Professional Documents
Culture Documents
Places where explosive atmospheres may occur will be classified into zones. The classification is
based on the nature, the frequency and the duration of such an atmosphere. The definition of zones
and divisions is shown in the following table.
G A S - E X - A R E A S
II 2
Legal marking
explosion protected
type of equipment,
level of protection
equipment group
I mining areas
equipment category
M1 very high level of protection
M2 high level of protection
11 very high level of protection
2 high level of protection
3 normal level of protection
II other areas
characteristics (exemplary)
IEC/EN 60079-...
Technical marking
equipment category
gas Ex area (ATEX)
is not likely to occur in normal operation but if so for a short period only
Ex e
Ex protection
Ex explosion protection
equipment group
I mining applications
d flameproof enclosure
e increased safety
explosion protected
Group
Category
Addition
ia
ib intrinsic safety
ic
ma
mb encapsulation
mc
II
II
II
Zone
EPL
Ga
Gb
Gc
temperature class
T1
T2
T3
T4
T5
T6
0
1
2
20
21
22
< 450C
< 300C
< 200C
< 135C
< 100C
< 85C
1
1
2
1
1
2
1
1
2
II 2
Zone
intended use
type of equipment,
level of protection
equipment group
I m
mining areas
equipment category
M1 very high
h leve
level of protection
M2 high
h lev
level of protection
11 very high level of protection
2 high level of protection
3 normal level of protection
dust
protection systems for installation in the hazardous area normally without category
equipment category
dust Ex area
(ATEX)
20
21
22
is not likely to occur in normal operation but if so for a short period only
IIC T6 Gb
type of protection
II other areas
Zone
Gas Dust
Definition
D U S T - E X - A R E A S
intended use
Division
Zone
Group
Category
Addition
20
II
21
II
22
II
Zone
EPL
20
Da
21
Db
22
Dc
IEC/EN 600079-...
II...D
Ex tb IIIC T80 Db
Ex protection
type of protection
Ex explosion protection
equipment group
temperature class
ta
protection by
tb
enclosures
tc
ia
ib intrinsic safety
ic
ma
encapsulation
mb
mc
p pressurized
enclosures
nA
nC type of protection n
nR (zone 2)
(nL)
o oil immersion
op pr optical
op sh radiation
op is
px
py pressurized enclosures
pz
q powder filling
Marking Code
Ex d
Ex e
Ex i
Ex m
Ex nA
Ex nC
Ex nR
Ex nL
Ex o
Ex op
Ex p
Ex q
Ex t
Protection Principle
Transmission of an
explosion to the
outside is excluded.
Prevention of sparks
and high temperatures.
Energy limitation of
sparks and temperatures.
Ex atmosphere is isolated
from the source of ignition.
Non-sparking device
Restricted breathing
enclosure
Energy-limited apparatus
(replaced by Ex ic)
Ex atmosphere is isolated
from the source of ignition.
Optical transmission is
limited or avoided or shut off.
Ex atmosphere is isolated
from the source of ignition.
Transmission of an explosion
to the outside is excluded.
Ex atmosphere is isolated
from ignition source
2
Gb
2
Gb
1, 2 or 3
Ga, Gb or Gc
Da, Db or Dc
1, 2 or 3
Ga, Gb or Gc
Da, Db or Dc
3
Gc
3
Gc
3
Gc
3
Gc
2
Gb
1, 2 or 3
Ga, Gb or Gc
2 or 3
Gb or Gc
Db or Dc
2
Gb
1,2 or 3
Da, Db or Dc
www.pepperl-fuchs.com
Subject to modifications Copyright Pepperl+Fuchs Printed in Germany Part No. 205620 10/12 01
Directive 94/9/EC
Zone