YLAE-SE

YLAE-HE
AIR COOLED LIQUID
CHILLER
R410A REFRIGERANT

AVAILABLE MODELS & NOMINAL COOLING CAPACITIES

TABLE 1

Model
Cooling Capacity (kW) (1)
Energy Efficiency Ratio (1)
Sound Power LWA dB(A) (2)(3)(4)

0255SE
243
2.6
97.0

COOLING CAPACITIES
172 kW to 243 kW

Model
Cooling Capacity (kW)
Energy Efficiency Ratio (1)
Sound Power LWA dB(A) (2)(3)(4)

YLAE air cooled liquid chillers provide


chilled liquid for all air conditioning
applications. They are completely
self-contained and are designed to be
located outside on the roof of a building or
at ground level.

Model
Cooling Capacity (kW)
Energy Efficiency Ratio (1)
Sound Power LWA dB(A) (2)(3)(4)

The range contains standard and high


efficiency models, low sound (LS)
versions of all models are also available.
In addition, optional integral Hydro Kits are
available on all models.
Each unit includes four or six hermetic
scroll compressors, a liquid cooler, air
cooled condensers, and a weather
resistant microprocessor control centre,
all mounted on a formed steel base.

CONTENTS
Specification
Accessories and Options

Model
Cooling Capacity (kW)
Energy Efficiency Ratio (1)
Sound Power LWA dB(A) (2)(3)(4)

0190SE
178
2.8
93.0

0215SE
201
2.8
94.0

0235SE
222
2.6
93.0

0190SE-LS 0215SE-LS 0235SE-LS 0255SE-LS


172
194
214
235
2.7
2.7
2.5
2.5
85.5
86.5
85.5
88.0
0195HE
181
2.9
93.0

0220HE
0240HE
205
227
2.9
2.7
94.0
93.0
]
0195HE-LS 0220HE-LS 0240HE-LS
174
195
216
2.8
2.8
2.6
85.5
86.5
85.5

(1) Capacity and EER at 7 C leaving chilled liquid and 35 C ambient.


(2) Sound Power reduced by 1 dB(A) with optional dual speed fans, operating at low speed.
(3) Sound Power reduced by 3 to 4 dB(A) with optional compressor sound enclosure.
(3) Sound Power reduced by a further 1 dB(A) at ambients below 30 C, with low speed fans.

FEATURES

BENEFITS

High efficiency.

Low operating costs.

Manufactured to ISO 9001/EN 29001.

High standard of quality control.

Full factory run test.

Verifies quality control and ensures that the unit operates


satisfactorily prior to delivery.

Optional low sound units.

Reduced sound levels for low sound applications.

Small footprint.

High capacity design ideal for reduced base area


applications.

Two refrigerant circuits.

System stand-by security.

Controls

Accessible components.

Ideal for maintenance operations

Operating Limitations

Microprocessor control with visual display of


temperatures and alarms.

Simple operation.

Refrigeration Flow Diagram

Optional Micro Gateway.

Interface to enable communication with building control


systems using BACnet or MODBUS protocols.

Selection Guide

Optional multi-unit sequencer.

Sequencing up to four chillers in parallel based on mixed


leaving liquid temperature.

Water Pressure Drops

Chiller remote alarm contacts.

Remote alarm notification.

Cooling Capacities

Single power and control supply.

Easy to install and minimises site wiring costs.

Physical Data

Optional Building Automation System (BAS) /


EMS Interface

Provides a means to reset the leaving chilled liquid


temperature for improved operating efficiency at part load
and reduced operating costs.

Factory fitted Integral Hydro Kit option.

Simplifies installation, whilst ensuring correct chilled liquid


distribution.

Electrical Data
Electrical Connections
Space Requirements
Dimensions

Page G.1
Doc. No. PC158-100 Rev 0 (12/05)

SPECIFICATION
The chillers shall be completely factory assembled with all
interconnecting refrigerant piping and wiring ready for field
installation. After assembly the unit shall have a run test with
water flowing through the cooler. The unit shall be pressure
tested, evacuated and fully charged with refrigerant and oil.
The unit structure is heavy-gauge, galvanised steel coated with
baked-on powder paint (Champagne (Munsell No.
9.8YR4.36/1.2)).
Compressors
The unit shall have hermetic scroll compressors. High efficiency
is achieved through a controlled orbit and the use of an
advanced scroll geometry. All rotating parts are statically and
dynamically balanced. The compressor motors shall have
integral protection against overloads. The overload protection
will automatically reset. Starting shall be direct on line. The
motor terminal boxes shall have IP-54 weather protection.

Factory mounted compressor contactors, compressor fuses


and overlaods (to provide overload and short circuit
protection).
Factory mounted fan contactors and manual motor starters
for overload and short circuit protection).
Factory mounted control transformer to convert the unit
supply voltage to 110 V - 1 - 50 Hz for the control system.
Control supply fuses and connections for a remote
emergency stop device.

FIGURE 1

STATUS

The compressors shall be switched On and Off by the unit


microprocessor to provide capacity control. Each compressor is
fitted with a crankcase strap heater.

Display/Print

Evaporator
The evaporator shall be stainless steel plate type heat
exchanger with a design working pressure of 10 bar g on the
water side. The evaporator shall be equipped with a
thermostatically controlled heaters for frost protection and
insulated with flexible closed-cell foam. Water connection to the
evaporator is via 3 inch victaulic groove connections.
Refrigerant Circuits
Each circuit will use copper refrigerant pipe formed on computer
controlled bending machines to reduce the number of brazed
joints resulting in a reliable and leak resistant system.
Liquid line components shall include: a service valve, a high
absorption removable core filter-drier, a solenoid valve, a sight
glass with moisture indicator and a thermal expansion valve.
Suction line components shall include: a pressure relief valve, a
pressure transducer and a service valve. Suction lines shall be
covered with closed-cell insulation.
Discharge lines shall include service and isolation (ball) valves,
one or two high pressure cutout switches, a pressure transducer
and a pressure relief valve on larger models.
Air Cooled Condensers
The condenser coils shall be seamless copper tubes, arranged
in staggered rows, mechanically expanded into corrugated
epoxy coated aluminium fins. Integral sub-cooling will be
included.
The condenser fans shall have metal 'sickle' blades integrated
into the rotor of an external rotor motor. They are designed for
maximum efficiency and statically and dynamically balanced for
vibration free operation. They shall be directly driven by
independent motors, and positioned for vertical air discharge.
The fan guards will be constructed of heavy-gauge, corrosion
resistant, coated steel.
The IP54 fan motors shall be totally enclosed air-over type. They
will feature ball bearings that are double-sealed and
permanently lubricated.
Power and Control Panels
All power and controls will be contained in a IP55 cabinet with
hinged and lockable outer doors. Power and control sections will
be housed in separate enclosures.

SYS
SYS

1 COMP S RUN 2
2 COMP S RUN 1

Entry

Setpoints

OPER DATA

COOLING
SETPOINTS

PRINT

SCHEDULE/
ADVANCE DAY

HISTORY

ENTER
/ADV

Unit
OPTIONS

CLOCK

PROGRAM

The control panel shall include:

A Liquid Crystal Display (two display lines of twenty


characters per line) with Light Emitting Diode back lighting for
outdoor viewing.
A Colour coded 12-button keypad.
Customer terminal block for control inputs and liquid flow
switch.
The microprocessor control will include:
Status Key for display of:

Status of the unit and each refrigerant circuit


System and unit safety fault messages
Display/Print Keys for display of:
Chilled liquid and ambient air temperatures
System pressures (each circuit)
Operating hours and starts (each compressor)
Load and unload timers and cooling demand
Liquid pump, evaporator heater, solenoid valve and
condenser fan status
Operating data for the systems
History including time, date and reason for last fault shutdown

An RS-232 port, in conjunction with this press-to-print button, is


provided to permit the capability of hard copy print-outs via a
separate printer (by others).
Entry Keys

To program and modify system values


Setpoints Keys for programming:

The power panel shall include:

A factory mounted non-fused disconnect switch with external,


lockable handle to enable connection of the unit power
supply. The disconnect switch can be used to isolate the
power for servicing.

Page G.2
Doc. No. PC158-100 Rev 0 (12/05)

CONTROL PANEL

Chilled liquid temperature setpoint and range


Remote reset temperature range
Set daily schedule/holiday for start/stop
Manual override for servicing
Low and high ambient cutouts
Low liquid temperature cutout
Low suction pressure cutout
High discharge pressure cutout
Anti-recycle timer (compressor start cycle time)

Unit Keys
To set time and unit options

Daily start/stop times


Holiday status
Automatic or manual system lead/lag control
Unit ON/OFF switch
Lead system definition
Compressor starts & operating hours (each compressor)
To activate or deactivate the unit
The microprocessor control system is capable of displaying the Status of evaporator heater and fan operation
Run permissive status
following:
Number of compressors running
Leaving liquid temperature
Liquid solenoid valve status
Low leaving liquid temperature cutout setting
Load & unload timer status
Low ambient temperature cutout setting
Water pump status
Ambient air temperature
Liquid Temperature Reset via a YORK ISN DDC or Building
Metric or Imperial data
Automation System (by others)
Discharge and suction pressure cutout settings
Provisions shall be included for: pumpdown at shutdown;
System discharge and suction pressures
optional remote chilled water temperature reset or up to two
Anti-recycle timer status
steps of demand load limiting (depending on model) from an
external building automation system.
Anti-coincident system start timer condition
Compressor run status
The operating program will be stored in non-volatile memory
No cooling load condition
(EPROM) to eliminate chiller failure due to AC power
Day, date and time
failure/battery discharge. Programmed setpoints shall be
retained in lithium battery backed RTC memory.

ACCESSORIES AND OPTIONS


Power Factor Correction - Factory mounted passive (static)
power factor correction capacitors to correct unit compressor
power factors to a target of 0.9 - 0.95 (depending on operating
conditions).

Pressure Relief (CE/PED)Dual Pressure Relief Valves


Standard single relief valves are replaced with two safety valves
in parallel of which one is operational to assist in valve
replacement during maintenance.

Building Automation System (BAS) / EMS Interface


Provides a means to reset the leaving chilled liquid temperature
and from the BAS / EMS (Factory Mounted):

Pressure Relief (CE/PED) Service Valve Kit


Each relief valve is mounted on a sealable ball valve to aid
maintenance.

Printed circuit board to accept 4 to 20 mA, 0 to 10 Vdc, or dry


contact closure input from the BAS / EMS.

Dual Speed Fans - Fans operate either in high mode (890 rpm)
or in low mode (690 rpm). Fan speed reduces automatically from
high to low mode as head pressure falls, or at programmed
times within the control software.

Note: A YORK ISN Building Automation System can provide a


Setpoint Temperature Reset signal direct to the standard control
panel via the standard on-board RS485 port. Cannot be fitted
when a Micro Gateway is fitted.

High Pressure Fans - Fans and motors suitable for high


external static conditions up to 120Pa.

Micro Gateway
Interface to enable communication with building control systems
using BACnet or MODBUS protocols. See separate York
documentation. (Cannot be fitted when a (BAS) Interface is
fitted).

Low Sound (LS) Unit - Includes low speed fans and


compressor acoustic enclosures (factory fit).

Language LCD and Keypad - Spanish, French, German, and


Italian unit LCD read-out and keypad available. Standard
language is English.

Low Ambient Kit - Kit includes all necessary components to


permit chiller operation down to -18C. This option includes
louvered panels.

ACCESSORIES
38 mm Insulation - Double thickness insulation provided for
enhanced efficiency, and low temperature applications.

Condenser Coil Wire Enclosure - Welded wire mesh guards


mounted over the condenser coils (factory mounted).

Evaporator Flange Kits


Field installed Victaulic PN10 Joint Kit (10bar).
Victualic PN10 Flange and Companion Flange. Supplied loose
for field installation. Includes all necessary nuts, bolts and
gaskets.
Evaporator Extension Kit
Evaporator extension kit simplifies connections to customer
pipework. Kit includes a flow switch and water strainer and
terminates with a 3" Victualic groove connection.

Compressor Acoustic Enclosures - Field or factory fit


enclosures for 3 to 4 dB(A) reduction in sound power.

Condenser Coil Louvered Panels - Louvered panels mounted


over the condenser coils (factory mounted).
Condenser Coil Wired Guards and Unit Louvered Panels Welded wire mesh guards mounted over the condenser coils,
and louvered panels mounted around the bottom of the unit
(factory mounted).
Condenser Coil Louvered Panels and Unit Wire Guards Louvered panels mounted over the condenser coils, and welded
wire mesh guards mounted around the bottom of the unit
(factory mounted).
Unit Wire Enclosure - Welded wire mesh guards over
condenser coils and around the bottom of the unit (field or
factory mounted options available).
Unit Louvered Panels - Louvered panels over condenser coils
and around the bottom of the unit (factory mounted).

Page G.3
Doc. No. PC158-100 Rev 0 (12/05)

Neoprene Pad Isolators - Recommended for normal


installations (field mounted).
25 mm Spring Isolators - Level adjustable, spring and cage
type isolators for mounting under the unit base rails (field
mounted).
Lifting Lug Kit - One set of ISO Mk5 cam locs to enable safe
and easy unit handling.
Containerisation - Units shipped complete with refrigerant
charge in standard containers.
Hydro Kit - Factory fitted Hydro Kit suitable for water glycol
systems with up to 20% glycol at leaving liquid temperatures
down to 0C. The kit is available in single or dual pump variants,
with open drive air cooled motor running at 2900 rpm.
Components are mounted on a painted galvanised steel base
plate and include: one or two pumps, two isolation valves per
pump, a flow switch, a water filter (20 microns), relief, bleed and
drain valves, a pressure gauge, a 17 litre expansion vessel.

All pipework and fittings are galvanised and outlets are 3"
victaulic groove type. 9 mm, thermal insulation is included.
Pressure tapping points are included for differential pressure
measurement. (gauges to be supplied by others).
Dual pump models have non return valves and a flow control
valve to ensure correct operation.
The table below details currently available models with flow
rates and head pressures:
Hydro Kits
Flow/Head Pressure
30 m3/hr (100 kPa)
3
34 m /hr (100 kPa)
3
39 m /hr (100 kPa)
3
43 m /hr (100 kPa)
3
30 m /hr (250 kPa)
3
34 m /hr (250 kPa)

YLAE Model
0190SE 0215SE 0235SE 0255SE
0195HE 0220HE 0240HE
X
X
X
X
X
X

The pumps and flow switch are factory wired to the chiller control
system to provide auto pump starting and running.

OPERATING LIMITATIONS

TABLE 2
Model
Chilled
Liquid

0190SE
Min. Max.
Liquid outlet
temperature

Water outlet
Glycol outlet
Temp. spread

Flow rate
Pressure drop
Max. working pressure
Ambient Air Entering
Standard units
Air
temperature
LS / Dual Speed fans
Low ambient units
Fan available
Standard fans
static pressure LS / Dual speed fans
High pressure fans
Power supply voltage 400 V, 3 , 50 Hz (nominal)
(1)
Recommended system volume
Model
Chilled
Liquid

Water outlet
Glycol outlet
Temp. spread

Flow rate
Pressure drop
Max. working pressure
Ambient Air Entering
Standard units
Air
temperature
LS / Dual Speed fans
Low ambient units
Fan available
Standard fans
static pressure LS / Dual speed fans
High pressure fans
Power supply voltage 400 V, 3 , 50 Hz (nominal)
(1)
Recommended system volume
(1) Table shows minimum water volume of system
Page G.4
Doc. No. PC158-100 Rev 0 (12/05)

0235SE
Min. Max.

0255SE
Min. Max.

5
C
-12
C
3.3 to 8
K
l/s
4.5
14.0
6.3 19.5 6.3 19.5 10.0 28.6
kPa 15.0 137.0 15.0 142.0 15.0 142.0 15.0 120.0
10
barg
-4 to 46
C
-10 to 46
C
-18 to 46
C
10
Pa
10
Pa
120
Pa
360 to 440
V
800
800
1000
l
600
0195HE
Min. Max.

Liquid outlet
temperature

0215SE
Min. Max.

0220HE
0240HE
Min. Max. Min. Max.
5
C
-12
C
3.3 to 8
C
l/s
4.5
14.0
6.3 19.5 6.3 19.5
kPa 15.0 137.0 15.0 142.0 15.0 142.0
10
barg
-4 to 46
C
-10 to 46
C
C
-18 to 46
Pa
10
10
Pa
120
Pa
360 to 440
V
800
800
l
600

REFRIGERANT FLOW DIAGRAM


Control Functions:
DV - Display Value
CHT - Chilled Liquid Temperature
HPC - High Pressure Cutout
LPC - Low Pressure Cutout
HPL - High Pressure Load Limiting
LTC - Low Temperature Cutout
HTC - High Temperature Cutout

Fans

FIGURE 2

Fans

Components:
Pressure Relief Valve
Service (Ball) Valve
Expansion Valve

Condenser

Solenoid Valve
Sight Glass

40.3 Bar
PS

38.7 Bar
PS

DV
HPL
HPC

Sensor Pressure
or Temperature

See P.R.V.
Options

Service (Stop) Access Valve

43.0 Bar

PS

Filter Drier
(Removable Core)

See P.R.V.
Options
ZCPR-3

ZCPR-2

ZCPR-1

Pressure Switch

See P.R.V.
Options
Chilled
Liquid
27.6 Bar

Evaporator

Compressors
DV
LPC

P
Ambient Air Sensor
DV
HTC
LTC

T
Chilled
Liquid

T
DV
CHT
LTC

-YLLSV

Note: Only one refrigerant circuit shown.


Low pressure liquid refrigerant enters the cooler and is evaporated and superheated by the heat energy absorbed from the chilled
liquid passing through the cooler shell. Low pressure vapour enters the compressor where pressure and superheat are increased.
The high pressure vapour is fed to the air cooled condenser coil and fans where the heat is removed. The fully condensed and
subcooled liquid passes through the expansion valve where pressure is reduced and further cooling takes place before returning to
the cooler.

Page G.5
Doc. No. PC158-100 Rev 0 (12/05)

SELECTION GUIDE - WATER


DATA REQUIRED
To select a YORK YLAE water chiller, the following information
is required:
1. Required cooling capacity.
2. Design chilled liquid entering and leaving temperatures.
3. Design chilled liquid flow rate if one of the temperatures in
item 2 are unknown.
4. Design condenser entering air temperature. This will normally
be the design summer ambient air temperature unless
location or other factors have an influence.
5. Altitude above sea level.
6. Design Cooler fouling factor.

4. Physical and electrical data can now be determined from


Tables 7 and 8.
5. Always re-check that selections fall within the design
limitations specified (Table 2).
YLAE SAMPLE SELECTION - WATER COOLING
A R410A chiller is required to cool water from 12C to 7C
having a cooling capacity of 220 kW.
Other design conditions applying are:
Ambient air entering condenser:
Fouling factor:
Altitude:

35C
0.044 m C/kW
Sea level

7. Static pressure resistance against condenser entering and


leaving air flow (where ducts, louvres, attenuators, etc., are
used) at full unit air volume.

From a cursory examination of capacity table 6 a YLAE0235SE


gives approximately the required capacity of 222.2 kW

Note: Items 1, 2 and 3 must be linked by the following formulae:

Since no correction factors for fouling or altitude apply, the


conditions will be as follows:

Cooling capacity kW = l/s chilled liquid x range (C)


0.2392
Where:
Range (C) = Entering liquid temperature - Leaving liquid
temperature.
CHILLER SELECTION METHOD
1. Determine the correct size of chiller by selecting the model
which most closely matches the required capacity at the
design conditions of leaving water temperature and entering
air temperature (Table 6).
2. Apply the relevant correction factors (Tables 3 and 4) to the
capacity and power values from the capacity table (Table 6).
Ensure the corrected capacity is still sufficient for
requirements.

Cooling capacity:
Compressor power:
Water temperature:
Water flow rate

222.2 kW
78.8 kW
12 C to 7 C
222.2 x 0.2392 = 10.6 l/s
5
Cooler pressure drop = 43.7 kPa (see Figure 3).
Note: When selecting chillers with optional dual speed fans, at
ambients below 30C the Low Sound Unit capacity tables should
be used to obtain unit capacity and power. At ambients above
30C the Standard Unit capacity tables should be used to obtain
unit capacity and compressor power.

3. Using the corrected capacity of the selected chiller adjust the


design temperature range, or flow rate, to balance the
formulae shown in Data Required.

FOULING FACTORS

Fouling Factor m C/kW


0.044
0.088
0.176
0.352

Altitude (m)
0
600
1200
1800
2400

Capacity Factor
1.000
0.987
0.973
0.958
0.943

EVAPORATOR PRESSURE DROPS

150
Power Factor
1.000
0.995
0.985
0.962

ALTITUDE FACTORS

TABLE 4

TABLE 5

COOLER
Capacity Factor
1.000
0.987
0.964
0.995

FIGURE 3

Power Factor
1.000
1.010
1.020
1.029
1.038

120
100
80

Pressure Drop (kPa)

TABLE 3

60
50
40
30
20

PRESSURE DROP CALCULATION

0190SE
Pressure Drop [kPa] = 0.8000 (Flow Rate [l/s]^1.9489)
0195HE

0190SE
0195HE

10
3

0215SE
0235SE SE255
0220HE
0240HE

10
Flow Rate l/s

0215SE
Pressure Drop [kPa] = 0.4566 (Flow Rate [l/s]^1.9323)
0220HE
0235SE
Pressure Drop [kPa] = 0.4566 (Flow Rate [l/s]^1.9323)
0240HE
0255SE Pressure Drop [kPa] = 0.2680 (Flow Rate [l/s]^2.0247)

Page G.6
Doc. No. PC158-100 Rev 0 (12/05)

15

20

25

30

YLAE0255SE

YLAE0235SE

YLAE0215SE

YLAE0190SE

Model

YLAE-SE COOLING CAPACITIES (0190 - 0305)


LCLT
C
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0

20
Cool
kW
194.9
200.9
206.8
212.8
218.8
224.8
230.8
236.7
220.2
227.8
235.3
242.0
248.7
255.3
262.0
268.7
243.4
251.5
259.6
266.2
272.9
279.6
286.2
292.9
267.8
276.0
284.3
292.5
300.8
309.0
317.2
325.5

25
Power
kW
42.0
42.3
42.6
43.1
43.5
44.0
44.5
44.9
49.4
49.7
50.1
50.6
51.2
51.8
52.4
52.9
59.1
59.6
60.2
60.9
61.6
62.4
63.1
63.9
66.3
66.7
67.2
67.9
68.6
69.4
70.1
70.9

Cool
kW
186.2
192.1
198.0
203.7
209.5
215.3
221.1
226.8
210.1
217.6
225.0
231.3
237.6
243.9
250.2
256.5
233.3
240.9
248.5
254.9
261.4
267.9
274.3
280.8
255.4
263.7
271.9
279.7
287.6
295.4
303.2
311.1

30
Power
kW
45.8
46.2
46.6
47.0
47.4
47.8
48.2
48.6
53.1
53.5
53.9
54.5
55.2
55.8
56.5
57.1
63.6
64.3
65.0
65.8
66.6
67.4
68.2
69.1
71.3
71.9
72.5
73.2
74.0
74.7
75.4
76.1

Cool
kW
177.4
182.6
187.9
193.5
199.2
204.8
210.5
216.1
200.0
206.4
212.9
218.8
224.7
230.6
236.5
242.4
221.2
228.3
235.3
241.8
248.3
254.7
261.2
267.7
243.1
250.3
257.5
264.9
272.3
279.7
287.2
294.6

Ambient Air Temperature


35
40
Power
Cool
Power
Cool
Power
kW
kW
kW
kW
kW
50.3
167.7
55.2
157.2
60.9
50.7
172.7
55.6
162.0
61.3
51.1
177.8
56.0
166.9
61.7
51.5
183.0
56.5
171.9
62.2
52.0
188.3
57.0
176.9
62.8
52.5
193.5
57.4
181.9
63.4
53.0
198.8
57.9
186.9
63.9
53.5
204.0
58.4
191.9
64.5
58.3
187.9
64.0
175.7
70.8
58.8
194.4
64.6
181.8
71.2
59.3
201.0
65.2
187.9
71.6
60.0
206.6
65.9
193.3
72.5
60.7
212.2
66.6
198.8
73.4
61.3
217.8
67.4
204.2
74.3
62.0
223.5
68.1
209.7
75.1
62.7
229.1
68.8
215.1
76.0
69.5
209.1
77.0
195.9
84.8
70.4
215.6
77.9
202.3
85.6
71.2
222.2
78.8
208.7
86.4
72.0
228.5
79.7
214.6
87.5
72.8
234.7
80.6
220.5
88.6
73.6
241.0
81.4
226.5
89.7
74.4
247.2
82.3
232.4
90.8
75.2
253.5
83.2
238.4
91.9
77.8
228.7
85.0
214.2
93.5
78.7
235.9
85.7
220.4
94.3
79.6
243.1
86.4
226.6
95.1
80.3
250.1
87.3
233.2
96.0
81.0
257.1
88.2
239.8
96.9
81.8
264.1
89.0
246.4
97.7
82.5
271.1
89.9
253.0
98.6
83.2
278.1
90.8
259.6
99.5

TABLE 6a
45

Cool
kW
146.2
151.1
155.9
160.7
165.5
170.2
175.0
179.8
164.6
170.2
175.7
94.5
98.3
102.1
105.9
109.7
134.4
138.1
141.8
145.5
149.2
152.9
156.7
160.4
110.0
114.3
118.5
122.8
127.1
131.4
135.7
140.0

46
Power
kW
67.3
67.7
68.1
68.7
69.3
69.9
70.5
71.1
78.4
79.1
79.8
33.4
33.7
34.0
34.3
34.6
55.2
55.5
55.8
56.1
56.3
56.6
56.9
57.2
43.6
44.0
44.4
44.6
44.7
44.9
45.0
45.2

YLAE0240HE

YLAE0220HE

YLAE0195HE

Model

YLAE-HE COOLING CAPACITIES (0195 - 0240)


LCLT
C
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0

20
Cool
kW
197.9
204.4
210.9
217.1
223.2
229.3
235.5
241.6
224.6
232.1
239.7
246.6
253.4
260.3
267.2
274.1
246.9
255.0
263.2
270.3
277.5
284.6
291.7
298.9

25
Power
kW
41.2
41.4
41.6
41.9
42.3
42.6
42.9
43.3
48.0
48.4
48.8
49.2
49.6
50.0
50.4
50.9
58.5
59.1
59.4
59.8
60.1
60.5
60.8
61.1

Cool
kW
189.6
195.5
201.4
207.3
213.2
219.2
225.1
231.0
214.3
221.7
229.1
235.4
241.7
248.1
254.4
260.8
234.6
243.8
253.0
259.5
266.0
272.6
279.1
285.6

30
Power
kW
44.6
44.9
45.2
45.6
46.0
46.4
46.8
47.2
52.0
52.4
52.8
53.3
53.8
54.2
54.7
55.2
62.8
63.4
63.7
64.2
64.6
65.1
65.5
66.0

Cool
kW
180.7
186.1
191.4
197.2
203.1
208.9
214.7
220.5
203.7
210.3
216.8
222.9
229.1
235.2
241.3
247.5
222.4
231.1
239.7
246.5
253.2
259.9
266.7
273.4

Ambient Air Temperature


35
40
Power
Cool
Power
Cool
Power
kW
kW
kW
kW
kW
49.0
170.9
54.0
160.4
59.5
49.3
176.0
54.4
165.5
59.8
49.6
181.1
54.8
170.5
60.1
50.1
186.5
55.2
175.6
60.6
50.5
191.9
55.7
180.8
61.1
51.0
197.3
56.1
185.9
61.5
51.4
202.7
56.6
191.0
62.0
51.9
208.1
57.0
196.1
62.5
56.8
192.3
62.4
180.0
68.8
57.2
198.4
63.0
186.1
69.4
57.6
204.5
63.6
192.3
70.0
58.1
210.4
64.1
197.7
70.7
58.7
216.3
64.7
203.1
71.4
59.2
222.2
65.3
208.5
72.1
59.8
228.1
65.8
213.9
72.8
60.3
234.0
66.4
219.3
73.5
68.9
210.1
76.0
199.9
83.6
69.6
218.3
76.6
206.1
84.3
70.0
226.5
76.8
212.2
84.5
70.4
233.0
77.4
218.7
85.0
70.9
239.5
77.9
225.2
85.5
71.3
246.0
78.5
231.8
86.0
71.7
252.6
79.0
238.3
86.4
72.1
259.1
79.5
244.8
86.9

Cool
kW
144.0
148.8
153.5
93.0
96.8
100.6
104.4
108.2
81.9
85.7
89.5
93.3
97.1
100.9
104.7
108.5
132.0
135.7
139.4
143.1
146.8
150.5
154.3
158.0
108.0
112.3
116.5
120.8
125.1
129.4
133.7
138.0

TABLE 6b
45

Cool
kW
149.8
154.7
159.6
164.5
169.4
174.3
179.2
184.1
168.5
174.3
180.0
96.9
100.7
104.6
108.4
112.3
187.7
143.5
147.3
151.0
154.7
158.5
162.3
166.0

Power
kW
68.9
69.1
69.3
34.3
34.6
34.9
35.2
35.5
33.6
33.9
34.2
34.5
34.8
35.1
35.4
35.7
56.4
56.7
57.0
57.3
57.5
57.8
58.1
58.4
44.8
45.0
45.2
45.4
45.5
45.7
45.8
46.0

46
Power
kW
65.3
65.7
66.1
66.7
67.2
67.8
68.3
68.9
76.3
76.8
77.4
31.5
31.8
32.1
32.4
32.7
92.7
54.3
54.6
54.9
55.1
55.4
55.7
56.0

Cool
kW
147.8
152.6
157.3
162.2
167.1
171.9
176.8
181.7
165.3
88.0
91.8
95.7
99.5
103.4
107.2
111.1
137.4
141.1
144.8
148.6
152.3
156.0
159.9
163.6

Power
kW
66.9
67.2
67.5
68.1
68.6
69.2
69.7
70.3
78.2
32.0
32.3
32.6
32.9
33.2
33.5
33.8
55.2
55.5
55.8
56.1
56.3
56.6
56.9
57.2

Part Load with largest compressor per system operating

Page G.7
Doc. No. PC158-100 Rev 0 (12/05)

YLAE-SE-LS COOLING CAPACITIES (0190 - 0305)

YLAE0255SELN

YLAE0235SELN

YLAE0215SELN

YLAE0190SELN

Model

TABLE 6c
LCLT
C
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0

20
Cool
kW
188.1
193.9
199.6
205.4
211.1
216.9
222.7
228.5
212.5
219.8
227.1
233.5
240.0
246.4
252.8
259.3
234.9
242.7
250.5
256.9
263.4
269.8
276.2
282.6
258.4
266.4
274.3
282.3
290.2
298.2
306.1
314.1

25
Power
kW
43.7
44.0
44.3
44.8
45.3
45.8
46.2
46.7
51.4
51.7
52.1
52.7
53.3
53.9
54.5
55.1
61.5
62.0
62.6
63.3
64.1
64.9
65.6
66.4
69.0
69.4
69.8
70.6
71.4
72.2
72.9
73.7

Model
YLAE0195HELN
YLAE0220HELN
YLAE0240HELN

5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0

Power
kW
47.6
48.0
48.4
48.9
49.3
49.7
50.1
50.5
55.2
55.6
56.0
56.7
57.4
58.0
58.7
59.4
66.1
66.9
67.6
68.4
69.3
70.1
71.0
71.8
74.1
74.8
75.4
76.2
76.9
77.7
78.4
79.2

Cool
kW
171.1
176.2
181.3
186.7
192.2
197.7
203.1
208.6
193.0
199.2
205.5
211.1
216.8
222.5
228.2
233.9
213.4
220.3
227.1
233.3
239.6
245.8
252.0
258.3
234.6
241.5
248.5
255.6
262.8
270.0
277.1
284.3

Ambient Air Temperature


35
40
Power
Cool
Power
Cool
Power
kW
kW
kW
kW
kW
52.3
161.8
57.4
151.7
63.3
52.7
166.7
57.8
156.3
63.7
53.1
171.5
58.2
161.0
64.2
53.6
176.6
58.7
165.8
64.7
54.1
181.7
59.2
170.7
65.3
54.6
186.7
59.7
175.5
65.9
55.1
191.8
60.2
180.3
66.5
55.6
196.9
60.7
185.2
67.1
60.6
181.3
66.6
169.6
73.7
61.1
187.6
67.2
175.4
74.1
61.7
194.0
67.8
181.3
74.5
62.4
199.4
68.6
186.5
75.4
63.1
204.8
69.3
191.8
76.3
63.8
210.2
70.1
197.1
77.2
64.5
215.6
70.8
202.3
78.1
65.2
221.1
71.6
207.6
79.1
72.3
201.8
80.1
189.1
88.2
73.2
208.1
81.0
195.2
89.0
74.0
214.4
82.0
201.4
89.8
74.8
220.5
82.9
207.1
91.0
75.7
226.5
83.8
212.8
92.1
76.5
232.6
84.7
218.6
93.3
77.3
238.6
85.6
224.3
94.5
78.2
244.6
86.5
230.0
95.6
80.9
220.7
88.4
206.7
97.3
81.8
227.6
89.1
212.7
98.1
82.8
234.6
89.9
218.7
98.9
83.5
241.3
90.8
225.0
99.8
84.3
248.1
91.7
231.4 100.7
85.0
254.8
92.6
237.8 101.7
85.8
261.6
93.5
244.1 102.6
86.5
268.4
94.4
250.5 103.5

45
Cool
kW
141.1
145.8
150.5
155.1
159.7
98.2
101.8
105.5
80.2
83.8
87.5
91.2
94.9
98.5
102.2
105.9
129.7
133.3
136.8
140.4
144.0
147.5
151.2
154.8
106.2
110.3
114.4
118.5
122.7
126.8
131.0
135.1

46
Power
kW
70.0
70.4
70.8
71.5
72.1
35.2
35.5
35.8
33.7
34.0
34.4
34.7
35.0
35.4
35.7
36.0
57.4
57.7
58.0
58.3
58.6
58.9
59.2
59.5
45.3
45.8
46.2
46.3
46.5
46.7
46.8
47.0

Cool
kW
78.6
82.3
86.0
89.7
93.4
97.1
100.7
104.4
79.0
82.7
86.4
90.0
93.7
97.4
101.0
104.7
127.4
131.0
134.5
138.1
141.7
145.2
148.9
152.5
104.2
108.4
112.4
116.6
120.7
124.9
129.0
133.2

Power
kW
68.0
68.4
68.8
69.4
69.9
70.5
34.4
34.7
31.9
32.2
32.5
32.8
33.1
33.4
33.7
34.0
56.2
56.5
56.8
57.1
57.3
57.6
57.9
58.2

Cool
kW
142.6
147.2
151.8
92.0
95.8
99.5
103.2
107.0
81.2
84.9
88.6
92.3
96.0
99.8
103.5
107.2
132.6
136.2
139.8
143.4
147.0
150.6
154.3
157.9

Power
kW
34.8
35.1
35.4
35.7
36.0
36.3
36.6
36.9
34.9
35.3
35.6
35.9
36.2
36.5
36.8
37.1
58.7
59.0
59.3
59.6
59.8
60.1
60.4
60.7
46.6
46.8
47.0
47.2
47.3
47.5
47.7
47.8

YLAE-HE-LS COOLING CAPACITIES (0195 - 0240)

TABLE 6d
LCLT
C

Cool
kW
179.7
185.4
191.0
196.6
202.2
207.8
213.3
218.9
202.7
209.9
217.2
223.2
229.3
235.4
241.5
247.6
225.1
232.5
239.8
246.0
252.2
258.5
264.7
271.0
246.5
254.5
262.4
270.0
277.5
285.1
292.6
300.2

30

20
Cool
kW
191.0
197.3
203.5
209.5
215.4
221.3
227.2
233.1
216.7
224.0
231.3
237.9
244.6
251.2
257.8
264.5
238.2
246.1
254.0
260.9
267.8
274.6
281.5
288.4

25
Power
kW
42.8
43.1
43.3
43.6
44.0
44.3
44.6
45.0
49.9
50.4
50.8
51.2
51.6
52.0
52.5
52.9
60.8
61.5
61.8
62.2
62.5
62.9
63.3
63.6

Cool
kW
183.0
188.7
194.3
200.1
205.8
211.5
217.2
222.9
206.8
213.9
221.1
227.2
233.3
239.4
245.5
251.6
226.4
235.3
244.1
250.4
256.7
263.0
269.3
275.6

30
Power
kW
46.3
46.6
47.0
47.4
47.8
48.2
48.6
49.1
54.1
54.5
54.9
55.4
55.9
56.4
56.9
57.4
65.3
65.9
66.2
66.7
67.2
67.7
68.2
68.6

Cool
kW
174.4
179.5
184.7
190.3
195.9
201.5
207.1
212.8
196.6
202.9
209.2
215.1
221.1
227.0
232.9
238.8
214.6
223.0
231.3
237.8
244.3
250.8
257.3
263.8

Ambient Air Temperature


35
40
Power
Cool
Power
Cool
Power
kW
kW
kW
kW
kW
51.0
165.0
56.2
154.8
61.9
51.3
169.8
56.6
159.7
62.2
51.6
174.7
57.0
164.6
62.5
52.1
180.0
57.4
169.5
63.0
52.6
185.2
57.9
174.4
63.5
53.0
190.4
58.4
179.4
64.0
53.5
195.6
58.8
184.3
64.5
53.9
200.8
59.3
189.2
65.0
59.0
185.5
64.9
173.7
71.5
59.5
191.4
65.5
179.6
72.1
59.9
197.4
66.1
185.5
72.8
60.4
203.1
66.7
190.7
73.5
61.0
208.7
67.3
195.9
74.2
61.6
214.4
67.9
201.2
75.0
62.2
220.1
68.4
206.4
75.7
62.8
225.8
69.0
211.6
76.4
71.7
202.8
79.0
192.9
86.9
72.4
210.7
79.7
198.8
87.6
72.8
218.5
79.9
204.8
87.9
73.3
224.8
80.5
211.1
88.4
73.7
231.1
81.1
217.4
88.9
74.2
237.4
81.6
223.7
89.4
74.6
243.7
82.2
230.0
89.9
75.0
250.0
82.7
236.3
90.3

Part Load with largest compressor per system operating

Page G.8
Doc. No. PC158-100 Rev 0 (12/05)

45
Cool
kW
144.6
149.3
154.0
158.7
163.5
168.2
104.3
108.1
82.4
86.2
89.8
93.5
97.2
100.9
104.6
108.4
134.8
138.5
142.1
145.7
149.3
152.9
156.6
160.2

46
Power
kW
69.6
69.9
70.2
34.6
34.9
35.2
35.5
35.8
33.0
33.3
33.6
33.9
34.2
34.5
34.8
35.1
57.4
57.7
58.0
58.3
58.6
58.9
59.2
59.5

PHYSICAL DATA
YLAE-SE
Refrigerant circuits
Refrigerant
Circuit 1 (1)
Charge
Circuit 2 (1)
Oil
Circuit 1
Charge
Circuit 2
Compressor
Quantity (circuit 1/circuit 2)

kg
kg
l
l
%

Unit Capacity Control (2)


Evaporator
Air
Cooled
Condenser
Standard Fans
LS Unit Fans
Dual
Speed Fans
(3)
Sound level
to EN 292 1991

Water volume per evaporator


Total coil face area
Number of tube rows
Number of fans (circuit 1/circuit 2)
Nominal speed (890 rpm) Total airflow
Nominal speed (690 rpm) Total airflow
High Speed (890 rpm) Total airflow
Low Speed (690 rpm) Total airflow
Standard Unit
Low Noise Unit
Unit with Dual Speed Fans (890 rpm)
Unit with Dual Speed Fans (690 rpm)
Dimensions
Length
Width
Height
Weight (coated
Operating
aluminum fins)
Shipping
Additional weight - units with optional copper fin coils
Additional weight - units with Hydro Kit option
Additional weight - units with louvered kit option
Additional weight - low sound units
YLAE-HE
Refrigerant circuits
Refrigerant
Circuit 1 (1)
(1)
Charge
Circuit 2
Oil
Circuit 1
Charge
Circuit 2
Compressor
Quantity (circuit 1/circuit 2)

l
m

m3/s
m3/s
m3/s
m3/s
dBA
dBA
dBA
dBA
mm
mm
mm
kg
kg
kg
kg
kg
kg

kg
kg
l
l
%

Unit Capacity Control (2)


Evaporator
Air
Cooled
Condenser
Standard Fans
LS Unit Fans
Dual
Speed Fans
Sound level (3)
to EN 292 1991

Water volume per evaporator


Total coil face area
Number of tube rows
Number of fans (circuit 1/circuit 2)
Nominal speed (890 rpm) Total airflow
Nominal speed (690 rpm) Total airflow
High Speed (890 rpm) Total airflow
Low Speed (690 rpm) Total airflow
Standard Unit
Low Noise Unit
Unit with Dual Speed Fans (890 rpm)
Unit with Dual Speed Fans (690 rpm)
Dimensions
Length
Width
Height
Weight (coated
Operating
aluminum fins)
Shipping
Additional weight - units with optional copper fin coils
Additional weight - units with Hydro Kit option
Additional weight - units with louvered kit option
Additional weight - low sound units

l
m

3
m /s
m3/s
3
m /s
3
m /s
dBA
dBA
dBA
dBA
mm
mm
mm
kg
kg
kg
kg
kg
kg

TABLE 7

0190SE
2
12
12
4.1 + 4.7
4.1 + 4.7
2/2
22 (28),
50, 72
(78), 100
13
8.45
3
2/2
21.1
16.4
21.1
16.4
72
66
72
70
2500
2214
2149
1551
1537
220
226
205
110

0215SE
2
13.5
13.5
4.7 x 2
4.7 x 2
2/2

0195HE
2
13.5
13.5
4.1 + 4.7
4.1 + 4.7
2/2
22(28), 50,
72 (78),
100
13
10.40
3
2/2
21.8
16.9
21.8
16.9
72
66
72
70
2960
2214
2149
1615
1601
268
313
205
110

0220HE
2
15
15
4.7 x 2
4.7 x 2
2/2

25, 50,
75, 100
18
8.45
3
2/2
21.1
16.4
21.1
16.4
73
67
73
72
2500
2214
2149
1652
1632
220
226
205
110

25, 50,
75, 100
18
10.40
3
2/2
21.8
16.9
21.8
16.9
72
67
72
70
2960
2214
2149
1716
1696
268
321
205
110

0235SE
2
14.5
14.5
4.1 x 3
4.1 x 3
3/3
17, 33, 50,
67, 83,
100
18
8.45
3
2/2
21.1
16.4
21.1
16.4
72
66
72
70
2500
2214
2149
1750
1730
220
226
205
110

0255SE
2
17
17
5.6 x 2
5.6 x 2
2/2
25, 50,
75, 100
20
10.40
3
2/2
21.8
16.9
21.8
16.9
76
68
76
74
2960
2214
2149
1756
1733
268
355
205
110

0240HE
2
16
16
4.1 x 3
4.1 x 3
3/3
17, 33, 50,
67, 83,
100
18
10.40
3
2/2
21.8
16.9
21.8
16.9
73
67
73
72
2960
2214
2149
1814
1794
268
355
205
110

(1) Liquid sub-cooling measured at the liquid line should be between 8.5 and 11.0 C at circuit full load.
(1) Sub-cooling is determined by the level of refrigerant charge in each system.
(2) The unit capacity control percentages stated in brackets, apply when the largest compressors
(2) on the lead and lag systems are stating first.
(3) Sound Pressure levels are 1 m from the Control Panel, at a height of 1.6 m from the unit base.
(2) Levels may vary at different positions around the unit. Levels do not include Hydro Kit Option.
Page G.9
Doc. No. PC158-100 Rev 0 (12/05)

ELECTRICAL DATA

TABLE 8
Nominal Running @ 400 V
Amps (1)
kW

63.0
72.2

128.8

87.6

156.8

151.2

341.7

85.8

153.6

99.4

177.6

172.8

328.2

93.4

165.6

107.0

192.0

184.4

399.5

61.8

112.6

78.2

139.8

135.4

309.9

71.0

127.2

87.0

155.6

150.0

323.7

83.8

151.2

100.6

180.0

174.0

326.2

Model
YLAE
0190SE
0215SE
0235SE
0255SE
0195HE
0220HE
0240HE

Start-up

Maximum Running
Amps @ 360 V (2) Amps @ 400 V
kW
Without Power Factor Correction
With Optional Power Factor Correction fitted
114.0
78.8
141.0
136.2

(2)

(3)

Amps

310.8

Locked Rotor

Current Amps
@ 400V
225.0
225.0
198.0
272.0
225.0
225.0
198.0

(1) Nominal running amps at 35C ambient air temperature and 7C leaving liquid temperature.
(2) Maximum running amps at highest ambient air temperature and cooling capacity before compressor unloading.
(3) Start-up amps is the largest compressor starting with all other compressors/fans operating at nominal conditions at 400 V.
(4) Locked rotor conditions are for the largest compressors.

TABLE 9

SOUND PRESSURE SPL dB(A) AT 10 METRES DISTANCE


Sound Pressure SPL dB(A) at 10 Metres Distance
Compressor Enclosure
(2)
No
Yes
Fan Speed
Fan Speed

Model

Low
High

Low (Option)

High

(3)

Ambient oC

30+
0190SE
61.0
60.0
58.0
NA
0215SE
62.0
61.5
58.0
NA
0235SE
61.0
60.0
58.0
NA
0255SE
64.9
63.9
58.9
NA
0190SELS
NA
NA
NA
53.5
0215SELS
NA
NA
NA
54.5
0235SELS
NA
NA
NA
53.5
0255SELS
NA
NA
NA
55.9
0195HE
60.9
59.9
57.9
NA
0220HE
61.9
61.4
57.9
NA
0240HE
60.9
59.9
57.9
NA
0195HELS
NA
NA
NA
53.4
0220HELS
NA
NA
NA
54.4
0240HELS
NA
NA
NA
53.4
o
o
(1) Cooling capacity and EER at 7 C leaving chilled water and 35 C ambient.
(2) Compressor acoustic enclosure is standard for LS chillers and an option for all other models.
(3) Low speed fan operation is standard for LS chillers and an option for all other models.

Page G.10
Doc. No. PC158-100 Rev 0 (12/05)

2957.0
56.0
57.0
57.9
52.5
52.5
52.5
54.9
56.9
55.9
56.9
52.4
52.4
52.4

(4)

4
SCREEN

33 34 25 26 29 30 23 24 27 28 31 32

FLOW
SWITCH

1st STAGE LOAD LIMIT

LK

2nd STAGE LOAD LIMIT


or PWM INPUT (Depending on Model)

PE

REMOTE
START/STOP

SYSTEM 2 ALARM STATUS

CHILLER RUN STATUS SYSTEM 2

LIQUID PUMP START CONTACTS

SYSTEM 1 ALARM STATUS

CHILLER RUN STATUS SYSTEM 1

-F4

FAN SPEED INHIBIT

REMOTE EMERGENCY
STOP DEVICE

ELECTRICAL CONNECTIONS

U V W

VIEW A

50 Hz
400 V

CUSTOMER POWER SUPPLY


YLAE INTERFACE

VIEW A

-F1

13 14 13 18 13 20 21 13

Page G.11
Doc. No. PC158-100 Rev 0 (12/05)

SPACE REQUIREMENTS
1500

1300
1500

1300

1500

1500

1500
1500

1300

1500

2500

1500

1500
1500

The recommended clearances and dimensions are the distances between the edge of the units and the architectural enclosure
surrounding them. It is important that adequate space is available to ensure that air discharged via the fans is not recirculated into
the condenser coil intake, which would reduce the unit capacity.
The dimensions at the front and rear of the units allow for access to the control panel and for component removal.
The enclosure height should not exceed the height of the units. Horizontal obstructions or overhangs should not be closer than 15
metres above the top of any unit and no obstructions are allowed directly above the unit.

Page G.12
Doc. No. PC158-100 Rev 0 (12/05)

788

100

View A

310

2340

2500

644

628
249.5

180

Outlet
3 Victualic

CL

2214

Inlet
3 Victualic

2149

70

Power Cable Entry


via Gland Plate
Control Cable Entry
Power Cable Entry
via Wiring Conduit
via Gland Plate

Notes:
Contact YORK Sales for details of liquid
connections when Hydro Kit or Evaporator
Extension Kit options are specified.
Unit height is increased by 18 mm
when optional Neoprene Pad Isolators are fitted.
Unit height is increased by 150 mm
when optional 25 mm Spring Isolators are fitted.
Unit height is increased by 120 mm
when optional High Pressure Fans are fitted.

YLAE Models 0190SE, 0215SE, 0235SE

DIMENSIONS

Page G.13
Doc. No. PC158-100 Rev 0 (12/05)

1171

788

180
310

2700

2960

1099

628
249.5

100

70

Page G.14
Doc. No. PC158-100 Rev 0 (12/05)

Outlet
3 Victualic

CL

2214

Inlet
3 Victualic

2149

Power Cable Entry


via Gland Plate
Control Cable Entry
Power Cable Entry
via Wiring Conduit
via Gland Plate

Notes:
Contact YORK Sales for details of liquid
connections when Hydro Kit or Evaporator
Extension Kit options are specified.
Unit height is increased by 18 mm
when optional Neoprene Pad Isolators are fitted.
Unit height is increased by 150 mm
when optional 25 mm Spring Isolators are fitted.
Unit height is increased by 120 mm
when optional High Pressure Fans are fitted.

YLAE Models 0255SE, 0195HE, 0220HE, 0240HE

DIMENSIONS

1171

HYDRO KIT OPTION


SINGLE PUMP OPTION

DUAL PUMP OPTION

Evaporator

Isolation /
Flow Control
Isolation
Valve
Non
Return
Valves
Pump
Filter
Pumps

Relief
Valve

Isolation /
Flow Control

Expansion
Vessel

Bleed

Filter

From
Water Pipework

Isolation
Valve

To
Water Pipework
Drain

FS

Pressure
Gauge

Page G.15
Doc. No. PC158-100 Rev 0 (12/05)

NOTES

Page G.16
Doc. No. PC158-100 Rev 0 (12/05)