INTRODUCTION
The Energy Storage Device ESD 202 is used
where a station battery source is not available
to provide circuit breaker trip power. The ESD
202 converts ac bus voltage to dc and stores
enough energy to trip the circuit breaker (191
Vdc @ 9.1 Joules) one time for 12 seconds
after ac power has been interrupted.
WARNING!
To prevent personal injury or equipment
damage, only qualified technicians or
operators should install, operate, or
service this device.

INSTRUCTION MANUAL
FOR
ENERGY STORAGE DEVICE
Model: ESD 202
Part Number: 9 2905 00 100
HIGHLAND, IL 62249
THEORY OF OPERATION (Refer to the
Functional Block Diagram)
Power input to the ESD 202 is 240 Vac. This
input is rectified and used to charge the output
capacitor (C1) to approximately 340 Vdc. As
long as the ac input is applied, C1 continues
to be charged in this manner. The capacitor
will hold a charge of at least 9.1 Joules at 191
Vdc for at least 12 seconds after the ac power
is removed from the input.
HUMAN-MACHINE INTERFACE
The LED DS1 indicates that the ESD 202 is
operationally ready. DS1 illuminates when the
capacitor has the minimum charge of 150 Vdc
at 5.6 Joules The LED does not indicate
whether or not the ac input is being applied.

ELECTRICAL SPECIFICATIONS

INTERCONNECTION

Output Power:
191-339 Vdc
9.1 Joules minimum at 191 Vdc
21.6 Joules minimum at 295 Vdc
24.2 Joules minimum at 311 Vdc
28.7 Joules minimum at 339 Vdc
There will be at least 9.1 Joules at 191 Vdc,
12 seconds after removal of ac input voltage.

The device should be connected as shown in


the Interconnection Diagram.

Power Input:
Operating range: 208 to 240 V +10%, Single
phase, 50/60 Hz, Burden 10.0 VA maximum.
Power Dissipation:
2.0 Watts maximum continuous.
PHYSICAL SPECIFICATIONS
Operating Temperature:
-25 C (-13 F) to +65 C (+149 F).
Storage Temperature:
-40 C (-40 F) to +85 C (+185 F).
Vibration:
Withstands 2 Gs at 10 to 200 Hz in each of
three mutually perpendicular axes.
Shock:
Withstands 15 Gs in each of three mutually
perpendicular axes.
Dimensions
Refer to the Outline Drawing.
Weight:
0.55 lb. (0.25 kg) Net.
Meets CSA C22.2, Number 14, Industrial
Control Equipment.
Meets UL 508, Industrial Control Equipment.

Each breaker should be provided with its own


ESD 202. The use of a single ESD 202 to
provide a tripping output for more than one
breaker (or other device) is not recommended.
Such
configurations
should
only
be
considered when it can be demonstrated,
through
independent
testing,
that
combinations of breakers (or devices) can be
reliably operated from a single ESD 202.
OPERATION
When the ESD 202 is properly interconnected
and after 240 Vac input power has been
applied, the unit is operationally ready. The
illumination of the LED indicates that the unit
is charged and ready. No adjustments of any
type should be necessary.
NOTE
Read DISCHARGING paragraph before
working on unit.

Publication:
9 2905 00 990
1997, 1998, Basler Electric Co., Highland, IL 62249
First Printing January 1997
Revision: A
ECA: 16560

PHONE 618/654-2341

January 1998

FAX 618/654-2351

DISCHARGING
Since more than 300 Vdc can be present on the
ESD 202 output terminals, it is advisable to
discharge the storage capacitors if the unit is to
be worked on for any reason. The following
procedure can be used for discharging the
storage capacitor.
CAUTION
Lethal voltages are present. Qualified
persons should install, operate or
service this device.
1. Obtain a 470 ohm, 5 watt wirewound
resistor.
2. Connect a few inches of 14 AWG, 600 V,
insulated wire to each end of the resistor.
3. Remove ac power input from terminals 1
and 4.
4. To discharge the capacitors, CAREFULLY
touch one wire to Terminal #3 and the
other wire to Terminal #4. Hold the wires
on the terminals for at least 5 seconds.
5. Insure that the capacitors are discharged
by connecting a dc Voltmeter across
terminals 4(-) and 3(+).
REPAIRS
The ESD 202 is not field repairable. Should
the device require repairs, return it to the
factory for service.
FIELD SERVICE AND ADJUSTMENT
The ESD 202 has been completely checked at
the factory. If for any reason the unit fails to
operate properly, it should be returned to the
factory for repair and/or replacement.

Functional Block Diagram

Note: Numbers are in inches (millimeters)


Outline Diagram
Interconnection Diagram