Assume you have a motor rated 500 HP, .95 power factor & 90 % efficiency energized from a 4.16 Kv
source, using a microprocessor motor protection relay, provide the typical settings.
The full load current can be taken from the motor nameplate as well as the service factor. The motor
full load current can be calculated from the following: I = 500 (.746)/1.732 (4.16)(.85)(.9) =60 amps
Motor and Line Data Functions
Adjustment / Display Range Setting
1 2000A, adjustable between
50-100% of Max Amp Rating.
FLA must be programmed Upper limit of range automatically adjusts
for relay to function
downward as Service factor is increased.
Function Description
Motor Nameplate FLA
Motor Nameplate
1.00 - 1.30 SF
Increments
Setting
60
.05
Class 20
NEMA / UL Class 5 30
Class 10
Overload Reset
.01
4.16
.60 15kV
Line Frequency
50 or 60 Hz
Acceleration Time
60
1 - 20 seconds
1
1(%)
30
15
1 (Second)
1 (%)
200
1 - 20 seconds
Under Current %
1 (%)
35
1 - 60 seconds
15
5 (%)
600
1 - 10 seconds
10(%)
0..01 - .5 seconds
1
.01
1000 (%)
.05
1 (%)
1
50
5
1 (%)
20
1 20 seconds
10
1 (%)
1 20 seconds
1 (%)
20
1 180 seconds
20
10
1 (%)
20
1 20 seconds
10
1 20 seconds
1 20 seconds
1 20 seconds
Motor KW Trip
1%
1
20(%)
1
.01 1
.01
.10
10
1 20 seconds
2
0 - 1, [0=Normal, 1= Reversed]
1 minute
0 = Disabled, or 1 10 starts
1 minute
12
Note: NEMA Class trip curves are based on a common tripping point of 600% of motor Full Load
Amps (FLA). Curves vary by the amount of time before the unit trips. As an example, a Class 20 curve
will trip in 20 seconds at 600% of FLA. Another example, Class 10 will trip in 10 seconds at 600% of
FLA.
PT Value:1-200 (: 1) 1:1 = direct voltage input, 2-200: 1 = kV Voltage Input 1
CT Value: 5-2000 (:5)
Number of Turns through CT:
5
1 5 (in 1 increments)
40 (4160/104) V
60
1
Typical Settings
Typical Settings and Remarks
PU: 1.1*VNOM/60; TD: 0.3; reset TD: 5 alarm P.U.: 1.18*VNOM/60
4
Synchronism Check Max Slip: 6RPM; Max phase angle error: 10 Max VMAG error:
2.5% VNOM
32
Reverse Power (one stage) PU: turbine 1% of rated; 15 s . PU: Reciprocating engine:
10% of rated; 5 s
32-1
40
46
49
50/87
50/27 IE
51N
Stator Ground Over- current (Low, Med Z Gnd, PU: 10% INOM; curve: EI; TD: 4. Inst:
Phase CT Residual)
none. Higher PU required to coordinate
with load. No higher than 25% INOM.
50/51N Stator Ground Over- current (Low, Med Z Gnd, P.U.: 10% INOM; Curve EI**, TD4; Inst
Neutral CT or Flux Summation CT)
100% INOM. Higher PU if required to
coordinate with load. No higher than
25% INOM.
51GN, 51N
Stator Ground Over- current (High Z Gnd) PU: 10% IFAULT at HV Term.; Curve:
VI***; TD:4.
51VC
51VR
67IE
10-11-13
Ground Overvoltage
Directional O/C for Inadvertent Energization PU: 75-100% INOM GEN; Definite Time (0.10.25 sec.) ; Inst: 200% INOM GEN
81
Over/under frequency
87G
87N
Generator Ground
87UD 13
Unit Differential
10-11-13