LINE
BUS
BUS
TO
REAL
REACTIVE
POWER
POWER
0.87458
0.16968
0.65549
NO TCSC
LINE 1
78
0.87495
0.15964
0.74755
LINE 2
96
0.94270
0.10296
0.66451
LINE 3
75
0.88400
0.14299
0.79435
LINE 4
54
0.87002
0.14629
0.66380
LINE 5
64
0.95424
0.06398
0.20554
LINE 6
98
0.86828
0.17100
0.89941
TABLE I.
Bus Voltage and Total Losses of IEEE 9 Bus System using 80% Series
Compensation of TCSC
VI. CONCLUSION
To choose the best line in Bus 6 to install with TCSC,
several testes have been made to determine which line
installing with TCSC will gives smaller result in power
losses. Based on the result, TCSC is installed at several
different locations of line to see the effect on system
performance. From the result on Table I, the optimal
location of TCSC is on line 5 because it gives lowest power
losses on the system when TCSC be install at that
particular line, that is 0.06398 p.u for real power losses and
0.20554 p.u for reactive power losses, it also give highest
improvement in bus 6 voltage that is 0.95424 p.u.This
can be observed more clearly in Figure 4.and Figure 5.
Figure4: Graph of Real and Reactive power losses versus TCSC Location