You are on page 1of 3

PO No. XX/ABB/SPEC. No. 71 DT XX.01.

2015

Annexure B
GUARANTEED TECHNICAL PARTICULARS OF VACUUM INTERRUPTER
Type VG4-02 EQUIVALENT TO V-207 GB

Sr. no
1
1.1
2
3
4
5
6
6.1
7
8
9

Required Specification
Name of manufacturer
Frequency
ISS/IEC reference
Type of Interrupter
Rated Max.line to line voltage
Normal current Rating
Rated short time current with duration
Short circuit making current
Degree of vacuum Interrupter inside bottle
Impulse withstand Voltage
a)Contact resistance at min closing force

10

b)Contact resistance after opening

11
12
13
14
15
16

Capacitor Switching Capacity


Contact Stroke
Opening Speed and Closing Speed
Maximum Over travel during Opening
Max Contact Bounce duration
Min. Added contact force for rated short
circuit making current
Electrical Life at rated Normal Current
Electrical Life at Short Circuit current
Mechanical Life
Shelf Life
Interrupter Weight
Capability is withstand
a) Fault operation
b) Short Circuit Operation
Operating temperature []
Electromagnetic compatibility
Percentage D. C. component of Rated
S.C. Breaking Current

17
18
19
20
21
22

23
24
25

11

Specification offered by
supplier
ABB, Nashik
50/60 Hz
IEC60056
VG4 with Drop in arrangement
12kV
2500A
26.3kA for 3 sec
65.75KA
less 10-7 mbar
95kV Peak
less 30 micro ohms
1X106 mega Ohms at 25oC
and 35% RH
400A
8+/-1 mm
1.2 to 1.5 m/sec
2 mm
2 ms
2200N
30000
100
50000
30 Years
2.7 kg
Minimum 100
Minimum 100

-15 to 40
IEC 62271
50 %

PO No. XX/ABB/SPEC. No. 71 DT XX.01.2015

Annexure B
GUARANTEED TECHNICAL PARTICULARS OF VACUUM INTERRUPTER
Type VG4-04 EQUIVALENT TO V-207 MV

Sr. no
1
1.1
2
3
4
5
6
6.1
7
8
9

Required Specification
Name of manufacturer
Frequency
ISS/IEC reference
Type of Interrupter
Rated Max.line to line voltage
Normal current Rating
Rated short time current with duration
Short circuit making current
Degree of vacuum Interrupter inside bottle
Impulse withstand Voltage
a)Contact resistance at min closing force

10

b)Contact resistance after opening

11
12
13
14
15
16

Capacitor Switching Capacity


Contact Stroke
Opening Speed and Closing Speed
Maximum Over travel during Opening
Max Contact Bounce duration
Min. Added contact force for rated short
circuit making current
Electrical Life at rated Normal Current
Electrical Life at Short Circuit current
Mechanical Life
Shelf Life
Interrupter Weight
Capability is withstand
a) Fault operation
b) Short Circuit Operation
Operating temperature []
Electromagnetic compatibility
Percentage D. C. component of Rated
S.C. Breaking Current

17
18
19
20
21
22

23
24
25

12

Specification offered by
supplier
ABB, Nashik
50/60 Hz
IEC 60056
VG4 with Drop in arrangement
12kV
2500A
26.3kA for 3 sec
65.75KA
less 10-7 mbar
95kV Peak
less 30 micro ohms
1X106 mega Ohms at 25oC
and
35% RH
400A
8+/-1
1.2 to 1.5
2 mm
2 ms
2200N
30000
100
50000
30 Years
2.7 kg
Minimum 100
Minimum 100
-15 to 40
IEC 62271
50 %

PO No. XX/ABB/SPEC. No. 71 DT XX.01.2015

Annexure B
GUARANTEED TECHNICAL PARTICULARS OF VACUUM INTERRUPTER
Type VG4-08 EQUIVALENT TO V-207GV

Sr. no
1
1.1
2
3
4
5
6
6.1
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22

23
24
25

Specification offered by
supplier
ABB, Nashik
50/60 Hz
IEC 56
VGE4 with Drop in
Type of Interrupter
arrangement
Rated Max.line to line voltage
12kV
Normal current Rating
2500A
Rated short time current with duration
26.3kA for 3 sec
Short circuit making current
65.75KA
Degree of vacuum Interrupter inside bottle less 10-7 mbar
Impulse withstand Voltage
95kV Peak
a)Contact resistance at min closing force less 30 micro ohms
1X106 mega Ohms at 25oC
b)Contact resistance after opening
and
35% RH
Capacitor Switching Capacity
400A
Contact Stroke
8+/-1
Opening Speed and Closing Speed
1.2 to 1.5
Maximum Over travel during Opening
2 mm
Max Contact Bounce duration
2 ms
Min. Added contact force for rated short
2200N
circuit making current
Electrical Life at rated Normal Current
30000
Electrical Life at Short Circuit current
100
Mechanical Life
50000
Shelf Life
30 Years
Interrupter Weight
2.7 kg
Capability is withstand
a) Fault operation
Minimum 100
Minimum 100
b) Short Circuit Operation
Operating temperature []
-15 to 40
Electromagnetic compatibility
IEC 62271
Percentage D. C. component of Rated
S.C. Breaking Current
50 %
Required Specification
Name of manufacturer
Frequency
ISS/IEC reference

13