Catalogue2015
Masterpact NT
and NW
LV power circuit breakers
and switch-disconnectors
208E0000.indd 1
09/12/2014 13:14:04
208E0000.indd 2
09/12/2014 13:14:05
Masterpact NT and NW
208E_CATALOGUE.indb 1
09/12/2014 14:15:36
> Hotels
> Hospitals
> Offices
> Retail
Data Centres
and Networks
Industry
Energy and
Infrastructures
> Airports
> Oil and gas
> Water
> Electrical energy
> Marine
An answer to specific
applications
All standards
Masterpact is compliant with international standards IEC 60947-1 and 2, IEC 68230 for type 2 tropicalisation,
UL489, ANSI, UL1066, CCC and GOST.
II
208E_CATALOGUE.indb 2
09/12/2014 14:15:38
> Masterpact NT, the worlds smallest true power circuit breaker, with ratings from 630 to 1600 A
> Masterpact NW, in two frame sizes, one from 800 to 4000 A and the other from 4000 to 6300 A.
5 performance levels
> N1 - for standard applications with low short-circuit levels.
> H1 - for industrial sites with high short-circuit levels or installations with two parallel-connected transformers.
> H2 - high-performance for heavy industry where very high short-circuits can occur.
> H3 - for incoming devices supplying critical applications requiring both high performance and a high level of discrimination.
> L1 - for high current-limiting capability and a discrimination level (37 kA) as yet unequalled by any other circuit breaker of its
type; intended for the protection of cable-type feeders or to raise the performance level of a switchboard when the
transformer power rating is increased.
sizes:
ka
08
10
NT
NT
ka
ka
ka
42
50
L1
15
06
NT
16
NT
T12
ka
N 65
1 4 ka
2
ka
H
1
H
2
10
ka
15
0
NW
20
NW
NW
40
NW
12
0
15
L1
H
3
08
NW
10
6
W1
25
NW
2
W3
50
NW
10
ka
0b
W4
15
0
ka
63
NW
III
208E_CATALOGUE.indb 3
09/12/2014 14:15:39
Optimised volumes
and ease of installation
Aiming at standardising electrical switchboards at a time when
installations are increasingly complex, Masterpact provides an
unequalled simplicity, both concerning choice and installation.
The smallest circuit breaker
in the world
Masterpact NT innovates by offering all the
performance of a power circuit breaker in an
extremely small volume. The 70 mm pole pitch
means a three-pole drawout circuit breaker can
be installed in a switchboard section 400 mm
wide and 400 mm deep.
Maximum security
The arc chutes absorb the energy released
during breaking, thus limiting the stresses
exerted on the installation.
They filter and cool the gases produced,
reducing effects perceptible from the outside.
Optimised volumes
Up to 4000 A, Masterpact NW circuit breakers
are all the same size, the same as the old M08
to 32 range.
From 4000 to 6300 A, there is just one size.
More than
60
Retrofit solutions
> Special connections terminals are available to replace a fixed or a drawout Masterpact M08 to 32 with a Masterpact NW,
without modifying the busbars or the door cut-out.
> "Plug and Play" retrofit solution: this solution enables retrofitting of Masterpact M units with considerably reducing on-site
intervention time and getting the performance of last generation device.
Masterpact M
y 3200 A
30
2
minutes
and
easy operations
IV
208E_CATALOGUE.indb 4
09/12/2014 14:15:40
Compliance with
environmental
requirements
208E_CATALOGUE.indb 5
09/12/2014 14:15:41
Energy management
has never been simpler
Simple-to-install Smart Panels connect your building to real savings
in 3 steps
Measure
Embedded and standalone metering & control
capabilities
Connect
Save
VI
208E_CATALOGUE.indb 6
09/12/2014 14:15:45
Measure
CLOUD
connect
Save
CLOUD
On-line Energy
Management services
StruXureWare Energy Operation
automates data collection via an open,
scalable, and secure energy management
information system.
With the help of the Schneider Electric energy
management services team, data is then
turned into actionable information to enable
customers to understand their facilities
performance on an ongoing basis.
Energy Operation leverages companies
current investments in their existing systems,
and can be used to communicate advanced
results and performance to a broad audience
for a shared understanding throughout an
organization.
VII
208E_CATALOGUE.indb 7
09/12/2014 14:15:47
VIII
208E_CATALOGUE.indb 8
09/12/2014 14:15:48
1.0
Masterpact NT and NW
General contents
Presentation
A-1
A-1
Installation recommendations
B-1
B-1
C-1
C-1
Electrical diagrams
D-1
D-1
Additional characteristics
E-1
E-1
F-1
F-1
208E_CATALOGUE.indb 1
09/12/2014 14:15:49
1.1
Presentation
General overview
Detailed contents
PB111801-19_r.eps
PB103360.eps
PB106363A50.eps
bb Ratings:
vv Masterpact NT 630 to 1600 A
vv Masterpact NW 800 to 6300 A.
bb Circuit breakers type N1, H1, H2, H3, L1.
bb Switch-disconnectors type NA, HA, HF.
bb 3 or 4 poles.
bb Fixed or drawout versions.
bb Option with neutral on the right.
bb Protection derating.
PB104804.eps
Power meter P
DB416829.eps
PB103798_9.eps
DB416830.eps
screen 2b.eps
Communication
Harmonic meter H
208E_CATALOGUE.indb 2
09/12/2014 14:15:52
Remote operation
PB100818-16.eps
PB100809-16.eps
PB104362A30.eps
PB104357A40.eps
PB104347A55.eps
Connections
PB100807-20.eps
PB100820-32.eps
PB100776-42.eps
Indication contacts
Accessories
PB104382A32.eps
PB100812-32.eps
PB100810-32.eps
Locking
bb Remote ON/OFF:
vv gear motor
vv XF closing or MX opening voltage releases
vv PF ready-to-close contact
options:
- RAR automatic or RES electrical remote reset
- BPFE electrical closing pushbutton.
bb Remote tripping function:
vv MN voltage release
- standard
- adjustable or non-adjustable delay
vv or second MX voltage release.
208E_CATALOGUE.indb 3
09/12/2014 14:15:53
TOOLS
Ecodial
Ecodial software is dedicated to LV electrical installation
calculation in accordance with the IEC60364
international standard or national standards.
This 4th generation, "Ecodial Advance Calculation 4",
offers a new ergonomic and new features:
ppoperating mode that allows easy calculation in case
of installation with different type of sources
(parallel transformers, back-up generators)
ppdiscrimination analysis associating curves checking
and discrimination tables
ppdirect access to protection settings including residual
current protections
ppeasy selection of alternate solutions or manual
selection of a product.
208E_CATALOGUE.indb 4
09/12/2014 14:15:54
Masterpact NT and NW
A-2
A-4
A-6
A-8
A-10
A-12
A-14
A-18
Operating-assistance functions
Switchboard-display functions
Communication
A-20
A-22
A-26
A-28
A-30
A-32
A-33
A-34
A-35
A-36
A-38
A-40
A-42
A-43
A-44
Overview of solutions
A-46
Accessories A-47
Locking
On the device
On the chassis
A-50
A-51
Indication contacts
Remote operation
A-52
Accessories
Source-changeover systems
A-58
Remote ON / OFF
Remote tripping
A-54
A-57
Presentation A-59
Presentation
>2
Installation recommendations
> B-1
Dimensions and connections
> C-1
Electrical diagrams
> D-1
Additional characteristics
> E-1
Catalogue numbers andorderform
> F-1
Interlocking of devices
Mechanical interlocking
Electrical interlocking
IVE unit
Controller selection
Standard configuration
Masterpact NW with corrosion protection 800-4000 A
Earthing switch Masterpact
A-60
A-62
A-63
A-64
A-65
A-67
A-1
208E_CATALOGUE.indb 1
09/12/2014 14:15:54
Circuit breakers
andswitch-disconnectors
Functions
and characteristics
Masterpact NW
Standard applications
Standard applications
Type of application
Standard applications
with low short-circuit
currents
Applications with
medium-level
short-circuit currents
Icu/Ics at 440 V
Icu/Ics at 1000 V
Icu/Ics at 500 V DC L/R < 15 ms
42 kA
-
50 kA
-
130 kA
-
42 kA
-
65 kA
-
Position of neutral
Fixed
Drawout
Switch-disconnector version
Front connection
Rear connection
Type of Micrologic control unit
Left
F
D
Yes
Yes
Yes
A, E, P, H
Left
F
D
No
Yes
Yes
A, E, P, H
Left
F
D
No
Yes
Yes
A, E, P, H
Left
F
D
Yes
Yes
Yes
A, E, P, H
Left or right
F
D
Yes
Yes up to 3200 A
Yes
A, E, P, H
NW08...NW16
N1
NT12, NT16
NW08...NW40
H1
H1
H2
L1
H1
H2
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
Connection
Drawout
FC
RC
Fixed
FC
RC
Dimensions (mm) H x W x D
Drawout
3P
4P
Fixed
3P
4P
Weight (kg) (approximate)
Drawout
3P/4P
Fixed
3P/4P
N1
H1
H2
L1
H10
b
b
b
b
b
b
b
b
b
b
b
b
b
b
NW20
H1
H2
H3
L1
H10
b
b
b
b
b
b
b
b
b
b
b
b
Connection
Drawout
FC
RC
Fixed
FC
RC
Dimensions (mm) H x W x D
Drawout
3P
4P
Fixed
3P
4P
Weight (kg) (approximate)
Drawout
3P/4P
Fixed
3P/4P
A-2
208E_CATALOGUE.indb 2
09/12/2014 14:15:55
Special applications
H2
H3
L1
NW H10
High-performance
circuit breaker for
heavy industry
with high
short-circuit
currents
Incoming device
with very high
performance for
critical
applications
1000 V systems,
e.g. mines and
wind power
100 kA
-
150 kA
-
Limiting circuit
breaker for
protection of
cable-type feeders
or upgraded
transformer
ratings
150 kA
-
NW H2 with
NW10...NW40
corrosion
N DC
protection
Environments with DC system
high sulphur
contents
50 kA
-
100 kA
-
Left or right
F
D
Yes
Yes up to 3200 A
Yes
A, E, P, H
Left
D
Yes
Yes up to 3200 A
Yes
A, E, P, H
Left
D
No
Yes up to 3200 A
Yes
A, E, P, H
Left
D
Yes
No
Yes
A, E, consult us
for P and H
Left
D
Yes
Yes up to 3200 A
Yes
A, E, P, H
H DC
NW earthing
switch
DC system
Installation
earthing
35 kA
85 kA
F
D
Yes
No
Yes
DC Micrologic
F
D
Yes
No
Yes
DC Micrologic
D
Yes
Yes up to 3200 A
Yes
-
H1
H2
H3
H10
H1
H2
b (1)
b
b (1)
b
b (1)
b
b (1)
b
b (1)
b
-
b
-
b
b
b
b
A-3
208E_CATALOGUE.indb 3
09/12/2014 14:15:55
Functions
and characteristics
Circuit breakers
andswitch-disconnectors
characteristics
NT06 to NT16
PB106365A49.eps
Common characteristics
Number of poles
Rated insulation voltage (V)
Impulse withstand voltage (kV)
Rated operational voltage (V AC 50/60 Hz)
Suitability for isolation
Degree of pollution
3/4
1000
12
690
Ui
Uimp
Ue
IEC 60947-2
IEC 60664-1
In
at 40 C/50 C (1)
Icu
220/415 V
440 V
525 V
690 V
% Icu
Basic sweatchgear
Ics
Icw
0.5 s
1s
3s
Icm
220/415 V
440 V
525 V
690 V
240 V
480 V
600 V
Icm
Icw
Ultimate breaking capacity Icu (kA rms) with an external protection relay
Maximum time delay: 350 ms
220 V
440 V
525/690 V
0.5 s
1s
3s
690 V
Durability
Mechanical
without maintenance
C/O cycles x 1000
Type of circuit breaker
Rated current
In (A)
C/O cycles x 1000 Electrical
without maintenance
IEC 60947-2
Type of circuit breaker or switch-disconnector
Rated operationnal current
Ie (A)
C/O cycles x 1000 Electrical
without maintenance
IEC 60947-3
Type of circuit breaker or switch-disconnector
Rated operationnal current
Ie (A)
Motor power
C/O cycles x 1000 Electrical
IEC 60947-3 Annex M/IEC 60947-4-1
without maintenance
440 V (4)
690 V
AC23A
440 V (4)
690V
AC3 (5)
380/415 V (kW)
440 V (kW)
440 V (4)
690 V
A-4
208E_CATALOGUE.indb 4
09/12/2014 14:15:56
Sensor selection
Sensor rating (A)
250 (1)
Ir threshold setting (A)
100 to 250
(1) For circuit breaker NT02, please consult us.
400
160 to 400
630
250 to 630
800
320 to 800
1000
400 to 1000
1250
500 to 1250
1600
640 to 1600
NT06
NT08
NT10
NT12
NT16
630
630
400 to 630
H1
H2
42
50
42
50
42
42
42
42
100 %
B
B
42
42
42
42
24
20
90
88
105
88
105
88
88
88
88
25
25
< 50
800
800
400 to 800
1000
1000
400 to 1000
1250
1250
630 to 1250
H1
H2
42
50
42
50
42
42
42
42
100 %
B
B
42
42
42
42
24
20
90
88
105
88
105
88
88
88
88
25
25
< 50
1600
1600
800 to 1600
42
42
42
50
50
42
L1 (2)
150
130
100
25
A
10
10 x In (3)
330
286
220
52
9
150
100
25
42
42
42
HA
75
75
75
36
36
20
36
50
50
42
HA
75
75
75
36
36
20
36
12.5
H1
H2
630
6
6
3
3
H1/H2/HA
630
6
3
H1/H2/HA
500
y 250
y 300
6
-
L1
3
2
H1
800
6
3
H2
L1
6
3
3
2
H1
1000
6
3
H2
L1
6
3
3
2
H1
1250
6
3
H2
6
3
H1
1600
6
3
H2
6
3
800
6
3
1000
6
3
1250
6
3
1600
3
1
630
250 to 335
300 to 400
800
335 to 450
400 to 500
1000
450 to 560
500 to 630
1000
450 to 560
500 to 630
A-5
208E_CATALOGUE.indb 5
09/12/2014 14:15:56
Functions
and characteristics
Circuit breakers
andswitch-disconnectors
characteristics
NW08 to NW63
PB106363A35.eps
Common characteristics
Number of poles
Rated insulation voltage (V)
Impulse withstand voltage (kV)
Rated operational voltage (V AC 50/60 Hz)
Suitability for isolation
3/4
Ui
1000 1250 for H10, HA10
Uimp
12
12
Ue
690 1150 for H10, HA10
IEC 60947-2
Degree of pollution
at 40 C / 50 C (1)
Icu
Ics
220/415/440 V
525 V
690 V
1150 V
% Icu
Icw
1s
3s
Icm
220/415/440 V
525 V
690 V
1150 V
240/480 V
600 V
Icu
Ics
Icw
220...690 V
% Icu
1s
3s
Icm
220...690 V
Type of switch-disconnector
Rated making capacity (kA peak)
AC23A/AC3 category V AC 50/60 Hz
Icm
220...690 V
1150 V
1s
3s
Icw
Earthing switch
Icw
135
1s
3s
Durability
Mechanical
C/O cycles x 1000
Type of circuit breaker
Rated current
C/O cycles x 1000
Electrical
IE C 60947-2
with maintenance
without maintenance
In (A)
without maintenance
without maintenance
440 V (5)
690 V
1150 V
AC23A
440 V (5)
690 V
AC3 (6)
380/415 V (kW)
440 V (5) (kW)
690 V (kW)
440/690 V (5)
A-6
208E_CATALOGUE.indb 6
09/12/2014 14:15:57
Sensor selection
250 (1)
400
100
160
to 250
to 400
(1) For circuit breaker NW02, please consult us.
630
250
to 630
800
320
to 800
1000
400
to 1000
1250
500
to 1250
1600
630
to 1600
2000
800
to 2000
2500
1000
to 2500
3200
1250
to 3200
4000
1600
to 4000
5000
2000
to 5000
6300
2500
to 6300
NW20
800
800
400
to 800
N1
42
42
42
100 %
B
42
22
88
88
88
25
< 70
1000
1000
400
to 1000
H1
65
65
65
-
1250
1250
630
to 1250
H2
100
85
85
-
1600
1600
800 to 1600
2000
2000
1000 to 2000
H10
50
H1
65
65
65
-
H2
100
85
85
-
H3
150
130
100
-
L1 (2)
150
130
100
-
H10
50
H3
150
130
100
-
H10
50
85
50
190
220
187
187
25
30
30
80
330
286
220
10
50
50
105
25
65
36
143
143
143
25
< 70
85
75
190
220
187
187
25
65
65
150
330
286
220
25
30
30
80
330
286
220
10
50
50
105
25
85
75
190
220
187
187
25
65
65
150
330
286
220
25
50
50
105
25
4000
4000
2000
to 4000
H1
100
100
100
100 %
B
100
100
220
220
220
25
< 80
5000
5000
2500
to 5000
H2
150
130
100
-
65
36
143
143
143
25
N1
42
42
42
100 %
B
42
22
88
88
88
25
< 70
3200
3200
1600
to 3200
H2
100
85
85
-
4000
4000
2000 to 4000
L1 (2)
150
130
100
-
2500
2500
1250
to 2500
H1
65
65
65
100 %
B
65
65
143
143
143
25
< 70
42
42
65
65
100
85
150
100
42
42
65
65
100
85
150
100
150
100
65
65
100
85
150
100
100
100
150
100
HA
50
100 %
50
36
-
HF (3)
85
HF (3)
85
85
75
-
HA
55
100 %
55
55
-
HF (3)
85
85
50
-
HA
50
100 %
50
36
-
85
75
-
HA
85
100 %
85
85
-
105
187
105
187
121
187
187
NW08/NW10/NW12/NW16
NA
88
42
-
HA
105
50
36
HF
187
85
50
NW20
HA10
105
50
50
HA
105
50
36
HF
187
85
75
1600
670 to 900
800 to 1000
1250 to 1600
20
10
N1/H1/H2 H3
2000
8
2
6
2
H1/H2/H3/HA/HF
2000
8
6
H1/H2/H3/HA/HF
2000
900 to 1150
1000 to 1300
1600 to 2000
HA10
105
50
50
NW25/NW32/NW40
HA
121
55
55
HF
187
85
75
HA10
105
50
50
6300
6300
3200
to 6300
100
100
270
330
286
220
25
NW40b/NW50/NW63
HA
187
85
85
60
50
25
12.5
N1/H1/H2
L1
800/1000/1250/1600
10
3
10
3
H1/H2/NA/HA/HF
800/1000/1250/1600
10
10
H1/H2/NA/HA/HF
800
1000
335 to 450
450 to 560
400 to 500
500 to 630
y 800
800 to 1000
6
H10
0.5
1250
560 to 670
500 to 800
1000 to 1250
L1
H10
3
3
-
0.5
H1/H2
H3
2500/3200/4000
5
1.25
2.5
1.25
H1/H2/H3/HA/HF
2500/3200/4000
5
2.5
H10
0.5
10
5
H1
H2
4000b/5000/6300
1.5
1.5
1.5
1.5
H1/H2/HA
4000b/5000/6300
1.5
1.5
A-7
208E_CATALOGUE.indb 7
09/12/2014 14:15:58
Functions
and characteristics
Dependability
Overview of functions
Accessories
DB101116.eps
2.0 E
Current protection
X Y Z
Protection:
long time
+ instantaneous
X: type of protection
bb 2 for basic protection
bb 5 for selective protection
bb 6 for selective + earth-fault protection
bb 7 for selective + earth-leakage protection.
Y: control-unit generation
Identification of the control-unit generation.
0 signifies the first generation.
DB101117.eps
Z: type of measurement
bb A for ammeter
bb E for energy
bb P for power meter
bb H for harmonic meter.
PB100772-32.eps
PB106351A32.eps
Protection:
long time
+ short time
+ instantaneous
DB101118.eps
DB101117.eps
DB101119.eps
DB101117.eps
A-8
208E_CATALOGUE.indb 8
09/12/2014 14:16:00
2.0 E
Micrologic 2.0 A
DB127405.eps
100 %
100 %
40 %
40 %
menu
menu
long time
alarm
100 %
40 %
menu
menu
long time
alarm
short time
alarm
6.0 E
6.0 P
Micrologic 6.0 E
6.0 H
DB101124.eps
short time
DB127408.eps
DB101123.eps
5.0 H
100 %
40 %
6.0 A
5.0 P
Micrologic 5.0 E
DB101122.eps
5.0 E
Micrologic 5.0 A
long time
alarm
instantaneous
DB127407.eps
DB127406.eps
instantaneous
DB101122.eps
long time
5.0 A
Micrologic 2.0 E
DB101124.eps
2.0 A
DB127404.eps
A: ammeter
bb I1, I2, I3, IN, Iearth-fault, Iearth-leakage and maximeter for these measurements
bb fault indications
bb settings in amperes and in seconds.
E: Energy
P: A + power meter + programmable protection
bb incorporates all the rms bb measurements of V, A, W, VAR, VA, Wh, VARh, VAh, Hz, Vpeak, Apeak, power factor and
measurements of
maximeters and minimeters
Micrologic A, plus voltage, bb IDMTL long-time protection, minimum and maximum voltage and frequency, voltage
power factor, power and
and current imbalance, phase sequence, reverse power
energy metering
bb load shedding and reconnection depending on power or current
measurements
bb measurements of interrupted currents, differentiated fault indications,
bb calculates the current
maintenance indications, H: P + harmonics
demand value
bb power quality: fundamentals, distortion, amplitude and
bb "Quickview" function for event histories and
time-stamping, etc.
phase of harmonics up to the 31st order
the automatic cyclical
bb waveform capture after fault, alarm or on request
display of the most useful
bb enhanced alarm programming: thresholds and actions.
values (as standard or by
selection).
100 %
40 %
menu
long time
alarm
short time
7.0 H
DB101124.eps
7.0 P
DB101124.eps
7.0 A
DB101123.eps
ground fault
A-9
208E_CATALOGUE.indb 9
09/12/2014 14:16:00
Functions
and characteristics
"Ammeter" measurements
Micrologic A ammeter
DB401463.eps
Communication option
In conjunction with the COM communication option, the control unit transmits the
following:
bb settings
bb all ammeter measurements
bb tripping causes
bb maximeter readings.
Protection
Protection thresholds and delays are set using the adjustment dials.
Overload protection
True rms long-time protection.
Thermal memory: thermal image before and after tripping.
Setting accuracy may be enhanced by limiting the setting range using a different
long-time rating plug.
Overload protection can be cancelled using a specific LT rating plug "Off".
Short-circuit protection
Short-time (rms) and instantaneous protection.
Selection of I2t type (ON or OFF) for short-time delay.
Earth-fault protection
Residual or source ground return earth fault protection.
Selection of I2t type (ON or OFF) for delay.
Residual earth-leakage protection (Vigi).
Operation without an external power supply.
q Protected against nuisance tripping.
k DC-component withstand class A up to 10 A.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral
protection at Ir (4P 4d).
Zone selective interlocking (ZSI)
A ZSI terminal block may be used to interconnect a number of control units to provide
total discrimination for short-time and earth-fault protection, without a delay before
tripping.
Overload alarm
A yellow alarm LED goes on when the current exceeds the long-time trip threshold.
Fault indications
1 long-time threshold and tripping delay
2 overload alarm (LED) at 1,125 Ir
3 short-time pick-up and tripping delay
4 instantaneous pick-up
5 earth-leakage or earth-fault pick-up and tripping delay
6 earth-leakage or earth-fault test button
7 long-time rating plug screw
8 test connector
9 lamp test, reset and battery test
10 indication of tripping cause
11 digital display
12 three-phase bargraph and ammeter
13 navigation buttons
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit breaker operation. For Micrologic 6.0 A and 7.0 A control units,
the operation of earth-fault or earth-leakage protection can be checked by pressing
the test button located above the test connector.
A-10
208E_CATALOGUE.indb 10
09/12/2014 14:16:01
Micrologic 2.0 A
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
1.5
Ammeter
Type of measurements
Instantaneous currents
10
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
I2t Off
I2t On
tsd (max resettable time)
tsd (max break time)
ANSI Code 50
Ii = In x
1.5
2.5
10
0
20
80
0.1
0.1
80
140
0.2
0.2
140
200
0.3
0.3
230
320
0.4
0.4
350
500
10
12
15
off
D
0.5
0.5
800
0.3
0.3
230
320
E
0.6
0.6
880
0.4
0.4
350
500
F
0.7
0.7
960
G
0.8
0.8
1040
H
0.9
0.9
1120
J
1
1
1200
10
20
30
350
350
500
800
800
1000
DB101127.eps
I2t Off
I2t On
tg (max resettable time)
tg (max break time)
ANSI Code 51G
IDn
Micrologic 6.0 A
A
B
C
0.3
0.3
0.4
0.2
0.3
0.4
500 640 720
0
0.1
0.2
0.1
0.2
20
80
140
80
140 200
Micrologic 7.0 A
0.5
1
2
Settings
Dt (max resettable time)
Dt (max break time)
60
60
140
140
140
200
230
230
320
DB101128.eps
Earth fault
Pick-up (A)
Accuracy: 10 %
2.5
DB101129.eps
Protection
Long time
ANSI Code 49
Current setting (A)
Ir = In x
Tripping between 1.05 and 1.20 x Ir
Time setting
Time delay (s)
Accuracy: 0 to -30 %
Accuracy: 0 to -20 %
Accuracy: 0 to -20 %
Thermal memory
(1) 0 to -40 % - (2) 0 to -60 %
Short time
ANSI Code 51
Pick-up (A)
Isd = Ir x
Accuracy: 10 %
Settings
Time setting tsd (s)
0.4
0.5
0.6
0.7
0.8
0.9
0.95 0.98 1
Other ranges or disable by changing long-time rating plug
0.5
1
2
4
8
12
16
20
24
12.5 25
50
100 200 300 400 500 600
2
4
8
12
16
20
24
0.7(1) 1
5.5
8.3
11
13.8 16.6
0.7(2) 0.69 1.38 2.7
20 minutes before and after tripping
DB101126.eps
Protection
Long time
ANSI Code 49
Current setting (A)
Tripping between 1.05 and 1.20 x Ir
Time setting
Time delay (s)
Accuracy: 0 to -30 %
Accuracy: 0 to -20 %
Accuracy: 0 to -20 %
Thermal memory
(1) 0 to -40 % - (2) 0 to -60 %
Instantaneous
ANSI Code 50
Pick-up (A)
Isd = Ir x
Accuracy: 10 %
Time delay
Range
0.2 x In to 1.2 x In
I1, I2, I3, IN
0.2 x In to In
Ig (6.0 A)
0 to 30 A
IDn (7.0 A)
0.2 x In to 1.2 x In
Current maximeters of
I1, I2, I3, IN
Note: all current-based protection functions require no auxiliary source.
The test / reset button resets maximeters, clears the tripping indication and tests the battery.
Accuracy
1.5 %
10 %
1.5 %
1.5 %
A-11
208E_CATALOGUE.indb 11
09/12/2014 14:16:01
DB126649.eps
Functions
and characteristics
Micrologic E energy
Communication option
In conjunction with the COM communication option, the control unit transmits the
following:
bb settings
bb all "ammeter" and "energy" measurements
bb enable connection to FDM
bb tripping causes
bb maximeter / minimeter readings.
Protection
14
15
Protection thresholds and delays are set using the adjustment dials.
Overload protection
True rms long-time protection.
Thermal memory: thermal image before and after tripping.
Setting accuracy may be enhanced by limiting the setting range using a different
long-time rating plug. Overload protection can be cancelled using a specific LT
rating plug "Off".
Short-circuit protection
Short-time (rms) and instantaneous protection.
Selection of I2t type (ON or OFF) for short-time delay.
Earth-fault protection
Source ground return earth fault protection.
Selection of I2t type (ON or OFF) for delay.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral
protection at Ir (4P 4d).
Zone selective interlocking (ZSI)
A ZSI terminal block may be used to interconnect a number of control units to provide
total discrimination for short-time and earth-fault protection, without a delay before
tripping.
Overload alarm
A yellow alarm LED goes on when the current exceeds the long-time trip threshold.
The M2C (two contacts) programmable contacts may be used to signal envents
(Ir, Isd, Alarm Ir, Alarm Ig, Ig). They can be programmed using the keypad on the
Micrologic E control unit or remotely using the COM option (BCM ULP).
Fault indications
1 long-time threshold and tripping delay
2 overload alarm (LED) at 1,125 Ir
3 short-time pick-up and tripping delay
4 instantaneous pick-up
5 earth-leakage or earth-fault pick-up and tripping delay
6 earth-leakage or earth-fault test button
7 long-time rating plug screw
8 test connector
9 lamp test, reset and battery test
10 indication of tripping cause
11 digital display
12 three-phase bargraph and ammeter
13 navigation button "quick View" (only with Micrologic E)
14 navigation button to view menu contents
15 navigation button to change menu
Test
(1) Display on FDM only.
Note: Micrologic E control units come with a transparent
lead-seal cover as standard.
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit breaker operation. For Micrologic 6.0 E control units, the
operation of earth-fault or earth-leakage protection can be checked by pressing the
test button located above the test connector.
A-12
208E_CATALOGUE.indb 12
09/12/2014 14:16:02
Micrologic 2.0 E
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
1.5
Earth fault
Pick-up (A)
Accuracy: 10 %
Energy
Type of measurements
Instantaneous currents
2.5
10
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
I2t Off
I2t On
tsd (max resettable time)
tsd (max break time)
ANSI Code 50
Ii = In x
1.5
2.5
10
0
20
80
0.1
0.1
80
140
0.2
0.2
140
200
0.3
0.3
230
320
0.4
0.4
350
500
10
12
15
off
E
0.6
0.6
880
0.4
0.4
350
500
F
0.7
0.7
960
G
0.8
0.8
1040
H
0.9
0.9
1120
J
1
1
1200
I2t Off
I2t On
tg (max resettable time)
tg (max break time)
Micrologic 6.0 E
A
B
C
0.3
0.3
0.4
0.2
0.3
0.4
500 640 720
0
0.1
0.2
0.1
0.2
20
80
140
80
140 200
D
0.5
0.5
800
0.3
0.3
230
320
DB101128.eps
Protection
Long time
ANSI Code 49
Current setting (A)
Ir = In x
Tripping between 1.05 and 1.20 x Ir
Time setting
Time delay (s)
Accuracy: 0 to -30 %
Accuracy: 0 to -20 %
Accuracy: 0 to -20 %
Thermal memory
(1) 0 to -40 % - (2) 0 to -60 %
Short time
ANSI Code 51
Pick-up (A)
Isd = Ir x
Accuracy: 10 %
Settings
Time setting tsd (s)
0.4
0.5
0.6
0.7
0.8
0.9
0.95 0.98 1
Other ranges or disable by changing long-time rating plug
0.5
1
2
4
8
12
16
20
24
12.5 25
50
100 200 300 400 500 600
2
4
8
12
16
20
24
0.7 (1) 1
5.5
8.3
11
13.8 16.6
0.7 (2) 0.69 1.38 2.7
20 minutes before and after tripping
DB101127.eps
Long time
ANSI Code 49
Current setting (A)
Tripping between 1.05 and 1.20 x Ir
Time setting
Time delay (s)
Accuracy: 0 to -30 %
Accuracy: 0 to -20 %
Accuracy: 0 to -20 %
Thermal memory
(1) 0 to -40 % - (2) 0 to -60 %
Instantaneous
ANSI Code 50
Pick-up (A)
Isd = Ir x
Accuracy: 10 %
Time delay
DB101126.eps
Protection
Range
0.2 x In to 1.2 x In
I1, I2, I3, IN
Ig (6.0 E)
0.05 x In to In
0.2 x In to 1.2 x In
Current maximeters of
I1, I2, I3, IN
0.2 x In to 1.2 x In
Demand currents of I1, I2, I3, Ig
Voltages
V12, V23, V31, V1N, V2N, V3N 100 to 690 V
Active power
P
30 to 2000 kW
Power factor
PF
0 to 1
Demand power
P demand
30 to 2000 kW
Active energy
Ep
-1010 GWh to 1010 GWh
Note: all current-based protection functions require no auxiliary source.
The test / reset button resets maximeters, clears the tripping indication and tests the battery.
Accuracy
1.5 %
10 %
1.5 %
1.5 %
0.5 %
2 %
2 %
2 %
2 %
A-13
208E_CATALOGUE.indb 13
09/12/2014 14:16:02
Functions
and characteristics
Protection.........................................................
Protection settings
DB120968.eps
Depending on the thresholds and time delays set using the keypad or remotely using
the COM option (BCM ULP), the Micrologic P control unit monitors currents and
voltage, power, frequency and the phase sequence. Each threshold overrun is
signalled remotely via the COM option (BCM ULP). Each threshold overrun may be
combined with tripping (protection) or an indication carried out by an optional M2C
or M6C programmable contact (alarm), or both (protection and alarm).
Load shedding and reconnection parameters may be set according to the power
or the current flowing through the circuit breaker. Load shedding is carried out by
a supervisor via the COM option (BCM ULP) or by an M2C or M6C programmable
contact.
The M2C (two contacts) and M6C (six contacts) auxiliary contacts may be used
to signal threshold overruns or status changes. They can be programmed using
the keypad on the Micrologic P control unit or remotely using the COM option
(BCM ULP).
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
A-14
208E_CATALOGUE.indb 14
09/12/2014 14:16:03
Settings
I2t Off
I2t On
tsd (max resettable time)
tsd (max break time)
ANSI Code 50
Ii = In x
0
20
80
0.1
0.1
80
140
0.2
0.2
140
200
0.3
0.3
230
320
0.4
0.4
350
500
I2t Off
I2t On
tg (max resettable time)
tg (max break time)
ANSI Code 51G
IDn
Settings
Dt (max resettable time)
Dt (max break time)
60
60
140
ANSI Code 46
Iunbalance
Imax demand : I1, I2, I3, IN,
Uunbalance
Umin
Umax
10
10
12
15
off
D
0.5
0.5
800
0.3
0.3
230
320
E
0.6
0.6
880
0.4
0.4
350
500
F
0.7
0.7
960
G
0.8
0.8
1040
H
0.9
0.9
1120
J
1
1
1200
10
20
30
140
140
200
230
230
320
350
350
500
800
800
1000
Threshold
0.05 to 0.6 Iaverage
0.2 In to In
Delay
1 to 40 s
15 to 1500 s
1 to 10 s
10 to 100 % In (3)
ANSI Code
47
2 to 30 % x Uaverage
1 to 40 s
27
100 to Umax between phases 1.2 to 10 s
59
Umin to 1200 between phases 1.2 to 10 s
rP
32P
5 to 500 kW
0.2 to 20 s
Fmin
Fmax
81L
81H
45 to Fmax
Fmin to 440 Hz
1.2 to 5 s
1.2 to 5 s
1/2/3 or 1/3/2
0.3 s
Measured value
Current
Power
2.5
Micrologic 6.0 P
A
B
C
0.3 0.3 0.4
0.2 0.3 0.4
500 640 720
0
0.1 0.2
0.1 0.2
20
80
140
80
140 200
Micrologic 7.0 P
0.5 1
2
It
Voltage
Voltage unbalance
Minimum voltage
Maximum voltage (4)
Power
Reverse power
Frequency
Minimum frequency
Maximum frequency
Phase sequence
Sequence (alarm)
Current
Current unbalance
Max. demand current
Earth fault alarm
1.5
I
P
DB101128.eps
ANSI Code 51
Isd = Ir x
DB101129.eps
Earth fault
Pick-up (A)
Accuracy: 10 %
DB101142.eps
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
Threshold
0.5 to 1 Ir per phases
200 kW to 10 MW
Delay
20 % tr to 80 % tr
10 to 3600 s
DB101143.eps
Thermal memory
(1) 0 to -40 % - (2) 0 to -60 %
Short time (rms)
Pick-up (A)
Accuracy: 10 %
Time setting tsd (s)
DB101130.eps
Protection
(3) In y 400 A 30 %
400 A < In < 1250 A 20 %
In u 1250 A 10 %
(4) For 690 V applications, a step-down transformer must be used if the voltage exceeds the nominal value of 690 V by more than 10 %.
Note: all current-based protection functions require no auxiliary source.
Voltage-based protection functions are connected to AC power via a voltage measurement input built into the circuit breaker.
A-15
208E_CATALOGUE.indb 15
09/12/2014 14:16:03
Default display.
Measurements..........................................................
DB101134.eps
DB101133.eps
Functions
and characteristics
The Micrologic P control unit calculates in real time all the electrical values (V, A, W,
VAR, VA, Wh, VARh, VAh, Hz), power factors and cosj factors.
The Micrologic P control unit also calculates demand current and demand power
over an adjustable time period. Each measurement is associated with a minimeter
and a maximeter.
In the event of tripping on a fault, the interrupted current is stored. The optional
external power supply makes it possible to display the value with the circuit breaker
open or not supplied.
Display of a maximum
current.
Instantaneous values
The value displayed on the screen is refreshed every second.
Minimum and maximum values of measurements are stored in memory (minimeters
and maximeters).
Currents
DB101133.eps
DB101133.eps
I rms
I max rms
Voltages
U rms
V rms
U average rms
U unbalance
Power, energy
P active, Q reactive, S apparent
E active, E reactive, E apparent
Display of a power.
DB101138.eps
DB101137.eps
Display of a voltage.
Power factor
Frequencies
F
A
A
A
A
1
E-fault
1
E-fault
V
V
V
%
12
23
31
1N
2N
3N
(U12 + U23 + U31) / 3
W, Var, VA
Wh, VARh, VAh
Totals
Totals consumed - supplied
Totals consumed
Totals supplied
PF
Total
3
N
E-leakage
3
N
E-leakage
Hz
Demand metering
The demand is calculated over a fixed or sliding time window that may be
programmed from 5 to 60 minutes. According to the contract signed with the power
supplier, an indicator associated with a load shedding function makes it possible to
avoid or minimise the costs of overrunning the subscribed power. Maximum demand
values are systematically stored and time stamped (maximeter).
Currents
I demand
I max demand
Display of a frequency.
Power
P, Q, S demand
P, Q, S max demand
A
A
A
A
1
E-fault
1
E-fault
W, Var, VA
W, Var, VA
Totals
Totals
2
2
3
N
E-leakage
3
N
E-leakage
screen 2b.eps
Logiciel PME.
Additional info
Accuracy of measurements (including sensors):
bb voltage (V) 0.5 %
bb current (A) 1.5 %
bb frequency (Hz) 0.1 %
bb power (W) and energy (Wh) 2 %.
A-16
208E_CATALOGUE.indb 16
09/12/2014 14:16:05
DB101140.eps
DB117041.eps
The last ten trips and alarms are recorded in two separate history files that may be
displayed on the screen:
bb tripping history:
vv type of fault
vv date and time
vv values measured at the time of tripping (interrupted current, etc.)
bb alarm history:
vv type of alarm
vv date and time
vv values measured at the time of the alarm.
Display after tripping.
All the other events are recorded in a third history file which is only accessible
through the communication network.
bb Event log history (only accessible through the communication network)
vv modifications to settings and parameters
vv counter resets
vv system faults
vv fallback position
vv thermal self-protection
vv loss of time
vv overrun of wear indicators
vv test-kit connections
vv etc.
Note: all the events are time stampled: time-stamping is activated as soon as time is set
manually or by a supervisor. No external power supply module is required (max. drift of 1 hour
per year).
Safety
Measurement functions are independent of the protection functions.
The high-accuracy measurement module operates independently of the protection
module.
Simplicity and multi-language
Navigation from one display to another is intuitive. The six buttons on the keypad
provide access to the menus and easy selection of values. When the setting cover is
closed, the keypad may no longer be used to access the protection settings, but still
provides access to the displays for measurements, histories, indicators, etc.
Micrologic is also multi-language, including the following languages: English,
Spanish, Portuguese, Russian, Chinese, French, German...
Intelligent measurement
Measurement-calculation mode:
bb energies are calculated on the basis of the instantaneous power values, in two
manners:
vv the traditional mode where only positive (consumed) energies are considered
vv the signed mode where the positive (consumed) and negative (supplied) energies
are considered separately
bb measurement functions implement the new zero blind time concept which
consists in continuously measuring signals at a high sampling rate. The traditional
blind window used to process samples no longer exists. This method ensures
accurate energy calculations even for highly variable loads (welding machines,
robots, etc.).
Always powered
All current-based protection functions require no auxiliary source. Voltage-based
protection functions are connected to AC power via a voltage measurement input
built into the circuit breaker.
Stored information
The fine setting adjustments, the last 100 events and the maintenance register
remain in the control-unit memory even when power is lost.
A-17
208E_CATALOGUE.indb 17
09/12/2014 14:16:05
Functions
and characteristics
Micrologic H harmonics
Measurements.................................................................................
The Micrologic H control unit offers all the measurements carried out
by Micrologic P, with in addition:
bb phase by phase measurements of:
vv power, energy
vv power factors
bb calculation of:
vv current and voltage total harmonic distortion (THD)
vv current, voltage and power fundamentals
vv current and voltage harmonics up to the 31st order.
DB117437.eps
A
A
A
A
1
E-fault
1
E-fault
V
V
V
%
12
23
31
1N
2N
3N
(U12 + U23 + U31) / 3
W, Var, VA
Wh, VARh, VAh
Power factor
PF
Totals
1
2
Totals consumed - supplied
Totals consumed
Totals supplied
Total
1
2
I max rms
2
2
3
N
E-leakage
3
N
E-leakage
Voltages
U rms
V rms
U average rms
U unbalance
Power, energy
3
Frequencies
F
Hz
Power-quality indicators
Total fundamentals
U I P Q S
THD
%
U I
U and Iharmonics
Amplitude
3 5 7 9 11 13
Harmonics 3, 5, 7, 9, 11 and 13, monitored by electrical utilities, are displayed on the screen.
Demand measurements
Similar to the Micrologic P control unit, the demand values are calculated over a fixed
or sliding time window that may be set from 5 to 60 minutes.
Currents
I demand
I max demand
A
A
A
A
1
E-fault
1
E-fault
W, Var, VA
W, Var, VA
Totals
Totals
2
2
3
N
E-leakage
3
N
E-leakage
Power
P, Q, S demand
P, Q, S max demand
Maximeters
Only the current maximeters may be displayed on the screen.
A-18
208E_CATALOGUE.indb 18
09/12/2014 14:16:05
208E_CATALOGUE.indb 19
09/12/2014 14:16:05
Functions
and characteristics
DB125911.eps
Display....................................................................
DB417640.eps
Main Menu
Quick view
Metering
Control
Alarms
12:00:05
S1-1 - Lighting/Level1
Quick view
Open
Alarm history
Control
OK
Ir
Maintenance
000 A
ESC
310
%
I3 302
315
%
ESC
S1-1 - Lighting/Level1
Quick view
Alarm history
Control
Maintenance
4/7
402 V
100
120
398 V
100
120
401 V
100
120
Quick view
Control
Maintenance
12:00:05
64
kW
kVar
51
kVA
Quick view
Control
ESC
Maintenance
12:00:05
kWh
8325
kVarh
Es
13035
kVAh
1/12
12:00:05
S1-1 - Lighting/Level1
Quick view
Alarm history
Control
U-V
E cumul
EpIn
EpOut
Maintenance
ESC
FDM121 display:
consumption.
Examples of measurement
screens on the FDM121
display unit.
PQS
127 kW
13 kVAr
129 kVA
Ptot
Qtot
Stot
20.12.2011
Measures
ESC
U-V
PQS
DB414403.eps
DB112134.eps
14397
V
V
V
1/10
ESC
Eq
406
415
409
The Micrologic continuously display the RMS value of the highest current of the three
phases and neutral (Imax). The navigation buttons can be used to scroll through the
main measurements.
In the event of a fault trip, the trip cause is displayed.
The Micrologic A measures phase, neutral, ground fault currents.
The Micrologic E offers voltage, power, Power Factor, measurements in addition to
the measurements provided by Micrologic A.
The Micrologic P/H offer frequency, cos.j in addition to the measurements provided
by Micrologic E.
Maximeters / minimeters
S1-1 - Lighting/Level1
Alarm history
PQS
20.12.2011
Measures
Ep
U-V
VL L
VL-L
V12
V23
V31
For all FDM, in addition to the information displayed on the Micrologic LCD, the FDM
screen shows demand, power quality and maximeter/minimeter values along with
histories and maintenance indicators.
Measurements.......................................................
DB414402.eps
DB112133.eps
38
A
A
A
A
1/10
ESC
S1-1 - Lighting/Level1
Measures
ESC
PQS
431
385
426
2
I1
I2
I3
IN
20.12.2011
Alarm history
PQS
U-V
I Current
DB414401.eps
DB112132.eps
U3
12:00:05
ESC
U2
The FDM121 switchboard display unit can be connected to a COM option (BCM
ULP) using a breaker ULP cord to display all measurements on a screen (1). The
result is a veritable 96 x 96 mm Power Meter.
The FMD121 display unit requires a 24 V DC power supply. The COM option (BCM
ULP) unit is supplied by the same power supply via the breaker ULP cord connecting
it to the FDM121.
Measures
U1
%
IN 23
000 A
I1
1/7
DB414400.eps
DB112131.eps
I1
Auto
Measures
Services
ESC
20.12.2011
1/3
FDM128 display:
consumption.
PQS
E
Reset
165 kWh
45 kWh
Energy metering
The Micrologic E/P/H also measures the energy consumed since the last reset of the
meter. The active energy meter can be reset via Micrologic keypad or the FDM
display unit or the communication system.
Micrologic E/P/H also calculates demand current and power values. These
calculations can be made using a block or sliding interval that can be set from 5 to 60
minutes in steps of 1 minute. The window can be synchronised with a signal sent via
the communication system. Whatever the calculation method, the calculated values
can be recovered on a PC via Modbus communication.
Ordinary spreadsheet software can be used to provide trend curves and forecasts
based on this data. They will provide a basis for load shedding and reconnection
operations used to adjust consumption to the subscribed power.
Power quality
Micrologic H calculates power quality indicators taking into account the presence of
harmonics up to the 15th order, including the total harmonic distortion (THD) of
current and voltage.
A-20
208E_CATALOGUE.indb 20
09/12/2014 14:16:08
PB111801-21_r.eps
PB103360.eps
PB106363A35.eps
Type
A/E
P/H
A/E
Average of phases
Display
Micrologic
LCD
FDM display
P/H
A/E
P/H
A/E
P/H
A/E
P/H
% Ig (pick-up setting)
A/E
P/H
% Iavg
- /E
P/H
Phase-to-phase
- /E
P/H
Phase-to-neutral
- /E
P/H
- /E
P/H
- /E
P/H
- /E
P/H
Phase sequence
1-2-3, 1-3-2
-/-
P/H
b (3)
Frequency (Hz)
Power system
-/-
P/H
Power
Active (kW)
P, total
- /E
P/H
P, per phase
- /E
P/H
b (2)
Q, total
- /E
P/H
Q, per phase
-/-
P/H
S, total
- /E
P/H
S, per phase
-/-
P/H
PF, total
- /E
P/H
-/-
P/H
Cos.j, total
-/-
P/H
-/-
P/H
A/E
P/H
- /E
P/H
- /E
P/H
Measurements
Instantaneous rms measurements
Currents (A)
Voltages (V)
Reactive (kVAR)
Apparent (kVA)
Power Factor
Cos.j
Maximeters / minimeters
Energy metering
Energy
- /E
P/H
b (2)
Demand power
- /E
P/H
- /E
P/H
b (2)
- /E
P/H
-/-
-/-
Calculation window
Power quality
Total harmonic
distortion (%)
A-21
208E_CATALOGUE.indb 21
09/12/2014 14:16:09
Functions
and characteristics
Operating-assistance functions
Micrologic A/E/P/H control unit
with COM option (BCM ULP)
Histories.................................................................
bb Trip indications in clear text in a number of user-selectable languages.
bb Time-stamping: date and time of trip.
Maintenance indicators.........................................
Micrologic control unit have indicators for, among others, the number of operating
cycles, contact wear P/H, load profile and operating times (operating hours counter)
of the Masterpact circuit breaker.
It is possible to assign an alarm to the operating cycle counter to plan maintenance.
The various indicators can be used together with the trip histories to analyse the
level of stresses the device has been subjected to.
Each circuit breaker equipped with a COM option (BCM ULP) can be identified via
the communication system:
bb serial number
bb firmware version
bb hardware version
bb device name assigned by the user.
This information together with the previously described indications provides a clear
view of the installed devices.
A-22
208E_CATALOGUE.indb 22
09/12/2014 14:16:10
PB111801-21_r.eps
PB103360.eps
PB106363A35.eps
Type
A/E
P/H
- /E
Mechanical cycles
Assignable to an alarm
Electrical cycles
Assignable to an alarm
Hours
Indicator
Load profile
Display
Micrologic
LCD
FDM display
P/H
A/E
P/H
A/E
P/H
A/E
P/H
Contact wear
-/-
P/H
A/E
P/H
Operating assistance
Trip history
Trips
Cause of tripping
Maintenance indicators
Counter
Each time Masterpact opens, the Micrologic P/H trip unit measures the interrupted current and
increments the contact-wear indicator as a function of the interrupted current, according to test
results stored in memory. Breaking under normal load conditions results in a very slight
increment. The indicator value may be read on the FDM display.
It provides an estimation of contact wear calculated on the basis of the cumulative forces
affecting the circuit breaker. When the indicator reaches 100 %, it is advised to inspect the circuit
breaker to ensure the availability of the protected equipment.
Micrologic A/E/P/H calculates the load profile of the circuit breaker protecting a load circuit.
The profile indicates the percentage of the total operating time at four current levels
(% of breaker In):
bb 0 to 49 % In
bb 50 to 79 % In
bb 80 to 89 % In
bb u 90 % In.
This information can be used to optimise use of the protected equipment or to plan ahead for
extensions.
A-23
208E_CATALOGUE.indb 23
09/12/2014 14:16:10
Functions
and characteristics
Switchboard-display functions
PB103807-32.eps
PB103582-32.eps
Main characteristics
Surface mount accessory.
PB103581-31.eps
FDM121 display.
Mounting
Connection
Connection with FDM121 display unit.
A-24
208E_CATALOGUE.indb 24
09/12/2014 14:16:10
DB112135.eps
310
%
I3 302
I2
315
2 Down
3 OK
%
IN 23
4 Up
5 Context
6 Alarm LED
ESC
2 3 4
5 6
Produit Id
Micrologic 5.3A
Serial number:
P07451
Firmware:
PQS
E
1.02
ESC
1/3
5111947
kWh
EpOut
12345678
kWh
F - PF - cos
OK
Metering: sub-menu.
DB125912.eps
Product identification.
EpIN
Main menu
When powered up, the FDM121 screen automatically displays the ON/OFF status of
the device.
U-V
ESC
NonResettableEnergy
Screens
Metering
LU432091
Part number:
Navigation
DB112136.eps
DB112140.eps
1 Escape
I1
Load Profile
Control
2/3
0..49%
610 H
50...79%
15 H
80..89%
360 H
90..100%
ESC
When not in use, the screen is not backlit. Backlighting can be activated by pressing
one of the buttons. It goes off after 3 minutes.
Fast access to essential information
bb Quick view provides access to five screens that display a summary of essential
operating information (I, U, f, P, E, THD, circuit breaker On / Off).
Access to detailed information
bb "Metering" can be used to display the measurement data (I, U-V, f, P, Q, S, E,
THD, PF) with the corresponding min/max values.
bb Alarms displays active alarms and the alarm history.
bb Services provides access to the operation counters, energy and maximeter reset
bb function, maintenance indicators, identification of modules connected to the
internal bus and FDM121 internal settings (language, contrast, etc.).
3H
ESC
Metering: meter.
Services.
Services.
Ethernet
Modbus-SL
- +
DB416741.eps
- +
DB416695.eps
IFM
ETH2
IFE
OR
1.3 m
C
Red Black
White Blue
E1 E2 E3 E4 E5 E6
E1 E2 E3 E4 E5 E6
B / Rx+ D1
A / Rx- D0
B / Tx+ D1
0V
A Modbus network
B Ethernet network
C Breaker ULP cord
White Blue
Red Black
A / Tx- D0
24 V
B / Rx+ D1
Connections
bb Masterpact is connected to the ULP
devices (FDM121 display, IFM, IFE or
I/O) unit via the breaker ULP cord.
vv cord available in three lengths:
0.35 m, 1.3 m and 3 m.
vv lengths up to 10 m possible using
extensions.
A / Rx- D0
B / Tx+ D1
LV434197
0V
LV434196
A / Tx- D0
24 V
LV434195
D FDM121 display
E ULP termination
F ULP cable
A-25
208E_CATALOGUE.indb 25
09/12/2014 14:16:13
Functions
and characteristics
Switchboard-display functions
Status indications
When the circuit breaker is equipped with the Breaker Status Command Module
(BSCM) and NSX cord, the FDM128 display can also be used to view circuit breaker
status conditions:
bb O/F: ON/OFF
bb SDE: Fault-trip indication (overload, short-circuit, ground fault)
bb CE, CD cradle management with I/O application module.
Remote control
When the circuit breaker is equipped with the BSCM, NSX cord and Communication
Motor Mechanism (MTC), the FDM128 display can also be used to control (open/
close) the circuit breaker.
bb 115.2 x 86.4 mm with 5.7" QVGA display 320 x 240 pixels.
bb Color TFT LCD, LED backlight.
bb Wide viewing angle: vertical 80, horizontal 70.
bb High resolution: excellent reading of graphic symbols.
bb Operating temperature range -10 C to +55 C.
bb CE / UL / CSA marking (pending).
bb 24 V DC power supply, with tolerances 24 V (limit 20.4 - 28.8 V DC).
bb Consumption y 6.8 W.
PB111802-32_r.eps
PB111801-32_r.eps
Main characteristics
Mounting
FDM128 display.
Connection
PB111805-32_r.eps
A-26
208E_CATALOGUE.indb 26
09/12/2014 14:16:14
12:00:05
S1-1 - Lighting/Level1
Quick view
Product ID
Information
Reset all
Counter
Measures
Alarm history
Control
Maintenance
ESC
Operation
xxx
Trip SDE
xxx
Close command
xxx
20.12.2011
12:00:05
S1-1 - Lighting/Level1
Quick view
Energy
Measures
Ep
Eq
Es
Alarm history
Control
11 318 kWh
257 kVArh
13 815 kVAh
Maintenance
ESC
3/3
Product identification.
DB414408.eps
DB414407.eps
DB414405.eps
20.12.2011
6/7
Navigation
Screens
Main menu
Metering: meter.
12:00:05
S1-1 - Lighting/Level1
Quick view
Product ID
Measures
Alarm history
Control
Maintenance
ESC
Services.
Information
Reset all
Metering
Maintenance.
Load profile
0 to 49%
50 to 79%
80 to 89%
Control
90 to 100%
2/3
A-27
208E_CATALOGUE.indb 27
09/12/2014 14:16:17
Functions
and characteristics
Db101524.eps
External sensors
PB100834-48.eps
06133779A.eps
Rectangular sensor.
PB100773-32.eps
Four interchangeable plugs may be used to limit the long-time threshold setting
range for higher accuracy.
The time delay settings indicated on the plugs are for an overload of 6 Ir (for further
details, see the characteristics on page A-11 and page A-15).
Long time rating plug.
PB101026_SE-32A.eps
Standard
Ir = In x 0.4
0.5
0.6
0.7
0.8
0.9
0.95 0.98 1
Low-setting option Ir = In x 0.4
0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.8
High-setting option Ir = In x 0.80 0.82 0.85 0.88 0.90 0.92 0.95 0.98 1
Off plug
No long-time protection (Ir = In for Isd setting)
Important: long-time rating plugs must always be removed before carrying out insulation or
dielectric withstand tests.
The external power-supply module makes it possible to use the display even if the
circuit breaker is open or not supplied (for the exact conditions of use, see the
electrical diagrams part of this catalogue).
This module powers both the control unit (100 mA) and the M2C and M6C
programmable contacts (100 mA).
With the Micrologic A/E control unit, this module makes it possible to display currents
of less than 20 % of In.
With the Micrologic P and H, it can be used to display fault currents after tripping.
If the COM option is used, a second dedicated power supply shall be used.
We recommend to use the AD power supply due to its low stray primary secondary
capacitance. Good operation of the Micrologic trip unit in noisy environment is not
guaranteed with other power supplies.
Characteristics
bb Power supply:
vv 110/130, 200/240, 380/415 V AC, 50/60 Hz (+10 % -15 %)
vv 24/30, 48/60, 100/125 V DC (+20 % -20 %).
bb Output voltage: 24 V DC 5 %, 1 A.
bb Ripple < 1 %.
bb Dielectric withstand : 3.5 kV rms between input/output, for 1 minute.
bb Overvoltage category: as per IEC 60947-1 cat. 4.
A-28
208E_CATALOGUE.indb 28
09/12/2014 14:16:17
PB100771-24.eps
Battery module
The battery module maintains display operation and communication with the
supervisor if the power supply to the Micrologic control unit is interrupted. It is
installed in series between the Micrologic control unit and the AD module.
Characteristics
bb Battery run-time: 4 hours (approximately).
bb Mounted on vertical backplate or symmetrical rail.
Battery module
PB100781-32.eps
PB100774-32.eps
These contacts are optional equipment for the Micrologic E, P and H control units.
They are described with the indication contacts for the circuit breakers.
M2C.
Micrologic
Type E
Types P, H
Characteristics
M2C
M2C/M6C
100 mA/24 V
5
3
1.8
1.5
0.4
0.15
100 mA/24 V
5
3
1.8
1.5
0.4
0.15
Minimum load
Breaking capacity (A)
p.f.: 0.7
M6C.
V AC 240
380
V DC 24
48
125
250
Spare parts
Lead-seal covers
A lead-seal cover controls access to the adjustment dials.
When the cover is closed:
bb it is impossible to modify settings using the keypad unless the settings lockout pin
on the cover is removed
bb the test connector remains accessible
bb the test button for the earth-fault and earth-leakage protection function remains
accessible.
Lead-seal cover.
Characteristics
bb Transparent cover for basic Micrologic and Micrologic A, E control units
bb Non-transparent cover for Micrologic P and H control units.
Spare battery
A battery supplies power to the LEDs identifying the tripping causes.
Battery service life is approximately ten years.
A test button on the front of the control unit is used to check the battery condition.
The battery may be replaced on site when discharged.
PB100837-68.eps
Test equipment
Hand-held test kit
The hand-held mini test kit may be used to:
bb check operation of the control unit and the tripping and pole-opening system
by sending a signal simulating a short-circuit
bb supply power to the control units for settings via the keypad when the circuit
breaker is open (Micrologic P and H control units).
Power source: standard LR6-AA battery.
A-29
208E_CATALOGUE.indb 29
09/12/2014 14:16:18
Functions
and characteristics
Ethernet has become the universal link between switchboards, computers and
communication devices inside the building. The large amount of information which
can be transferred makes the connection of Enerlin'X digital system to hosted web
services of Schneider Electric a reality. More advantages are offered to integrators
thanks to configuration web pages available remotely or on the local Ethernet network.
Products overview
F
B
4
E
Ethernet
Modbus SL
ULP
A-30
208E_CATALOGUE.indb 30
09/12/2014 14:16:21
Function
Port
Com'X 200
Modbus
Energy Server
Master
with Ethernet
Gateway (1) function
Analog. Bin.
Input
Output
Cial. Ref.
Ethernet cable 6
+ WiFi
EBX200
FDM128
Ethernet LCD
colour touch screen
Ethernet
LV434128
FDM121
TRV00121
IFE
interface +
gateway
Ethernet
Ethernet interface (2) Modbus
& Gateway
Master & ULP
LV434011
IFE
interface
Ethernet interface
for circuit breakers
ULP
Ethernet
LV434010
Acti9
Smartlink
Ethernet
Ethernet interface
with Input/Output
functions &
Gateway
Modbus
Master
Ethernet
14
A9XMEA08
Acti9
Smartlink
Modbus
Modbus interface
with Input/Output
functions
Modbus Slave
22
11
A9XMSB11
IFM
Modbus interface
for circuit breaker
ULP
Modbus Slave
TRV00210
I/O
Input/Output
application module
for circuit breaker
ULP
ULP
LV434063
(to device)
A
B
C
D
G
H
ULP
Bin.
Input
(to server)
(1) Gateway: transfers data from a network to another (ie.: Modbus to Ethernet).
(2) Interface: transfers data from an equipment to a network.(ie.: ULP to Modbus).
A-31
208E_CATALOGUE.indb 31
09/12/2014 14:16:25
Communication
Functions
and characteristics
PB108180.eps
G
O
E
A
B
F
K
J
Q
H
I
P
L
L N
0.35 m
1.3 m
3m
LV434195
LV434196
LV434197
D Modbus cable
LV434010 or LV434011
L IFE: Ethernet interface
M External 24 V DC power supply module
0.3 m
0.6 m
1m
2m
3m
5m
TRV00803
TRV00806
TRV00810
TRV00820
TRV00830
TRV00850
Q NSX cord
0.35 m
1.3 m
3m
LV434200
LV434201
LV434202
E Ethernet cable
F FDM121: Front Display Module
TRV00121
LV434128
H Smartlink
A9XMSB11
I Acti9
J ULP line terminators
TRV00880
LV434063
TRV00210
O Com'X 200
Ethernet
Modbus
ULP
24 V DC
A-32
208E_CATALOGUE.indb 32
09/12/2014 14:16:26
Overview of functions
PB104804.eps
Status indications
ON/OFF (O/F)
Spring charged CH
Ready to close
Fault-trip SDE
Connected / disconnected / test position
CE/CD/CT (I/O application module only)
Controls
MX1 open
XF close
Measurements
Instantaneous measurement information
Averaged measurement information
Maximeter / minimeter
Energy metering
Demand for current and power
Power quality
Switchdisconnectors
Circuit breaker
b
b
b
b
b
A
A
A
A
A
E
E
E
E
E
P
P
P
P
P
H
H
H
H
H
b
b
A
A
E
E
P
P
H
H
b
b
b
b
b
b
A
A
E
E
E
E
E
P
P
P
P
P
H
H
H
H
H
H
A
A
A
A
E
E
E
E
P
P
P
P
H
H
H
H
Operating assistance
Protection and alarm settings
Histories
Time stamped event tables
Maintenance indicators
A: Micrologic with ammeter
E: Micrologic Energy
P: Micrologic Power
H: Micrologic Harmonics
Note: see the description of the Micrologic control units for
further details on protection and alarms, measurements,
waveform capture, histories, logs and maintenance indicators.
Modbus principle
The Modbus RS 485 (RTU protocol) system is an open bus on which communicating Modbus
devices (Compact NS with Modbus COM, Power Meter PM700, PM800, Sepam, Vigilohm,
Compact NSX, etc.) are installed. All types of PLCs and microcomputers may be connected to
the bus.
Addresses
The Modbus communication parameters (address, baud rate, parity) are entered using the
keypad on the Micrologic A, E, P, H. For a switch-disconnector, it is necessary to use the
Electrical Asset Manager or RSU (Remote Setting Utility) Micrologic utility.
Number of devices
The maximum number of devices that may be connected to the Modbus bus depends on the
type of device (Compact with Modbus COM, PM700, PM800, Sepam, Vigilohm, Compact NSX,
etc.), the baud rate (19200 is recommended), the volume of data exchanged and the desired
response time. The RS 485 physical layer offers up to 32 connection points on the bus (1 master,
31 slaves).
A fixed device requires only one connection point (communication module on the device). A
drawout device uses two connection points (communication modules on the device and on the
chassis).
The number must never exceed 31 fixed devices or 15 drawout devices.
Length of bus
The maximum recommended length for the Modbus bus is 1200 meters.
Ethernet principle
Ethernet is a data link and physical layer protocol defined by IEEE 802 10 and 100 Mbps
specifications that connects computer or other Ethernet devices. Ethernet is an asynchronous
Carrier Sense Multiple Access with Collision detection (referred as CSMA/CD) protocol. Carrier
Sense means that the hosts can detect whether the medium (coaxial cable) is idle or busy.
Multiple Access means that multiple hosts can be connected to the common medium. Collision
Detection means a host detects whether its transmission has collided with the transmission of
another host (or hosts).
IFE Ethernet interface can be connected to a PC or a laptop over Ethernet. The maximum length
of Ethernet cable is 100 meters. IFE Ethernet interface + gateway provides a Modbus TCP/IP
gateway over Ethernet to enable Modbus TCP communication from a Modbus TCP master to
any Modbus slave devices connected to it. The maximum active Modbus TCP client connection
is twelve.
IFE Ethernet interface has an embedded web server (web page).
The Modbus RS 485 (RTU protocol) system is an open bus on which communicating Modbus
devices (Compact NS with Modbus COM, Power Meter PM700, PM800, Sepam, Vigilohm,
Compact NSX, etc.) are installed. All types of PLCs and microcomputers may be connected to
the bus.
A-33
208E_CATALOGUE.indb 33
09/12/2014 14:16:27
Functions
and characteristics
Communication
For fixed and Drawout devices, the common communication option is made
up of:
bb a BCM ULP module, installed behind the Micrologic control unit and supplied with
its set of sensors (OF, SDE, PF and CH micro switches) its kit for connection to XF
and MX1 communicating voltage releases and its COM terminal block (inputs E1 to
E6). This module is independent of the control unit. It receives and transmits
information on the communication network. An infra-red link transmits data between
the control unit and the communication module.
Consumption: 30 mA, 24 V.
bb IFM, this module required for connection to the network, contains the Modbus
address (1 to 99) declared by the user via the two dials in front. It automatically
adapts (baud rate, parity) to the Modbus network in which it is installed.
PB106674-20.eps
Or
bb IFE, the Ethernet interface for LV circuit breaker enables an intelligent modular
unit (IMU), for example a Masterpact NT/NW or Compact NSX circuit breaker to be
connected to an Ethernet network. Each circuit breaker has its own IFE and a
corresponding IP address.
For drawout device the Cradle Management option must be added:
I/O (Input/Output) application module for LV breaker, the I/O application module is
delivered with withdrawable devices ordered with the COM option, for cradle
management. It must be installed on a DIN rail near the device. It must be connected
to the ULP system and to the position contacts (CD, CT, CE) that transmit the
position of the device in the cradle.
DB416829.eps
BCM ULP.
A-34
208E_CATALOGUE.indb 34
09/12/2014 14:16:27
Communication architecture
Electrical operated
Fixed device
Drawout device
Modbus
DB416883.eps
DB416882.eps
Ethernet
24VDC
Modbus
Ethernet
24VDC
ETH2
ETH1
ETH2
ETH2
ETH1
ETH1
I
tory
(fac
.YY.ZZ
ETH2
ETH1
s-SL
Modbu
set)
IFE_XX
IFE
CT
-100/A
LK/10
ETH1
CT
-100/A
LK/10
tus
ETH2
e Sta
Modul
tus
rk Sta
two
Ne
tory
(fac
.YY.ZZ
set)
IFE_XX
IFE
s-SL
Modbu
11
LV4340
CT
-100/A
LK/10
ETH1
CT
-100/A
LK/10
tus
ETH2
e Sta
Modul
Status
rk
Netwo
11
LV4340
or
or
ULP system
ULP system
I1
I2
I3
I4
I6
I5
I4
I3
I2
I1
I6
I5
+
DC
24V
A1
O1
O2
O3
I1
I2
I3
I4
I5
I6
APP
dule
IO Mo
O3
O2
O1
13
23
33
T1
A1
T2
34
24
14
G
D
C
MX1
XF
OF
SD
SDE
PF
CH
MX1 - XF
BCM ULP
OF, SDE ... microswitches
COM terminal block (E1 to E6)
MX1 and XF communicating voltage releases
CE, CD and CT contacts
B
OF
SDE
PF
CH
A
B
C
D
E
CT
CD CE
F
G
H
I
J
A-35
208E_CATALOGUE.indb 35
09/12/2014 14:16:28
Functions
and characteristics
PB112059-55.eps
The IFE interface and IFE interface + gateway enable LV circuit breakers
as Masterpact NT/NW, Compact NSX or Powerpact to be connected to an Ethernet
network.
DB416830.eps
bb Dual 10/100 Mbps Ethernet port for simple daisy chain connection.
bb Device profile web service for discovery of the IFE interface, IFE interface +
gateway on the LAN.
bb ULP compliant for localization of the IFE interface in the switchboard.
bb Ethernet interface for Compact, Masterpact and Powerpact circuit breakers.
bb Gateway for Modbus-SL connected devices (IFE interface + gateway only).
bb Embedded set-up web pages.
bb Embedded monitoring web pages.
bb Embedded control web pages.
bb Built-in e-mail alarm notification.
Mounting
The IFE interface, IFE interface + gateway are DIN rail mounting devices. A stacking
accessory enables the user to connect several IFMs (ULP to Modbus interfaces) to
an IFE interface + gateway without additional wiring.
24 V DC power supply
IFE interface + gateway, ref.: LV434011
The IFE interface, IFE interface + gateway must always be supplied with 24 V DC.
The IFMs stacked to an IFE interface + gateway are supplied by the IFE interface +
gateway, thus it is not necessary to supply them separately. It is recommended to
use an UL listed and recognized limited voltage/limited current or a class 2 power
supply with a 24 V DC, 3 A maximum.
DB406743.eps
Characteristic
Structure
Device type
Turnaround time
Maximum length of cable
Type of bus connector
Type
Method
Modbus
Ethernet
Modbus
Ethernet
Modbus
Ethernet
Modbus
Ethernet
A-36
208E_CATALOGUE.indb 36
09/12/2014 14:16:30
DB417466.eps
General characteristics
Environmental characteristics
Conforming to standards
Certification
Ambient temperature
Relative humidity
Level of pollution
Flame resistance
24VDC
ETH1
ETH2
Mechanical characteristics
Shock resistance
Resistance to sinusoidal vibrations
A
I
Electrical characteristics
K
ETH1
1000 m/s2
-5 Hz < f < 8.4 Hz
ETH2
Physical characteristics
IFE
ETH1 LK/10-100/ACT
ETH2 LK/10-100/ACT
Module Status
Modbus-SL
Network Status
LV434011
C
D
E
F
Dimensions
Mounting
Weight
Degree of protection of the installed IO
Connections
bb
bb
bb
Statistics
Device information
IMU information
Read device registers
Communication check
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
A-37
208E_CATALOGUE.indb 37
09/12/2014 14:16:30
Functions
and characteristics
PB103798-50.eps
Function
Once connected, the circuit breaker is considered as a slave by the Modbus master.
Its electrical values, alarm status, open/close signals car be monitored or controlled
by a Programmable Logic Controller or any other system.
Characteristics
ULP port
DB417545.eps
5
3
9
0
5
6
7
4
3
2
1
2
1
6
7
C
D
Test
E
F
odbus address
B M
switches.
G Mechanical lock.
F Test button.
H ULP RJ45 connectors.
I Stacking accessory
connection.
A-38
208E_CATALOGUE.indb 38
09/12/2014 14:16:31
Technical characteristics
Dimensions
Maximum number of stacked IFM
Degree of protection Part projecting beyond
of the installed
the escutcheon
module
Other module parts
Connectors
Operating temperature
Power supply voltage
Consumption
Typical
Maximum
18 x 72 x 96 mm
12
IP4x
IP3x
IP2x
-25...+70 C
24 V DC -20 %/+10 % (19.2...26.4 V DC)
21 mA/24 V DC at 20 C
30 mA/19.2 V DC at 60 C
Certification
CE
UL
CSA
IEC/EN 60947-1
UL 508 - Industrial Control Equipment
No. 142-M1987 - Process Control
Equipment
bb CAN/CSA C22.2 No. 0-M91 General requirements - Canadian Electrical
Code Part
bb CAN/CSA C22.2 No. 14-05 Industrial Control Equipment
DB406714.eps
Staking IFM
Stacking accessories
Up to 12 stacked IFM
HRB49218-01_p49.eps
A-39
208E_CATALOGUE.indb 39
09/12/2014 14:16:32
Functions
and characteristics
DB416829.eps
Description
The I/O input/output application module for LV breaker is part of an ULP system with
built-in functionalities and applications to enhance the application needs. The ULP
system architecture can be built without any restrictions using the wide range of
circuit breakers.
The I/O application is compliant with the ULP system specifications.
Two I/O application module can be connected in the same ULP network.
The ranges of LV circuit breakers enhanced by the I/O are:
bb Masterpact NW
bb Masterpact NT
bb Compact NS1600b-3200
bb Compact NS630b-1600
bb Compact NSX100-630 A.
Pre-defined applications
User-defined applications
Mounting
7
8
The setting locking pad on the front panel of the I/O enables the setting of the I/O by
the customer engineering tool.
DB416828.eps
3
2
The application rotary switch enables the selection of the pre-defined application.
It has 9 positions and each position is assigned to a pre-defined application.
The factory set position of the switch is pre-defined application 1.
DB416828.eps
DB416827.eps
A-40
208E_CATALOGUE.indb 40
09/12/2014 14:16:33
DB417467.eps
General characteristics
Environmental characteristics
I1
I2
I3
I4
I5
Conforming to standards
Certification
Ambient temperature
Relative humidity
Level of pollution
Flame resistance
I6
Mechanical characteristics
Shock resistance
Resistance to sinusoidal
vibrations
A
Electrical characteristics
I1
24VDC
I2
I3
I4
I5
Resistance to electromagnetic
discharge
Immunity to radiated fields
Immunity to surges
Consumption
I6
4
3
2
APP
7
8
I1
L
K
J
AI
I2
I3
O1
I4
O2
I5
O3
I6
O2
14
23
O3
24
33
34
T1
13
E
F
LV434063
O1
13
IO
14
23
A1
T2
24
33
34
T1
T2
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
10 V/m
Conforming to IEC/EN 61000-4-5
165 mA
Dimensions
Mounting
Weight
Degree of protection of the
installed I/O application module
Connections
Digital inputs
Digital input type
019.8 V DC, 0 mA
10 m (33 ft)
Note: for a length greater than 10 m (33 ft) and up to 300 m (1,000 ft), it is mandatory to use a
shielded twisted cable. The shield cable is connected to the I/O functional ground of the I/O
application module.
Physical characteristics
C
1000 m/s2
-5 Hz < f < 8.4 Hz
Digital outputs
Bistable relay
Rated load
5 A at 250 V AC
5A
5A
10 mA at 5 V DC
Contact resistance
30 m
10 m (33 ft)
Analog inputs
The I/O application module analog input can be connected to a Pt100 temperature sensor
Range
-30 to 200 C
-22 to 392 F
Accuracy
2 C from -30 to 20 C
1 C from 20 to 140 C
2 C from 140 to 200 C
Refresh interval
5s
5s
A-41
208E_CATALOGUE.indb 41
09/12/2014 14:16:34
Functions
and characteristics
Ethernet
DB416897.eps
DB416896.eps
Ethernet
Connect the IFE to a drawout Masterpact NT/NW or circuit breaker using the
breaker ULP cord
24 Vdc
24 Vdc
24VDC
24VDC
ETH2
ETH1
ETH1
ETH2
ETH1
I1
I2
I3
I4
I6
I5
I4
I3
I2
I1
ETH2
ETH2
ETH1
I6
I5
+
C
24VD
A1
O1
O2
O3
dule
IO Mo
O3
11
LV4340
O2
O1
13
23
33
T1
A1
T2
34
24
14
J
I
H
D
E
F
E
G
A
B
C
D
E
A
B
C
D
E
F
G
H
I
J
K
A-42
208E_CATALOGUE.indb 42
09/12/2014 14:16:35
DB416894.eps
Modbus
Connect the IFM to a drawout Masterpact NT/NW or circuit breaker using the
breaker ULP cord
Modbus
DB416895.eps
I1
I2
I3
I4
I6
I5
I4
I3
I2
I1
I6
I5
+
C
24VD
A1
O1
O2
O3
I1
dule
IO Mo
O3
O2
O1
13
23
33
T1
A1
T2
34
24
14
B
B
C
J
I
H
E
F
A
B
C
D
E
G
A IFM Ethernet interface for LV circuit
B
C
D
E
breaker
ULP cable
Breaker ULP cord
Circuit breaker disconnected position
contact (CD)
Circuit breaker cradle
F
G
H
I
A-43
208E_CATALOGUE.indb 43
09/12/2014 14:16:37
Functions
and characteristics
Capture1b.eps
Introduction
Electrical Asset Manager is a software application that helps the user to manage a
project as part of designing, testing, site commissioning, and maintenance of the
project life cycle.
It enables the user to prepare the settings of the devices offline (without connecting
to the device) and configure them when connected with the devices.
Also it provides lot of other value added features for the user to manage the project
such as, safe repository in cloud, attach artifacts to each device or at the project
level, organize devices in switchboard wise, manage a hierarchical structure of the
installation etc.
Capture3b.eps
References:
Electrical Asset Manager software package can be downloaded from our website
www.schneider-electric.com.
Features
Capture4b.eps
A-44
208E_CATALOGUE.indb 44
09/12/2014 14:16:39
Capture5b.eps
Functions
Offline Mode
A project can be built in offline mode through 2 different ways:
bb through BOM file import
bb through Device Selection.
Online Mode
A project can be built in online mode through device discovery also other than the
methods possible through offline method.
Once the project is built, the following functions can be performed in addition to the
functions available in offline mode:
bb compare the device parameters with project parameters
bb load parameters from project to the device and vice versa
bb firmware downloads to the device
bb monitor the measurement, maintenance, device status and I/O status
bb control functions.
User Interface
Electrical Asset Manager software provides fast direct access to the project and the
devices in the project through different tabs.
bb Project: to provide the project information including customer details, project
references and to add project artifacts (documents related to the project).
bb Configuration: to build up the tree structure of the project architecture ; to have a
table view of the devices added in the project ; to set the parameters of the devices ;
to transfer the device settings ; to view the tripping curves; to attach device artifacts
and to download the latest firmware, to do the communication test for all the devices
and generate the test report.
bb Monitoring: this allows the user to monitor the real time values of different devices
through different sub tabs namely Monitoring, Logs and Control.
bb Reports: report tab allows you to generate and print a report of the project settings
from the report tab. The user details and project characteristics are automatically
filled with the details entered in the Project page.
Capture8b.eps
Capture7b.eps
Capture6b.eps
Additionally, the user can open an existing project and modify the settings offline.
The user can do the discrimination curve check and firmware compatibility check for
devices in the project.
A-45
208E_CATALOGUE.indb 45
09/12/2014 14:16:41
Connections
Functions
and characteristics
Rear connection
Vertical
PB104355A40.eps
Horizontal
PB104354A40.eps
Overview of solutions
PB104356A40.eps
Front connection
PB104358A40.eps
PB104359A40.eps
PB104357A40.eps
Mixed connection
Note: Masterpact circuit breakers can be connected indifferently with bare-copper, tinned-copper
and tinned-aluminium conductors, requiring no particular treatment.
A-46
208E_CATALOGUE.indb 46
09/12/2014 14:16:41
Accessories
(4)
(4)
(4)
DB101149.eps
DB101148.eps
Interphase
barriers
(1)
Drawout
Front
connection
Front
connection
Rear
connection
(1)
Rear
connection
DB101149
(4)
Rear
connection
DB101149.eps
Front
connection
DB101156.eps
Rear
connection
DB101147.eps
Cable lug
adapters
Front
connection
DB101156.eps
Vertical connection
adapters
DB101147.eps
Type of accessory
(2)
(2)
(4)
DB101152.eps
Safety shutters
with padlocking
standard
standard
DB101154.eps
Shutter position
indication and
locking
Db101153.eps
DB101151.eps
Disconnectable
front-connection
adapter
DB418156.eps
(4)
DB101150.eps
DB101150.eps
Spreaders
DB101155.eps
DB101155.eps
(3)
(1) Mandatory for voltages u 500 V, not compatible with
spreaders.
(2) Except for an NW40 equipped for horizontal rear
connection, and for fixed NW40b-NW63.
(3) Mandatory for fixed NT front-connection versions with
vertical-connection adapters oriented towards
the front.
(4) Spreaders, vertical connection adapters and cable lugs
adapters are not compatible with voltages u 500 V.
A-47
208E_CATALOGUE.indb 47
09/12/2014 14:16:42
Functions
and characteristics
Connections
Accessories
PB104360A30.eps
PB104361A30.eps
PB104350A30.eps
PB104362A30.eps
Spreaders (option)
Mounted on the front or rear connectors, spreaders are used to increase the distance
between bars in certain installation configurations.
DB117039.eps
A-48
208E_CATALOGUE.indb 48
09/12/2014 14:16:43
PB104363A50.eps
PB104364A50.eps
Mounted on the chassis, the safety shutters automatically block access to the
disconnecting contact cluster when the device is in the disconnected or test positions
(degree of protection IP 20) When the device is removed from its chassis, no live
parts are accessible.
The shutter-locking system is made up of a moving block that can be padlocked
(padlock not supplied). The block:
bb prevents connection of the device
bb locks the shutters in the closed position.
DB101158.eps
This option located on the chassis front plate indicates that the shutters are closed.
It is possible to independently or separately padlock the two shutters using one to
three padlocks (not supplied).
A-49
208E_CATALOGUE.indb 49
09/12/2014 14:16:44
Locking
Functions
and characteristics
DB126650.eps
On the device
gic 6.0
Microlo
100 %
40 %
menu
alarm
long
time
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
short
time
4 5
3
6
8
2.5
2
10
1.5 Ir
x
Isd
E F
ground
(s)
2
1
taneou
Ii
.4
.3
.2
.1
(s)
G
H
8 12
16
20
24
.5 at 6 Ir
.3
.2
.1
on
tg
setting
Ig D
C
B
A
tr
tsd 4 .4 .3
.2
(s) .
on
.1
I t
instan
4
3
6
2
8 10
12
15
off
x In
test
delay
.4 .3 2
.
.1
0
2
off
I t
fault
PB100811-32.eps
The transparent cover blocks access to the pushbuttons used to open and close the
device.
It is possible to independently lock the opening button and the closing button.
The locking device is often combined with a remote operating mechanism.
The pushbuttons may be locked using either:
bb padlock (not supplied), 5 to 8 mm
bb lead seal
bb two screws.
PB100810-32.eps
PB100812-32.eps
The circuit breaker is locked in the OFF position by physically maintaining the
opening pushbutton pressed down:
bb using padlocks (one to three padlocks, not supplied), shackle diameter: 5 to 8 mm
bb using keylocks (one or two different keylocks, supplied).
Keys may be removed only when locking is effective (Profalux or Ronis type locks).
The keylocks are available in any of the following configurations:
bb one keylock
bb one keylock mounted on the device + one identical keylock supplied separately
for interlocking with another device
bb two different key locks for double locking.
Profalux and Ronis keylocks are compatible with each other.
A locking kit (without locks) is available for installation of one or two keylocks (Ronis,
Profalux, Kirk or Castell).
Accessory-compatibility
For Masterpact NT: 3 padlocks or 1 keylock.
For Masterpact NW: 3 padlocks and/or 2 keylocks.
PB104365A40.eps
This option prevents door opening when the circuit breaker is closed and prevents
circuit breaker closing when the door is open.
For this, a special plate associated with a lock and a cable is mounted on the right
side of the circuit breaker.
With this interlock installed, the source changeover function cannot be implemented.
This option is identical for fixed and drawout version.
A-50
208E_CATALOGUE.indb 50
09/12/2014 14:16:44
On the chassis
1
2
3
4
5
6
7
PB104367A34.eps
PB104366A32.eps
DB126651.eps
Mismatch protection.
Door interlock.
Racking interlock.
Keylock locking.
Padlock locking.
Position indicator.
Chassis front plate
(accessible with cubicle
door closed).
8 Racking-handle entry.
9 Reset button.
10 Racking-handle storage.
Disconnected position
locking by padlocks.
Disconnected position
locking by keylocks.
Mounted on the chassis and accessible with the door closed, these devices lock the
circuit breaker in the disconnected position in two manners:
b using padlocks (standard), up to three padlocks (not supplied)
b using keylocks (optional), one or two different keylocks are available.
Profalux and Ronis keylocks are available in different options:
b one keylock
b two different keylocks for double locking
b one (or two) keylocks mounted on the device + one (or two) identical keylocks
supplied separately for interlocking with another device.
A locking kit (without locks) is available for installation of one or two keylocks (Ronis,
Profalux, Kirk or Castell).
PB104352A32.eps
The connected, disconnected and test positions are shown by an indicator andc
are mechanically indexed. The exact position is obtained when the racking handle
blocks. A release button is used to free it.
As standard, the circuit breaker can be locked only in "disconnected position". On
request, the locking system may be modified to lock the circuit breaker in any of the
three positions: "connected", "disconnected" or "test".
PB104368A32.eps
Door interlock.
Mounted on the right or left-hand side of the chassis, this device inhibits opening of
the cubicle door when the circuit breaker is in connected or test position. It the
breaker is put in the connected position with the door open, the door may be closed
without having to disconnect the circuit breaker.
This device prevents insertion of the racking handle when the cubicle door is open.
PB100815-32R_SE.eps
Racking interlock.
This option makes it necessary to press the OFF pushbutton in order to insert the
racking handle and holds the device open until the handle is removed.
This option discharges the springs before the breaker is removed from the chassis.
Mismatch protection.
Mismatch protection ensures that a circuit breaker is installed only in a chassis with
compatible characteristics. It is made up of two parts (one on the chassis and one on
the circuit breaker) offering twenty different combinations that the user may select.
A-51
208E_CATALOGUE.indb 51
09/12/2014 14:16:46
Indication contacts
Two types of contacts indicate the ON or OFF position of the circuit breaker:
bb micro switch type changeover contacts for Masterpact NT
bb rotary type changeover contacts directly driven by the mechanism for Masterpact
NW. These contacts trip when the minimum isolation distance between the main
circuit breaker contacts is reached.
OF
NT
NW
Supplied as standard
Maximum number
Breaking capacity (A)
p.f.: 0.3
AC12/DC12
PB100807-20.eps
PB100806-32.eps
Functions
and characteristics
Standard
V AC
V DC
240/380
480
690
24/48
125
250
Low-level
V AC
ON/OFF indication contacts
(OF) (rotary type).
V DC
24/48
240
380
24/48
125
250
4
4
4
12
Minimum load: 100 mA/24 V
6
10/6 (1)
6
10/6 (1)
6
6
2.5
10/6 (1)
0.5
10/6 (1)
0.3
3
Minimum load: 2 mA/15 V
5
6
5
6
5
3
5/2.5
6
0.5
6
0.3
3
PB100820-32.eps
Supplied as standard
Maximum number
Breaking capacity (A)
p.f.: 0.3
AC12/DC12
NT/NW
Standard
V AC
V DC
240/380
480
690
24/48
125
250
Low-level
V AC
PB100816-32.eps
Additional fault-trip
indication contacts (SDE)
V DC
24/48
240
380
24/48
125
250
1
2
Minimum load: 100 mA/24 V
5
5
3
3
0.3
0.15
Minimum load: 2 mA/15 V
3
3
3
3
0.3
0.15
The contact combines the device connected and the device closed information to
produce the circuit closed information. Supplied as an option for Masterpact NW, it
is mounted in place of the connector of an additional OF contact.
EF
Maximum number
Breaking capacity (A)
p.f.: 0.3
AC12/DC12
NW
Standard
V AC
V DC
Combined contacts.
240/380
480
690
24/48
125
250
Low-level
V AC
V DC
24/48
240
380
24/48
125
250
8
Minimum load: 100 mA/24 V
6
6
6
2.5
0.8
0.3
Minimum load: 2 mA/15 V
5
5
5
2.5
0.8
0.3
A-52
208E_CATALOGUE.indb 52
09/12/2014 14:16:46
Indication contacts
PB100817-32.eps
Three series of optional auxiliary contacts are available for the chassis:
bb changeover contacts to indicate the connected position CE
bb changeover contacts to indicate the disconnected position CD. This position is
indicated when the required clearance for isolation of the power and auxiliary circuits
is reached
bb changeover contacts to indicate the test position CT. In this position, the power
circuits are disconnected and the auxiliary circuits are connected.
Additional actuators
A set of additional actuators may be installed on the chassis to change the functions
of the carriage switches.
PB100778-32.eps
NT
Contacts
Maximum number
Standard
with additional actuators
Standard
V AC
V DC
M2C programmable contacts: circuit breaker internal relay with
two contacts.
PB100781-32.eps
Low-level
V AC
V DC
240
380
480
690
24/48
125
250
24/48
240
380
24/48
125
250
CE/CD/CT
3
2
1
NW
CE/CD/CT
3
3
3
9
0
0
6
3
0
6
0
3
3
6
0
Minimum load: 100 mA/24 V
8
8
8
8
8
8
6
6
2.5
2.5
0.8
0.8
0.3
0.3
Minimum load: 2 mA/15 V
5
5
5
5
5
5
2.5
2.5
0.8
0.8
0.3
0.3
These contacts, used with the Micrologic E, P and H control units, may be
programmed via the control unit keypad or via a supervisory station with the COM
communication option. They require an external power supply module.
The M2C (two contacts) and M6C (six contacts) auxiliary contacts may be used to
signal threshold overruns or status changes. They can be programmed using the
keypad on the Micrologic P control unit or remotely using the COM option (BCM
ULP).
Micrologic
Type E
Characteristics
Minimum load
Breaking capacity (A)
p.f.: 0.7
V AC
M2C: 24 VDC
power supplied
by control unit
(consumption
100mA).
Types P, H
M2C / M6C
100 mA/24 V
5
3
1.8
1.5
0.4
0.15
DB117038.eps
V DC
240
380
24
48
125
250
M2C
100 mA/24 V
5
3
1.8
1.5
0.4
0.15
A-53
208E_CATALOGUE.indb 53
09/12/2014 14:16:47
Functions
and characteristics
Remote operation
The remote ON / OFF function is used to remotely open and close the circuit breaker.
It is made up of:
bb an electric motor MCH equipped with a springs charged limit switch contact CH
bb two voltage releases:
vv a closing release XF
vv an opening release MX.
Remote ON / OFF
PB104349A68.eps
DB111783.eps
COM
A-54
208E_CATALOGUE.indb 54
09/12/2014 14:16:48
PB100808-32.eps
PB100797-23.eps
The electric motor automatically charges and recharges the spring mechanism when
the circuit breaker is closed. Instantaneous reclosing of the breaker is thus possible
following opening. The spring-mechanism charging handle is used only as a backup
if auxiliary power is absent.
The electric motor MCH is equipped as standard with a limit switch contact CH that
signals the charged position of the mechanism (springs charged).
Characteristics
Power supply
V AC 50/60 Hz
V DC
Operating threshold
Consumption (VA or W)
Motor overcurrent
Charging time
Operating frequency
CH contact
DB417155.eps
200 ms
min.
for MX
Characteristics
Power supply
XF
V AC 50/60 Hz
V DC
Operating threshold
Consumption (VA or W)
PB100809-16.eps
Circuit breaker
response time at Un
MX
PB100818-16.eps
The ready to close position of the circuit breaker is indicated by a mechanical indicator
and a PF changeover contact. This signal indicates that all the following are valid:
bb the circuit breaker is in the OFF position
bb the spring mechanism is charged
bb a maintained opening order is not present:
vv MX energised
vv fault trip
vv remote tripping second MX or MN
vv device not completely racked in
vv device locked in OFF position
vv device interlocked with a second device.
Characteristics
Maximum number
Breaking capacity (A)
p.f.: 0.3
AC12/DC12
NT/NW
Standard
V AC
V DC
240/380
480
690
24/48
125
250
Low-level
V AC
Ready to close contacts PF.
V DC
24/48
240
380
24/48
125
250
1
Minimum load: 100 mA/24 V
5
5
3
3
0.3
0.15
Minimum load: 2 mA/15 V
3
3
3
3
0.3
0.15
A-55
208E2300.indd 55
10/12/2014 10:31:17
Remote operation
Functions
and characteristics
Remote ON / OFF
PB100798-56.eps
DB101167.eps
Located on the front panel, this pushbutton carries out electrical closing of the circuit
breaker. It is generally associated with the transparent cover that protects access to
the closing pushbutton.
Electrical closing via the BPFE pushbutton takes into account all the safety functions
that are part of the control/monitoring system of the installation.
The BPFE connects to the closing release (XF com) in place of the COM module.
The COM module is incompatible with this option.
Different types of voltage exist and the XF electromagnet is compulsary if the BPFE
option is selected.
DB116359.eps
A-56
208E_CATALOGUE.indb 56
09/12/2014 14:16:49
Remote tripping
PB104369A68.eps
This function opens the circuit breaker via an electrical order. It is made up of:
bb a shunt release second MX
bb or an undervoltage release MN
bb or a delayed undervoltage release MNR: MN + delay unit.
These releases (2nd MX or MN) cannot be operated by the communication bus.
The delay unit, installed outside the circuit breaker, may be disabled by an
emergency OFF button to obtain instantaneous opening of the circuit breaker.
DB117188.eps
DB101175.eps
PB100809-16.eps
DB101172.eps
MX or MN voltage release.
When energised, the MX voltage release instantaneously opens the circuit breaker.
A continuous supply of power to the second MX locks the circuit breaker in the OFF
position.
Characteristics
Power supply
V AC 50/60Hz
V DC
Operating threshold
Permanent locking function
Consumption (VA or W)
Circuit breaker response time at Un
The MN release instantaneously opens the circuit breaker when its supply voltage
drops to a value between 35 % and 70 % of its rated voltage. If there is no supply on
the release, it is impossible to close the circuit breaker, either manually or electrically.
Any attempt to close the circuit breaker has no effect on the main contacts. Circuit
breaker closing is enabled again when the supply voltage of the release returns to
85 % of its rated value.
Characteristics
Power supply
V AC 50/60 Hz
V DC
Operating threshold Opening
Closing
Consumption (VA or W)
MN consumption
with delay unit (VA or W)
Circuit breaker response time at Un
MN delay units
To eliminate circuit breaker nuisance tripping during short voltage dips, operation of
the MN release can be delayed. This function is achieved by adding an external
delay unit in the MN voltage-release circuit. Two versions are available, adjustable
and non-adjustable.
Characteristics
Power supply
V AC 50-60 Hz /DC
Operating threshold
Non-adjustable
100/130 - 200/250
Adjustable
48/60 - 100/130 - 200/250 - 380/480
Opening
0.35 to 0.7 Un
Closing
0.85 Un
Pick-up: 200 (200 ms)
Hold: 4.5
Non-adjustable
0.25 s
Adjustable
0.5 s - 0.9 s - 1.5 s - 3 s
A-57
208E_CATALOGUE.indb 57
09/12/2014 14:16:49
Functions
and characteristics
Accessories
PB104740.eps
Optional equipment mounted on the chassis, the shield prevents access to the
terminal block of the electrical auxiliaries.
PB104382A32.eps
The operation counter sums the number of operating cycles and is visible on the front
panel. It is compatible with manual and electrical control functions.
This option is compulsory for all the source-changeover systems.
DB101173.eps
Escutcheon CDP
Optional equipment mounted on the door of the cubicle, the escutcheon increases
the degree of protection to IP40 (circuit breaker installed free standing: IP30).
It is available in fixed and drawout versions.
Used with the escutcheon, this option closes off the door cut-out of a cubicle not yet
equipped with a device. It may be used with the escutcheon for both fixed and
drawout devices.
PB100776-42.eps
Optional equipment mounted on the escutcheon, the cover is hinged and secured by
a screw. It increases the degree of protection to IP54, IK10. It adapts to drawout
devices.
This option allows the grounding of the breaker mechanism while the front cover is
removed. The grounding is made via the chassis for the drawout version and via the
fixation side plate for the fixed version.
A-58
208E_CATALOGUE.indb 58
09/12/2014 14:16:50
PB191613-50.eps
Functions
and characteristics
Source-changeover systems
Presentation
Some installations use two supply sources to counter the temporary loss of the main
supply.
A source-changeover system is required to safely switch between the two sources.
The replacement source can be a generator set or another network.
System
Applications
65587-117.eps
Small commercial buildings and small and medium industrial activities where the
need for continuity of service is significant but not a priority.
System
Applications
P109832-104.eps
Large infrastructures, industry, critical buildings & process where the continuity of
service is a priority.
In this case, no direct human intervention is required. The time required to switch
from the S1 source to S2 source is fixed.
System
Applications
Industry & Infrastructure where continuity of service requirements are meaningful but
not a priority.
A-59
208E_CATALOGUE.indb 59
09/12/2014 14:16:53
Functions
and characteristics
Interlocking of devices
Mechanical interlocking
PB113431_R.eps
The two devices must be mounted one above the other (either 2 fixed or
2 drawout devices).
Combinations are possible between Masterpact NT and Masterpact NW devices.
Installation
This function requires:
bb an adaptation fixture on the right side of each circuit breaker or
switch-disconnector
bb a set of connecting rods with no-slip adjustments.
The adaptation fixtures, connecting rods and circuit breaker or switch-disconnectors
are supplied separately, ready for assembly by the customer.
The maximum vertical distance between the fixing planes is 900 mm.
A-60
208E_CATALOGUE.indb 60
09/12/2014 14:16:54
PB100842_68_SE.eps
For cable interlocking, the circuit breakers may be mounted one above the other or
side-by-side.
The interlocked devices may be fixed or drawout, three-pole or four-pole, and have
different ratings and sizes.
Interlocking between two devices (Masterpact NT and NW)
This function requires:
bb an adaptation fixture on the right side of each device
bb a set of cables with no-slip adjustments
bb the use of a mechanical operation counter CDM is compulsory.
The maximum distance between the fixing planes (vertical or horizontal) is 2000mm.
PB113432_R.eps
Normal N
NT06 to NT16
Ratings 250... 1600 A
NW08 to NW40
Ratings 320... 4000 A
NW40b to NW63
Ratings 4000... 6300 A
Replacement R
NT06 to NT16
NW08 to NW40
NW40b to NW63
bb
bb
bb
bb
bb
bb
bb
bb
bb
NT06 to NT16
Ratings 250... 1600 A
NW08 to NW40
Ratings 320... 4000 A
NW40b to NW63
Ratings 4000... 6300 A
NW08 to NW40
NW40b to NW63
bb
bb
bb
bb
A-61
208E_CATALOGUE.indb 61
09/12/2014 14:16:56
Functions
and characteristics
Electrical interlocking
IVE unit
PG134060_L50.eps
IVE unit.
Necessary equipment
For Masterpact NT and NW, each circuit breaker must be equipped with:
bb a remote-operation system made up of:
vv MCH gear motor
vv MX or MN opening release
vv XF closing release
vv PF ready to close contact
vv CDM mechanical operation counter
bb an available OF contact
bb one to three CE connected-position contacts (carriage switches) on drawout
circuit breakers (depending on the installation).
A-62
208E_CATALOGUE.indb 62
09/12/2014 14:16:56
Controller selection
Controller
BA
UA
Automatic operation
Forced operation on Normal source
Forced operation on Replacement source
Stop (both Normal and Replacement sources off)
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
4-position switch
Automatic operation
DB403809.eps
Test
Indications
Other functions
BA controller.
bb
bb
bb
bb
bb
Options
DB403810.eps
Communication option
Power supply
110 V
220 to 240 V 50/60 Hz
380 to 415 V 50/60 Hz
and 440 V 60 Hz
bb
bb
bb
bb
bb
bb
Undervoltage
Phase failure
Voltage presence
bb
bb
bb
bb
bb
Front
Side
Connectors
Front
IP40
IP30
IP20
IK07
bb
bb
bb
bb
bb
bb
bb
bb
Operating thresholds
UA controller.
bb
bb
bb
bb
AC
DC
Utilisation category (IEC 947-5-1)
AC12 AC13 AC14 AC15 DC12 DC13
Operational current (A)
24 V
8
7
5
5
8
2
48 V
8
7
5
5
2
110 V
8
6
4
4
0.6
220/240 V
8
6
4
3
250 V
0.4
380/415 V
5
440 V
4
660/690 V
(1) For example, 220 V single-phase or 220 V three-phase.
(2) The controller is powered by the ACP control plate. The same voltage must be used for the
ACP plate, the IVE unit and the circuit-breaker operating mechanisms. If this voltage is the same
as the source voltage, then the Normal and Replacement sources can be used directly for the
power supply. If not, an isolation transformer must be used.
A-63
208E_CATALOGUE.indb 63
09/12/2014 14:16:57
Functions
and characteristics
Masterpact NT and NW
Standard configuration
Diagram no.
2 devices
Db101574.eps
QN
0
Masterpact NW only
QR
0
51201142
51201143
51201144
51156904
51156905
51156903
Diagram no.
QN1
0
1
0
bb electrical interlocking:
vv without lockout after fault
vv with lockout after fault
51156906
51156907
51156908
51156909
bb electrical interlocking:
vv without lockout after fault
vv with lockout after fault
51156910
51156911
Db101576.eps
Db101575.eps
QR
0
0
1
Db101577.eps
QS1
0
1
0
0
QS2
0
0
1
0
QS3
0
0
0
1
Db101578.eps
51156912
51156913
51156914
A-64
208E_CATALOGUE.indb 64
09/12/2014 14:16:57
PB106363A50.eps
Functions
and characteristics
Maximum safety
The Masterpact NW range with corrosion protection offers the same safety features
as the standard version:
bb positive contact indication
bb high impulse withstand voltage (12 kV)
bb suitable for isolation in compliance with IEC 60947-2, as indicated
by the disconnector symbol on the front face:
bb front face insulation class 2, allowing class 2 installations with breaker control
from outside.
A-65
208E_CATALOGUE.indb 65
09/12/2014 14:16:58
Functions
and characteristics
NW08H2
3, 4
1000
690
< 50
40 C
800
45 C
800
50 C
800
55 C
800
60 C
800
40 C
800
45 C
800
50 C
800
55 C
800
60 C
800
800
220/440 V 100
690 V
85
100 %
Ui (V)
Ue (V)
In (A)
Vertical connection
Horizontal connection
4 th pole rating
Rated utlimate breaking
capacity
Total maxi
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
100
85
100 %
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
100
85
100 %
1600
1600
1600
1550
1500
1600
1550
1500
1450
1400
1600
100
85
100 %
2000
2000
2000
1900
1800
2000
1900
1800
1700
1600
2000
100
85
100 %
2500
2500
2500
2500
2500
2500
2500
2500
2400
2300
2500
100
85
100 %
3200
3200
3200
3150
3000
3200
100
85
100 %
4000
4000
4000
4000
4000
4000
4000
4000
4000
3900
4000
150
100
100 %
DB124952.eps
DB124951.eps
H
H
Drawout device
800 to 3200 A
4000 A
L (mm)
3P
441
786
4P
556
1016
H (mm)
P (mm)
439
479
395
395
Connections
bb Power circuits:
vv vertical rear connections as standard
vv possibility of conversion to horizontal rear connections on-site by rotating
the connectors, except for NW32, available with vertical rear connections only.
bb Auxiliaries connected to terminal block on circuit breaker front face.
A-66
208E_CATALOGUE.indb 66
09/12/2014 14:16:58
Main characteristics
PB104426A50.eps
Remote indication
1000 V
690 V
800 to 4000 A
135 kA peak
60 kA/1s
50 kA/3s
Compatible with drawout NW08 to NW40 circuit breakers, types
N1/H1/NA/HA, 3-pole and 4-pole rear connected versions
12 ON/OFF indication contacts that can be used according to
the chassis auxiliary wiring
The Earthing Switch is compatible with Masterpact NW08 to NW40 type N1, H1,
NA and HA circuit breakers in both 3-pole and 4-pole versions. It has two parts:
bb a chassis earthing kit for installation on the Masterpact NW chassis. Two different
versions are available for 3-pole and 4-pole chassis.
bb the Earthing Switch itself, which is a specific Masterpact NW device that can be
racked into any chassis equipped with an earthing kit, in place of the circuit breaker.
Two versions are available (3-pole and 4-pole).
An earthing kit must be installed on the chassis of each circuit breaker protecting a
circuit that may require earthing while work is being carried out. However, a single
earthing switch is often sufficient for an entire installation if only one circuit is to be
serviced at any given time.
The standard Earthing Switch comes with the short-circuit bar installed across the
bottom (downstream) connections for earthing of the upstream portion of the circuit.
The user can easily move the short-circuit bar to the top connections if the
downstream portion of the circuit needs to be earthed.
Earthing switch
(front view)
DB125558.eps
DB125557.eps
Earthing kit
(for chassis)
DB125560.eps
DB125559.eps
DB125561.eps
With short-circuit bar on the bottom connections. With short-circuit bar on the top connections.
A-67
208E_CATALOGUE.indb 67
09/12/2014 14:16:59
Functions
and characteristics
Typical applications
Application n1
Earthing of one section of a coupled busbar arrangement
DB120865.EPS
When working on section B, the bus coupler is normally open. To protect personnel
in the event of accidental closing of this device, an earthing switch with the upstream
terminals earthed is installed in place of the circuit breaker at B. In this way section B
will remain at earth potential under all circumstances and the personnel can work in
complete safety.
Application n2
Earthing an outgoer
DB120866.EPS
Application n3
Earthing of an MV/LV transformer
DB120867.EPS
A-68
208E_CATALOGUE.indb 68
09/12/2014 14:17:00
DB125563.eps
DB125562.eps
A-69
208E_CATALOGUE.indb 69
09/12/2014 14:17:00
TOOLS
schneider-electric.com
This international site allows you
to access all the Schneider Electric
Solution and Product information via :
ppcomprehensive descriptions
pprange data sheets
ppa download area
ppproduct selectors
pp...
You can also access the information
dedicated to your business and get
in touch with your Schneider Electric
country support.
208E_CATALOGUE.indb 70
09/12/2014 14:17:01
Masterpact NT and NW
Installation recommendations
Presentation
Functions and characteristics
2
A-1
Operating conditions
B-2
Installation in switchboard
B-4
B-6
Power connection
B-8
B-10
B-11
Busbar sizing
B-12
Temperature derating
Power dissipation and input/output resistance
B-14
Derating in switchboards
B-15
Substitution kit
Fixed / drawout devices 800to3200A
B-22
Control wiring
B-23
Masterpact Retrofit
B-24
C-1
D-1
E-1
F-1
B-1
208E_CATALOGUE.indb 1
09/12/2014 14:17:01
Installation
recommendations
Operating conditions
Ambient temperature
DB402052.eps
Masterpact devices have successfully passed the tests defined by the following
standards for extreme atmospheric conditions:
bb IEC 60068-2-1: dry cold at -40 C
bb IEC 60068-2-2: dry heat at +85 C
bb IEC 60068-2-30: damp heat (temperature +55 C, relative humidity 95 %)
bb IEC 60068-2-52 level 2: salt mist.
Masterpact devices can operate in the industrial environments defined by standard
IEC 60947 (pollution degree up to 4).
It is nonetheless advised to check that the devices are installed in suitably cooled
switchboards without excessive dust.
DB128163.eps
Vibrations
B-2
208E_CATALOGUE.indb 2
09/12/2014 14:17:02
DB128162.eps
(m)
2000
Altitude
At altitudes higher than 2000 metres, the modifications in the ambient air (electrical
resistance, cooling capacity) lower the following characteristics as follows:
Altitude (m)
Impulse withstand voltage Uimp (kV)
Rated insulation voltage (Ui)
Maximum rated operationnal NT, NW except H10
voltage 50/60 Hz Ue (V)
NW H10
Rated current 40 C
2000
12
1000
690
1000
1 x In
3000
11
900
690
890
0.99 x In
4000
10
780
630
795
0.96 x In
5000
8
700
560
700
0.94 x In
DB128164.eps
Electromagnetic disturbances
B-3
208E_CATALOGUE.indb 3
09/12/2014 14:17:02
Installation in switchboard
Installation
recommendations
Db101429.eps
Db101428.eps
DB101427.eps
Possible positions
Power supply
DB101430.eps
Masterpact devices can be supplied either from the top or from the bottom without
reduction in performance, in order to facilitate connection when installed in a
switchboard.
Db101431.eps
DB101432.eps
It is important to distribute the weight of the device uniformily over a rigid mounting
surface such as rails or a base plate.
This mounting plane should be perfectly flat (tolerance on support flatness: 2 mm).
This eliminates any risk of deformation which could interfere with correct operation
of the circuit breaker.
Masterpact devices can also be mounted on a vertical plane using the special
brackets.
Db101433.eps
Mounting on rails.
B-4
208E_CATALOGUE.indb 4
09/12/2014 14:17:03
Db101434.eps
Partitions
Interphase barrier
Db101436.eps
Db101439.eps
Busbars (NT)
DB103879.eps
DB101438.eps
DB117045.eps
Db101435.eps
B-5
208E_CATALOGUE.indb 5
09/12/2014 14:17:04
DB418008.eps
Installation
recommendations
X
61
Dimensions (mm)
(1)
135
205
215
330
660
775
(2)
168
168
215
215
215
215
11.5
2
(1)
(2)
NT06-16.
DB418009.eps
Type
NT08-16 (3P)
NT08-16 (4P)
NW08-40 (3P)
NW08-40 (4P)
NW40b-63 (3P)
NW40b-63 (4P)
X
15
8
17
(1)
(2)
NT08-63.
(1)
(2)
DB418014.eps
DB418012.eps
DB418010.eps
F
Door
(1)
(1)
(2)
Door
Door
F
NW08-40.
NT06-16.
(2)
NW40b-63.
DB418011.eps
DB418013.eps
NW08-40.
NT06-16.
NW40b-63.
Dimensions (mm)
Type
NT
NW08-40
NW40b-63
(1)
5
83
87
(2)
23
103
53
B-6
208E_CATALOGUE.indb 6
09/12/2014 14:17:06
Db101446.eps
Db101447.eps
Db101445.eps
Note: the door interlock can either be mounted on the right side
or the left side of the breaker.
: datum.
B-7
208E_CATALOGUE.indb 7
09/12/2014 14:17:06
Db101453.eps
Db101452.eps
Busbars connections
Db101451.eps
Db101450.eps
Db101448.eps
Cables connections
Db101449.eps
Power connection
Installation
recommendations
Electrodynamic stresses
The first busbar support or spacer shall be situated within a maximum distance from
the connection point of the breaker (see table below). This distance must be
respected so that the connection can withstand the electrodynamic stresses
between phases in the event of a short circuit.
Maximum distance A between busbar to circuit breaker connection and the first busbar
support or spacer with respect to the value of the prospective short-circuit current.
Isc (kA)
Distance A (mm)
30
350
50
300
65
250
80
150
100
150
150
150
B-8
208E_CATALOGUE.indb 8
09/12/2014 14:17:07
Db101454.eps
Clamping
1
2
3
4
5
6
Db101457.eps
DB101456.eps
Db101455.eps
Examples
Tightening torques
(mm)
(mm)
Nominal Drilling
10 11
37.5
Busbar drilling
Db101460.eps
Db101459.eps
DB101458.eps
Examples
Db101461.eps
Isolation distance
Dimensions (mm)
Ui
600 V
1000 V
X min
8 mm
14 mm
Db101462.eps
Busbar bending
When bending busbars maintain the radius indicated below (a smaller radius would
cause cracks).
Dimensions (mm)
e
5
10
Radius of curvature r
Min
5
15
Recommended
7.5
18 to 20
B-9
208E_CATALOGUE.indb 9
09/12/2014 14:17:08
Installation
recommendations
Db101467.eps
Db101466.eps
Db101465.eps
DB101464.eps
DB101463.eps
Rear connection
Db101471.eps
Db101470.eps
Db101465.eps
Db101483.eps
Bottom connection
Db101482.eps
Db101481.eps
Top connection
DB101464.eps
DB101463.eps
DB101463.eps
Front connection
B-10
208E_CATALOGUE.indb 10
09/12/2014 14:17:09
Db101473.eps
Db101472.eps
NW40b to NW50
Db101475.eps
Db101465.eps
DB101464.eps
Db101474.eps
DB101463.eps
Db101477.eps
Db101476.eps
Bottom connection
Db101479.eps
Db101478.eps
Top connection
Db101465.eps
DB101464.eps
DB101463.eps
B-11
208E_CATALOGUE.indb 11
09/12/2014 14:17:10
Busbar sizing
Installation
recommendations
Basis of tables:
bb maximum permissible busbars temperature: 100 C
bb Ti: temperature around the circuit breaker and its
connection
bb busbar material is unpainted copper.
DB101484.eps
Masterpact
NT06
NT06
NT08 or NW08
NT10 or NW10
NT12 or NW12
Maximum
service
current
Ti : 40 C
No. of 5 mm
thick bars
400
630
800
1000
1250
2b.30 x 5
2b.40 x 5
2b.50 x 5
3b.50 x 5
3b.50 x 5
2b.80 x 5
3b.63 x 5
3b.80 x 5
3b.80 x 5
3b.100 x 5
4b.100 x 5
4b.100 x 5
4b.100 x 5
5b.100 x 5
6b.100 x 5
No. of 10 mm
thick bars
Ti : 50 C
No. of 5 mm
thick bars
No. of 10 mm
thick bars
1b.30 x 10
2b.30 x 5
1b.30 x 10
1b.40 x 10
2b.40 x 5
1b.40 x 10
1b.50 x 10
2b.50 x 5
1b.50 x 10
1b.63 x 10
3b.50 x 5
2b.50 x 10
2b.40 x 10
3b.50 x 5
2b.50 x 10
2b.40 x 10
2b.80 x 5
NT16 or NW16 1400
2b.40 x 10
3b.63 x 5
2b.50 x 10
NT16 or NW16 1600
2b.63 x 10
3b.80 x 5
2b.63 x 10
NW20 1800
2b.63 x 10
3b.80 x 5
2b.63 x 10
NW20 2000
2b.80 x 10
3b.100 x 5
2b.80 x 10
NW25 2200
2b.80 x 10
4b.100 x 5
2b.80 x 10
NW25 2500
2b.100 x 10
4b.100 x 5
2b.100 x 10
NW32 2800
3b.80 x 10
4b.100 x 5
3b.80 x 10
NW32 3000
3b.80 x 10
6b.100 x 5
3b.100 x 10
NW32 3200
3b.100 x 10
8b.100 x 5
3b.100 x 10
NW40 3800
4b.100 x 10
5b.100 x 10
NW40 4000
5b.100 x 10
5b.100 x 10
NW50 4500
6b.100 x 10
6b.100 x 10
NW50 5000
7b.100 x 10
7b.100 x 10
With Masterpact NT, it is recommanded to use 50 mm wideness bars (see Recommended busbars drilling).
Ti : 60 C
No. of 5 mm
thick bars
No. of 10 mm
thick bars
2b.30 x 5
2b.40 x 5
2b.50 x 5
3b.63 x 5
3b.63 x 5
1b.30 x 10
1b.40 x 10
1b.63 x 10
2b.50 x 10
2b.50 x 10
3b.80 x 5
3b.80 x 5
3b.100 x 5
3b.100 x 5
4b.100 x 5
4b.100 x 5
5b.100 x 5
8b.100 x 5
2b.63 x 10
3b.50 x 10
2b.80 x 10
3b.63 x 10
2b.100 x 10
3b.80 x 10
3b.100 x 10
4b.80 x 10
4b.100 x 10
5b.100 x 10
6b.100 x 10
7b.100 x 10
Example
Conditions:
bb drawout version
bb horizontal busbars
bb Ti:50 C
bb service current:1800 A.
Solution:
For Ti = 50 C, use an NW20 which can be connected
with three 80 x 5 mm bars or two 63 x 10 mm bars.
Note: the values indicated in these tables have been extrapolated from test data and theoretical
calculations. These tables are only intended as a guide and cannot replace industrial experience
or a temperature rise test.
B-12
208E_CATALOGUE.indb 12
09/12/2014 14:17:10
Basis of tables:
bb maximum permissible busbars temperature: 100 C
bb Ti: temperature around the circuit breaker and its
connection
bb busbar material is unpainted copper.
Db101487.eps
Masterpact
NT06
NT06
NT08 or
NT10 or
NT12 or
NT16 or
NT16 or
NW08
NW10
NW12
NW16
NW16
NW20
NW20
NW25
NW25
NW32
NW32
NW32
NW40
NW40
NW50
NW50
NW63
NW63
Maximum
service
current
Ti : 40 C
No. of 5 mm
thick bars
400
630
800
1000
1250
1400
1600
1800
2000
2200
2500
2800
3000
3200
3800
4000
4500
5000
5700
6300
2b.30 x 5
2b.40 x 5
2b.50 x 5
2b.50 x 5
2b.63 x 5
2b.80 x 5
3b.63 x 5
2b.100 x 5
3b.100 x 5
3b.100 x 5
4b.100 x 5
4b.100 x 5
5b.100 x 5
6b.100 x 5
No. of 10 mm
thick bars
1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.50 x 10
1b.63 x 10
1b.80 x 10
2b.50 x 10
1b.80 x 10
2b.63 x 10
2b.63 x 10
2b.80 x 10
2b.100 x 10
3b.80 x 10
3b.100 x 10
4b.100 x 10
4b.100 x 10
5b.100 x 10
5b.100 x 10
7b.100 x 10
8b.100 x 10
Ti : 50 C
No. of 5 mm
thick bars
2b.30 x 5
2b.40 x 5
2b.50 x 5
2b.50 x 5
3b.50 x 5
2b.80 x 5
3b.63 x 5
2b.100 x 5
3b.100 x 5
3b.100 x 5
4b.100 x 5
4b.100 x 5
6b.100 x 5
6b.100 x 5
No. of 10 mm
thick bars
1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.50 x 10
2b.40 x 10
2b.50 x 10
2b.50 x 10
2b.50 x 10
2b.63 x 10
2b.63 x 10
2b.80 x 10
2b.100 x 10
3b.100 x 10
3b.100 x 10
4b.100 x 10
4b.100 x 10
5b.100 x 10
6b.100 x 10
7b.100 x 10
8b.100 x 10
Ti : 60 C
No. of 5 mm
thick bars
2b.30 x 5
2b.40 x 5
2b.50 x 5
2b.63 x 5
3b.50 x 5
3b.63 x 5
3b.80 x 5
3b.80 x 5
3b.100 x 5
3b.100 x 5
4b.100 x 5
4b.100 x 5
5b.100 x 5
No. of 10 mm
thick bars
1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.63 x 10
2b.40 x 10
2b.50 x 10
2b.63 x 10
2b.63 x 10
2b.80 x 10
2b.80 x 10
3b.80 x 10
3b.80 x 10
4b.80 x 10
4b.100 x 10
4b.100 x 10
4b.100 x 10
6b.100 x 10
7b.100 x 10
8b.100 x 10
Example
Conditions:
bb drawout version
bb vertical connections
bb Ti:40 C
bb service current:1100 A.
Solution :
ForTi = 40 C use an NT12 or NW12 which can be
connected with two 63 x 5 mm bars or with one
63x10mm bar.
Note: the values indicated in these tables have been extrapolated from test data and theoretical
calculations. These tables are only intended as a guide and cannot replace industrial experience
or a temperature rise test.
B-13
208E_CATALOGUE.indb 13
09/12/2014 14:17:11
Temperature derating
Power dissipation and
input/output resistance
Installation
recommendations
Temperature derating
Drawout
Front or rear horizontal
40
45
50
NT06 H1/H2/L1
NT08 H1/H2/L1
NT10 H1/H2/L1
NT12 H1/H2
NT16 H1/H2
630
800
1000
1250
1600
NW08 N/H/L
NW10 N/H/L
NW12 N/H/L
NW16 N/H/L
NW20 H1/H2/H3
NW20 L1
NW25 H1/H2/H3
NW32 H1/H2/H3
NW40 H1/H2/H3
800
1000
1250
1600
2000
2000
2500
3200
4000
NW40b H1/H2
NW50 H1/H2
NW63 H1/H2
4000
5000
Version
Connection
Temp. Ti
1520
630
800
1000
1250
1600
NW08 N/H/L
NW10 N/H/L
NW12 N/H/L
NW16 N/H/L
NW20 H1/H2/H3
NW20 L1
NW25 H1/H2/H3
NW32 H1/H2/H3
NW40 H1/H2/H3
800
1000
1250
1600
2000
2500
3200
4000
NW40b H1/H2
NW50 H1/H2
NW63 H1/H2
4000
5000
1480
60
1440
1900
3900
3100
3800
Fixed
Front or rear horizontal
40
45
50
NT06 H1/H2/L1
NT08 H1/H2/L1
NT10 H1/H2/L1
NT12 H1/H2
NT16 H1/H2
Power dissipation
1560
55
3030
3700
2950
3600
55
60
1560
65
1200
1400
1830
1950
2450
2880
3500
Rear vertical
40
45
70
55
60
65
70
1140
1360
630
800
1000
1250
1600
1560
1520
1480
1440
1520
1750
1900
2370
2800
3400
800
1000
1250
1600
2000
2000
2500
3200
4000
3900
3800
3700
3100
3600
6200
6000
5800
60
65
70
4000
5000
6300
65
1520
Rear vertical
40
45
70
1480
1920
1850
1770
3900
3140
3800
3050
3700
2960
3600
4000
5000
6300
Version
NT06 H1/H2/L1
NT08 H1/H2/L1
NT10 H1/H2/L1
NT12 H1/H2
NT16 H1/H2
NW08 N1
NW08 H/L
NW10 N1
NW10 H/L
NW12 N1
NW12 H/L
NW16 N1
NW16 H/L
NW20 H/L
NW25 H1/H2/H3
NW32 H1/H2/H3
NW40 H1/H2/H3
NW40b H1/H2
NW50 H1/H2
NW63 H1/H2
50
55
630
800
1000
1250
1600
800
1000
1250
1600
2000
2500
3200
4000
50
1560
Drawout
Power dissipation (Watts)
55/115 (H1/L1)
90/140 (H1/L1)
150/230 (H1/L1)
250
460
137
100
220
150
330
230
480
390
470
600
670
900
550
950
1200
3900
3800
6200
Fixed
Power dissipation (Watts)
30/45
50/80
80/110
130
220
62
42
100
70
150
100
220
170
250
260
420
650
390
660
1050
B-14
208E_CATALOGUE.indb 14
09/12/2014 14:17:11
Derating in switchboards
Basis of tables
bb switchboard dimensions
b number of circuit breakers installed
b type of breaker connections
b drawout versions
b ambient temperature outside of the switchboard: Ta (IEC 60439-1).
Masterpact NT06-16 H1/H2/L1 (switchboard 2000 x 400 x 400) - area of outlet vents: 150 cm2
Type
NT06 H1/H2/L1
NT08 H1/H2/L1
NT10 H1/H2/L1
NT12 H1/H2
NT16 H1/H2
2b. 40 x 5
2b. 50 x 5
3b. 63 x 5
3b. 63 x 5
3b. 80 x 5
Switchboard composition
4
3
2
1
Connection type
Busbar dimensions (mm)
3b. 50 x 5
Ventilated switchboard
( IP31)
DB108437.eps
Ta = 35 C
Ta = 45 C
Db101495.eps
Ta = 55 C
4
3 630
2
1
4
3 630
2
1
4
3 630
2
1
H1/L1
H1/L1
1000/1000 1000/1000
630
800
800
630
800
800
1000/950
1000/1000
630
800
800
1000/890
1000/960
630
800
800
1000/960
1000/1000
630
800
800
1000/910
1000/980
1220
630
800
800
1000/860
1000/930
1150
3b. 63 x 5
1250
1250
1400
1520
1250
1250
1330
1440
1250
1250
1340
1250
1330
1400
1250
1260
1330
1200
1260
1200
1250
1230
Note: the values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot
replace industrial experience or a temperature rise test.
The values indicated for the cross-sectional area of the vents should be considered as general indications only given that the thermal performance of a switchboard
with natural ventilation depends on many parameters, e.g. shape, porosity and location of vents and air flow within the switchboard.
B-15
208E_CATALOGUE.indb 15
09/12/2014 14:17:11
Derating in switchboards
Installation
recommendations
Masterpact NT06-08 H1/H2/L1 (switchboard 2300 x 1100 x 500) - area of outlet vents: 300 cm
Type
NT06 H1/H2/L1
NT08 H1/H2/L1
2b. 40 x 5
2b. 50 x 5
Switchboard composition
5
4
3
2
1
Connection type
Busbar dimensions (mm)
DB108444.eps
Ta = 45 C
Ta = 55 C
Ta = 35 C
Ta = 45 C
Ta = 55 C
5
4
3
2 630
1
5
4
3
2 630
1
5
4
3
2 630
1
5
4
3
2 630
1
5
4
3
2 630
1
5
4
3
2 630
1
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
Note: the values indicated in these tables have been extrapolated from test data and theoretical
calculations. These tables are only intended as a guide and cannot replace industrial experience
or a temperature rise test.
The values indicated for the cross-sectional area of the vents should be considered as general
indications only given that the thermal performance of a switchboard with natural ventilation
depends on many parameters, e.g. shape, porosity and location of vents and air flow within the
switchboard.
B-16
208E_CATALOGUE.indb 16
09/12/2014 14:17:12
Masterpact NT10-16 H1/H2/L1 (switchboard 2300 x 1100 x 500) - area of outlet vents: 300 cm
Type
NT10 H1/H2/L1
NT12 H1/H2
NT16 H1/H2
3b. 63 x 5
3b. 63 x 5
3b. 80 x 5
Switchboard composition
5
4
3
2
1
Connection type
Busbar dimensions (mm)
DB108444.eps
Ta = 45 C
Ta = 55 C
Db101489.eps
Ta = 45 C
Ta = 55 C
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
H1/L1
2b. 63 x 5
H1/L1
H1/L1
H1/L1
1000/1000
1000/10001000/1000
1000/10001000/10001000/10001000/1000
1000/1000
1000/10001000/1000
1000 /960 1000/10001000/10001000/1000
1000 /920
1000 /950 1000 /930
1000 /900 1000/1000 1000 /970 1000 /950
5
4
1000 /950
1000/1000 1000 /960
3
2 1000/10001000/10001000/1000 1000 /970
5
1000 /900
4
3
1000 /950 1000 /910
2 1000 /950 1000/1000 1000 /960 1000 /930
5
4
1000 /850
3
1000 /900 1000 /860
2 1000 /880 1000 /970 1000 /910 1000 /870
3b. 50 x 5
1250
1250
1250
1250
1250
1210
3b. 63 x 5
1250
1250
1250
1250
1250
1250
1460
1600
1500
1550
1250
1250
1250
1250
1250
1250
1400
1500
1420
1480
1250
1250
1250
1250
1250
1250
1300
1400
1330
1370
1250
1250
1250
1250
1250
1250
1400
1500
1370
1400
1250
1250
1250
1180
1190
1220
1350
1430
1300
1320
1250
1200
1210
1120
1130
1150
1250
1350
1210
1250
Note: the values indicated in these tables have been extrapolated from test data and theoretical
calculations. These tables are only intended as a guide and cannot replace industrial experience
or a temperature rise test.
The values indicated for the cross-sectional area of the vents should be considered as general
indications only given that the thermal performance of a switchboard with natural ventilation
depends on many parameters, e.g. shape, porosity and location of vents and air flow within the
switchboard.
B-17
208E_CATALOGUE.indb 17
09/12/2014 14:17:13
Derating in switchboards
Installation
recommendations
Masterpact NW08-10 N/H/L (switchboard 2300 x 800 x 900) - area of outlet vents: 350 cm
Type
NW08 N/H/L
NW10 N/H/L
2b. 50 x 5
3b. 63 x 5
2b. 63 x 5
Switchboard composition
4
3
2
1
Connection type
Busbar dimensions (mm)
DB108438.eps
Ta = 45 C
Ta = 55 C
Ta = 35 C
Ta = 45 C
Ta = 55 C
4
3
2
1 800
4
3
2
1 800
4
3
2
1 800
4
3
2
1 800
4
3
2
1 800
4
3
2
1 800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
800
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
Note: the values indicated in these tables have been extrapolated from test data and theoretical
calculations. These tables are only intended as a guide and cannot replace industrial experience
or a temperature rise test.
The values indicated for the cross-sectional area of the vents should be considered as general
indications only given that the thermal performance of a switchboard with natural ventilation
depends on many parameters, e.g. shape, porosity and location of vents and air flow within the
switchboard.
B-18
208E_CATALOGUE.indb 18
09/12/2014 14:17:14
Masterpact NW12-16 N/H/L (switchboard 2300 x 800 x 900) - area of outlet vents: 350 cm
Type
NW12 N1
NW12 H/L
NW16 N1
NW16 H/L
3b. 63 x 5
3b. 50 x 5
3b. 63 x 5
3b. 50 x 5
3b. 80 x 5
3b. 63 x 5
3b. 80 x 5
3b. 63 x 5
Switchboard composition
4
3
2
1
Connection type
Busbar dimensions (mm)
DB108438.eps
Ta = 45 C
Ta = 55 C
Db101491.eps
Ta = 45 C
Ta = 55 C
4
3
2
1 1250
4
3
2
1 1250
4
3
2
1 1250
4
3
2
1 1250
4
3
2
1 1200
4
3
2
1 1130
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1240
1250
1250
1250
1210
1250
1170
1210
1250
1200
1140
1200
1100
1170
1200
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1550
1600
1600
1600
1600
1600
1600
1600
1250
1250
1250
1250
1250
1250
1470
1600
1500
1600
1600
1600
1600
1600
1250
1250
1250
1250
1250
1250
1380
1500
1380
1500
1520
1600
1470
1600
1250
1250
1250
1250
1250
1250
1440
1550
1425
1550
1600
1600
1600
1600
1250
1250
1250
1250
1250
1250
1360
1470
1360
1470
1500
1600
1500
1600
1250
1250
1250
1250
1250
1250
1280
1380
1280
1380
1400
1520
1400
1520
Note: the values indicated in these tables have been extrapolated from test data and theoretical
calculations. These tables are only intended as a guide and cannot replace industrial experience
or a temperature rise test.
The values indicated for the cross-sectional area of the vents should be considered as general
indications only given that the thermal performance of a switchboard with natural ventilation
depends on many parameters, e.g. shape, porosity and location of vents and air flow within the
switchboard.
B-19
208E_CATALOGUE.indb 19
09/12/2014 14:17:14
Derating in switchboards
Installation
recommendations
Masterpact NW20-40 N/H/L (switchboard 2300 x 800 x 900) - area of outlet vents: 350 cm
Type
NW20 H1/H2/H3
NW20 L1
NW25 H1/2/3
NW32 H1/2/3
NW40 H1/2/3
3b. 100 x 5
4b. 100 x 5
3b. 100 x 10
4b. 100 x 10
Switchboard composition
4
3
2
1
Connection type
DB108438.eps
Ta = 45 C
Ta = 55 C
Ta = 35 C
Ta = 45 C
Ta = 55 C
3b. 100 x 5
4
3
2 2000
2000
1
4
3
2 2000
2000
1
4
3
2 2000
2000
1
4
3
2 2000
1
4
3
2 1900
1
4
3
2 1800
1
2000
2000
2000
2000
1830
2000
2375
2500
3040
3200
3320
3700
2000
2000
1810
1960
1750
1920
2250
2380
2880
3100
3160
3500
2000
2000
1700
1850
1640
1800
2100
2250
2690
2900
2960
3280
2000
2000
2000
1800
1900
1750
1890
2125
2275
2650
2850
3040
3320
1960
1900
1960
1680
1810
1660
1800
2000
2150
2550
2700
2880
3120
1920
1780
1920
1590
1700
1550
1700
1900
2020
2370
2530
2720
2960
Note: the values indicated in these tables have been extrapolated from test data and theoretical
calculations. These tables are only intended as a guide and cannot replace industrial experience
or a temperature rise test.
The values indicated for the cross-sectional area of the vents should be considered as general
indications only given that the thermal performance of a switchboard with natural ventilation
depends on many parameters, e.g. shape, porosity and location of vents and air flow within the
switchboard.
B-20
208E_CATALOGUE.indb 20
09/12/2014 14:17:15
Masterpact NW40b-63 H1/H2 (switchboard 2300 x 1400 x 1500) - area of outlet vents: 500 cm
Type
NW40b H1/H2
NW50 H1/H2
NW63 H1/H2
7b. 100 x 10
8b. 100 x 10
4700
5000
5850
4450
4850
5670
4200
4600
5350
4000
4350
4650
5290
4000
4100
4400
5040
3840
3850
4150
4730
Switchboard composition
4
3
2
1
Connection type
DB108445.eps
Ta = 45 C
Ta = 55 C
Db101492.eps
Ta = 45 C
Ta = 55 C
5b. 100 x 10
4
3
2 4000
4000
1
4
3
2 4000
4000
1
4
3
2 4000
4000
1
4
3
2 4000
1
4
3
2 4000
1
4
3
2 3840
1
Note: the values indicated in these tables have been extrapolated from test data and theoretical
calculations. These tables are only intended as a guide and cannot replace industrial experience
or a temperature rise test.
The values indicated for the cross-sectional area of the vents should be considered as general
indications only given that the thermal performance of a switchboard with natural ventilation
depends on many parameters, e.g. shape, porosity and location of vents and air flow within the
switchboard.
B-21
208E_CATALOGUE.indb 21
09/12/2014 14:17:15
Substitution kit
Installation
recommendations
Mounting diagram
DB117049.eps
Drawout version
DB117050.eps
Fixed version
Fixing points are identical for Masterpact (M08 to M32) and Masterpact (NW08 to NW32),
except for the four-pole chassis.
: Masterpact NW
: Masterpact M
Door cut-out
DB117048.eps
Fixed version
Power connection
Select a set of retrofit connectors to replace the standard connectors and avoid any
modifications to the busbars (see the retrofit section in orders and quotations).
Note:
(1) Without escutcheon.
(2) With escutcheon.
References X and Y represent the symmetry planes for
three-pole devices.
B-22
208E_CATALOGUE.indb 22
09/12/2014 14:17:16
Control wiring
During pick-up, the power consumed is approximately 150 to 200 VA. For low control
voltages (12, 24, 48 V), maximum cable lengths are imposed by the voltage and the
cross-sectional area of cables.
Recommended maximum cable lengths (meter).
12 V
24 V
2.5 mm2 1.5 mm2 2.5 mm2
MN
U source 100 %
58
U source 85 %
16
MX-XF U source 100 %
21
12
115
U source 85 %
10
6
75
Note: the indicated length is that of each of the two wires.
1.5 mm2
35
10
70
44
48 V
2.5 mm2
280
75
550
350
1.5 mm2
165
45
330
210
24 V DC power-supply module
External 24 V DC power-supply module for Micrologic (F1-, F2+)
bb It is recommended to use the AD power supply due to its low stray primarysecondary capacitance. Good operation of the Micrologic Trip Unit in noisy
environment is not guaranteed with other power supplies.
bb The dedicated AD power supplies shall be used only for the Micrologic trip units. If
the COM option is used, a second dedicated power supply shall be used.
bb M2C and M6C modules can be supplied by Micrologic external AD power supply.
bb The consumption of a Micrologic Trip Unit is approximately 100mA.
bb The consumption of M2C and M6C modules is approximately 100mA.
bb A number of 5 devices (Micrologic control units with M2C or M6C) can be
connected to the same AD power supply. Add other AD power supply for more than 5
devices.
bb For Micrologics control units alone, a number of 10 devices can be connected to
the same AD power supply. Add other AD power supply for more than 10 Micrologics.
bb If the installation is shared between several panels, one AD power supply shall be
added for each panel.
bb AD power supply dedicated to Micrologics trip units shall not be connected to
earth. (F1-, F2+).
External 24 V DC power supply for Communication bus
bb A dedicated 24 V DC power supply shall be used for the communication devices.
bb Do not connect the positive terminal (E1) to earth.
bb The negative terminal (E2) can be connected to earth.
bb A number of communication modules (BCM, IFE, IFM, I/O, FDM) can be
connected to the same 24 V DC power supply. Refer bellow the devices
consumption table to avoid exceeding the maximum current delivered by the
24 V DC power supply.
ULP module consumption
The table below lists the ULP module consumption.
Module
Typical Consumption
Maximum Consumption
(24 V DC at 20 C / 68 F) (19.2 V DC at 60 C / 140 F)
40 mA
65 mA
30 mA
55 mA
9 mA
15 mA
15 mA
19 mA
30 mA
21 mA
30 mA
120 mA
3 A (with gateway)
165 mA
420 mA
Maintenance module
0 mA (the maintenance
0 mA (the maintenance
module has its own power module has its own power
supply)
supply)
Installation recommendation
bb The 24 V DC wires (output of the 24 V DC power supply) shall be twist together.
bb The 24 V DC wires (output of the 24 V DC power supply) must cross all power
cables perpendicularly.
bb The technical characteristics of the external 24 V DC power-supply module for
Micrologic control units are indicated on page A-28.
Note: wiring of ZSI: it is recommended to use twisted shielded cable. The shield must be
connected to earth at both ends.
B-23
208E3300.indd 23
11/12/2014 10:38:19
Installation
recommendations
Masterpact Retrofit
Remote operation
DB117052.eps
Power
Chassis contacts
DB117051.eps
Indication contacts
Identical to Masterpact M.
New or additional functions.
B-24
208E_CATALOGUE.indb 24
09/12/2014 14:17:17
Masterpact NT and NW
Presentation
Functions and characteristics
Installation recommendations
2
A-1
B-1
C-2
C-6
C-10
C-12
C-14
C-16
C-18
C-20
NT/NW accessories
C-22
C-24
C-30
C-31
Electrical diagrams
Additional characteristics
Catalogue numbers andorderform
D-1
E-1
F-1
C-1
208E_CATALOGUE.indb 1
09/12/2014 14:17:17
Dimensions
and connections
DB101188.eps
Db101189.eps
Dimensions
Db101192.eps
Db101191.eps
Db101190.eps
Db101195.eps
Door cutout
Db101194.eps
Db101193.eps
Safety clearances
A
B
: datum.
(1) Without escutcheon.
(2) With escutcheon.
Metal
0
0
Energised
100
60
C-2
208E_CATALOGUE.indb 2
09/12/2014 14:17:18
Connections
Db101200.eps
Db101199.eps
Detail
Db101198.eps
Db101197.eps
Db101204.eps
Db101230.eps
Detail
Db101202.eps
Db101201.eps
View A detail.
Db101231.eps
Detail
Db101206.eps
Db101205.eps
Front connection
Bottom connection
Db101208.eps
Top connection
View A detail.
C-3
208E_CATALOGUE.indb 3
09/12/2014 14:17:20
Dimensions
and connections
Connections
Detail
Db101527.eps
Db101528.eps
Db101210.eps
Db101211.eps
Db101217.eps
Db101216.eps
Detail
Db101215.eps
DB101214.eps
Spreader detail
Left or right spreader for 3P.
Db101221.eps
Db101218.eps
View A detail.
: datum.
C-4
208E_CATALOGUE.indb 4
09/12/2014 14:17:21
Connections
Db101225.eps
Db101232.eps
Detail
Db101223.eps
Db101222.eps
View A detail.
Db101233.eps
Detail
Db101229.eps
Db101227.eps
Db101226.eps
Front connection via vertical connection adapters fitted with cable-lug adapters
View A detail.
C-5
208E_CATALOGUE.indb 5
09/12/2014 14:17:22
Dimensions
and connections
Db101235.eps
DB101234.eps
Dimensions
Db101238.eps
Db101236.eps
Db101240.eps
Door cutout
Db101239.eps
Db101256.eps
Safety clearances
Parts
Insulated
0
10
0
Metal
0
10
0
Energised
30
60
30
: datum.
(1) Without escutcheon.
(2) With escutcheon.
Note: X and Y are the symmetry planes for a 3-pole device.
C-6
208E_CATALOGUE.indb 6
09/12/2014 14:17:23
Connections
Db101200.eps
Db101244.eps
Detail
Db101243.eps
Db101242.eps
Db101250.eps
Db101249.eps
Detail
Db101247.eps
Db101246.eps
View A detail.
Db101254.eps
Detail
Db101252.eps
Db101251.eps
Front connection
Bottom connection
Db101255.eps
Top connection
View A detail.
C-7
208E_CATALOGUE.indb 7
09/12/2014 14:17:24
Dimensions
and connections
Connections
Db101265.eps
Db101266.eps
Db101258.eps
Db101257.eps
Spreader detail
Left or right spreader for 3P.
Db101221.eps
Db101218.eps
View A detail.
: datum.
C-8
208E_CATALOGUE.indb 8
09/12/2014 14:17:24
Connections
Db101264.eps
Db101229.eps
Db101262.eps
Db101261.eps
Front connection via vertical connection adapters fitted with cable-lug adapters
View A detail.
C-9
208E_CATALOGUE.indb 9
09/12/2014 14:17:24
Dimensions
and connections
Db101268.eps
Db101267.eps
Dimensions
Db101270.eps
Mounting detail
Db101269.eps
A
B
Db101273.eps
Door cutout
Db101272.eps
Db101271.eps
Safety clearances
Insulated
parts
Metal
parts
Energised
parts
0
0
0
0
100
60
: datum.
C-10
208E_CATALOGUE.indb 10
09/12/2014 14:17:25
Connections
Db101278.eps
DB101277.eps
Detail
Db101276.eps
Db101274.eps
DB101282.eps
Db101287.eps
Detail
Db101280.eps
Db101279.eps
View A detail.
Db101288.eps
Detail
Db101284.eps
Db101283.eps
Front connection
Bottom connection
Db101286.eps
Top connection
View A detail.
Note: recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.
C-11
208E_CATALOGUE.indb 11
09/12/2014 14:17:26
Dimensions
and connections
Db101290.eps
DB101289.eps
Dimensions
Mounting detail
Db101291.eps
Db101292.eps
A
B
Db101295.eps
Door cutout
Db101294.eps
Db101293.eps
Safety clearances
Insulated
parts
Metal
parts
Energised
parts
0
0
0
0
0
60
: datum.
C-12
208E_CATALOGUE.indb 12
09/12/2014 14:17:27
Connections
Db101278.eps
Db101298.eps
Detail
Db101297.eps
Db101296.eps
DB101282.eps
Db101307.eps
Detail
Db101301.eps
Db101300.eps
View A detail.
Db101308.eps
Detail
Db101304.eps
Db101303.eps
Front connection
Bottom connection
Db101306.eps
Top connection
View A detail.
Note: recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.
C-13
208E_CATALOGUE.indb 13
09/12/2014 14:17:28
Dimensions
and connections
Db101268.eps
Db101267.eps
Dimensions
Db101270.eps
Mounting detail
Db101269.eps
A
B
Db101273.eps
Door cutout
Db101272.eps
Db101271.eps
Safety clearances
Insulated
parts
Metal
parts
Energised
parts
0
0
0
0
100
60
: datum.
C-14
208E_CATALOGUE.indb 14
09/12/2014 14:17:28
Connections
Db101276.eps
DB101309.eps
Db101315.eps
Db101310.eps
DB101311.eps
Detail
Db101313.eps
Db101312.eps
Db101314.eps
Db101287.eps
Detail
View A detail.
C-15
208E_CATALOGUE.indb 15
09/12/2014 14:17:29
Dimensions
and connections
Db101290.eps
DB101289.eps
Dimensions
Mounting detail
Db101291.eps
Db101292.eps
A
B
Db101295.eps
Door cutout
Db101294.eps
Db101293.eps
Safety clearances
Insulated
parts
Metal
parts
Energised
parts
0
0
0
0
0
60
: datum.
C-16
208E_CATALOGUE.indb 16
09/12/2014 14:17:29
Connections
Db101297.eps
Db101316.eps
DB101311.eps
Db101314.eps
Db101315.eps
Db101317.eps
Db101319.eps
Detail
Db101318.eps
View A detail.
Db101307.eps
Detail
C-17
208E_CATALOGUE.indb 17
09/12/2014 14:17:30
NW40b to NW63
circuit breakers
Dimensions
and connections
Db101320.eps
Db101267.eps
Dimensions
Db101321.eps
Mounting detail
Db101269.eps
A
B
Db101322.eps
Door cutout
Db101323.eps
Db101271.eps
Safety clearances
Insulated
parts
Metal
parts
Energised
parts
0
0
0
0
100
60
: datum.
C-18
208E_CATALOGUE.indb 18
09/12/2014 14:17:30
Connections
Db101278.eps
Db101325.eps
Detail
Db101324.eps
Db101332.eps
DB101282.eps
Db101333.eps
Detail
Db101328.eps
Db101327.eps
View A detail.
Db101314.eps
Db101333.eps
Detail
Db101331.eps
Db101330.eps
Front connection
View A detail.
C-19
208E_CATALOGUE.indb 19
09/12/2014 14:17:31
NW40b to NW63
circuit breakers
Dimensions
and connections
DB101335.eps
DB101334.eps
Dimensions
Mounting detail
Db101336.eps
Db101337.eps
A
B
Db101339.eps
Door cutout
Db101338.eps
Db101293.eps
Safety clearances
Insulated
parts
Metal
parts
Energised
parts
0
0
0
0
0
60
C-20
208E_CATALOGUE.indb 20
09/12/2014 14:17:32
Connections
Db101343.eps
Detail
Db101278.eps
Db101342.eps
Db101341.eps
Db101349.eps
Detail
DB101282.eps
Db101344.eps
Db101345.eps
View A detail.
Db101349.eps
Detail
Db101314.eps
Db101348.eps
Db101347.eps
View A detail.
C-21
208E_CATALOGUE.indb 21
09/12/2014 14:17:33
NT/NW accessories
Dimensions
and connections
Db101351.eps
Db101350.eps
Db101278.eps
Db101354.eps
Detail
Db101353.eps
Db101352.eps
View A detail.
DB101282.eps
Db101358.eps
Detail
Db101356.eps
DB417984.eps
View A detail.
: datum.
C-22
208E_CATALOGUE.indb 22
09/12/2014 14:17:34
Db125695.eps
NW08 to NW40
Rear view
Db101362.eps
DB101361.eps
NW40b to NW63
Rear view
Escutcheon
Drawout device
Db101364.eps
Db101363.eps
Masterpact NT
Fixed device
Drawout device
Db101366.eps
Db101365.eps
Masterpact NW
Fixed device
: datum.
C-23
208E_CATALOGUE.indb 23
09/12/2014 14:17:35
Dimensions
and connections
Db101368.eps
DB101367.eps
DB102199.eps
DB117026.eps
Db102076.eps
DB102077.eps
Db101373.eps
Mounting
C-24
208E_CATALOGUE.indb 24
09/12/2014 14:17:35
Db101375.eps
DB117025.eps
Db101379.eps
Sensor
ETH1
DB416698.eps
DB416697.eps
IFE
ETH1 LK/10-100/ACT
45
ETH2 LK/10-100/ACT
Module Status
Modbus-SL
Network Status
84.8
92
105
LV434011
72
63.6
71
C-25
208E_CATALOGUE.indb 25
09/12/2014 14:17:36
Dimensions
and connections
I1
24VDC
I2
I3
I4
I5
I1
I2
I3
I4
I5
I6
I6
A1
O1
O2
O3
IO
45
84.8
92
115
LV434063
O1
13
DB416700.eps
DB416699.eps
O2
14
23
O3
24
33
34
T1
A1
T2
63.6
72
71
DB416702.eps
DB416701.eps
45
85
92
105
66
18
73
DB417077.eps
DB417076.eps
ComX 200
3
90
144
45
85
106
63
69
C-26
208E_CATALOGUE.indb 26
09/12/2014 14:17:38
Dimensions
400/1600 A (NT06 to NT16)
Db101381.eps
DB117024.eps
DB117023.eps
Db101385.eps
Installation
400/1600 A (NT06 to NT16)
Db101387.eps
C-27
208E_CATALOGUE.indb 27
09/12/2014 14:17:39
Dimensions
and connections
DB101389.eps
Db101392.eps
Db101391.eps
Busbars
Window (mm)
Weight (kg)
I y 1600 A
I y 3200
280 x 115
14
470 x 160
18
Busbars path
470 x 160 mm window
Db101393.eps
DB117029.eps
M1M2M3
2 bars 50 x 10.
Db101395.eps
DB117028.eps
4 bars 100 x 5.
2 bars 100 x 5.
4 bars 125 x 5.
C-28
208E_CATALOGUE.indb 28
09/12/2014 14:17:41
DB114992.eps
DB114991.eps
Dimensions
96
96
Y
Mounting
DB118545.eps
DB416963.eps
DB114993.eps
Through panel
+ 0.8
92 0
+ 0.8
10.6
20.7
92 0
23
DB115122.eps
DB115121.eps
DB115270.eps
DB114996.eps
On panel
2 22.5
16.5
99.3
X
19
15
37
20
2 22.5
13
+0.5
-
32
+
- 0.3
+1.5
-
33
17
Connector (optional).
99.3
Y
C-29
208E_CATALOGUE.indb 29
09/12/2014 14:17:42
Dimensions
and connections
DB416736.eps
DB416703.eps
Dimensions
129
163
Y
Mounting
On panel
DB416738.eps
DB416704.eps
DB416737.eps
1.5...6
100
X
30.6
17.5
100
100
+0
DB416740.eps
DB416739.eps
39
22,5 -0,30
100
X
100
+0
30 -0,20
Y
C-30
208E_CATALOGUE.indb 30
09/12/2014 14:17:44
Masterpact NT and NW
Electrical diagrams
Presentation
Functions and characteristics
Installation recommendations
Dimensions and connections
2
A-1
B-1
C-1
D-2
D-4
Masterpact NT and NW
Earth-fault and earth-leakage protection
Neutral protection
Zone selective interlocking
D-6
Communication D-8
D-9
D-10
Masterpact NT and NW
24 V DC external power supply AD module
Additional characteristics
Catalogue numbers andorderform
D-11
E-1
F-1
D-1
208E_CATALOGUE.indb 1
09/12/2014 14:17:44
Electrical diagrams
Remote operation
DB101401.eps
Power
Control unit
Terminal block
marking
UC1
Remote operation
UC2
UC3
Z5 M1 M2 M3
F2+
V3
484
Q3
184
E3 E4
Z3 Z4
T3 T4
VN
V2
474
Q2
182
E1 E2
Z1 Z2
T1 T2
F1
V1
471
Q1
181
Control unit
Com : E1-E6 communication
b
b
b
b
A : digital ammeter.
E : energy.
SDE2 /
E5 E6
Com
Res
SDE1
MN
/ MX2
K2
84
D2
C12
82
/
K1
81
D1
C11
MX1
XF
PF
MCH
C2
A2
254
B2
C3
A3
252
B3
C1
A1
251
B1
Remote operation
SDE2 : fault-trip indication contact
or
Res : remote reset
SDE1 : fault-trip indication contact (supplied as standard)
MN : undervoltage release
or
MX2 : shunt release
MX1 : shunt release (standard or communicating)
XF :
PF :
ready-to-close contact
or
D-2
208E_CATALOGUE.indb 2
09/12/2014 14:17:44
Electrical diagrams
Db101407.eps
Chassis contacts
Db101406.eps
Indication contacts
Indication contacts
Chassis contacts
OF4
OF3
OF2
OF1
CD2
CD1
CE3
CE2
CE1
CT1
44
34
24
14
824
814
334
324
314
914
42
32
22
12
822
812
332
322
312
912
41
31
21
11
821
811
331
321
311
911
Indication contacts
OF4 / OF3 / OF2 / OF1 : ON/OFF indication contacts.
CE3 :
CE2
CE1
connected
position
contacts
CT1 :
test
position
contacts
DB117043.eps
Chassis contacts
CD2 : disconnected
CD1
position
contacts
Key:
drawout device only.
XXX SDE1, OF1, OF2, OF3, OF4 supplied as standard.
interconnected connections
(only one wire per connection point).
D-3
208E_CATALOGUE.indb 3
09/12/2014 14:17:45
Electrical diagrams
Remote operation
DB101401.eps
Power
Control unit
Terminal block
marking
Com
UC1
Remote operation
UC2
UC3
UC4
M2C / M6C
E5 E6
Z5 M1 M2 M3
F2+
V3
484
Q3
184
E3 E4
Z3 Z4
T3 T4
VN
V2
474
Q2
182
E1 E2
Z1 Z2
T1 T2
F1
V1
471
Q1
181
Control unit
Com : E1-E6 communication
b
b
b
b
b
b
SDE2 /
Res
SDE1
MN
/ MX2
K2
84
D2
C12
82
/
K1
81
D1
C11
MX1
XF
PF
MCH
C2
A2
254
B2
C3
A3
252
B3
C1
A1
251
B1
Remote operation
SDE2 : fault-trip indication contact
or
Res : remote reset
SDE1 : fault-trip indication contact (supplied as standard)
MN : undervoltage release
or
MX2 : shunt release
MX1 : shunt release (standard or communicating)
XF :
VN external voltage connector (must be
connected to the neutral with a 3P circuit breaker) PF :
b (1)
or
A : digital ammeter.
P : A + power meter + additional protection.
E : energy.
H : P + harmonics.
(1) The PTE option with Micrologic E is not compatible with an external potential CT.
D-4
208E_CATALOGUE.indb 4
09/12/2014 14:17:45
Electrical diagrams
Chassis contacts
Db101409.eps
Indication contacts
Indication contacts
Chassis contacts
OF4
OF3
OF2
OF1
CD3
CD2
CD1
CE3
CE2
CE1
CT3
CT2
CT1
44
34
24
14
244
234
224
214
144
134
124
114
834
824
814
334
324
314
934
924
914
42
32
22
12
242
232
222
212
142
132
122
112
832
822
812
332
322
312
932
922
912
41
31
21
11
111
831
821
811
331
321
311
931
921
911
CE6
CE5
CE4
CE9
CE8
CE7
241
or
231
or
221
or
211
or
141
or
131
or
121
or
or
or
248
238
228
218
148
138
128
118
364
354
344
394
384
374
246
236
226
216
146
136
126
116
362
352
342
392
382
372
245
235
225
215
145
135
125
115
361
351
341
391
381
371
Indication contacts
OF4 :
OF3
OF2
OF1
or
Chassis contacts
OF24 or
EF24
OF23 or
EF23
OF22 or
EF22
OF21 or
EF21
OF14 or
EF14
OF13 or
EF13
OF12 or
EF12
OF11 or
EF11
Combined
connected-deconnected
indication contacts
CD3
CD2
CD1
disconnected CE3
position
CE2
contacts
CE1
or
CE6
CE5
CE4
connected
position
contacts
connected
position
contacts
CT3
CT2
CT1
or
CE9
CE8
CE7
or
CD6
CD5
CD4
test position
contacts
connected
position
contacts
disconnected
position
contacts
Key:
drawout device only.
XXX SDE1, OF1, OF2, OF3, OF4 supplied as standard.
interconnected connections
(only one wire per connection point).
D-5
208E_CATALOGUE.indb 5
09/12/2014 14:17:46
Masterpact NT and NW
Electrical diagrams
DB125601.eps
Shield Drain
DB416705.eps
D-6
208E_CATALOGUE.indb 6
09/12/2014 14:17:46
Masterpact NT and NW
Electrical diagrams
Db101415.eps
Earth-leakage protection
Neutral protection
bb Three pole circuit breaker:
vv neutral protection is impossible with Micrologic A, E
vv Masterpact equipped with Micrologic P or H
vv the current transformer for external neutral is
necessary (the wiring diagram is identical to the one
used for the residual earth-fault protection)
bb Four pole circuit breaker:
vv Masterpact equipped with Micrologic A, E, P or H
vv the current transformer for external neutral is not
necessary.
Zone-selective interlocking is used to reduce the
electrodynamic forces exerted on the installation by shortening
the time required to clear faults, while maintaining time
discrimination between the various devices.
A pilot wire interconnects a number of circuit breakers equipped
with Micrologic A/E/P/H control units, as illustrated in the
diagram above.
The control unit detecting a fault sends a signal upstream and
checks for a signal arriving from downstream. If there is a signal
from downstream, the circuit breaker remains closed for the full
duration of its tripping delay. If there is no signal from
downstream, the circuit breaker opens immediately, regardless
of the tripping-delay setting.
Fault 1.
Only circuit breaker A detects the fault. Because it receives no
signal from downstream, it opens immediately, regardless of its
tripping delay set to 0.3.
Fault 2.
Circuit breakers A and B detect the fault. Circuit breaker A
receives a signal from B and remains closed for the full duration
of its tripping delay set to 0.3. Circuit breaker B does not
receive a signal from downstream and opens immediately, in
spite of its tripping delay set to 0.2.
Wiring
bb Maximum impedance: 2.7 W / 300 m.
bb Capacity of connectors: 0.4 to 2.5 mm2.
bb Wires: single or multicore.
bb Maximum lenght: 3000 m.
bb Limits to device interconnection:
vv the common ZSI - OUT (Z1) and the output ZSI - OUT (Z2)
can be connected to a maximum of 10 upstream device
vv a maximum of 100 downstream devices may be connected
to the common ZSI - IN (Z3) and to an input ZSI - IN CR ( Z4) or
GF (Z5).
Db101420.eps
D-7
208E_CATALOGUE.indb 7
09/12/2014 14:17:47
Masterpact NT and NW
Electrical diagrams
Communication
DB417985.eps
Communication architecture
Ethernet
24 V DC
Modbus
A
24 V DC
24 V DC
I
+24V
0V
Eth2
Eth1
+24V
0V
+24V
0V
Eth2
Eth1
Eth2
Eth1
I
I
I1
I2
I3
I4
I6
I5
I4
I3
I2
I1
I6
I5
+
DC
24V
A1
O1
O2
O3
dule
IO Mo
I3
I2
I1
I4
I6
I5
O3
I6
I1
O2
I6
I5
I3
I2
I1
O1
13
I2
23
33
T1
A1
T2
34
24
14
+
DC
24V
I1
I2
I6
I5
I3
+
DC
24V
dule
IO Mo
T1
O2
O1
13
T1
O2
O1
13
23
23
A1
T2
24
14
A1
T2
24
14
A FDM121 (TRV00121)
Masterpact NT/NW
C IFE (LV434010)
G Compact NS630b-3200
D IFM (TRV00210)
H Compact NSX
ULP cable
J FDM128 (LV434128)
(1)
N Modbus Termination
(VW3A8306DRC)
M NSX cord
Ethernet
Modbus
(1) Modbus termination is mandatory, see ULP system user guide TRV99101.
D-8
208E_CATALOGUE.indb 8
09/12/2014 14:17:48
Electrical diagrams
DB416707.eps
FDM
Color
Red
E1
24 V
Black
E2
0V
White
E5
Blue
E6
Breaker ULP
cord
Black
Red
White Blue
E1 E2 E3 E4 E5 E6
B / Rx+ D1
A / Rx- D0
B / Tx+ D1
0V
A / Tx- D0
24 V
Ethernet
Modbus-SL
- +
ULP cable
24VDC
ETH1
ETH2
IFE
IFM
ULP Termination
ULP Termination
OR
D-9
208E_CATALOGUE.indb 9
09/12/2014 14:17:50
Withdrawable Masterpact
NT and NW
Electrical diagrams
DB416708.eps
FDM
24VDC
Color
Red
E1
24 V
Black
E2
0V
White
E5
Blue
E6
I/O
application
module
ULP cable
Breaker ULP
cord
Red Black
White Blue
E1 E2 E3 E4 E5 E6
B / Rx+ D1
A / Rx- D0
B / Tx+ D1
0V
A / Tx- D0
24 V
Modbus-SL
Ethernet
24 V DC
24 V DC
24VDC
ETH1
ETH2
IFE
IFM
ULP Termination
ULP Termination
OR
D-10
208E_CATALOGUE.indb 10
09/12/2014 14:17:51
Masterpact NT and NW
Electrical diagrams
bb The 24 V DC external power-supply (AD module) for the Micrologic control unit
(F1- F2+) is not required for basic protections LSIG.
bb The 24 V DC external power-supply (AD module) for the programmable contact
M2C/M6C is required.
bb The 24 V DC external power-supply for the BCM ULP communication module
(E1-E2) is required.The same 24 V DC external power supply can be used for the
communication devices (IFE, IFM, I/O, FDM).
bb If the 24 V DC external power supply (AD module) is used to supply Micrologic
control unit, this power supply shall be used only for supplying Micrologic control
units and M2C/M6C.
bb The dedicated AD power supplies shall be used only for the Micrologic trip units. If
the COM option is used, a second dedicated 24 V DC external power supply shall be
used.
bb With Micrologic A/E, it is recommended to connect 24 V DC external power-supply
(AD module) to the Micrologic control unit (F1- F2+) in order to keep available
the display and the energy metering, even if Current < 20 % In.
Note: in case of using the 24 V DC external power supply (AD module), maximum cable length
between 24 V DC (G1, G2) and the control unit (F1-, F2+) must not exceed 10 meters.
The BAT battery module, mounted in series upstream of the AD module, ensures
an uninterrupted supply of power if the AD module power supply fails.
The internal voltage taps are connected to the botton side of the circuit breaker.
With Micrologic P/H, external voltage taps are possible using the PTE option.
With this option, the internal voltage taps are disconnected and the voltage taps are connected
to terminals VN, V1, V2, V3.
The PTE option is required for voltages less than 220 V and greater than 690 V (in which case
a voltage transformer is compulsory). For three-pole devices, the system is supplied with
terminal VN connected only to the control unit (Micrologic P).
110/415 V AC
24/125 V DC
When the PTE option is implemented, the voltage measurement input must be protected against
short-circuits. Installed as close as possible to the busbars, this protection function is ensured
by a P25M circuit breaker (1 A rating) with an auxiliary contact (cat. no. 21104 and 21117).
This voltage measurement input is reserved exclusively for the control unit and must not ever be
used to supply other circuits outside the switchboard.
Connection
The maximum length for each conductor supplying power to the trip unit or M6C
module is 10 m.
Do not ground F2+, F1-, or power supply output:
bb the positive terminal (F2+) on the trip unit must not be connected to earth ground
bb the negative terminal (F1-) on the trip unit must not be connected to earth ground
bb the output terminals (- and +) of the 24 V DC power supply must not be grounded.
Reduce electromagnetic interference:
bb the input and output wires of the 24 V DC power supply must be physically
separated as much as possible
bb the 24 V DC wires (output of the 24 V DC power supply) shall be twisted together.
bb the 24 V DC wires (output of the 24 V DC power supply) must cross all power
cables perpendicularly
bb power supply conductors must be cut to length. Do not loop excess conductor.
D-11
208E_CATALOGUE.indb 11
09/12/2014 14:17:52
TOOLS
Ecodial
Ecodial software is dedicated to LV electrical installation
calculation in accordance with the IEC60364
international standard or national standards.
This 4th generation, "Ecodial Advance Calculation 4",
offers a new ergonomic and new features:
ppoperating mode that allows easy calculation in case
of installation with different type of sources
(parallel transformers, back-up generators)
ppdiscrimination analysis associating curves checking
and discrimination tables
ppdirect access to protection settings including residual
current protections
ppeasy selection of alternate solutions or manual
selection of a product.
208E_CATALOGUE.indb 12
09/12/2014 14:17:52
Masterpact NT and NW
Additional characteristics
Contents
Presentation
Functions and characteristics
Installation recommendations
Dimensions and connections
Electrical diagrams
Tripping curves
2
A-1
B-1
C-1
D-1
E-2
Limitation curves
Current limiting
E-4
Energy limiting
E-5
F-1
E-1
208E_CATALOGUE.indb 1
09/12/2014 14:17:53
Tripping curves
Additional
characteristics
DB105112.EPS
Micrologic 2.0
Db105113.eps
E-2
208E_CATALOGUE.indb 2
09/12/2014 14:17:53
Tripping curves
Additional
characteristics
DB101505.eps
(1)
Ig = In x...
In < 400 A
400 A y In y 1200 A
In > 1200 A
0.3
0.2
500
0.3
0.3
640
0.4
0.4
720
0.5
0.5
800
0.6
0.6
880
0.7
0.7
960
0.8
0.8
1040
0.9
0.9
1120
1
1
1200
DB101506.eps
E-3
208E_CATALOGUE.indb 3
09/12/2014 14:17:53
Limitation curves
Additional
characteristics
Current limiting
Voltage 380/415/440 V AC
Db101515.eps
Voltage 660/690 V AC
Db101516.eps
E-4
208E_CATALOGUE.indb 4
09/12/2014 14:17:54
Limitation curves
Additional
characteristics
Energy limiting
Voltage 380/415/440 V AC
Db101513.eps
Limited energy
Voltage 660/690 V AC
Db101514.eps
Limited energy
E-5
208E_CATALOGUE.indb 5
09/12/2014 14:17:54
TOOLS
schneider-electric.com
This international site allows you
to access all the Schneider Electric
Solution and Product information via :
ppcomprehensive descriptions
pprange data sheets
ppa download area
ppproduct selectors
pp...
You can also access the information
dedicated to your business and get
in touch with your Schneider Electric
country support.
208E_CATALOGUE.indb 2
09/12/2014 14:17:55
Masterpact NT and NW
Catalogue numbers
andorderform
Presentation 2
Functions and characteristics
A-1
Dimensions and connections
C-1
Installation recommendations
B-1
Electrical diagrams
D-1
Additional characteristics
E-1
F-2
F-3
Masterpact NT
Connection F-4
Micrologic control unit, communication option, accessories
F-5
Remote operation
F-6
F-7
Clusters F-8
Circuit breaker locking and accessories
F-9
F-10
Indication contacts
F-11
Instructions F-12
F-13
Masterpact NW
Connection F-14
Micrologic control unit, communication option, accessories
F-15
Remote operation
F-16
F-17
Clusters F-18
Circuit breaker locking and accessories
F-19
F-20
Indication contacts
F-21
Instructions F-22
F-23
Masterpact NT and NW
F-24
F-1
208E_CATALOGUE.indb 1
09/12/2014 14:17:55
Catalogue numbers
Device to be replaced
Connection to be ordered
Top
Bottom
Type H1/H2/HI/HF
Top
Bottom
3x
3x
3P
EF548951
EF548964
4x
4x
4P
EF548951
EF548964
3x
3x
EF548954
EF548965
4x
4x
EF548954
EF548965
3x
3x
EF548954
EF548965
4x
4x
EF548954
EF548965
3x
3x
EF548957
EF548958
4x
4x
EF548957
EF548958
1x
1x
EF548962
EF548961
1x
1x
EF548960
EF548960
Masterpact M16
Type N1/NI/H1/H2/HI/HF
Top
Bottom
Masterpact M32
Type H1/H2/HI/HF
Top
Bottom
Device to be replaced
Connection to be ordered
Type N1/NI
Top
Bottom
Type H1/H2/HI/HF
Top
Bottom
3x
3x
3P
EF548952
EF548952
4x
4x
4P
EF548952
EF548952
3x
3x
EF548953
EF548953
4x
4x
EF548953
EF548953
3x
3x
EF548953
EF548953
4x
4x
EF548953
EF548953
3x
3x
EF548956
EF548956
4x
4x
EF548956
EF548956
1x
1x
EF548959
EF548959
1x
1x
EF548963
EF548963
1x
4P
EF548927
1x
4P
EF548928
1x
4P
EF548930
Masterpact M16
Type N1/NI/H1/H2/HI/HF
Top
Bottom
Type N1/NI/H1/H2/HI/HF
Top
Bottom
Masterpact M32
Type H1/H2/HI/HF
Top
Bottom
Installation kits
Device to be replaced
kit to be ordered
1x
3P
EF548927
Device to be replaced
kit to be ordered
1x
Device to be replaced
3P
EF548928
kit to be ordered
Type N1/NI/H1/H2/HI/HF
1x
3P
EF548930
208E_CATALOGUE.indb 2
09/12/2014 14:17:55
Catalogue numbers
Device to be replaced
Connection to be ordered
3x
3x
3P
EF548951
EF548964
4x
4x
4P
EF548951
EF548964
3x
3x
EF548954
EF548965
4x
4x
EF548954
EF548965
Type N1/NI/H1/H2/HI/HF/L1
Top
Bottom
3x
3x
EF548954
EF548965
4x
4x
EF548954
EF548965
Type N1/NI/H1/H2/HI/HF
Top
Bottom
3x
3x
EF548957
EF548958
4x
4x
EF548957
EF548958
Type H1/H2/HI/HF/M20/L1
Top
Bottom
1x
1x
EF548973
EF548973
1x
1x
EF548976
EF548977
1x
1x
EF548973
EF548973
1x
1x
EF548977
EF548976
Top
Bottom
Type H1/H2/HI/HF/L1
Top
Bottom
Masterpact M16
Top
Bottom
Device to be replaced
Connection to be ordered
3x
3x
3P
EF548966
EF548966
4x
4x
4P
EF548966
EF548966
3x
3x
EF548969
EF548969
4x
4x
EF548969
EF548969
Type N1/NI/H1/H2/HI/HF/L1
Top
Bottom
3x
3x
EF548969
EF548969
4x
4x
EF548969
EF548969
Type N1/NI/H1/H2/HI/HF
Top
Bottom
3x
3x
EF548970
EF548970
4x
4x
EF548970
EF548970
Type H1/H2/HI/HF
Top
Bottom
1x
1x
EF548974
EF548974
1x
1x
EF548978
EF548978
1x
4P
EF548927
1x
4P
EF548928
1x
1x
4P
EF548930
EF548929
Top
Bottom
Type H1/H2/HI/HF/L1
Top
Bottom
Masterpact M16
Installation kits
Device to be replaced
kit to be ordered
1x
3P
EF548927
Device to be replaced
kit to be ordered
1x
Device to be replaced
3P
EF548928
kit to be ordered
Type N1/NI/H1/H2/HI/HF
1x
1x
3P
EF548930
EF548929
F-3
208E_CATALOGUE.indb 3
09/12/2014 14:17:56
Catalogue numbers:
spare parts
Masterpact NT
Connection
Connection
DB404388.eps
250/630-1600 A
DB402836.eps
DB402835.eps
DB402869.eps
250/630-1600 A
DB402836.eps
DB402835.eps
Installation manual
Rear connection (vertical or horizontal mounting) / Replacement kit (3 or 4 parts)
250/630-1600 A
Vert. mounting.
Connection accessories
DB404389.eps
33584
33585
33588
33589
47102
33586
33587
47102
4P
33642
33643
Installation manual
47102
47070
3P
33644
Installation manual
47102
47069
47102
4P
47102
Installation manual
Rear connection (vertical or horizontal mounting) / Replacement kit (3 or 4 parts)
250/630-1600 A
Vert. mounting.
3P
33622
Installation manual
47102
33645
33623
DB404392.eps
33648
33768
47102
33648
33768
47335
47336
Installation manual
47102
DB404393.eps
F-4
208E_CATALOGUE.indb 4
09/12/2014 14:17:57
Catalogue numbers:
spare parts
Masterpact NT
Long-time rating plug (limits setting range for higher accuracy) / 1 part
DB404394.eps
Standard
Low-setting option
High-setting option
Without long-time protection
0.4 at 1 x Ir
0.4 at 0.8 x Ir
0.8 at 1 x Ir
off
33542
33543
33544
33545
For Micrologic A, E
For Micrologic P and H
33593
33592
47067
LV434010
LV434011
Battery + cover
DB404395.eps
Battery (1 part)
Cover (1 part)
menu
Communication option
DB417414.eps
DB111441.eps
DB417415.eps
IFE
TRV00210
LV434063
DOCA0084EN-00
DOCA0055EN-00
Accessories
DB404382.eps
DB404382.eps
DB404381.eps
External sensors
External sensor for earth-fault protection (TCE) / 1 part
Sensor rating
400/1600 A
33576
33579
48891
33573
54440
54441
54442
54443
54444
54445
24 V DC
54446
1 battery
47090
L4
L3
t
Inpu
24VDC
Output
24VDC G2
AD 220
G1
DB404386.eps
33594
33595
34559
34560
33590
F-5
208E_CATALOGUE.indb 5
09/12/2014 14:17:59
Catalogue numbers:
spare parts
Masterpact NT
Remote operation
Remote operation
Gear motor
DB404397.eps
MCH (1 part)
AC 50/60 Hz
DC
DB404398.eps
DB404399.eps
33186
33176
33177
33179
33179
33193
33185
33186
33187
33188
47074
33098
48 V
100/130 V
200/240 V
277/415 V
440/480 V
+ resistor
24/30 V
48/60 V
100/125 V
200/250 V
For fixed circuit breaker
For drawout circuit breaker
Fixed.
Drawout.
47103
Installation manual
33658
33659
33660
33661
33662
33663
33664
12 V DC
24/30 V DC, 24 V AC
48/60 V DC, 48 V AC
100/130 V AC/DC
200/250 V AC/DC
277 V AC
380/480 V AC
Communicating coil (1 part)
AC 50/60 Hz
12 V DC
DC
24/30 V DC, 24 V AC
48/60 V DC, 48 V AC
100/130 V AC/DC
200/250 V AC/DC
277 V AC
380/480 V AC
Terminal block (1 part)
For fixed circuit breaker
For drawout circuit breaker
33032
33033
33034
33035
33036
33037
33038
47074
33098
Installation manual
47103
33668
33669
33670
33671
33673
47074
33098
Installation manual
47103
DB404398.eps
DB404399.eps
DB404400.eps
Fixed.
Drawout.
DB404398.eps
DB404399.eps
DB404400.eps
Undervoltage release MN
Fixed.
Drawout.
MN delay unit
DB404320.eps
Installation manual
48/60 V AC/DC
100/130 V AC/DC
200/250 V AC/DC
380/480 V AC/DC
33684
33685
Rr (adjustable)
33680
33681
33682
33683
47103
F-6
208E_CATALOGUE.indb 6
09/12/2014 14:18:00
Catalogue numbers:
spare parts
Masterpact NT
Chassis locking
By padlocks
VCPO
Standard
64909
64910
64911
33173
33174
33175
Installation manual
64912
64913
64914
33189
33190
33191
33192
33769
33770
33771
33772
47104
33172
Installation manual
47104
33788
Installation manual
47104
By Profalux keylocks
Profalux
1 keylock Profalux
(without adaptation kit):
By Ronis keylocks
Ronis
1 keylock Ronis
(without adaptation kit):
Adaptation kit
(without keylock):
DB404401.eps
DB404402.eps
DB404329.eps
Chassis accessories
33767
Installation manual
47104
Terminal shield
3P
4P
47104
Installation manual
DB404403.eps
33763
33764
3P
4P
Installation manual
Note: the locking of safety shutters is integrated.
33765
33766
47104
F-7
208E_CATALOGUE.indb 7
09/12/2014 14:18:02
Catalogue numbers:
spare parts
Masterpact NT
Clusters
Clusters
DB403280.eps
64906
47554
Racking handle
47098
DB418007.eps
DB417990.eps
DB403281.eps
F-8
208E_CATALOGUE.indb 8
09/12/2014 14:18:02
Catalogue numbers:
spare parts
Masterpact NT
33897
Installation manual
47103
64918
64919
33173
33174
33175
64920
64921
33189
33190
33191
33192
47515
47516
47517
47518
47103
DB125617.eps
33895
Installation manual
47103
Escutcheon
DB403099.eps
DB403098.eps
DB403097.eps
Cover
Escutcheon
Transparent cover (IP54)
Escutcheon blanking plate
Blanking plate
Fixed
33718
47103
Installation manual
Drawout
33857
33859
33858
Front cover
47094
Installation manual
47103
DB404405.eps
47092
Installation manual
47103
DB404406.eps
Installation manual
3P
3 x 47095
3 x 47096
4P
4 x 47095
4 x 47096
47103
F-9
208E_CATALOGUE.indb 9
09/12/2014 14:18:04
Catalogue numbers:
spare parts
Masterpact NT
33912
33913
33200
33201
33209
DB416840.eps
33920
33921
F-10
208E_CATALOGUE.indb 10
09/12/2014 14:18:05
Catalogue numbers:
spare parts
Masterpact NT
Indication contacts
Indication contacts
47076
47077
47074
33098
47103
DB402876.eps
DB402865.eps
BPFE
64917
Installation manual
47103
DB402916.eps
PF
47080
47081
47074
33098
47103
1 pushbutton
47078
47079
47074
33098
47103
33170
33170
33170
33171
33171
33171
33098
47900
47104
F-11
208E_CATALOGUE.indb 11
09/12/2014 14:18:06
Catalogue numbers:
spare parts
Instructions
Chassis accessories
Circuit breaker accessories
Fixed and drawout circuit breaker
Micrologic user manual
20/50 (French)
20/50 (English)
2A/7A (French)
2A/7A (English)
2E/6E (French)
2E/6E (English)
5P/7P (French)
5P/7P (English)
5H/7H (French)
5H/7H (English)
NT user manual
French
English
Modbus communication notice for manual
Masterpact NT
Instructions
47104
47103
47102
33076
33077
33079
33080
33079
33080
33082
33083
33085
33086
47106
47107
33088
F-12
208E_CATALOGUE.indb 12
09/12/2014 14:18:06
Catalogue numbers:
spare parts
Communication option
DB417414.eps
DB111441.eps
DB417415.eps
IFE
Communication,
monitoring and control,
for NT/NW
Ethernet interface for LV breaker
Ethernet interface for LV breakers and gateway
LV434010
LV434011
TRV00210
LV434063
DOCA0084EN-00
DOCA0055EN-00
TRV00121
TRV00128
LV434128
DB111445.eps
DB111444.eps
DB115623.eps
DB111443.eps
DB127985.eps
LV434195
LV434196
LV434197
VW3A8306DRC (2)
TRV00870
TRV00880
TRV00803
TRV00806
TRV00810
TRV00820
TRV00830
TRV00850
F-13
208E_CATALOGUE.indb 13
09/12/2014 14:18:07
Catalogue numbers:
spare parts
Masterpact NW
Connection
Connection
3P
4P
Top
Top
47990
47992
47991
47993
Bottom
Bottom
47932
47942
47933
47943
800-1600 A
2000/3200 A
DB404367.eps
DB404366.eps
DB404408.eps
DB404373.eps
Installation manual
Rear connection (vertical or horizontal mounting) / Replacement kit (3 or 4 parts)
800-2000 A
Vertical
Horizontal
2500/3200 A
Vertical
Horizontal
Vertical mounting
4000 A
Vertical
Horizontal
4000b/5000 A
Vertical
Horizontal
6300 A
Vertical
Horizontal mounting
Installation manual
DB404367.eps
DB404366.eps
DB404373.eps
47950
47964
47964
47966
47966
47968
47970
2x 47966
2x 47966
2x 47968
47950
47965
47965
47967
47967
47969
47971
2x 47967
2x 47967
2x 47969
47960
47962
47961
47963
Top or bottom
Top or bottom
Installation manual
Rear connection (vertical or horizontal mounting) / Replacement kit (3 or 4 parts)
800-2000 A types N1/H1/H2 Vertical
800-1600 A types H3/L1
Horizontal
2500/3200 A types H1/H2
Vertical
2000/3200 A types H3/L1
Horizontal
Vertical mounting
4000 A
Vertical
Horizontal
4000b/5000 A
Vertical
Horizontal
6300 A
Vertical
Horizontal mounting
Installation manual
47950
47964
47964
47966
47966
47968
47970
2x 47966
2x 47966
2x 47968
47950
47965
47965
47967
47967
47969
47971
2x 47967
2x 47967
2x 47969
3P
4P
1600 A
2000/3200 A
48464
48465
48466
48467
Installation manual
Connection accessories
DB404409.eps
DB418156.eps
DB404368.eps
48599
48600
Installation manual
47950
48599
48600
DB404369.eps
47829
48556
48557
48557
DB414775.eps
F-14
208E_CATALOGUE.indb 14
09/12/2014 14:18:09
Catalogue numbers:
spare parts
Masterpact NW
Long-time rating plug (limits setting range for higher accuracy) / 1 part
DB404394.eps
Standard
Low-setting option
High-setting option
Without long-time protection
0.4 at 1 x Ir
0.4 at 0.8 x Ir
0.8 at 1 x Ir
off
33542
33543
33544
33545
For Micrologic A, E
For Micrologic P and H
33593
33592
47067
LV434010
LV434011
Battery + cover
DB404395.eps
Battery (1 part)
Cover (1 part)
menu
DB417414.eps
DB111441.eps
DB417415.eps
Communication option
IFE
TRV00210
LV434063
DOCA0084EN-00
DOCA0055EN-00
Accessories
DB404382.eps
DB404382.eps
DB404381.eps
External sensors
External sensor for earth-fault protection (TCE) / 1 part
Sensor rating
400/2000 A
1000/4000 A
4000/6300 A
34035
34036
48182
33579
48891
Rectangular sensor for earth-leakage protection + Vigi cable / 1 part (up to 3200 A)
280 mm x 115 mm
470 mm x 160 mm
33573
33574
1 battery
47090
24-30 V DC
48-60 V DC
100-125 V DC
110-130 V AC
200-240 V AC
380-415 V AC
54440
54441
54442
54443
54444
54445
24 V DC
54446
L4
L3
t
Inpu
24VDC
Output
24VDC G2
AD 220
G1
DB404386.eps
33594
33595
34559
34560
33590
F-15
208E_CATALOGUE.indb 15
09/12/2014 14:18:11
Catalogue numbers:
spare parts
Masterpact NW
Remote operation
Remote operation
Gear motor
DB404410.eps
MCH (1 part)
AC 50/60 Hz
DB404398.eps
DB404322.eps
DC
Fixed.
Drawout.
47889
47893
47894
47895
47896
47897
47888
47889
47890
47891
47074
47849
48 V
100/130 V
200/240 V
250/277 V
380/415 V
440/480 V
24/30 V
48/60 V
100/125 V
200/250 V
For fixed circuit breaker
For drawout circuit breaker
47951
Installation manual
DB404398.eps
DB404322.eps
DB404400.eps
Fixed.
Drawout.
33658
33659
33660
33661
33662
33663
33664
12 V DC
24/30 V DC, 24 V AC
48/60 V DC, 48 V AC
100/130 V AC/DC
200/250 V AC/DC
277 V AC
380/480 V AC
Communicating coil (1 part)
AC 50/60 Hz
12 V DC
DC
24/30 V DC, 24 V AC
48/60 V DC, 48 V AC
100/130 V AC/DC
200/250 V AC/DC
277 V AC
380/480 V AC
Terminal block (1 part)
For fixed circuit breaker
For drawout circuit breaker
33032
33033
33034
33035
33036
33037
33038
47074
47849
Installation manual
47951
33668
33669
33670
33671
33673
47074
47849
Installation manual
47951
DB404398.eps
DB404322.eps
DB404400.eps
Undervoltage release MN
Fixed.
MN delay unit
Drawout.
DB404320.eps
Installation manual
F-16
208E_CATALOGUE.indb 16
48/60 V AC/DC
100/130 V AC/DC
200/250 V AC/DC
380/480 V AC/DC
33684
33685
Rr (adjustable)
33680
33681
33682
33683
47951
F-16
09/12/2014 14:18:13
Catalogue numbers:
spare parts
Masterpact NW
Chassis locking
By padlocks
VCPO
Standard
64934
64935
64936
33173
33174
33175
Installation manual
64937
64938
64939
33189
33190
33191
33192
48564
48565
48566
47952
47914
Installation manual
47952
5 parts
64940
Installation manual
47952
By Profalux keylocks
Profalux
1 keylock Profalux
(without adaptation kit):
By Ronis keylocks
Ronis
1 keylock Ronis
(without adaptation kit):
Adaptation kit
(without keylock):
DB404326.eps
DB404327.eps
Racking interlock
DB404329.eps
33767
Installation manual
47952
Chassis accessories
800/4000 A
4000b/6300 A
3P
4P
3P
4P
64942
48596
48597
48598
3P
4P
3P
4P
48721
48723
48722
48724
47952
800/4000 A
4000b/6300 A
Installation manual
DB404333.eps
48591
Installation manual
47952
3P
4P
48433
48434
F-17
208E_CATALOGUE.indb 17
09/12/2014 14:18:15
Catalogue numbers:
spare parts
Masterpact NW
Clusters
Clusters
64906
DB403280.eps
L1
24
24
24
24
24
42
Masterpact NW 4P
N1
H1/H2 H3
8
8
8
8
16
16
16
16
16
16
32
32
48
56
96
96
96
32
32
48
56
L1
32
32
32
32
32
56
47554
Racking handle
47944
For NW10/20 DC
48642
For NW40 DC
48643
DB418007.eps
DB417990.eps
DB403281.eps
Racking handle
DC rear connection
DB105110.eps
DB105109.eps
F-18
208E_CATALOGUE.indb 18
09/12/2014 14:18:16
Catalogue numbers:
spare parts
Masterpact NW
48536
Installation manual
47951
By padlocks
48539
By Profalux keylocks
Profalux
1 keylock Profalux
(without adaptation kit):
By Ronis keylocks
Ronis
1 keylock Ronis
(without adaptation kit):
Adaptation kit
(without keylock):
64928
64929
64930
33173
33174
33175
64931
64932
64933
33189
33190
33191
33192
64925
64926
64927
47951
Installation manual
48535
Installation manual
47951
DB403099.eps
DB403098.eps
DB403097.eps
Escutcheon Cover
Blanking plate
Fixed
48601
Escutcheon
Transparent cover (IP 54)
Escutcheon blanking plate
Drawout
48603
48604
48605
48605
47951
Installation manual
DB404412.eps
47939
Installation manual
47951
DB404413.eps
47940
Installation manual
47951
DB404414.eps
3x
3x
6x
3x
3x
3x
3P
47935
47935
47936
47936
47937
47934
4x
4x
8x
4x
4x
4x
4P
47935
47935
47936
47936
47937
47934
47951
F-19
208E_CATALOGUE.indb 19
09/12/2014 14:18:17
Catalogue numbers:
spare parts
Masterpact NW
Mechanical interlocking
for source changeover
48612
48612
47926
47926
33209
48610
48609
48608
48614
F-20
208E_CATALOGUE.indb 20
09/12/2014 14:18:18
Catalogue numbers:
spare parts
Masterpact NW
Indication contacts
Indication contacts
DB404321.eps
64922
47074
47849
Installation manual
47951
6 A - 240 V
Low-level
For fixed circuit breaker
For drawout circuit breaker
47951
Installation manual
DB404415.eps
Changeover contacts
CE, CD, CT
47915
47916
47074
47849
6 A - 240 V
Low-level
Installation manual
PF
47080
47081
47074
47849
47951
33170
33171
47952
48560
DB404322.eps
Combined closed / connected contacts for use with 1 auxiliary contact / 1 part
1 contact (5 A - 240 V)
or 1 low-level contact
48477
48478
Installation manual
47952
DB404319.eps
BPFE
48534
Installation manual
47951
47849
47850
47900
F-21
208E_CATALOGUE.indb 21
09/12/2014 14:18:19
Catalogue numbers:
spare parts
Instructions
Chassis accessories
Circuit breaker accessories
Fixed and drawout circuit breaker
User manual
NW AC (French)
NW AC (English)
NW DC (French)
NW DC (English)
Micrologic user manual
20/50 (French)
20/50 (English)
2A/7A (French)
2A/7A (English)
2E/6E (French)
2E/6E (English)
5P/7P (French)
5P/7P (English)
5H/7H (French)
5H/7H (English)
Modbus communication notice for manual
Masterpact NW
Instructions
47952
47951
47950
47954
47955
64923
64924
33076
33077
33079
33080
33079
33080
33082
33083
33085
33086
33088
F-22
208E_CATALOGUE.indb 22
09/12/2014 14:18:19
Catalogue numbers:
spare parts
Communication option
DB417414.eps
DB111441.eps
DB417415.eps
IFE
Communication, monitoring
and control
LV434010
LV434011
TRV00210
LV434063
DOCA0084EN-00
DOCA0055EN-00
TRV00121
TRV00128
LV434128
LV434195
LV434196
LV434197
DB111443.eps
VW3A8306DRC (2)
DB115623.eps
TRV00870
TRV00880
DB111445.eps
DB127985.eps
DB111444.eps
TRV00803
TRV00806
TRV00810
TRV00820
TRV00830
TRV00850
F-23
208E_CATALOGUE.indb 23
09/12/2014 14:18:20
Masterpact NT and NW
Order form
Masterpact type
NT
NW
Rating
A
Sensor rating
A
Circuit breaker
N1, H1, H2, H3, L1
Special circuit breaker H2 anticorrosion, H10 (NW)
Special circuit breaker NW16/32 H1T, NT16 H2T
Switch-disconnector NA, HA, HF, ES, HA10 (NW)
Number of poles
3 or 4
Schneider Electric
Brand
Option: neutral on right side (NW)
Type of equipment
Fixed
Drawout with chassis
Drawout without chassis
(moving part only)
Chassis alone
Earthing switch kit for chassis
Qty
Indication contacts
Remote operation
Remote ON/OFF
A - ammeter
2.0
5.0
6.0
7.0
E - energy
2.0
5.0
6.0
P - power meter
5.0
6.0
7.0
H - harmonic meter
5.0
6.0
7.0
LR - long-time rating plug Standard 0.4 to 1 Ir
Low setting 0.4 to 0.8 Ir
High setting 0.8 to 1 Ir
LR OFF
AD - external power-supply module
V
BAT - battery module
TCE - external sensor (CT) for neutral
and residual earth-fault protection
TCE - external sensor (CT) for over sized neutral
(3P - Micrologic P / H) and residual earth-fault protection
TCW - external sensor for SGR protection
Rectangular sensor
NT (280 x 115 mm)
for earth-leakage protection
NW (470 x 160 mm)
PTE - external voltage connector
Communication
COM module
Device
(BCM-ULP)
Cradle
management
with I/O
application
module
(Chassis)
Connection
Horizontal
Vertical
Front
Vertical-connection adapters
Cable-lug adapters
Arc chute screen
Interphase barriers
Spreaders
Disconnectable
front connection adapter
Lugs for 240v or 300v cables
Mounting accessories
Top
Bottom
Top
Bottom
Top
Bottom
NT - FC fixed, draw.
NT - FC fixed, draw.
NT - FC fixed
NT, NW fixed, drawout
NT fixed, drawout
NW fixed
Remote tripping
Locking
Low level
6 A-240 V AC
V
V
V
V
V
V
V
Accessories
On backplates
Portable test kit
NT fixed, drawout
F-24
208E_CATALOGUE.indb 24
09/12/2014 14:18:21
Notes
F-25
208E_CATALOGUE.indb 25
09/12/2014 14:18:21
Notes
F-26
208E_CATALOGUE.indb 26
09/12/2014 14:18:21