Professional Documents
Culture Documents
Description
Features
U.S. EPA
Model
Standby rating
60 Hz
50 Hz
kW (kVA)
kW (kVA)
DGDK
125 (156)
100 (125)
Prime rating
60 Hz
50 Hz
kW (kVA)
kW (kVA)
113 (141)
Continuous rating
60 Hz
50 Hz
kW (kVA)
kW (kVA)
90 (113)
2008|Cummins Power Generation Inc.|All rights reserved|Specifications subject to change without notice|Cummins Power Generation
and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry InPower and Our energy working for you. are
trademarks of Cummins Power Generation. Other company, product or service names may be trademarks or service marks of others.
S-1577a (5/08)
Data sheets
60 Hz
50 Hz
D-3429
D-3430
Engine specifications
Design
Bore
Stroke
Displacement
Cylinder block
Battery capacity
Battery charging alternator
Starting voltage
Fuel system
Fuel filter
Air cleaner type
Lube oil filter type(s)
Standard cooling system
Alternator specifications
Design
Stator
Rotor
Insulation system
Standard temperature rise
Exciter type
Phase rotation
Alternator cooling
AC waveform total harmonic distortion
Telephone influence factor (TIF)
Telephone harmonic factor (THF)
Available voltages
60 Hz
Reconnectable
Non-Reconnectable
3-phase
1-phase
3-phase
120/208
120/240
120/240
220/380
139/240
347/600
127/220
240/416
254/440
277/480
Note: Consult factory for other voltages.
50 Hz
Reconnectable
3-phase
120/208
120/240
139/240
254/440
240/416
127/220
277/480
Non-Reconnectable
1-phase
3-phase
120/240
220/380
347/600
Alternator
105 C (221 F) rise alternator
125 C (257 F) rise alternator
120/240 V, 100 W
anti-condensation heater
PMG excitation
Single phase
Exhaust system
Genset mounted muffler
Heavy duty exhaust elbow
Slip on exhaust connection
Cooling system
50 C (122 F) ambient
cooling
Generator set
AC entrance box
Batteries
Battery charger
Enclosure: aluminum, steel,
weather protective or sound
attenuated
Note: Some options may not be available on all models - consult factory for availability.
Control system
PowerCommand control is an integrated generator
set control system providing governing, voltage
regulation, engine protection and operator interface
functions.
Control includes integral AmpSentry protection
providing a full range of alternator protection functions
that are matched to the alternator provided.
Controls provided include battery monitoring and
testing features, and smart starting control system.
Engine data
DC voltage
Lube oil pressure
Coolant temperature
Lube oil temperature (optional)
Other data
Genset model data
Start attempts, starts, running hours
kW hours (total and since reset)
Fault history
Load profile (hours less than 30% and hours more than
90% load)
System data display (optional with network and other
PowerCommand gensets or transfer switches)
Governing
Integrated digital electronic isochronous governor
Temperature dynamic governing
Smart idle speed mode
Glow plug control (some models)
Voltage regulation
Integrated digital electronic voltage regulator
Three phase line-to-neutral sensing
PMG (optional)
Single and three phase fault regulation
Configurable torque matching
Control functions
Data logging on faults
Fault simulation (requires InPower)
Time delay start and cooldown
Cycle cranking
PCCNet interface
(4) Configurable customer inputs
(4) Configurable customer outputs
(8) Configurable network inputs and (16) outputs (with
optional network)
Options
Analog AC meter display
Thermostatically controlled space heater
Key-type mode switch
Ground fault module
Engine oil temperature
Auxiliary relays (3)
Echelon LONWORKS interface
Digital input and output module(s) (loose)
Remote annunciator (loose)
Ratings definitions
Emergency standby power (ESP):
Applicable for supplying power to varying electrical load
for the duration of power interruption of a reliable utility
source. Emergency Standby Power (ESP) is in
accordance with ISO 8528. Fuel Stop power in
accordance with ISO 3046, AS 2789, DIN 6271 and BS
5514.
Limited-time running power (LTP):
Applicable for supplying power to a constant electrical
load for limited hours. Limited Time Running Power (LTP)
is in accordance with ISO 8528.
Prime power (PRP):
Applicable for supplying power to varying electrical load
for unlimited hours. Prime Power (PRP) is in accordance
with ISO 8528. Ten percent overload capability is
available in accordance with ISO 3046, AS 2789, DIN
6271 and BS 5514.
Base load (continuous) power (COP):
Applicable for supplying power continuously to a
constant electrical load for unlimited hours. Continuous
Power (COP) in accordance with ISO 8528, ISO 3046, AS
2789, DIN 6271 and BS 5514.
Model
DGDK
Dim A
mm (in.)
2662 (104.8)
Dim B
mm (in.)
1016 (40.0)
Dim C
mm (in.)
1252 (49.3)
Set Weight*
dry kg (lbs)
Set Weight*
wet kg (lbs)
1179 (2600)
* Weights represent a set with standard features. See outline drawings for weights of other configurations.