-012

250

0.345

1.255

1.645

1.885

1.995

975

1451

2397

3567

253

8A

8A/8B

19031-10-012

350

0.345

1.365

1.850

2.090

2.200

1343

1999

3058

4551

302

8A

8A/8B

19031-12-012

500

1/0

0.345

1.506

1.990

2.230

2.340

1868

2780

3729

5549

360

9/9A

9/9A/9B

19031-14-012

750

2/0

0.345

1.620

2.105

2.345

2.485

2723

4052

4758

7081

434

9/9A

9/9A/9B

19031-15-012

1000

2/0

0.345

1.810

2.280

2.520

2.660

3491

5195

5740

8542

486

9/9A

9/9A/9B

Note: A
 ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.

CO N TR O L

MED IU M VOLTAGE
SH IEL D ED

INSULATION

CONCENTRIC COPPER
BOND CONDUCTOR

ARMOUR

24 |

Universal Toll Free Phone: 1.877.777.5776

* See pages 30 & 31 for corresponding connector.


Non-ferrous connectors only.

Teck 90 Armoured Power


OUTER JACKET

INSULATION

INNER JACKET
TAPE

FILLERS

BOND
CONDUCTOR

Shielded Three Conductor


345 MIL 133% 28kV
TR-XLPE/PVC/AIA/PVC

COPPER
TAPE

SPECIFIC ATIONS

CONSTRUC TION

CSA FT1 & FT4

Conductor: Bare copper Class B compact or compressed stranded

CSA C22.2 No. 131 & 174

Conductor Shield: Extruded thermoset semi-conducting shield

CSA C68.3

Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)

IEEE 383 & 1202 (70,000


BTU/hr) Flame Test

Insulation Shield: Extruded thermosetting semi-conducting shield

ICEA T-29-520 (210,000


BTU/hr) Vertical Flame Test

Ground (Bonding) Conductor: Stranded bare copper conductor

ICEA T-30-520 (70,000


BTU/hr) Vertical Flame Test

Armour: Aluminum Interlocked Armour (AIA)

CONDUCTOR

Metallic Shield: Helically applied 15% gapped copper tape


Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black

*Refer to CE Code for details

Options: G
 alvanized Steel Interlocked Armour (GSIA)
Other coloured outer jacket and constructions available upon request
Helically applied 20% overlapped copper tape shield

HL
AWG Size
Part
Number

Insulation
Thickness
(in.)

Approximate
Diameter (Over)

Copper
Content

Net Weight
w/ Armour

Insul.
(in.)

Inner
Outer
Jacket Armour
Jacket
(in.)
(in.)
(in.)

LB/
MFT

KG/
KM

LB/
MFT

KG/
KM

0.345

1.040

2.680

2.970

3.100

988

1470

3980

5930

0.345

1.080

2.760

3.050

3.180

1200

1786

4360

0.345

1.120

2.920

3.210

3.360

1466

2182

4950

3/0

0.345

1.170

3.020

3.310

3.460

1848

2750

19027-05-012

4/0

0.345

1.220

3.140

3.430

3.580

2264

19027-06-012

250

0.345

1.270

3.260

3.550

3.700

19027-08-012

350

0.345

1.420

3.560

3.850

4.000

19027-10-012

500

0.345

1.506

3.740

3.900

4.150

Cond.

Bond
Wire

19027-01-012

19027-02-012

1/0

19027-03-012

2/0

19027-04-012

Note: A
 ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.

Amp.
(40C
Ambient)

Recommended
Connector*
TMC2

TMC2X

187

10/10A

10/10A

6490

215

10/10A

10/10A

7370

246

11/11A

11/11A

5490

8160

283

11/11A

11/11A

3369

6090

9060

325

11/11A

11/11A

2635

3921

6660

9910

359

11/11A

11/11A

3621

5389

7960

11840

438

12/12A

12/12A

2893

3980

8008

11917

536

12/12A

12/12A

* See pages 30 & 31 for corresponding connector.

| 25

CO N TR O L

Universal Toll Free Phone: 1.877.777.5776

MED IU M VOLTAGE
SH IEL D ED

CONDUCTOR
SHIELD

INSULATION
SHIELD

ARMOUR

Teck 90 Armoured Power


OUTER JACKET

INNER JACKET

INSULATION
SHIELD
CONDUCTOR
SHIELD

Shielded One Conductor


345 MIL 100% 35kV
TR-XLPE/PVC/AIA/PVC

TAPE

SPECIFIC ATIONS

CONSTRUC TION

CSA FT1 & FT4

Conductor: Bare copper Class B compact or compressed stranded

CSA C22.2 No. 131 & 174

Conductor Shield: Extruded thermoset semi-conducting shield

CSA C68.3

Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)

IEEE 383 & 1202 (70,000


BTU/hr) Flame Test

Insulation Shield: Extruded thermosetting semi-conducting shield

ICEA T-29-520 (210,000


BTU/hr) Vertical Flame Test

Ground (Bonding/Shield) Conductor: Stranded bare copper conductor

ICEA T-30-520 (70,000


BTU/hr) Vertical Flame Test

Armour: Aluminum Interlocked Armour (AIA)

Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black

*Refer to CE Code for details

Options: Other coloured outer jacket and constructions available upon request

AWG Size
Part
Number

19030-02-010

CONDUCTOR

Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)

HL

Cond.

Bond
Wire

1/0

Insulation
Thickness
(in.)

0.345

Approximate
Diameter (Over)

Copper
Content

Net Weight
w/ Armour

Insul.
(in.)

Inner
Outer
Jacket Armour
Jacket
(in.)
(in.)
(in.)

LB/
MFT

KG/
KM

LB/
MFT

KG/
KM

1.076

1.465

453

674

1565

2329

1.705

1.815

Amp.
(40C
Ambient)

159

Recommended
Connector*
TMC2

TMC2X

6A/7

6A/7

19030-03-010

2/0

0.345

1.116

1.505

1.745

1.885

538

801

1841

2740

181

7/7A

7/7A

19030-04-010

3/0

0.345

1.160

1.525

1.765

1.875

678

1009

1982

2950

205

7/7A

7/7A

19030-05-010

4/0

0.345

1.215

1.605

1.845

1.955

818

1217

2204

3280

232

7/7A

7/7A

19030-06-010

250

0.345

1.255

1.645

1.885

1.995

975

1451

2397

3567

253

8/8A

8/8A/8B

19030-08-010

350

0.345

1.365

1.850

2.090

2.200

1343

1999

3058

45511

302

8A

8A/8B

19030-10-010

500

1/0

0.345

1.506

1.990

2.230

2.340

1868

2780

3729

5549

360

9/9A

9/9A/9B

19030-12-010

750

2/0

0.345

1.620

2.105

2.345

2.485

2723

4052

4758

7081

434

9/9A

9/9A/9B

19030-15-010

1000

2/0

0.345

1.810

2.280

2.520

2.660

3491

5195

5740

8542

486

9/9A

9/9A/9B

Note: A
 ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.

CO N TR O L

MED IU M VOLTAGE
SH IEL D ED

INSULATION

CONCENTRIC COPPER
BOND CONDUCTOR

ARMOUR

26 |

Universal Toll Free Phone: 1.877.777.5776

* See pages 30 & 31 for corresponding connector.


Non-ferrous connectors only.

Teck 90 Armoured Power


OUTER JACKET

INSULATION

INNER JACKET
TAPE

FILLERS

BOND
CONDUCTOR

Shielded Three Conductor


345 MIL 100% 35kV
TR-XLPE/PVC/AIA/PVC

COPPER
TAPE

SPECIFIC ATIONS

CONSTRUC TION

CSA FT1 & FT4

Conductor: Bare copper Class B compact or compressed stranded

CSA C22.2 No. 131 & 174

Conductor Shield: Extruded thermoset semi-conducting shield

CSA C68.3

Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)

IEEE 383 & 1202 (70,000


BTU/hr) Flame Test

Insulation Shield: Extruded thermosetting semi-conducting shield

ICEA T-29-520 (210,000


BTU/hr) Vertical Flame Test

Ground (Bonding) Conductor: Stranded bare copper conductor

ICEA T-30-520 (70,000


BTU/hr) Vertical Flame Test

Armour: Aluminum Interlocked Armour (AIA)

CONDUCTOR

Metallic Shield: Helically applied 15% gapped copper tape


Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black

*Refer to CE Code for details

Options: G
 alvanized Steel Interlocked Armour (GSIA)
Other coloured outer jacket and constructions available upon request
Helically applied 20% overlapped copper tape shield

HL
AWG Size
Part
Number

Insulation
Thickness
(in.)

Approximate
Diameter (Over)

Copper
Content

Insul.
(in.)

Inner
Outer
Jacket Armour
Jacket
(in.)
(in.)
(in.)

0.345

1.080

2.760

3.050

0.345

1.120

2.920

0.345

1.170

3.020

4/0

0.345

1.220

19028-06-010

250

0.345

19028-08-010

350

19028-11-010

500

Cond.

Bond
Wire

19028-02-010

1/0

19028-03-010

2/0

19028-04-010

3/0

19028-05-010

Net Weight
w/ Armour

LB/
MFT

KG/
KM

LB/
MFT

KG/
KM

3.180

1200

1786

4360

6488

3.210

3.360

1466

2182

4950

3.310

3.460

1848

2750

5490

3.140

3.430

3.580

2264

3369

1.270

3.260

3.550

3.700

2635

0.345

1.420

3.560

3.850

4.000

0.345

1.510

3.740

3.980

4.250

Note: A
 ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.

Amp.
(40C
Ambient)

Recommended
Connector*
TMC2

TMC2X

215

10/10A

10/10A

7366

246

11/11A

11/11A

8170

283

11/11A

11/11A

6090

9063

325

11/11A

11/11A

3921

6660

9911

359

11/11A

11/11A

3621

5389

7960

11846

438

12/12A

12/12A

2893

4305

8006

11914

536

12/12A

12/12A

* See pages 30 & 31 for corresponding connector.