You are on page 1of 61

MIST ELIMINATOR

Mist Eliminator
Specification
Gas Flow Rate
Gas Flow Rate
Operation Pressure
Operation Temperature
Flue Gas Density(Operation)
Net Face Area
Face Velocity
Pressure Drop
Limit Droplet Size
MOTOR
GENERAL
Manufacturer
Equipment driven by motor
Motor type
Quantity
DESIGN & PERFORMANCE DATA
Frame size
Type of duty
Type of enclosure & method of cooling
Degree of protection
Applicable standard to which motor
generally confirms
Type of mounting
Direction of rotation viewed from DE
Standard continuous rating at 40 deg.C
ambient temp. as per Indian Std. Kw
Derated rating for specified normal
condition i.e. 50 deg. C ambient ( Kw)
Rated voltage (volts)
Permissible variation of
voltage (volts)
Frequency (Hz)
Combined voltage & frequency
Minimum permissible starting
voltage(v)
Rated speed at rated voltage &
frequency
At rated voltage and frequency
Full load current ( A )
No load current ( approx) ( A )
Power factor at
100% load
No load

71.582 Sm3/h
78.266 m3/h
1,130 bar,abs
60,0 Degree C
1,233 kg/m3
5,9 m2
3,70 m/s
35 pa
40 Micron

CROMPTON GREAVES LTD.


As Per Customer
3PHASE, AC SQUIRREL CAGE
INDUCTION MOTOR
4
ND160L
S1
TEFC Safe Area IC 411
IP55
IS:1231,IS:12075,IS:12065,IS:325,
B3
Clockwise from DE
20.11
18.50
415.00
+-10%
50+/-5%
10% ( Absolute)
80%
2920.00
32.00
9.0/ 12.0
0.88
0.1 to 0.2

Starting
Efficiency (%)at rated voltage &
frequency
100% load
75% load
50% load
Starting current % FLC at
100% voltage
85% voltage
80% voltage

0.4 to 0.5

90.00
90.00
88.00
650.00
552.50
520.00

Starting time with minimum permissible


voltage
without driven equipment coupled
1.6 second
with driven equipment coupled
2 second
Safe stall time with 110% of rated
voltage
From hot condition in sec.
From cold condition in sec.

8.26
16.53

Torques - % FLT
Starting torque at min. permissible V
starting torq at rated V.
Pull up torque at rated voltage
Pull out torque
Min. accelerating torque available
Rated torque - kg-m

176.00
275.00
192.50
325.00
0.10
6.17

Stator winding resistance per phase


(Ohm/milli ohm at 20 C.) ( Indicative )

0.388/ 0.407

GD square value of motor - kg-m sq.


No. of permissible successive starts
when motor is in hot condition

0.21
2.00

Locked rotor KVA input


Locked rotor KVA / KW

179.42
9.70

Bearings
Type
Manufacturer
Self lubricated or forced lubricated
Recommended lubricants
Guaranteed life in hours
Whether dial type thermometer
provided
Oil pressure guage/switch
range
Contact Nos. and ratings
Accuracy
Vibration

Antifriction deep groove ball/ roller


SKF/FAG/NTN/EQUIVALENT
Self lubricated
Greased for life
> 40,000 hours
NO
N.A.

As per IS:12075

Velocity mm/s
Displacement microns
Noise level db(A) at 1 m at no load
CONSTRUCTIONAL FEATURES
Stator winding insulation
Class & type
Tropicalised (yes/no)
Temperature rise over specificed max.
i. cold water temp. of 38 deg. C
ii. Ambient air 50 deg. C.
Method of temperature measurement
Stator winding connection
Number of terminals braught out
Type of terminal box for
Stator leads
space heater
Temperature detectors
instrument switch etc.
For main terminal box
Location
Entry of cables
Recommended cable size
(to be matched with cable size
envisaged by owner)
Fault level (MVA)

As Per IS:12065

F (Temp. rise limited to class B)


NO
N.A.
70.00
by resistance
Delta
6.00
cast iron non phase seggregated
cast iron on top of main t.b.
N.A.
N.A.
RHS FROM DE
Side
1 * 3C,50-MM
50KA rms for 0.25 seconds

Temperature detector for stator winding


Type
Nos. provided
Location
make
resistance value at 0 deg. C (ohms)
space heaters
Number
Location
Power requirement (watt)
Paint shade

NO
NO
NO
NO
NO
Yes
N.A.
Winding overhang
N.A.
631 as per IS:5

weight of
Motor stator
Motor rotor
Total weight (kg)

85.20
56.80
142.00

WASTE WATER PUMP


Pump
Model
Quantity
Capacity M3/hr
Head M
Sealing
Performance Curve
Pump Speed RPM
Effeciency
Mechanical Seal
MOTOR
GENERAL
Manufacturer
Equipment driven by motor
Motor type
Quantity
DESIGN & PERFORMANCE DATA
Frame size
Type of duty
Type of enclosure & method of cooling
Degree of protection
Applicable standard to which motor
generally Confirmes
Type of mounting
Direction of rotation viewed from DE
Standard continuous rating at 40 deg.C
ambient temp. as per Indian Std. Kw
Derated rating for specified normal
condition i.e. 50 deg. C ambient ( Kw)
Rated voltage (volts)
Permissible variation of
voltage (volts)
Frequency (Hz)
Combined voltage & frequency
Minimum permissible starting
voltage(v)
Rated speed at rated voltage &
frequency
At rated voltage and frequency
Full load current ( A )
No load current ( approx) ( A )
Power factor at
100% load
No load

1.5/1AH
4
15
10
Expeller
WPA151B02A/1
1640
50%

CROMPTON GREAVES LTD.


As Per Customer
3PHASE, AC SQUIRREL CAGE
INDUCTION MOTOR
2.00

ND90L
S1
TEFC Safe Area IC 411
IP55
IS:1231,IS:12075,IS:12065,IS:325,
B3
Clockwise from DE
1.63
1.50
415.00

+-10%
50+/-5%
10% ( Absolute)
80%
1415.00
3.00
1.2/1.8

0.81
0.1 to 0.2

Starting
Efficieny (%)at rated voltage &
frequency
100% load
75% load
50% load
Starting current % FLC at
100% voltage
85% voltage
80% voltage

0.4 to 0.5

80.00
79.00
77.00
500.00
425.00
400.00

Starting time with minimum permissible


voltage
without driven equipment coupled
1.6 second
with driven equipment coupled
2.0 second
Safe stall time with 110% of rated
voltage
From hot condition in sec.
From cold condition in sec.

6.61
13.22

Torques - % FLT
Starting torque at min. permissible V
starting torq at rated V.
Pull up torque at rated voltage
Pull out torque
Min. accelerating torque available
Rated torque - kg-m

128.00
200.00
140.00
275.00
0.10
1.03

Stator winding resistance per phase


(ohm/milli ohm at 20 C.) ( Indicative )

4.915/ 5.161

GD square value of motor - kg-m sq.


No. of permissible successive starts
when motor is in hot condition

0.00

Locked rotor KVA input


Locked rotor KVA / KW

12.94
8.63

Bearings
Type
Manufacturer
Self lubricated or forced lubricated
Recommended lubricants
Guaranteed life in hours
Whether dial type thermometer
provided
Oil pressure guage/switch
range

2.00

Antifriction deep groove ball/ roller


SKF/FAG/NTN/EQUIVALENT
Self lubricated
Greased for life
> 40,000 hours
NO
N.A.

Contact Nos. and ratings


Accuracy
Vibration
Velocity mm/s
Displacement microns
Noise level db(A) at 1 m at no load
CONSTRUCTIONAL FEATURES
Stator winding insulation
Class & type
Tropicalised (yes/no)
Temperature rise over specificed max.
i. cold water temp. of 38 deg. C
ii. Ambient air 50 deg. C.
Method of temperature measurement
Stator winding connection
Number of terminals braught out
Type of terminal box for
Stator leads
space heater
Temperature detectors
instrument switch etc.
For main terminal box
Location
Entry of cables
Recommended cable size
(to be matched with cable size
envisaged by owner)
Fault level (MVA)

As per IS:12075

As Per IS:12065

F (Temp. rise limited to class B)


NO
N.A.
70.00
by resistance
Delta
3.00
cast iron non phase seggregated
cast iron on top of main t.b.
N.A.
N.A.

RHS FROM DE
Side
1 * 3C,2.5-MM

50KA rms for 0.25 seconds

Temperature detector for stator winding


Type
Nos. provided
Location
make
resistance value at 0 deg. C (ohms)
space heaters
Number
Location
Power requirement (watt)
Paint shade

NO
NO
NO
NO
NO
Yes
N.A.
Winding overhang
N.A.
631 as per IS:5

weight of
Motor stator
Motor rotor
Total weight (kg)

14.40
9.60
24.00

LIME SLURRY PUMP


Pump Specifications
Model
Quantity
Capacity M3/hr
Head M
Sealing
Performance Curve
Pump Speed RPM
Effeciency
Mechanical Seal
Motor Specifications
GENERAL
Manufacturer
Equipment driven by motor
Motor type
Quantity
DESIGN & PERFORMANCE DATA
Frame size
Type of duty
Type of enclosure & method of cooling
Degree of protection
Applicable standard to which motor
generally confirms
Type of mounting
Direction of rotation viewed from DE
Standard continuous rating at 40 deg.C
ambient temp. as per Indian Std. Kw
Derated rating for specified normal
condition i.e. 50 deg. C ambient ( Kw)
Rated voltage (volts)
Permissible variation of
voltage (volts)
Frequency (Hz)
Combined voltage & frequency
Minimum permissible starting
voltage(v)
Rated speed at rated voltage &
frequency
At rated voltage and frequency
Full load current ( A )
No load current ( approx) ( A )
Power factor at
100% load
No load

1.5/BAH
6
13
12
Expeller
WPA151B02A/1
1780
48%

CROMPTON GREAVES LTD.


As Per Customer
3PHASE, AC SQUIRREL CAGE
INDUCTION MOTOR
6.00

ND112M
S1
TEFC Safe Area IC 411
IP55
IS:1231,IS:12075,IS:12065,IS:325,
B3
Clockwise from DE
4.02
3.70
415.00

+-10%
50+/-5%
10% ( Absolute)
80%
1440.00
7.00
3.3/4.0

0.82
0.1 to 0.2

Starting
Efficieny (%)at rated voltage &
frequency
100% load
75% load
50% load
Starting current % FLC at
100% voltage
85% voltage
80% voltage

0.4 to 0.5

85.00
85.00
83.00
600.00
510.00
480.00

Starting time with minimum permissible


LOAD GD2 ASSUMED=MOTOR GD2.
voltage
0.05 secs.
without driven equipment coupled
0.07 secs.
with driven equipment coupled
Safe stall time with 110% of rated
voltage
From hot condition in sec.
From cold condition in sec.

6.61
13.22

Torques - % FLT
Starting torque at min. permissible V
starting torq at rated V.
Pull up torque at rated voltage
Pull out torque
Min. accelerating torque available
Rated torque - kg-m

128.00
200.00
140.00
250.00
0.10
2.50

Stator winding resistance per phase


(ohm/milli ohm at 20 C.) ( Indicative )

4.555/ 4.783

GD square value of motor - kg-m sq.


No. of permissible successive starts
when motor is in hot condition

0.05

Locked rotor KVA input


Locked rotor KVA / KW

36.23
9.79

Bearings
Type
Manufacturer
Self lubricated or forced lubricated
Recommended lubricants
Guaranteed life in hours
Whether dial type thermometer
provided
Oil pressure guage/switch
range
Contact Nos. and ratings

2.00

Antifriction deep groove ball/ roller


SKF/FAG/NTN/EQUIVALENT
Self lubricated
Greased for life
> 40,000 hours
NO
N.A.

Accuracy
Vibration
Velocity mm/s
Displacement microns
Noise level db(A) at 1 m at no load
CONSTRUCTIONAL FEATURES
Stator winding insulation
Class & type
Tropicalised (yes/no)
Temperature rise over specificed max.
i. cold water temp. of 38 deg. C
ii. Ambient air 50 deg. C.
Method of temperature measurement
Stator winding connection
Number of terminals braught out
Type of terminal box for
Stator leads
space heater
Temperature detectors
instrument switch etc.
For main terminal box
Location
Entry of cables
Recommended cable size
(to be matched with cable size
envisaged by owner)
Fault level (MVA)
Temperature detector for stator winding
Type
Nos. provided
Location
make
resistance value at 0 deg. C (ohms)
space heaters
Number
Location
Power requirement (watt)
Paint shade
weight of
Motor stator
Motor rotor
Total weight (kg)

As per IS:12075

As Per IS:12065

F (Temp. rise limited to class B)


NO
N.A.
70.00
by resistance
Delta
6.00

cast iron non phase seggregated


cast iron on top of main t.b.
N.A.
N.A.

RHS FROM DE
Side
1 * 3C,10-MM

50KA rms for 0.25 seconds


NO
NO
NO
NO
NO
Yes
N.A.
Winding overhang
N.A.
631 as per IS:5
27.00
18.00
45.00

EMERGENCY SLURRY PUMP


Pump Specification
Model
Quantity
Capacity M3/hr
Head M
Sealing
Performance Curve
Pump Speed RPM
Efficiency
Mechanical Seal

2/1.5AH
2
25
15
Mechanical Seal
WPA215B02/1
1675
48%
Flow Serve

Motor
GENERAL
Manufacturer
Equipment driven by motor
Motor type
Quantity
DESIGN & PERFORMANCE DATA
Frame size
Type of duty
Type of enclosure & method of cooling
Degree of protection
Applicable standard to which motor
generally confirms
Type of mounting
Direction of rotation viewed from DE
Standard continuous rating at 40 deg.C
ambient temp. as per Indian Std. Kw
Derated rating for specified normal
condition i.e. 50 deg. C ambient ( Kw)
Rated voltage (volts)
Permissible variation of
voltage (volts)
Frequency (Hz)
Combined voltage & frequency
Minimum permissible starting voltage(v)
Rated speed at rated voltage & frequency
At rated voltage and frequency
Full load current ( A )
No load current ( approx) ( A )
Power factor at
100% load
No load
Starting

CROMPTON GREAVES LTD.


As Per Customer
3PHASE, AC SQUIRREL CAGE INDUCTION
MOTOR
2.00

ND132M
S1
TEFC Safe Area IC 411
IP55
IS:1231,IS:12075,IS:12065,IS:325,
B3
Clockwise from DE
8.15
7.50
415.00

+-10%
50+/-5%
10% ( Absolute)
80%
1455.00
14.00
5.6/6.8

0.88
0.1 to 0.2
0.4 to 0.5

Efficieny (%)at rated voltage & frequency


100% load
75% load
50% load
Starting current % FLC at
100% voltage
85% voltage
80% voltage

87.00
86.00
84.00
600.00
510.00
480.00

Starting time with minimum permissible


voltage
without driven equipment coupled
with driven equipment coupled

0.07 secs
0.09 secs

Safe stall time with 110% of rated voltage


From hot condition in sec.
From cold condition in sec.

6.61
13.22

Torques - % FLT
Starting torque at min. permissible V
starting torq at rated V.
Pull up torque at rated voltage
Pull out torque
Min. accelerating torque available
Rated torque - kg-m

160.00
250.00
175.00
300.00
0.10
5.02

Stator winding resistance per phase


(ohm/milli ohm at 20 C.) ( Indicative )

1.804/ 1.859

GD square value of motor - kg-m sq.


No. of permissible successive starts
when motor is in hot condition

0.15

Locked rotor KVA input


Locked rotor KVA / KW

72.46
9.66

Bearings
Type
Manufacturer
Self lubricated or forced lubricated
Recommended lubricants
Guaranteed life in hours
Whether dial type thermometer provided
Oil pressure guage/switch
range
Contact Nos. and ratings
Accuracy
Vibration
Velocity mm/s
Displacement microns
Noise level db(A) at 1 m at no load

2.00

Antifriction deep groove ball/ roller


SKF/FAG/NTN/EQUIVALENT
Self lubricated
Greased for life
> 40,000 hours
NO
N.A.

As per IS:12075

As Per IS:12065

CONSTRUCTIONAL FEATURES
Stator winding insulation
Class & type
Tropicalised (yes/no)
Temperature rise over specificed max.
i. cold water temp. of 38 deg. C
ii. Ambient air 50 deg. C.
Method of temperature measurement
Stator winding connection
Number of terminals braught out
Type of terminal box for
Stator leads
space heater
Temperature detectors
instrument switch etc.
For main terminal box
Location
Entry of cables
Recommended cable size
(to be matched with cable size
envisaged by owner)
Fault level (MVA)

F (Temp. rise limited to class B)


NO
N.A.
70.00
by resistance
Delta
0.00
cast iron non phase seggregated
cast iron on top of main t.b.
N.A.
N.A.

RHS FROM DE
Side
1 * 3C,16-MM

50KA rms for 0.25 seconds


NO
NO

Temperature detector for stator winding


Type
Nos. provided
Location
make
resistance value at 0 deg. C (ohms)
space heaters
Number
Location
Power requirement (watt)
Paint shade

NO
NO
NO
Yes
N.A.
Winding overhang
N.A.
631 as per IS:5

weight of
Motor stator
Motor rotor
Total weight (kg)

47.40
31.60
79.00

RECOVERED WATER PUMP


Pump Specification:Model
Quantity
Capacity M3/hr
Head M
Sealing
Performance Curve
Pump Speed RPM
Effeciency
Mechanical Seal

1.5/1AH
4
25
40.5
Expeller
WPA151B02A/1
3185
49%

Motor
GENERAL
Manufacturer
Equipment driven by motor
Motor type
Quantity
DESIGN & PERFORMANCE DATA
Frame size
Type of duty
Type of enclosure & method of cooling
Degree of protection
Applicable standard to which motor
generally confirms
Type of mounting
Direction of rotation viewed from DE
Standard continuous rating at 40 deg.C
ambient temp. as per Indian Std. Kw
Derated rating for specified normal
condition i.e. 50 deg. C ambient ( Kw)
Rated voltage (volts)
Permissible variation of
voltage (volts)
Frequency (Hz)
Combined voltage & frequency
Minimum permissible starting voltage(v)
Rated speed at rated voltage & frequency
At rated voltage and frequency
Full load current ( A )
No load current ( approx) ( A )
Power factor at
100% load
No load
Starting

CROMPTON GREAVES LTD.


As Per Customer
3PHASE, AC SQUIRREL CAGE INDUCTION
MOTOR
4

ND160M
S1
TEFC Safe Area IC 411
IP55
IS:1231,IS:12075,IS:12065,IS:325,
B3
Clockwise from DE
10.11
9.30
415

+-10%
50+/-5%
10% ( Absolute)
80%
1460
17
7/ 9

0.84
0.1 to 0.2
0.4 to 0.5

Efficieny (%)at rated voltage & frequency


100% load
75% load
50% load
Starting current % FLC at
100% voltage
85% voltage
80% voltage

88.5
88.5
86.5
500
425
400

Starting time with minimum permissible


voltage
without driven equipment coupled
with driven equipment coupled

1.6 second
2 second

Safe stall time with 110% of rated voltage


From hot condition in sec.
From cold condition in sec.

8.26446281
16.52892562

Torques - % FLT
Starting torque at min. permissible V
starting torq at rated V.
Pull up torque at rated voltage
Pull out torque
Min. accelerating torque available
Rated torque - kg-m

112
175
122.5
225
10%
6.20

Stator winding resistance per phase


(ohm/milli ohm at 20 C.) ( Indicative )

1.242/ 1.304

GD square value of motor - kg-m sq.


No. of permissible successive starts
when motor is in hot condition

0.28

Locked rotor KVA input


Locked rotor KVA / KW

73
7.88

Bearings
Type
Manufacturer
Self lubricated or forced lubricated
Recommended lubricants
Guaranteed life in hours
Whether dial type thermometer provided
Oil pressure guage/switch
range
Contact Nos. and ratings
Accuracy
Vibration
Velocity mm/s

Antifriction deep groove ball/ roller


SKF/FAG/NTN/EQUIVALENT
Self lubricated
Greased for life
> 40,000 hours
NO
N.A.

As per IS:12075

Displacement microns
Noise level db(A) at 1 m at no load
CONSTRUCTIONAL FEATURES
Stator winding insulation
Class & type
Tropicalised (yes/no)
Temperature rise over specificed max.
i. cold water temp. of 38 deg. C
ii. Ambient air 50 deg. C.
Method of temperature measurement
Stator winding connection
Number of terminals braught out
Type of terminal box for
Stator leads
space heater
Temperature detectors
instrument switch etc.
For main terminal box
Location
Entry of cables
Recommended cable size
(to be matched with cable size
envisaged by owner)
Fault level (MVA)

As Per IS:12065

F (Temp. rise limited to class B)


NO
N.A.
70
by resistance
Delta
6
cast iron non phase seggregated
cast iron on top of main t.b.
N.A.
N.A.

RHS FROM DE
Side
1 * 3C,35-MM

50KA rms for 0.25 seconds


NO
NO

Temperature detector for stator winding


Type
Nos. provided
Location
make
resistance value at 0 deg. C (ohms)
space heaters
Number
Location
Power requirement (watt)
Paint shade

NO
NO
NO
Yes
N.A.
Winding overhang
N.A.
631 as per IS:5

weight of
Motor stator
Motor rotor
Total weight (kg)

66
44
110

PROCESS WATER PUMP- motor


GENERAL
Manufacturer
Equipment driven by motor
Motor type
Quantity

CROMPTON GREAVES LTD.


As Per Customer
3PHASE, AC SQUIRREL CAGE INDUCTION
MOTOR
4

DESIGN & PERFORMANCE DATA


Frame size
Type of duty
Type of enclosure & method of cooling
Degree of protection
Applicable standard to which motor

ND160M
S1
TEFC Safe Area IC 411
IP55
IS:1231,IS:12075,IS:12065,IS:325,

generally confirms
Type of mounting
Direction of rotation viewed from DE

B3
Clockwise from DE

Standard continuous rating at 40 deg.C


ambient temp. as per Indian Std. Kw

16.30

Derated rating for specified normal


condition i.e. 50 deg. C ambient ( Kw)
Rated voltage (volts)

15.00
415.00

Permissible variation of
voltage (volts)
Frequency (Hz)
Combined voltage & frequency

Minimum permissible starting voltage(v)


Rated speed at rated voltage & frequency

+-10%
50+/-5%
10% ( Absolute)

80%
2920.00

At rated voltage and frequency


Full load current ( A )
No load current ( approx) ( A )

26.00
8.0/ 12.0

Power factor at
100% load

0.88

No load
Starting

0.1 to 0.2
0.4 to 0.5

Efficieny (%)at rated voltage & frequency


100% load
75% load
50% load

89.50
89.50
87.50

Starting current % FLC at


100% voltage
85% voltage
80% voltage

650.00
552.50
520.00

Starting time with minimum permissible


voltage
without driven equipment coupled
with driven equipment coupled

1.6 second
2 second

Safe stall time with 110% of rated voltage


From hot condition in sec.
From cold condition in sec.

8.26
16.53

Torques - % FLT
Starting torque at min. permissible V
starting torq at rated V.
Pull up torque at rated voltage
Pull out torque
Min. accelerating torque available
Rated torque - kg-m

Stator winding resistance per phase

160.00
250.00
175.00
300.00
0.10
5.00

0.468/ 0.491

(ohm/milli ohm at 20 C.) ( Indicative )

GD square value of motor - kg-m sq.

0.17

No. of permissible successive starts


when motor is in hot condition

2.00

Locked rotor KVA input


Locked rotor KVA / KW

145.78
9.72

Bearings
Type
Manufacturer
Self lubricated or forced lubricated
Recommended lubricants
Guaranteed life in hours
Whether dial type thermometer provided
Oil pressure guage/switch

Antifriction deep groove ball/ roller


SKF/FAG/NTN/EQUIVALENT
Self lubricated
Greased for life
> 40,000 hours
NO
N.A.

range
Contact Nos. and ratings
Accuracy
Vibration

As per IS:12075

Velocity mm/s
Displacement microns
Noise level db(A) at 1 m at no load

As Per IS:12065

CONSTRUCTIONAL FEATURES
Stator winding insulation
Class & type
Tropicalised (yes/no)

F (Temp. rise limited to class B)


NO

Temperature rise over specificed max.


i. cold water temp. of 38 deg. C
ii. Ambient air 50 deg. C.
Method of temperature measurement
Stator winding connection
Number of terminals braught out

N.A.
70.00
by resistance
Delta
6.00

Type of terminal box for


Stator leads
space heater
Temperature detectors

cast iron non phase seggregated


cast iron on top of main t.b.
N.A.

instrument switch etc.

N.A.

For main terminal box


Location
Entry of cables
Recommended cable size

RHS FROM DE
Side
1 * 3C,35-MM

(to be matched with cable size


envisaged by owner)
Fault level (MVA)

Temperature detector for stator winding


Type

50KA rms for 0.25 seconds

NO
NO

Nos. provided
Location
make
resistance value at 0 deg. C (ohms)
space heaters
Number
Location
Power requirement (watt)
Paint shade

NO
NO
NO
Yes
N.A.
Winding overhang
N.A.
631 as per IS:5

weight of
Motor stator
Motor rotor
Total weight (kg)

66.00
44.00
110.00

BLEED PUMP
Pump Specifications:Model
Quantity
Capacity M3/hr
Head M
Sealing
Performance Curve
Pump Speed RPM
Effeciency
Mechanical Seal

3/2CAH
4
36
46
Mechanical Seal
WPA32A01A/2
2300
51%
Flow Serve

Motor
GENERAL
Manufacturer
Equipment driven by motor
Motor type
Quantity
DESIGN & PERFORMANCE DATA
Frame size
Type of duty
Type of enclosure & method of cooling
Degree of protection
Applicable standard to which motor
generally confirms
Type of mounting
Direction of rotation viewed from DE
Standard continuous rating at 40 deg.C
ambient temp. as per Indian Std. Kw
Derated rating for specified normal
condition i.e. 50 deg. C ambient ( Kw)
Rated voltage (volts)
Permissible variation of
voltage (volts)
Frequency (Hz)
Combined voltage & frequency
Minimum permissible starting voltage(v)
Rated speed at rated voltage & frequency
At rated voltage and frequency
Full load current ( A )
No load current ( approx) ( A )
Power factor at
100% load
No load
Starting

CROMPTON GREAVES LTD.


As Per Customer
3PHASE, AC SQUIRREL CAGE INDUCTION
MOTOR
4.00

ND180M
S1
TEFC Safe Area IC 411
IP55
IS:1231,IS:12075,IS:12065,IS:325,
B3
Clockwise from DE
20.11
18.50
415.00

+-10%
50+/-5%
10% ( Absolute)
80%
1475.00
34.00
11.5/13.5

0.83
0.1 to 0.2
0.4 to 0.5

Efficieny (%)at rated voltage & frequency


100% load
75% load
50% load
Starting current % FLC at
100% voltage
85% voltage
80% voltage

91.00
91.00
89.00
500.00
425.00
400.00

Starting time with minimum permissible


voltage
without driven equipment coupled
with driven equipment coupled

1.6 second
2 second

Safe stall time with 110% of rated voltage


From hot condition in sec.
From cold condition in sec.

8.26
16.53

Torques - % FLT
Starting torque at min. permissible V
starting torq at rated V.
Pull up torque at rated voltage
Pull out torque
Min. accelerating torque available
Rated torque - kg-m

128.00
200.00
140.00
250.00
0.10
12.22

Stator winding resistance per phase


(ohm/milli ohm at 20 C.) ( Indicative )

0.461/ 0.484

GD square value of motor - kg-m sq.


No. of permissible successive starts
when motor is in hot condition

0.71

Locked rotor KVA input


Locked rotor KVA / KW

146.64
7.93

Bearings
Type
Manufacturer
Self lubricated or forced lubricated
Recommended lubricants
Guaranteed life in hours
Whether dial type thermometer provided
Oil pressure guage/switch
range
Contact Nos. and ratings
Accuracy
Vibration
Velocity mm/s

2.00

Antifriction deep groove ball/ roller


SKF/FAG/NTN/EQUIVALENT
Self lubricated
Greased for life
> 40,000 hours
NO
N.A.

As per IS:12075

Displacement microns
Noise level db(A) at 1 m at no load
CONSTRUCTIONAL FEATURES
Stator winding insulation
Class & type
Tropicalised (yes/no)
Temperature rise over specificed max.
i. cold water temp. of 38 deg. C
ii. Ambient air 50 deg. C.
Method of temperature measurement
Stator winding connection
Number of terminals braught out
Type of terminal box for
Stator leads
space heater
Temperature detectors
instrument switch etc.
For main terminal box
Location
Entry of cables
Recommended cable size
(to be matched with cable size
envisaged by owner)
Fault level (MVA)

As Per IS:12065

F (Temp. rise limited to class B)


NO
N.A.
70.00
by resistance
Delta
6.00
cast iron non phase seggregated
cast iron on top of main t.b.
N.A.
N.A.

RHS FROM DE
Side
1 * 3C,50-MM

50KA rms for 0.25 seconds


NO
NO

Temperature detector for stator winding


Type
Nos. provided
Location
make
resistance value at 0 deg. C (ohms)
space heaters
Number
Location
Power requirement (watt)
Paint shade

NO
NO
NO
Yes
N.A.
Winding overhang
N.A.
631 as per IS:5

weight of
Motor stator
Motor rotor
Total weight (kg)

97.20
64.80
162.00

HAMMER MILL
Crusher Specifications:
Type of Crusher

Hammer Mill

Rotor Diameter

800 mm

Width

600 mm

Machine RPM

1008 rpm

Rotor Peripheral Speed

42.22 Mts/Sec

Maximum Feed Size

60 to 65 mm(90% passing)

Product(mm)

-20

Capacity

20 TPH at 10mm gap setting

Gap Setting

10 mm

Motor
GENERAL
Manufacturer
Equipment driven by motor
Motor type
Quantity

CROMPTON GREAVES LTD.


As Per Customer
3PHASE, AC SQUIRREL CAGE INDUCTION
MOTOR
1.00

DESIGN & PERFORMANCE DATA


Frame size
Type of duty
Type of enclosure & method of cooling
Degree of protection
Applicable standard to which motor

ND200L
S1
TEFC Safe Area IC 411
IP55
IS:1231,IS:12075,IS:12065,IS:325,

generally confirms
Type of mounting
Direction of rotation viewed from DE

B3
Bidirectional

Standard continuous rating at 40 deg.C


ambient temp. as per Indian Std. Kw

32.61

Derated rating for specified normal


condition i.e. 50 deg. C ambient ( Kw)
Rated voltage (volts)

Permissible variation of

30.00
415.00

voltage (volts)
Frequency (Hz)
Combined voltage & frequency

Minimum permissible starting voltage(v)


Rated speed at rated voltage & frequency

+-10%
50+/5%
10% ( Absolute)

80%
1475.00

At rated voltage and frequency


Full load current ( A )
No load current ( approx) ( A )

52.00
15.0/ 19.0

Power factor at
100% load
No load
Starting

0.87
0.1 to 0.2
0.4 to 0.5

Efficieny (%)at rated voltage & frequency


100% load
75% load
50% load

92.00
92.00
90.50

Starting current % FLC at


100% voltage
85% voltage
80% voltage

600.00
510.00
480.00

Starting time with minimum permissible


voltage
without driven equipment coupled
with driven equipment coupled

1.6 second
2 second

Safe stall time with 110% of rated voltage


From hot condition in sec.
From cold condition in sec.

9.92
19.83

Torques - % FLT
Starting torque at min. permissible V

144.00

starting torq at rated V.


Pull up torque at rated voltage
Pull out torque
Min. accelerating torque available
Rated torque - kg-m

Stator winding resistance per phase

225.00
157.50
275.00
0.10
19.81

0.232/ 0.244

(ohm/milli ohm at 20 C.) ( Indicative )

GD square value of motor - kg-m sq.

1.62

No. of permissible successive starts


when motor is in hot condition

Locked rotor KVA input


Locked rotor KVA / KW

2.00

269.13
8.97

Bearings
Type
Manufacturer
Self lubricated or forced lubricated
Recommended lubricants
Guaranteed life in hours
Whether dial type thermometer provided
Oil pressure guage/switch

Antifriction deep groove ball/ roller


SKF/FAG/NTN/EQUIVALENT
Self lubricated
Greased for life
> 40,000 hours
NO
N.A.

range
Contact Nos. and ratings
Accuracy
Vibration

As per IS:12075

Velocity mm/s
Displacement microns
Noise level db(A) at 1 m at no load

CONSTRUCTIONAL FEATURES
Stator winding insulation

As Per IS:12065

Class & type


Tropicalised (yes/no)

F (Temp. rise limited to class B)


NO

Temperature rise over specificed max.


i. cold water temp. of 38 deg. C
ii. Ambient air 50 deg. C.
Method of temperature measurement
Stator winding connection
Number of terminals braught out

N.A.
70.00
by resistance
Delta
6.00

Type of terminal box for


Stator leads
space heater
Temperature detectors
instrument switch etc.

cast iron non phase seggregated


cast iron on top of main t.b.
N.A.
N.A.

For main terminal box


Location
Entry of cables
Recommended cable size

RHS FROM DE
Side
2 * 3C,95-MM

(to be matched with cable size


envisaged by owner)
Fault level (MVA)

Temperature detector for stator winding


Type

50KA rms for 0.25 seconds

NO
NO

Nos. provided
Location
make
resistance value at 0 deg. C (ohms)
space heaters
Number
Location
Power requirement (watt)
Paint shade

weight of

NO
NO
NO
Yes
SPACE HEATER 60WX1 (200/225)
Winding overhang
SPACE HEATER 60WX1 (200/225)
631 as per IS:5

Motor stator
Motor rotor
Total weight (kg)

151.20
100.80
252.00

OXIDATION BLOWER
MOTOR
GENERAL
Manufacturer
Equipment driven by motor
Motor type
Quantity
DESIGN & PERFORMANCE DATA
Frame size
Type of duty
Type of enclosure & method of cooling
Degree of protection
Applicable standard to which motor
generally confirms
Type of mounting
Direction of rotation viewed from DE
Standard continuous rating at 40 deg.C
ambient temp. as per Indian Std. Kw
Derated rating for specified normal
condition i.e. 50 deg. C ambient ( Kw)
Rated voltage (volts)
Permissible variation of
voltage (volts)
Frequency (Hz)
Combined voltage & frequency
Minimum permissible starting voltage(v)
Rated speed at rated voltage & frequency
At rated voltage and frequency
Full load current ( A )
No load current ( approx) ( A )
Power factor at
100% load
No load
Starting
Efficieny (%)at rated voltage & frequency
100% load
75% load
50% load
Starting current % FLC at
100% voltage
85% voltage
80% voltage
Starting time with minimum permissible

CROMPTON GREAVES LTD.


As Per Customer
3PHASE, AC SQUIRREL CAGE INDUCTION
MOTOR
4.00

ND315L
S1
TEFC Safe Area IC 411
IP55
IS:1231,IS:12075,IS:12065,IS:325,
B3
Clockwise from DE
143.48
132.00
415.00

+-10%
50+/-5%
10% ( Absolute)
80%
990.00
226.00
68/75

0.86
0.1 to 0.2
0.4 to 0.5

94.50
94.50
93.00
500.00
425.00
400.00

voltage
without driven equipment coupled
with driven equipment coupled

1.6 second
2 second

Safe stall time with 110% of rated voltage


From hot condition in sec.
From cold condition in sec.

12.40
24.79

Torques - % FLT
Starting torque at min. permissible V
starting torq at rated V.
Pull up torque at rated voltage
Pull out torque
Min. accelerating torque available
Rated torque - kg-m

128.00
200.00
140.00
250.00
0.10
129.87

Stator winding resistance per phase


(ohm/milli ohm at 20 C.) ( Indicative )

29.000/30.450

GD square value of motor - kg-m sq.


No. of permissible successive starts
when motor is in hot condition

25.26

Locked rotor KVA input


Locked rotor KVA / KW

974.72
7.38

Bearings
Type
Manufacturer
Self lubricated or forced lubricated
Recommended lubricants
Guaranteed life in hours
Whether dial type thermometer provided
Oil pressure guage/switch
range
Contact Nos. and ratings
Accuracy
Vibration
Velocity mm/s
Displacement microns
Noise level db(A) at 1 m at no load
CONSTRUCTIONAL FEATURES
Stator winding insulation
Class & type
Tropicalised (yes/no)
Temperature rise over specificed max.
i. cold water temp. of 38 deg. C
ii. Ambient air 50 deg. C.
Method of temperature measurement

2.00

Antifriction deep groove ball/ roller


SKF/FAG/NTN/EQUIVALENT
Self lubricated
Lithium base grease grade II
> 40,000 hours
NO
N.A.

As per IS:12075

As Per IS:12065

F (Temp. rise limited to class B)


NO
N.A.
70.00
by resistance

Stator winding connection


Number of terminals braught out
Type of terminal box for
Stator leads
space heater
Temperature detectors
instrument switch etc.
For main terminal box
Location
Entry of cables
Recommended cable size
(to be matched with cable size
envisaged by owner)
Fault level (MVA)

Delta
6.00
cast iron non phase seggregated
cast iron on top of main t.b.
N.A.
N.A.

RHS FROM DE
Side
1 * 3C,300-MM

50KA rms for 0.25 seconds


NO
NO

Temperature detector for stator winding


Type
Nos. provided
Location
make
resistance value at 0 deg. C (ohms)
space heaters
Number
Location
Power requirement (watt)
Paint shade

NO
NO
NO
Yes
SPACE HEATER 60WX2 (CE280/315)
Winding overhang
SPACE HEATER 60WX2 (CE280/315)
631 as per IS:5

weight of
Motor stator
Motor rotor
Total weight (kg)

696.00
464.00
1160.00

BOOSTER FAN
1. GENERAL
i) Manufacturer
ii) Equipment driven by Motor
iii) Motor Type
iv) Quantity
2. DESIGN & PERFORMANCE DATA
i) Frame Size
ii) Type of duty
iii) Type of Enclosure & Method of cooling
iv) Applicable Standard to which motor
generally conforms
v) Type of Mounting
vi) Direction of Rotation as viewed from DE END
vii) Standard continuous rating at 40 deg.C.
ambient temperature (KW)
viii) De-rated rating for specified normal
condition
i.e. 50 deg.C ambient temperature (KW)
ix) Rated Voltage (volts)
x) Permissible variation of
a) Voltage (Volts)
b) Frequency (Hz)
c) Combined Voltage & Frequency
xi) Minimum permissible starting voltage (Volts)
xii) Rated speed at rated Voltage & Frequency
xiii) At rated Voltage & Frequency
a) Full Load Current
b) No Load Current
xiv) Power factor at
a) 100% Load
b) No Load
c) Starting
xv) Efficieny at rated Voltage & Frequency
a) 100% Load
b) 75% Load
c) 50% Load
xv) Starting Current (Amps) at
a) 100% Voltage
b) 85% Voltage
c) 80% Voltage
d) Min. permissible Voltage

xvii) Starting time with minimum permissible


voltage ( 85%)
a) Without driven equipment coupled
b) With driven equipment coupled

BHEL-BHOPAL , INDIA
BOOSTER FAN
SCIM
2

1LA7803-6
S1
TETV & IC-511
IS:325
HORIZONTAL (B3)
UNIDIRECTIONAL (ANTI CLOCKWISE)
1230 KW

1150 KW
11000 V
+/- 6%
+ 3% , - 5%
+ 10% ABSOLUTE
8800 V
994
75 AMP
25 AMP
0.84
0.05
0.13
95.5
95.2
94.3
450 AMP
380 AMP
360 AMP
85 % OF RATED VOLTAGE *
*Min Starting voltage requirement as 85% of
rated voltage vide Clause
6.03.00 sub section IIIB-10 , motor section ,
Technical specification

2 SECONDS
17 SECONDS

xviii) safe stall time with 100% and 110% of


rated
voltage
a) From hot condition
b) From cold condition
xix) Torques:
a) Starting torque at min. permissible
voltage(kg-mtr)
b) Pull up torque at rated voltage(kg-mtr)
c) Pull out torque(kg-mtr)
d) Min accelerating torque(kg.m)
available
e) Rated torque (kg.m.)
xx) Stator winding resistance per phase (ohms
at 20 deg.C.)
xxi) GD2 value of motor
xxii) No. of permissible successive starts when
motor is in
hot condition
xxiii) a) Locked rotor KVA input
b) Locked rotor KVA/KW
xxiv) Bearings
a) Type
b) Manufacturer
c) Self Lubricated or Forced Lubricated
d) Recommended Lubricants
e) Guranteed Life in Hours
f) Whether Dial Type thermometer
provided
g) Oil pressure Gauge/switch
i) range
ii) Contact Nos. & ratings
iii) Accuracy
xxv) Vibration
a) Velocity (mm/s)
b) Displacement (microns)
xxvi) Noise Level (dB)
3. CONSTRUCTIONAL FEATURES
i) Stator winding insulation (AC)/Armature
winding insulation
in case of AC
a) Class & Type
b) Tropicalised (Yes/No)
c) Temperature rise over specified max.
i) Cold water temperature of 38
deg.C
ii) Ambient air 50 deg.C
d) Method of temperature measurement
e) Stator winding connection
f) Number of terminals brought out
ii) Type of terminal box for
a) Stator leads
b) Space heater

25 SEC (FOR 100%) , 20 SEC ( F0R 110%)


35 SEC (FOR 100%) , 28 SEC ( F0R 110%)

530
840
2800
MIN 10% OF RATED TORQUE ( 113 kg-mtr)
1127
0.513
376 KG M2
2
6430
5.6
ANTIFRICTION TYPE
REPUTED SUPPLIERS (SKF / NSK / FAG )
SELF LUBRICATED
GREASE IOC-SERVOGEM-3/ EQUIVALENT
40,000 HOURS
PROVIDED 2 NOS ( EACH AT DE AND NDE SIDE)
NA

AS PER IS:12075
AS PER IS:12075
AS PER IS:12065

CLASS F & VPI


YES

NA
70
BY RESISTANCE METHOD
STAR
6
ELASTIMOLD TYPE
FABRICATED TYPE

c) Temperature detectors
d) Instrument switch etc.
iii) For main terminal box
a) Location
b) Entry of cables
c) Recommended cable size(To be
matched with
cable size envisaged by owner)
d) Fault level
iv) For bearing
a) Type
b) Manufacturer
c) Recommended lubricant
d) Oil quantity
e) Max. cold oil temp. to bearing
f) Guranteed life in Hrs.
g) Lubrication type
h) Whether dial type thermometer
provided
i) Oil pressure gauge/switch
v) Type of cooler (CACA/CACW) / Number
vi) Cooling water requirements
a) Quantity required
b) Maximum permissible inlet water
temp. in deg.C
c) Pressure of water at inlet to coolers
d) Outlet temperature of water at full
load
e) Cold air temp. at outlet
vii) Paint shade
viii) Max. permissible temperature of rotor
(deg.C)
ix) Temp. rise of rotor during 1st start (deg.C)
x) Temp. rise of rotor during 2nd start (deg.C)
xi) Surge withstand voltage (stator winding)
a) 0.3/3 micro sec surge (KVp)
b) 1.2/3 micro sec surge (KVp)
xii) Weight of
a) Motor stator (Kg)
b) Motor rotor (Kg)
c) Total weight (Kg)
4. LIST OF ACCESSORIES
a) RTDs for winding
(Type/Nos/Leads/Location/make
/Res at 0 deg.C)
b) RTDs for bearing
(Type/Nos/Leads/Location/make
/Res at 0 deg.C)
c) RTDs for Hot Air (Type/No/Leads)
d) RTDs for Cold Air (Type/No/Leads)
e) Space Heaters
i) Nos.

FABRICATED TYPE
NA
RHS AS VIEWED FROM DE
BOTTOM
CABLE SIZES SHALL BE FURNISHED BY
CUSTOMER
SHORT TIME CURRENT RATING OF 25KA FOR
0.17 SEC AS PER IEEE:386.

ANTIFRICTION TYPE
REPUTED SUPPLIERS
GREASE IOC-SERVOGEM-3/ EQUIVALENT
NA
NA
40,000 HOURS
GREASE
PROVIDED 2 NOS ( EACH AT DE AND NDE SIDE)
NA
NA
NA
NA
NA
NA
NA
631 OF IS:5
350
181
242
AS PER IS:60034-15
AS PER IS:60034-15
6950 (APPROX)
2200 (APPROX)
9150 (APPROX)

Pt-100/ 12 NOS / 3 WIRE / SIMPLEX

Pt-100/ 2 NOS / 3 WIRE / DUPLEX


NA
NA
4 NOS

ii) Power (Watts)


iii) Supply Voltage
f) Stator Terminal Box
i) Type
ii) Fault Level
iii) Fault Level duration (secs)
g) Neutral TB
i) Type
h) Current Transformer
i) Nos.
ii) Ratio
iii) Accuracy Class
iv) Knee Point Voltage - Vk (Volts)
v) Exciting Current
vi) Max. Secondary Resistance
j) Dial Type Thermometer (Type/Make/Accuracy
/Connection type & size)
i) For Bearings (Nos.)
ii) For Air Temp. (Nos.)
a) Hot Air
b) Cold Air
iii) Contact rating
iv) Range
v) Supply Voltage
k) Rotor Terminal Box
l) TBs for RTDs, BTDs & Space Heater (Yes/No)
m) Sole Plate (Yes/No)
n) Fondation & Anchoring bolts (Yes/No)
o) Base Frame (Yes/No)
p) Speed Switch (Yes/No)
i) No. of contacts & contact ratings of
speed switch
q) Insulation of bearing (Yes/No)
r) Forced oil lubrication (Yes/No)
s) Oil Level Indicator (Yes/No)
t) Noise Reducer (Yes/No)
u) Flow switch for CACW motor (Quantity)
i) No. of contacts & contact ratings
v) Water Leakage Detector
i) No. of contacts & contact ratings
w) Grounding pads
i) No. & size on motor body
ii) Nos. on terminal box
x) Vibration pads
i) No. & size
ii) Location
y) Any other fitments

1000 W
240V , 50 HZ , 1 PHASE
ELASTIMOLD TYPE
SHORT TIME CURRENT RATING OF 25KA FOR
0.17 SEC AS PER IEEE:386.
0.17 SEC
PSTB TYPE
NA
NA
NA
NA
NA
NA

2
NA
NA
0.5 / 5 A AT 220 / 240V DC / AC
0 - 120 DEG C
240V , 50 HZ , 1 PHASE
NA
YES
NO
AS PER OGA DRG:34020044329
NO
NO
NA
YES
NO
NO
NO
NA
NA
2
2
2 , SIZE 80X80X80 MM3
EACH AT DE AND NDE ENDSHIELD
NA

RC PUMP MOTOR
1. GENERAL
i) Manufacturer
ii) Equipment driven by Motor
iii) Motor Type
iv) Quantity
2. DESIGN & PERFORMANCE DATA
i) Frame Size
ii) Type of duty
iii) Type of Enclosure & Method of
cooling
iv) Applicable Standard to which motor
generally conforms
v) Type of Mounting
vi) Direction of Rotation as viewed from
DE END
vii) Standard continuous rating at 40
deg.C.
ambient temperature (KW)
viii) De-rated rating for specified
normal condition
i.e. 50 deg.C ambient temperature
(KW)
ix) Rated Voltage (volts)
x) Permissible variation of
a) Voltage (Volts)
b) Frequency (Hz)
c) Combined Voltage & Frequency
xi) Minimum permissible starting
voltage (Volts)
xii) Rated speed (RPM)at rated Voltage
& Frequency
xiii) At rated Voltage & Frequency
a) Full Load Current
b) No Load Current (INDICATIVE)
xiv) Power factor at
a) 100% Load
b) No Load(Indicative)
c) Starting(Indicative)
xv) Efficieny at rated Voltage &
Frequency
a) 100% Load
b) 75% Load
c) 50% Load
xv) Starting Current (Amps) at
a) 100% Voltage
b) 85% Voltage
c) 80% Voltage
d) Min. permissible Voltage
xvii) Starting time with minimum

Crompton Greaves Ltd. / India


RC PUMP
SQUIRREL CAGE ROTOR INDUCTION
MOTOR
8
TPC450
S1 (CONTINUOUS)
CACA / IC6 A1A1
IS:325 & OTHER
B3
BI-DOR CLOCKWISE

321
300
11000
10%
5%
10%
80%
989
21
10
0.79
0.062
0.113
93
92
90
126
107
101
80% of RV

permissible voltage
a) Without driven equipment coupled
b) With driven equipment coupled(SEC)
xviii) safe stall time with 100% and
110% of rated
voltage
a) From hot condition
b) From cold condition
xix) Torques:
a) Starting torque at min. permissible
voltage(80%)(kg-mtr)
b) Pull up torque at rated voltage
c) Pull out torque at rated voltage
d) Min accelerating torque(kg.m)
available
e) Rated torque (kg.m.)
xx) Stator winding resistance per phase
(ohms at 20 deg.C.)
xxi) GD2 value of motor
xxii) No. of permissible successive
starts when motor is in
hot condition
xxiii)
a) Locked rotor MVA input
b) Locked rotor KVA/KW
xxiv) Bearings
a) Type
b) Manufacturer
c) Self Lubricated or Forced Lubricated
d) Recommended Lubricants
e) Guranteed Life in Hours
f) Whether Dial Type thermometer
provided
g) Oil pressure Gauge/switch
i) range
ii) Contact Nos. & ratings
iii) Accuracy
xxv) Vibration
a) Velocity (mm/s)
b) Displacement (microns)
xxvi) Noise Level (dB)
3. CONSTRUCTIONAL FEATURES
i) Stator winding insulation
(AC)/Armature winding insulation
in case of AC
a) Class & Type
b) Tropicalised (Yes/No)
c) Temperature rise over specified max.
i) Cold water temperature of 38 deg.C
ii) Ambient air 50 deg.C
d) Method of temperature
measurement

< than 3 Seconds


3

20 / 17 Seconds
30 / 25 Seconds
212
266
693
122
295
2.68
105
2
2.4
8
Ball and Roller Bearings
SKF
Self Lubricated
Servogem - 2 or equivalent
Min. 40000 working hours
Yes
NA
NA
NA
2.8
75
As per IS 12065

F / VPI Resin Poor


Yes
NA
70
By Res. Method

e) Stator winding connection


f) Number of terminals brought out
ii) Type of terminal box for
a) Stator leads
b) Space heater
c) Temperature detectors
d) Instrument switch etc.
iii) For main terminal box
a) Location
b) Entry of cables
c) Recommended cable size(To be
matched with
cable size envisaged by owner)
d) Fault level (MVA)
iv) For bearing
a) Type
b) Manufacturer
c) Recommended lubricant
d) Oil quantity
e) Max. cold oil temp. to bearing
f) Guranteed life in Hrs.
g) Lubrication type
h) Whether dial type thermometer
provided
i) Oil pressure gauge/switch
v) Type of cooler (CACA/CACW) /
Number
vi) Cooling water requirements
a) Quantity required
b) Maximum permissible inlet water
temp. in deg.C
c) Pressure of water at inlet to coolers
d) Outlet temperature of water at full
load
e) Cold air temp. at outlet

STAR
Three + Three

vii) Paint shade


viii) Max. permissible temperature of
rotor (deg.C)
ix) Temp. rise of rotor during 1st start
(deg.C)
x) Temp. rise of rotor during 2nd start
(deg.C)
xi) Surge withstand voltage (stator
winding)
a) 0.3/3 micro sec surge (KVp)
b) 1.2/3 micro sec surge (KVp)
xii) Weight of
a) Motor stator (Kg)
b) Motor rotor (Kg)
c) Total weight (Kg)
4. LIST OF ACCESSORIES

631 of IS 5
450

PSTB
FABRICATED
FABRICATED
NA
RHS FORM DE
FROM BOTTOM
1R X3C X150 SQ.MM
750MVA
Ball and Roller Bearings
SKF
Servogem - 2 or equivalent
NA
NA
Min. 40000 working hours
Self Lubricated
Yes
NA
CACA
NA
NA
NA
NA
NA

137
155

32
49
2850
1550
4400

a) RTDs for winding


(Type/Nos/Leads/Location/make
/Res at 0 deg.C)
b) BTDs for bearing
(Type/Nos/Leads/Location/make
/Res at 0 deg.C)
c) RTDs for Hot Air (Type/No/Leads)
d) RTDs for Cold Air (Type/No/Leads)
e) Space Heaters
i) Nos.
ii) Power (Watts)
iii) Supply Voltage
f) Stator Terminal Box
i) Type
ii) Fault Level (MVA)
iii) Fault Level duration (secs)
g) Neutral TB
i) Type
h) Current Transformer
i) Nos.
ii) Ratio
iii) Accuracy Class
iv) Knee Point Voltage - Vk (Volts)
v) Exciting Current
vi) Max. Secondary Resistance
j) Dial Type Thermometer
(Type/Make/Accuracy
/Connection type & size)
i) For Bearings (Nos.)
ii) For Air Temp. (Nos.)
a) Hot Air
b) Cold Air
iii) Contact rating
iv) Range
v) Supply Voltage
k) Rotor Terminal Box
l) TBs for RTDs, BTDs & Space Heater
(Yes/No)
m) Sole Plate (Yes/No)
n) Fondation & Anchoring bolts (Yes/No)
o) Base Frame (Yes/No)

PT-100 / 06/ Between Coil Side/oorja

p) Speed Switch (Yes/No)


i) No. of contacts & contact ratings of
speed switch
q) Insulation of bearing (Yes/No)

NA
NA

r) Forced oil lubrication (Yes/No)


s) Oil Level Indicator (Yes/No)
t) Noise Reducer (Yes/No)
u) Flow switch for CACW motor

PT-100 / 02 / oorja ,techno


NA
NA
1
250
240
PSTB
750
0.25
PSTB FOR STAR
NA
NA
NA
NA
NA
NA
NA
MERCURY IN STEEL/+/-1.1FSD/REF
DWG 417328
2
1
1
5 AMPS / 240 V
0 0C TO 120 0C
NA
NA
Yes
NA
No.
No.

NO,NDE SIED ENDSHIEL TO BE


INSULATED
No.
No.
No.
NA

(Quantity)
i) No. of contacts & contact ratings
v) Water Leakage Detector
i) No. of contacts & contact ratings
w) Grounding pads
i) No. & size on motor body
ii) Nos. on terminal box
x) Vibration pads
i) No. & size
ii) Location
y) Any other fitments

NA
NA
2
2
2+2
AT DE & NDE SIDE
No.

Wet Ball Mill


Description
Diameter of the Shell
Active Length of Shell
Active Cubage of Shell
The Number of Rotation
Motor Style
Motor Power
Motor Voltage
Motor Rev
Speed Reducer Style
Speed Reducer Center to center Spacing
Speed Reducer reduction Ratio
Max Weight of Looding Balls
Granularity for the feed
Granularity for the Discharge
Output
Total Weight(Exluding Motor)
MOTOR
1. GENERAL
i) Manufacturer
ii) Equipment driven by Motor
iii) Motor Type
iv) Quantity
2. DESIGN & PERFORMANCE DATA
i) Frame Size
ii) Type of duty
iii) Type of Enclosure & Method of cooling
iv) Applicable Standard to which motor generally
conforms
v) Type of Mounting
vi) Direction of Rotation as viewed from DE END
vii) Standard continuous rating at 40 deg.C. ambient
temperature (KW)

2060mm
5400mm
18m3
21.8 r/min
YTM500-8
280 Kw
11000V
750 r/min
ZDR60
600 mm
4.5
23T
20 mm
44m
6.3 T/H
48 T

Changsha Motor Company


ball mill
YTM500-8
2
273015401720(mm)
s1
IP54 , IC611
yes
IMB3
direction of rotation as per wet
ball mill
280KW

viii) De-rated rating for specified normal condition i.e.


50 deg.C ambient temperature (KW)

280KW

ix) Rated Voltage (volts)


x) Permissible variation of
a) Voltage (Volts)
b) Frequency (Hz)
c) Combined Voltage & Frequency
xi) Minimum permissible starting voltage (Volts)
xii) Rated speed at rated Voltage & Frequency
xiii) At rated Voltage & Frequency
a) Full Load Current
b) No Load Current
xiv) Power factor at
a) 100% Load 100%
b) No Load
c) Starting
xv) Efficieny at rated Voltage & Frequency

11KV
5
+3-5
5
85%
744r/mm
21.5A
11.2A
0.74
0.69
0.58

a) 100% Load100%
b) 75% Load 75%
c) 50% Load 50%
xv) Starting Current (Amps) at
a) 100% Voltage
b) 85% Voltage
c) 80% Voltage
d) Min. permissible Voltage
xvii) Starting time with minimum permissible voltage
a) Without driven equipment coupled
b) With driven equipment coupled
xviii) safe stall time with 100% and 110% of rated
voltage
a) From hot condition
b) From cold condition
xix) Torques
a) Starting torque at min. permissible voltage(kgmtr)
b) Pull up torque at rated voltage
c) Pull out torque
d) Min accelerating torque(kg.m) available
e) Rated torque (kg.m.)
xx) Stator winding resistance per phase (ohms at 20
deg.C.
xxi) GD2 value of motor
xxii) No. of permissible successive starts when motor is
in hot condition
xxiii) a) Locked rotor KVA input
b) Locked rotor KVA/KW
xxiv) Bearings
a) Type
b) Manufacturer
c) Self Lubricated or Forced Lubricated
d) Recommended Lubricants
e) Guranteed Life in Hours
f) Whether Dial Type thermometer provided

g) Oil pressure Gauge/switch


i) range
ii) Contact Nos. & ratings
iii) Accuracy
xxv) Vibration
a) Velocity (mm/s)
b) Displacement (microns)
xxvi) Noise Level (dB)
3. CONSTRUCTIONAL FEATURES
i) Stator winding insulation (AC)/Armature winding
insulation in case of AC
a) Class & Type

92.82%
81.9A
77.0A
96.3A
85%
15s~25s
45s

15s/12s
71s/59s
458kg.m
Pull up torque dose not exist for
asynchronous motor
2.73
Yes
369kg.m

117.2kg.m2
2 NO.s
Nu228 , 6328
specified by customer
lubricated by itself
ZL-3 lithium lubricating grease
30000
Yes. Indicate: The temperature
for alarm is 85 The
temperature for shutdown is
90.
NO
2.8mm/s
by national standard

F Level

b) Tropicalised (Yes/No)
c) Temperature rise over specified max.
i) Cold water temperature of 38 deg.C
ii) Ambient air 50 deg.C
d) Method of temperature measurement
e) Stator winding connection
f) Number of terminals brought out
ii) Type of terminal box for
a) Stator leads
b) Space heater
c) Temperature detectors
d) Instrument switch etc.
iii) For main terminal box
a) Location
b) Entry of cables

c) Recommended cable size(To be matched with


cable size envisaged by owner)
d) Fault level (MVA)

iv) For bearing


a) Type
b) Manufacturer
c) Recommended lubricant
d) Oil quantity
e) Max. cold oil temp. to bearing
f) Guranteed life in Hrs
g) Lubrication type
h) Whether dial type thermometer provided
i) Oil pressure gauge/switch
v) Type of cooler (CACA/CACW) / Number
vi) Cooling water requirements
a) Quantity required
b) Maximum permissible inlet water temp. in deg.C
c) Pressure of water at inlet to coolers
d) Outlet temperature of water at full load
e) Cold air temp. at outlet
vii) Paint shade
viii) Max. permissible temperature of rotor (deg.C)
ix) Temp. rise of rotor during 1st start (deg.C)
x) Temp. rise of rotor during 2nd start (deg.C)
xi) Surge withstand voltage (stator winding)
a) 0.3/3 micro sec surge (KVp)

Yes
70 deg C(max.)
Resistance Value
Y
3
Terminal Box shall be Phase
separated or Phase segregated
Terminal Box.
glass reinforced plastics
steel plate; indicate: 230VAC
steel plate
No
Specified by customer
the underside of junction
box;Terminal Box shall be
suitable for 3C x 150 Sq mm
Armoured cable.
JEH-10000V cableJB6213.2
40kA,0.25sec750MVA,0.25sec
; Phase to phase & Phase to
Earth clearance shall be such
that the terminal box shall
withstand Lightning Impulse
test(1.2/50) at 49 KV.
shaft-extension endNU228;
non shaft-extension end6328
specified by customer
No
30000Hours
lubricated by itself
Yes
NO
CACA/1 piece
No
Light grey, Shade 631 as per IS5
rised temperature 80K
80K
80K

b) 1.2/3 micro sec surge (KVp)


xii) Weight of
a) Motor stator (Kg)
b) Motor rotor (Kg)
c) Total weight (Kg)
4. LIST OF ACCESSORIES
a) RTDs for winding
(Type/Nos/Leads/Location/make)
b) RTDs for bearing
(Type/Nos/Leads/Location/make)
c) RTDs for Hot Air (Type/No/Leads)
d) RTDs for Cold Air (Type/No/Leads)
e) Space Heaters
i) Nos.
ii) Power (Watts)
iii) Supply Voltage
f) Stator Terminal Box
i) Type
ii) Fault Level (MVA)
iii) Fault Level duration (secs)
g) Neutral TB
i) Type
h) Current Transformer
i) Nos.
ii) Ratio
iii) Accuracy Class
iv) Knee Point Voltage - Vk (Volts)
v) Exciting Current
vi) Max. Secondary Resistance
j) Dial Type Thermometer (Type/Make/Accuracy
/Connection type & size)
i) For Bearings (Nos.)
ii) For Air Temp. (Nos.)
a) Hot Air
b) Cold Air
iii) Contact rating
iv) Range
v) Supply Voltage
k) Rotor Terminal Box
l) TBs for RTDs, BTDs & Space Heater (Yes/No)
m) Sole Plate (Yes/No)
n) Fondation & Anchoring bolts (Yes/No)
o) Base Frame (Yes/No)
p) Speed Switch (Yes/No)
i) No. of contacts & contact ratings of speed switch
q) Insulation of bearing (Yes/No)
r) Forced oil lubrication (Yes/No)

2820kg
1190kg
4950kg
Pt100/6 nos Duplex type RTD
/connect
directly/Inner
eduction/as per requirements of
customer/100
Pt100/2
nos
Duplex
type
RTD
/connect directly/inner
eduction/as per requirements of
customer/100
NO
NO
1
750W
240V AC
No
The motor less than 2000KW
has not neutral TB.
No
Ok
2 nos
2 nos
1
1
0 ~ 90
220V
NO
Yes
NO
NO
NO
NO
NO
NO

s) Oil Level Indicator (Yes/No)


t) Noise Reducer (Yes/No)
u) Flow switch for CACW motor (Quantity)
i) No. of contacts & contact ratings
v) Water Leakage Detector
i) No. of contacts & contact ratings
w) Grounding pads
i) No. & size on motor body
ii) Nos. on terminal box
x) Vibration pads
i) No. & size
ii) Location
y) Any other fitments

NO
NO
NO
NO
1 piece
1 piece
2 NO.s
nO

Agitator for Lime Stone Slurry Tank


Description
Quantity

Tank Baffles

Impeller speed(Rev/Min)

45

Lower Impeller

3(A510/E22)

Critical Speeds(rev/min)

90

Motor Details
Type
Make

TEFC/IP55/Vertical Flange
Mounted/STD
CGL

Speed(Rev/Min)

1440

Motor kw

2.2

Frame

100 L

Rating(v/ph/Hz)

415/3/50

Gear box

Helical:M0720/32.12/P100L/V1/P
BL MAKE
Pin & Bush Type RB 178

Flexible Coupling
Shaft Sealing:Stuffing box,gland
packing(spitman/12mm square)
Downward Load

Asbestos free graphited teflon

Torque

1.90kNm

Bending moment

5.74KNm

Force on each baffle

207 N

Gear box weight

47 KG

Motor Weight

32 KG

Shaft/Impellers/Coupling/Lantern

442 KG

Total

521 KG

10.222 Kn

Agitator for Recovered water Tank


Description
Quantity
Tank Baffles
Impeller speed(Rev/Min)
Upper/Lower Impeller
Critical Speeds(rev/min)
Motor Details
Type
Make
Speed(Rev/Min)
Motor kw
Frame
Rating(v/ph/Hz)
Gear box
Flexible Coupling
Shaft Sealing:Stuffing box,gland
packing(spitman/12mm square)
Downward Load
Torque
Bending moment
Force on each baffle
Gear box weight
Motor Weight
Shaft/Impellers/Coupling/Lantern
Total

2
4
56
3(A510/E22)
149
TEFC/IP55/Vertical Flange Mounted/STD
CGL
1415
1.1
90 S
415/3/50
Helical:M0620/25.25/P90S/V1/PBL MAKE
Pin & Bush Type RB 178
Asbestos free graphited teflon
7.063 Kn
0.752kNm
3.35KNm
107 N
33 KG
22 KG
305 KG
360 KG

Agitator for Emergency Slurry Tank


Description
Quantity
Tank Baffles
Impeller speed(Rev/Min)
Upper/Lower Impeller
Critical Speeds(rev/min)
Motor Details
Type
Make
Speed(Rev/Min)
Motor kw
Frame
Rating(v/ph/Hz)
Gear box
Flexible Coupling
Shaft Sealing:Stuffing box,gland
packing(spitman/12mm square)
Downward Load
Torque
Bending moment
Force on each baffle
Gear box weight
Motor Weight
Shaft/Impellers/Coupling/Lantern
Total

2
NA
45
3(A510/E22)
64
TEFC/IP55/Vertical Flange Mounted/STD
CGL
1440
3.7
112 M
415/3/50
Helical:M0820/32.35/P112M/V1/PBL
MAKE
Pin & Bush Type RB 178
Asbestos free graphited teflon
26.754 Kn
3.164kNm
11.50KNm
NA
73 KG
42 KG
1250 KG
1365 KG

Agitator for Ball mill tank


Description
Quantity
Tank Baffles
Impeller speed(Rev/Min)
Lower Impeller
Critical Speeds(rev/min)
Motor Details
Type
Make
Speed(Rev/Min)
Motor kw
Frame
Rating(v/ph/Hz)
Gear box
Flexible Coupling
Shaft Sealing:Stuffing box,gland
packing(spitman/12mm square)
Downward Load
Torque
Bending moment
Force on each baffle
Gear box weight
Motor Weight
Shaft/Impellers/Coupling/Lantern
Total

1
4
82
3(A510/E22)
197
TEFC/IP55/Vertical Flange Mounted/STD
CGL
1410
0.55
80
415/3/50
Helical:M0420/17.25/P80/V1/PBL MAKE
Pin & Bush Type RB 178
Asbestos free graphited teflon
10.407Kn
0.256kNm
0.614KNm
51 N
14 KG
17 KG
500 KG
531 KG

Agitator for Absorber


Description
Quantity
Tank Baffles
Impeller speed(Rev/Min)
Lower Impeller
Critical Speeds(rev/min)
Motor Details
Type
Make
Speed(Rev/Min)
Motor kw
Frame
Rating(v/ph/Hz)
Gear box
Flexible Coupling
Shaft Sealing:Stuffing boX (Split type),gland
packing(spitman/12mm square)
Downward Load
Torque
Bending moment
Force on each baffle
Gear box weight
Motor Weight
Shaft/Impellers/Coupling/Lantern
Total

8
4
37
3(A510/E32)
62
TEFC/IP55/Foot cum Flange
Mounted/STD
CGL
1470
22
180 L
415/3/50
Bevel Helical:A903UR/38.8:1/B5B7/P180
Pin & Bush Type RB 178
Asbestos free graphited teflon
27.468Kn
5.677kNm
13.779KNm
812N
442KG
210 KG
2200 KG
2800 KG

Gypsum Belt Conveyor


Conveyor
Equipement No
Type
Qty
Belt Width
Belt Speed

GBC-01
Belt Conveyor
1 No
650 mm
0.65 m/sec

Material
Material to be Handled
Bulk Density(t/m3)
Temp

Gypsum
2.2
Ambient

Belting
Belt Width
Type
Rating
Grade
Cover
Cover Thickness
No Of Plies
Make

650 mm
Nylon
315/3
M 24
Rubber
5 mmTop & 2mm Bottom
3
MRF/DUNLOP/GOOD
YEAR/INDUS/DYNAMIC

Drive Unit
Motor
Type
Rating/Rpm/Frame Size
Make
Gear box
Type
Size/Ratio
Make
Input Couping
Type
Size
Make
Output Couping
Type
Size
Make
Safety Switches
Zero Speed Switch
Pull Coard Switch

TEFC Sq Cage induction motor 415 V


50Hz IP55,Class Insulation
7.5 Kw/1500 Rpm
Siemens/Bharath
Bijlee/Kirlosker/Hindustan
Worm& warm wheel,Reduction
6 inch/40:1
Greaves/Shanthi/Elecon/Naw
Pin& Bush/Tyre type
Suitable
Fenner/Lovejoy/Elecon/Naw/Concord
Pin& Bush/Tyre type
Suitable
Fenner/Lovejoy/Elecon/Naw/Concord
2NO+2NC Contact with ip-65
protection suitable for 24 DC
2NO+2NC Contact with ip-65
protection

Pulley
Qty
Pulley Dia W/O Lagging
Face Width
Shaft Dia BRG
Bearing CRS
Lagging Thickness
Type of Rubber Lagging
Bearing No

1
323
750
65
1050
12
Diamond Pattern
22215CK

Bearing Type
Bearing Make
Plummer Block No
Plummer Block Make

Spherical Roller
SKF/FAG/NTN/ABL/TATA/ZKL/EQVT
SN 515
MASTA/SIBCO/HARI/EQVT

Idler
Qty
Type
Troughing Angle
(Deg)
No Of Roll ( Nos)
Roller Dia (mm)
Lagging Thk (mm)
Lagging Material
Shaft Dia at BRG
(mm)
Pitch
Bearing No
Bearing Make
Brg Type

Head Pulley

Impact

Tail Pulley

Snub Pulley

1
273
750
50
1050
10
Plain
1211K
Self Alighning Ball
BRG

2
219
750
40
1050
10
Plain
1209K
Self Alighning Ball
BRG

SN 511

SN 509

17
Troughed

12
Troughed

2
Troughed

8
Flat

SA Return
1
Flat

30
3
139.7

30
3
88.9
5

30
3
88.9
5

1
88.9
5

1
88.9
5

20
1200

20
15000

20
3000

20
3000

Natural Rubber-Shore Hardness 50-60Degreee


20
400
420204
SKF/FAG/ABL/ZKL/NBC
Seize Resistant Ball Bearing

Carrying

SA Carrying

Return

Continuous Discharge Belt Type Bucket Elevator


Conveyor
Equipement No
Type
Qty
Belt Speed
Capacity
Material
Material to be Handled
Bulk Density(t/m3)
Belting
Belt Width
Type
Rating
Grade
Cover
Cover Thickness
No Of Plies
Make

303 BE-01
Continous Discharge Belt Type Bucket
Elevator
1 No
0.5 m/sec

Crushed Lime Stone


2.5
300 mm
Nylon/Nylon
800/5
M 24
Rubber
1.5 mmThk Bucket Side ,4 mm Thk
Pulley Side
5
MRF/DUNLOP/EQVT/INDUS/DYNAMIC

Drive Unit
Motor
Type
Rating/Rpm/Frame Size
Make
Gear box
Type
Size/Ratio
Make
Input Couping
Type
Size
Make
Output Couping
Type
Size
Make
Bucket
Type
Size
Spacing
Capacity
Weight
No Of Buckets

TEFC Sq Cage induction motor 415 V


50Hz IP55,
9.3 Kw/1500 Rpm/160M
Siemens/Bharath
Bijlee/Kirlosker/Hindustan
Worm& warm wheel,Reduction
8 inch/60:1
Greaves/Shanthi/Elecon/Naw
Pin& Bush/Tyre type
Suitable
Fenner/Lovejoy/Elecon/Naw/Concord
Pin& Bush/Tyre type
Suitable
Fenner/Lovejoy/Elecon/Naw/Concord
B-2
250mm x150 mm x175 mm
200 mm
3.65 Liters
4.50 kgs
325 Nos

Pulley
Qty
Pulley Dia W/O Lagging
Face Width
Shaft Dia BRG
Bearing CRS
Lagging Thickness
Type of Rubber Lagging
Bearing No
Bearing Type
Bearing Make
Plummer Block No
Plummer Block Make

Head Pulley
Tail Pulley
1
1
500
400
400
400
100
80
850
850
10
Diamond Pattern
222225CK
Spherical Roller
SKF/FAG/NTN/ABL/TATA/ZKL/EQVT
SN 520
SN 516
MASTA/SIBCO/HARI/EQVT

Lime Stone Reversible Belt Conveyor


Conveyor
Equipement No

303 RBC-01

Type

Reversible Belt Conveyor

Qty

1 No

Belt Width

650 mm

Belt Speed

0.62 m/sec

Capacity

20 TPH

Material
Material to be Handled

Crushed Lime Stone

Bulk Density(t/m3)

1.5

Temp

70%

Belting
Belt Width

650 mm

Type

Nylon

Rating

315/3

Grade

M 24

Cover

Rubber

Cover Thickness

5 mmTop & 2mm Bottom

No Of Plies

Make

MRF/DUNLOP/GOOD
YEAR/INDUS/DYNAMIC

Drive Unit
Motor
Type
Rating/Rpm/Frame Size
Make

TEFC Sq Cage induction motor 415 V


50Hz IP55,Class f Insulation
5.5 Kw/1500 Rpm
Siemens/Bharath
Bijlee/Kirlosker/Hindustan

Gear box
Type

Worm& warm wheel,Reduction

Size/Ratio

6 inch/40:1

Make

Greaves/Shanthi/Elecon/Naw

Input Couping

Type

Pin& Bush/Tyre type

Size

Suitable

Make

Fenner/Lovejoy/Elecon/Naw/Concord

Output Couping
Type

Pin& Bush/Tyre type

Size

Suitable

Make

Fenner/Lovejoy/Elecon/Naw/Concord

Safety Switches
Zero Speed Switch
Pull Coard Switch

2NO+2NC Contact with ip-65 protection


suitable for 24 DC
2NO+2NC Contact with ip-65 protection

Pulley
Qty
Pulley Dia W/O Lagging
Face Width
Shaft Dia BRG
Bearing CRS
Lagging Thickness
Type of Rubber
Lagging
Bearing No
Bearing Type
Bearing Make
Plummer Block No
Plummer Block Make

Idler
Qty
Type
Troughing Angle
(Deg)
No Of Roll ( Nos)
Roller Dia (mm)
Lagging Thk (mm)
Lagging Material
Shaft Dia at BRG
(mm)
Pitch
Bearing No
Bearing Make
Brg Type

Head Pulley
1
323
750
65
1050
12

Tail Pulley
1
273
750
50
1050
10

Diamond Pattern
22215CK

Plain
1211K
Self Alighning Ball
Spherical Roller
BRG
SKF/FAG/NTN/ABL/TATA/ZKL/EQVT
SN 515
SN 511
MASTA/SIBCO/HARI/EQVT

Snub Pulley
2
219
750
40
1050
-

1209K
Self Alighning Ball
BRG
SN 509

Impact
8
Troughed

Carrying
7
Troughed

SA Carrying
2
Troughed

Return
6
Flat

35
3
139.7

35
3
88.9
5

35
3
88.9
5

1
88.9
5

20
1200

20
15000

20
3000

Natural Rubber-Shore Hardness 50-60Degreee


20
400

420204
SKF/FAG/ABL/ZKL/NBC
Seize Resistant Ball Bearing

CHARGER
Description
Type of Charger
Mains AC Input
Battery Details
AH Capacity
Each Cell Of
No Of Cells
Type of Battery
Float Voltage
Boost Voltage
DC output(Float mode)
Voltage
Current
DC output(Boost mode)
Voltage
Current
Ripple
Regulation
Voltage
Current
Ambient
Protection
AC Input Voltage Surges
Diode/SCR Against Voltage Surge
Control Circuit
Output short circuit
Tripping Charger
Annunciation

Indication
Metering

Float cum boost:cv-cc-220v/70A


415V+10%50Hz+5%,3Phase,4wire
AC supply
94AH
1.2V
169 Nos
NI-CD
1.4V to 1.42 V/CELL
1.6 to 1.7V/Cell
237 V
70 A
287 V
19 A
1%
1%
2%
50 Degree C
RC Surge suppressor
RC Surge suppressor
HRC fuse
SCR Contoller
AC Input Over Load
AC MAINS FALL
RECT FS BLOWN
SURGE SUPPRESSOR FS BLOWN
FILTER COND FS BLOWN
LOAD LIMIT OPERATED
CHARGER TRIP
BATTERY ON BOOST
CH DC U/V
CH DC O/V
DC FUSE BLOWN
AC input ON
AC input Voltmeter
DC output Voltmeter
DC Output Ammeter

Equipement Details
Construction
Overall dimension
Cable entry
Colour
Sheet Steel Thickness

Floor mounting Indoor type


L-1000 mm XD750mm x H-1900
mm
Bottom from back side
Light grey shade 631 of IS 5(Powder
Coated)
1.6/2mm CRCA

Hydraulically Operated duplex Tandem Multi Louver Damper


Inlet
Description
Damper actuation
Design Pressure
Operating Pressure
Design Temperature
Operating Temperature
Fail Safe
Orientation
Flow medium
Damper Duty
Damper Location

Hydarulic
400mm WC
30MM WC
155 Degree C
140 Degree c
Close
Horizontal
Flue Gas
100% isolation with SAF
FGD Inlet

Blower
Description
Type of Blower
Make
Model
Qty
Inlet pressure
Differential Pressure
Discharge Pressure
Capacity( flow Rate)
Blower RPM
Blower BHP
Motor Details
Type
RPM
HP/KW
Material of Construction(Blower)
Casing
Lobe
Shaft
Gear
Type
Material of Construction
Bearing
Make
Type
Drive Arrangement
Static Load
Bare shaft blower weight
Accessories Weight excluding Motor & acoustic
enclosure
Total Weight
Dynamic Load
inlet temperature
Discharge Temperature

Positive Displacement Twin lobe blower


KAY
1016 WC
04 Nos
Atmospheric
1KG/CM2
1KG/CM2+Atmospheric
2800 M3/HR
1003
143.63
Foot mounted 3 phase TEFC SCR
Induction Motor
1000
170/127
CIFG-260,IS:210
CIFG-260,IS:210
(EN-24) 817 M40,BS:970
Helical Taper Bore(Casr hardened &
Ground)
(EN-353) 815 M17,BS:970
SKF/Eqpi(Imported)
Spherical Roller Bearing at Pulley side
and Cylindrical Roller Bearing at gear
side
Pulley and V Belt Drive
730 KG
724 KG
1454 KG
1.5 Xstatic Load
40 degree C
140 degree C

DC Distribution Board
Description
Main DC input

200 VDC from Charger

Ambient Temp

50 Degree C

Annunciation

Annunciation of DCDB is displayed on Charger


panel
BUS A DC EARTH FAULT
BUS B DC EARTH FAULT

Metering

DC Voltmeter for bus section-A


Charge/Discharge Ammeter for Battery-A
DC Voltmeter for bus section-B
Charge/Discharge Ammeter for Battery-B

Equipement Details
Construction

Floor Mounting,Indoor Type

Overall Dimension

L-2100mm x D-520 mm X H-1900 mm

Cable Entry

Bottom Side

Colour

Light Grey Shade 631 OF IS5(Power coated)

Sheet Steel Thickness

1.6/2 mm

You might also like