102 Capacity
a. The electrical power available shall be sufficient to supply all services essential for safety
in an emergency, due regard being paid to simultaneous operation of all services, also
taking into account starting currents and transitory nature of certain loads. (Interpretation
of SOLAS Ch. II-1/43.2)
b. Where the emergency source of electrical power is an accumulator battery it shall be
capable of carrying the emergency electrical load without recharging while maintaining
the voltage of the battery as required by A200. (Interpretation of SOLAS Ch. II1/43.3.2.1)
c. When non-emergency consumers are supplied by the emergency source of power, it shall
either be possible to supply all consumers simultaneously, or automatic disconnection of
non-emergency consumers upon start of the generator shall be arranged. The system shall
be so arranged that the largest consumer connected to the emergency power supply
system can be started at all times without overloading the generator unless automatically
disconnected upon start of the emergency generator. (Interpretation of SOLAS Ch. II1/43.5.5)
d. Starting air compressors, preheaters and lubrication oil pumps for the main engine or
auxiliary engines may be equipped for automatic disconnection from the emergency
switchboard. Such consumers necessary for starting from dead ship, if supplied from the
emergency source of power, shall be possible to connect manually at the emergency
switchboard also when the emergency generator is running. If they may cause
overloading of the emergency generator, warning signs shall be fitted also stating the load
of the consumers.
Ch.2 Sec.2 C
VHF radio installation required by Torremolinos Convention reg. IX/6(1)(a) and (b)
Internal communication equipment
Fire detecting system
Signals which may be required in an emergency
Navigation lights if solely electrical
Emergency lighting
of launching stations and overside of the vessel
in all alleyways, stairways and exits
in spaces containing machinery or the emergency source of power
in control station
in fish handling and fish processing space
Electrical driven emergency fire pump if any.
g.
If applicable:
The MF radio installation required by Torremolinos Convention IX/8(1)(a) and (b) and reg.
IX/9(1)(b) and (c)
The ship earth station required by Torremolinos Convention regulation IX/9(1)(a)
MF/HF radio installation required by Torremolinos Convention IX/9(2)(a) and (b) and reg.
IX/10(1).
Table C1 Services to be supplied by an emergency source and by a transitional source,
including required duration for main class
Ch.2 Sec.2 C
Ch.2 Sec.2 C
c. In normal operation, the emergency switchboard shall be supplied from the main
switchboard by an interconnecting feeder. This feeder shall be protected against overload
and short circuit at the main switchboard, and shall be disconnected automatically at the
emergency switchboard upon failure of the supply from the main source of electrical
power. (Interpretation of SOLAS Ch. II-1/43.5.4)
d. Where the emergency switchboard is arranged for the supply of power back to the main
distribution system, the interconnecting cable shall, at the emergency switchboard end, be
equipped with switchgear suitable for at least short circuit protection.
e. The emergency switchboard and emergency distribution boards shall not be considered as
part of the main distribution system, even though supplied from such during normal
operation.
f. Technical requirements for functionality and construction for main switchboards, apply to
emergency switchboards.
g. Provision shall be made for the periodic testing of the complete emergency system and
shall include the testing of automatic starting arrangements. (Interpretation of
SOLAS Ch. II-1/43.7)
h. No accumulator batteries, except the starting battery for the emergency generator prime
mover and control and monitoring for the emergency system, shall be installed in the
same space as the emergency switchboard. (Interpretation of SOLAS Ch. II-1/43.5.3)
i. Cables between equipment installed in the emergency generator room, shall be run inside
the boundary of the room. If, for exceptional reasons, it is accepted that cables passes this
boundary, fire resistant cable shall be used.
Ch.2 Sec.2
c. The battery source shall be able to operate, without recharging, while maintaining the
voltage of the battery throughout the discharge period as required by A200. The battery
capacity shall be sufficient to supply automatically, in case of failure of either the main or
the emergency source of electrical power, for the duration specified, at least the services
required by Table C1, if they depend upon an electrical source for their operation. See
notes to Table C1.
(Interpretation of SOLAS Ch. II-1/43.4)
Ch.2 Sec.2
Ch.2 Sec.2 C
Ch.2 Sec.2 C
303
Starting arrangements for emergency generating sets
a. An emergency generating set shall be capable of being readily started in its cold
condition at a temperature of 0C. If this is impracticable, or the vessel is intended for
operation at lower ambient temperatures, provisions shall be made for heating
arrangements to ensure ready starting of the generating sets. (Interpretation of SOLAS
Ch. II-1/44.1)
b. Emergency generating set shall be equipped with starting device with a stored energy
capability of at least three consecutive starts. A second source of energy shall be provided
for an additional three starts within 30 minutes, unless manual starting can be
demonstrated to be effective. One starting motor is sufficient. (Interpretation of SOLAS
Ch. II-1/44.2)
c. Stored energy for starting shall be maintained at all times, and shall be powered from the
emergency switchboard. All starting, charging and energy storing devices shall be located
in the emergency generator space. Compressed air starting systems may however be
maintained by the main or auxiliary compressed air system through a suitable non-return
valve fitted in the emergency generator space.
(Interpretation of SOLAS Ch. II-1/44.3)
d. If accumulator batteries are used for starting of the emergency generator prime mover,
every such prime mover shall have separate batteries that are not used for any purpose
other than the operation of the emergency generating set.
e. If the emergency generator set is equipped with an electronic governor, electronic AVR,
priming pumps or other auxiliaries dependent upon electric power supply for a successful
start, power supply to this equipment shall be in accordance with the requirements for
energy for starting.
Guidance note:
If the emergency generating set is arranged so as not to be automatically started, then manual starting may
be permissible, such as manual cranking, inertial starters, manually charged hydraulic accumulators, or
powder charge cartridges, where it can be demonstrated as being effective within 30 minutes.
When manual starting is not practicable, each emergency generating set may be equipped with starting
devices with a stored energy capability of at least three consecutive starts. A second source of energy may
be provided for three additional starts within 30 minutes. (Interpretation of SOLAS Ch. II-1/44.4)
---e-n-d---o-f---G-u-i-d-a-n-c-e---n-o-t-e---
Ch.2 Sec.2 C
b. To prevent the generator or its prime mover from becoming overloaded when used in
port, arrangements shall be provided to shed sufficient non-emergency loads to ensure its
continued safe operation.
c. The prime mover shall be arranged with fuel oil filters and lubrication oil filters,
monitoring equipment and protection devices as required for the prime mover for main
power generation and for unattended operation.
d. The fuel oil supply tank to the prime mover shall be provided with a low level alarm,
arranged at a level ensuring sufficient fuel oil capacity for the emergency services for the
required period.
e. Fire detectors shall be installed in the location where the emergency generator set and
emergency switchboard are installed.
f. Means shall be provided to readily change over to emergency operation.
g. Control, monitoring and supply circuits, for the purpose of the use of the emergency
generator in port shall be so arranged and protected that any electrical fault will not
influence the operation of the main and emergency services. When necessary for safe
operation, the emergency switchboard shall be fitted with switches to isolate the circuits.
h. Instructions shall be provided on board to ensure that when the vessel is under way all
control devices (e.g. valves, switches) are in a correct position for the independent
emergency operation of the emergency generator set and emergency switchboard. These
instructions are also to contain information on required fuel oil tank level, position of
harbour or sea mode switch if fitted, ventilation openings etc.