H3 MCCBs :
Low voltage protection devices

H3 MCCBs
160 to 1600 A

Technical characteristics

References guide

MCCBs and free tripping switches x160

Accessories for MCCBs


and free tripping switches x160

10

MCCBs and free tripping switches x250

12

Accessories for MCCBs


and free tripping switches x250

13

MCCBs and free tripping switches h250

15

Accessories for MCCBs


and free tripping switches h250

16

MCCBs and free tripping switches h400-h630

18

Accessories for MCCBs


and free tripping switches h400-h630

19

MCCBs and free tripping switches


h800-h1000

21

Accessories for MCCBs


and free tripping switches h800-h1200

22

MCCBs and free tripping switches


h1250-h1600

24

Accessories for MCCBs


and free tripping switches h1250-h1600

25

H3 MCCBs and switch disconnectors


16 to 1600 A
Easy mounting and safety
The new H3 range of MCCBs provides safe and easy solutions for low voltage electrical
circuits protection. The state of the art circuit breakers offers both designers and installers wide
range of features and benefits.
Special attention has been given to ergonomics, especially with the integration of these
devices in the TP&N and panelboard.

Your benefits:

Technical data :

Ease of installation

Comply with IEC 60947-2

Quick, easy and safety mounting of accessories

6 frame sizes: x160, x250, h250, h630, h1000, h1600

Wide range of rated current ratings and breaking capacities

Breaking capacity: 18, 25, 40, 50, 65, 70 kA

Calibrated at 50 Deg centigrade

Thermal magnetic and electronic trip units

Switch disconnectors

1 pole to 4 poles
Current limiting type
Complete range of accessories
International certification and approvals

Expert
tips
1

Design by Hager

Electronic trip unit (LSI)

Breaking capacity

Easy mounting of
auxiliaries

In harmony with Hager


enclosures and modular
products.

Is permitting total selectivity and


generator protection.

18 to 70kA, Icu 415V AC, covers


all applications.

Easy opening of secondary


cover, clip-on type auxiliaries.

Visibility of auxiliaries
fitted

Integrated padlocking
facility

Complete range of
accessories

Flexible connection

Indicates type of auxiliary


mounted in breaker.

Nice solution for maintenance.

Rotary handles, padlocks,


motors, terminal covers.

Collar terminals, front and rear


connections, extended
connections, spreaders ...

MCCBs H3 : technical characteristics


Frame
Product
Reference
Number of poles
Electrical characteristics
Rated current
Current rated range
Rated service voltage, (AC)
Frequency
Rated insulation voltage
Rated impulse withstand voltage
Rated ultimate short-circuit breaking capacity, (Icu)
(AC) 50-60 Hz 220/230 V
(AC) 50-60 Hz 380/415 V
(AC) 50-60 Hz 480/500/525 V
(AC) 50-60 Hz 660/690 V
(DC) 250 V - 2 poles in series
Rated service short-circuit breaking capacity, (Ics)
(AC) 50-60 Hz 220/230 V
(AC) 50-60 Hz 380/415 V
(AC) 50-60 Hz 480/500/525 V
(AC) 50-60 Hz 660/690 V
(DC) 250 V - 2 poles in series
Rated short-circuit making capacity
Rated short-time withstand current for 1s
Category of utilisation (EN 60947-2)
Calibration temperature
Derating

x160
Switch
HCA
[No.] 3-4
In

MCCB
HDA
1-2-3-4

HHA
1-2-3-4

HNA
3-4

x250
Switch
HCB
3-4
250
250
220 - 440
50/60
800
8

MCCB
HHB

HNB

250
20 - 250
220 - 690
50/60
800
8

[A]
[A]
Ue
[V]
f
[Hz]
Ui
[V]
Uimp [kV]

160
125 -160
220 - 440
50/60
690
8

Icu
Icu
Icu
Icu
Icu

[kA]
[kA]
[kA]
[kA]
[kA]

35
25
10

85
40
10

35
25
9

85
40
9

35
25
10
25

Ics
Ics
Ics
Ics
Ics
Icm
Icw

[kA]
[kA]
[kA]
[kA]
[kA]
[kA]
[kA]

25
25
20
18
5
5
2,8
2
A
50C
100%
100%
95%
93%
90%
ok
10000
20000
-25 to +70C
-35 to +70C
39
IEC 60947-3 IEC 60947-2
ok
ok
ok
ok
0,63 to 1 x In
-

40
20

25
20

40
20

27
19
7,5
19
A
50C
100%
100%
94%
91%
88%
ok
10000
30000
-25 to +70C
-35 to +70C
65
IEC 60947-2
ok
ok
0,63 to 1 x In
6-8-10-13 x In

16-125 (1P), 16-160 (2,3,4P)

25
18
10

100 - 250

Releases: LSI (electronic)


Long delay
Short delay

5
5
9
3,6
A
50C
100%
100%
94%
91%
88%
ok
10000
20000
-5 to +70C
-35 to +70C
60
IEC 60947-3 IEC 60947-2
ok
ok
ok
ok
0,63 to 1 x In
6-8-10-13 x In (200A)
5-7-9-11 x In (250A)
-

Time delay
Accessories
Auxiliary switches
Alarm switches
Shunt release
Undervoltage release
Rotary handle mechanism
Motor operator
Padlockable handle
Interphase barriers
Din rail adapter
Terminations
Standard terminal type
Maximum terminal capacity
Terminal width
Terminal shields
Cage terminal
Extended connections
Rear connections
Dimensions
Height
Width

40C
50C
55C
60C
65C

Suitability for isolation


Electric endurance in number of cycles
Mechanical endurance in number of operations
Operating temperature
Storage temperature
Power loss (at In for 3P)
Reference standard
Releases: switch
Releases: TM (thermomagnetic)
T fixed, M fixed
T adjustable, M fixed
T adjustable, M adjustable
Thermal adjustment value
Magnetic adjustment value

Depth
Weight

h250 TM
MCCB
HHG
3-4

[W]

mm

1P
2P
3P
4P
1P
2P
3P
4P

mm
mm
mm
mm
mm
mm
kg
kg
kg
kg

5
-

#1
#1
#1
#1
ok
integrated
ok
ok

#1
#1
#1
#1
ok
ok
integrated
integrated
-

#2
#2
#2
#2
ok
ok
ok
integrated
-

cage
95 mm2
ok
integrated
ok
no

lugs
185 mm2 (cage)
25
ok
ok
ok
ok

lugs
185 mm2 (cage)
25
ok
ok
ok
ok

165
105
140
68
1,3
1,6

165
105
140
68
1,5
1,9

130
75
100
68
0,715
0,95

25
50

0,29
0,48

HNG

HEG

h400
MCCB
HHD
3-4

HND

400
250 - 400
220 - 690
50/60
800
8

h630
Switch
HCD
3-4
630
400 - 630
220 - 690
50/60
800
8

85
50
30
20
40

MCCB
HND

HED

h1000
Switch
HCE
3-4

MCCB
HNE

HEE

1000
800 - 1000
220 - 690
50/60
800
8

250 - 630

85
65
25
7,5
40

35
25
10
7,5
25

65
25
25
7,5
40

85
36
25
7,5
40

85
35
50
25
30
10
15
7,5
40
25
A
50C
100%
100%
95%
92%
89%
ok
4500
15000
-25 to +70C
-35 to +70C
75
IEC 60947-2
ok
ok
0,63 to 1 x In
6-8-10-12 x In

85
85
50
50
30
30
15
15
9
5 (0,3s)
B (400A) - A (630A)
50C
100%
100%
95%
90%
80%
ok
4500
15000
-25 to +70C
-35 to +70C
150
IEC 60947-3 IEC 60947-2
ok
-

#2
#2
#2
#2
ok
ok
ok
integrated
-

#2
#2
#2
#2
ok
ok
ok
integrated
-

#2
#2
#2
#3
ok
ok
ok
integrated
-

#2
#2
#2
#3
ok
ok
ok
integrated
-

lugs
240 mm2 (cage)
30
ok
ok
ok
ok

lugs
30
ok
integrated
ok

lugs
45
ok
integrated
ok

lugs
45
ok
integrated
ok

260
140
185
97
4,2
5,6

260
140
185
97
4,3
5,7

273/433
210
280
99,5
11
14,8

370/570
210
280
140
27

85
50
30
20

ok
0,4 to 1 x Ir
2,5 to 10 x Ir (400A)
2,5 to 8 x Ir (630A)
0,1 - 0,2s

MCCB
HNF

HEF

100
50
45
25
-

100
70
65
45
-

1600
1250 - 1600
220 - 690
50/60
800
8

85
50
25
7,5
40

100
70
30
20

h1600
Switch
HCF
3-4

85
50
30
20
-

100
70
30
20
-

85
85
50
50
30
30
15
15
20
10kA (0,3s) B (800A) - A (1000A)
50C
100%
100%
95%
90%
80%
ok
4500
15000
-25 to +70C
-35 to +70C
150
IEC 60947-3 IEC 60947-2
ok
-

75
75
50
50
50
45
34
25
45
20 (0,3s)
B
50C
100%
100%
95%
90%
80%
ok
4500
15000
-25 to +70C
-35 to +70C
170
IEC 60947-3 IEC 60947-2
ok
-

ok
0,4 to 1 x Ir
2,5 to 10 x Ir

0,1 - 0,2s

ok
0,4 to 1 x Ir
2,5 to 10 x Ir (800A)
2,5 to 8 x Ir (1000A)
0,1 - 0,2s

MCCBs H3 : references guide


Product
Serie

MCCBs
x160

x250

h250

h400

h630

h1000

h1600

HDA

HHA

HNA

HHB

HNB

HHG

HNG

HEG

HHD

HND

HND

HED

HNE

HEE

HNF

HEF

Icu415VAC 18kA

25kA

40kA

25kA

40kA

25kA

50kA

65kA

25kA

50kA

50kA

70kA

50kA

70kA

50kA

70kA

Pole Trip unit

1P

2P

TM fix

TM fix

TM fix

16

HDA014Z HHA014Z

20

HDA018Z HHA018Z

25

HDA023Z HHA023Z

32

HDA030Z HHA030Z

40

HDA038Z HHA038Z

50

HDA048Z HHA048Z

63

HDA061Z HHA061Z

80

HDA078Z HHA078Z

100

HDA098Z HHA098Z

125

HDA123Z HHA123Z

16

HDA015Z HHA015Z

20

HDA019Z HHA019Z

25

HDA024Z HHA024Z

32

HDA031Z HHA031Z

40

HDA039Z HHA039Z

50

HDA049Z HHA049Z

63

HDA062Z HHA062Z

80

HDA079Z HHA079Z

100

HDA099Z HHA099Z

125

HDA124Z HHA124Z

160

HDA159Z HHA159Z

16

HDA016Z HHA016Z HNA016Z

20

HDA020Z HHA020Z HNA020Z

25

HDA025Z HHA025Z HNA025Z

32

HDA032Z HHA032Z HNA032Z

40

HDA040Z HHA040Z HNA040Z

50

HDA050Z HHA050Z HNA050Z

63

HDA063Z HHA063Z HNA063Z

80

HDA080Z HHA080Z HNA080Z

100

HDA100Z HHA100Z HNA100Z HHB100Z HNB100Z

125

HDA125Z HHA125Z HNA125Z HHB125Z HNB125Z

160

HDA160Z HHA160Z HNA160Z HHB160Z HNB160Z

200

HHB200Z HHB200Z

250
25

HHB250Z HNB250Z
HDA025U HHA025U HNA025U

32

3P

TM adj

LSI adj

HHG032U

40

HDA040U HHA040U HNA040U

63

HDA063U HHA063U HNA063U

80

HDA080U HHA080U HNA080U

100

HDA100U HHA100U HNA100U

HNB100U HHG100U HNG100U HEG100U

125

HDA125U HHA125U HNA125U

HNB125U HHG125U HNG125U HEG125U

160

HDA160U HHA160U HNA160U

HNB160U HHG160U HNG160U HEG160U

HHG063U HNG063U HEG063U

200

HNB200U HHG200U HNG200U HEG200U

250

HNB250U HHG250U HNG250U HEG250U HHD250U HND250U

400

HHD400U HND400U

400

HED400U

630

HND630U HED630U

800

HNE800U HEE800U

1000

HNE970U HEE970U

1250

HNF980U HEF980U

1600

TM fix

HNF990U HEF990U

16

HDA017Z HHA017Z HNA017Z

20

HDA021Z HHA021Z HNA021Z

25

HDA026Z HHA026Z HNA026Z

32

HDA033Z HHA033Z HNA033Z

40

HDA041Z HHA041Z HNA041Z

50

HDA051Z HHA051Z HNA051Z

63

HDA064Z HHA064Z HNA064Z

80

HDA081Z HHA081Z HNA081Z

100

HDA101Z HHA101Z HNA101Z HHB101Z HNB101Z

125

HDA126Z HHA126Z HNA126Z HHB126Z HNB126Z

160

HDA161Z HHA161Z HNA161Z HHB161Z HNB161Z

200

HHB201Z HNB201Z

250
4P

TM adj

HDA026U

40

HDA041U

63

HDA064U

80

HDA081U

100

HDA101U

HNB101U

125

HDA126U

HNB126U

160

HDA161U

HNB161U

200

HNB201U

250

HNB251U

400

LSI adj

HHB251Z HNB251Z

25

HND251U
HND401U

400

HED401U

630

HND631U HED631U

800

HNE801U HEE801U

1000

HNE971U HEE971U

1250

HNF981U HEF981U

1600

HNF991U HEF991U

Switches and accessories for H3


references guide
Switches and accessories
Products

Version

pole

In A / Ue V

x160

125

HCA125Z

160

HCA160Z

250

3P

x250

h250

HCB250Z

h400-h630

400

HCD400U

630

HCD630U

h1000

800

HCE800U

1000

HCE970U

1250

HCF980U

1600

Switches

HCF990U

125

HCA126Z

160

HCA161Z

250

4P

HCB251Z

400

HCD401U

630

HCD631U

800

HCE801U

1000

HCE971U

1250

HCF981U

1600

Shunt trip release

Undervoltage release

3/4P

3/4P

Auxiliaries

HCF991U

24V DC

HXA001H

HXC001H

48V DC

HXA002H

HXC002H

110V AC

HXA003H

HXC003H

230V AC

HXA004H

HXC004H

400V AC

HXA005H

HXC005H

24V DC

HXA011H

HXC011H

HXE011H

110V AC

HXA013H

HXC013H

HXE013H

230V AC

HXA014H

HXC014H

HXE014H

400V AC

HXA015H

HXC015H

HXE015H

HXC021H

Auxiliary contact

3/4P

1NO+1NC

HXA021H

Alarm contact

3/4P

1NO+1NC

HXA024H

HXC024H

Direct rotary handle

HXA030H

HXB030H

HXC030H

HXD030H

HXE030H

HXF030H

Extended rotary handle

HXA031H

HXB031H

HXC031H

HXD031H

HXE031H

HXF031H

Padlock

HXA039H

HXC039H

HXD039H

HXF039H

24V DC

HXB040H

HXC040H

HXD040H

HXE040H

HXF040H

220V AC

HXB042H

HXC042H

HXD042H

HXE042H

HXF042H

Motor operator

3/4P

Interlocking wire type

3/4P

HXB065H

HXC065H

HXD065H

HXE065H

3P

included

HYA001

HYC003H

HYD003H (400)

4P

included

HYA002H

HYC004H

HYD004H (400)

included

included

Collar terminal
Extended connection
straight

3/4P

HYA013H

HYB010H

HYC010H

HYD010H (400)
HYD013H (630)

3P

HYA014H

HYB011H

HYC011H

HYD011H (400)
HYD014H (630)

4P

HYA015H

HYB012H

HYD012H (400)
HYD015H (630)

Extended connection
spreaders

Connections

h1600

short

HYA019H

long

HYB019H

included

included

included

included

HYB021H

HYC021H

HYD021H

HYE021H

HYA022H

HYB022H

HYD022H

HYE022H

3P

HYA023H

HYB023H

HYD023H

4P

HYA024H

HYB024H

HYD024H

Terminal cover short for rear connections

3P

HYB025H

HYC025H

HYD025H

HYE025H

4P

HYB026H

HYD026H

HYE026H

Terminal cover for


collar terminal

3P

HYA027H

HYB027H

HYC027H

HYD027H

4P

HYA028H

HYB028H

HYD028H

3P

HYB031H

HYC031H

HYD031H (400)
HYD033H (630)

HYE031H (400)
HYE033H (630)

4P

HYB032H

HYD032H (400)
HYD034H (630)

HYE032H (400)
HYE034H (630)

included

DIN rail adaptor

3/4P

HYA033H

Compact lugs 120mm2 D:10

3/4P

HYD093H

Compact lugs 150mm2 D:8,5

3/4P

Compact lugs 150mm2 D:10,5

3/4P

HYD095H

Compact lugs 185mm2 D:10,5

3/4P

HYD096H

Compact lugs 185mm2 D:12,8

3/4P

HYD097H*

Compact lugs 240mm2 D:12,8

3/4P

HYD098H*

Interphase barrier

3/4P

Terminal cover for


extended connections

3P

HYA021H

4P

Terminal cover large for


spreaders

Rear connections

* with spreaders

MCCBs and switch disconnectors x160


Moulded case circuit breakers
x160
Thermal magnetic trip unit, 2 versions:
- Z version: fixed thermal and fixed
magnetic
- U version: adjustable thermal and
fixed magnetic

Switch disconnectors
allows tripping at distance using a
voltmetrical trip unit (optional)
Complies with IEC 60947-3
AC 22/23A

settings,
integrated padlocking handle
4mm.
Connection capacity
95 rigid cables
70 flexible cables
Complies with IEC 60947-2

1P, 2P, 3P and 4P


Mechanical test button, lockable

Designation

For technical data,


see pages 28 to 35.

In

Cat. ref.
1P

2P

3P

4P

16A
20A
25A
32A
40A
50A
63A
80A
100A
125A
160A

HDA 014Z
HDA 018Z
HDA 023Z
HDA 030Z
HDA 038Z
HDA 048Z
HDA 061Z
HDA 078Z
HDA 098Z
HDA 123Z
-

HDA 015Z
HDA 019Z
HDA 024Z
HDA 031Z
HDA 039Z
HDA 049Z
HDA 062Z
HDA 079Z
HDA 099Z
HDA 124Z
HDA 159Z

HDA 016Z
HDA 020Z
HDA 025Z
HDA 032Z
HDA 040Z
HDA 050Z
HDA 063Z
HDA 080Z
HDA 100Z
HDA 125Z
HDA 160Z

HDA 017Z
HDA 021Z
HDA 026Z
HDA 033Z
HDA 041Z
HDA 051Z
HDA 064Z
HDA 081Z
HDA 101Z
HDA 126Z
HDA 161Z

adjustable thermal
0,63 - 0,8 - 1 x In
fixed magnetic
> 10 x In

25A
40A
63A
80A
100A
125A
160A

HDA 025U
HDA 040U
HDA 063U
HDA 080U
HDA 100U
HDA 125U
HDA 160U

HDA 026U
HDA 041U
HDA 064U
HDA 081U
HDA 101U
HDA 126U
HDA 161U

MCCBs x160 25kA


breaking capacity
Ics : 20 kA
(400/415 V AC)

16A
20A
25A
32A
40A
50A
63A
80A
100A
125A
160A

HHA 014Z
HHA 018Z
HHA 023Z
HHA 030Z
HHA 038Z
HHA 048Z
HHA 061Z
HHA 078Z
HHA 098Z
HHA 123Z
-

HHA 015Z
HHA 019Z
HHA 024Z
HHA 031Z
HHA 039Z
HHA 049Z
HHA 062Z
HHA 079Z
HHA 099Z
HHA 124Z
HHA 159Z

HHA 016Z
HHA 020Z
HHA 025Z
HHA 032Z
HHA 040Z
HHA 050Z
HHA 063Z
HHA 080Z
HHA 100Z
HHA 125Z
HHA 160Z

HHA 017Z
HHA 021Z
HHA 026Z
HHA 033Z
HHA 041Z
HHA 051Z
HHA 064Z
HHA 081Z
HHA 101Z
HHA 126Z
HHA 161Z

25A
40A
63A
80A
100A
125A
160A

HHA 025U
HHA 040U
HHA 063U
HHA 080U
HHA 100U
HHA 125U
HHA 160U

MCCBs x160 18kA


breaking capacity
Ics : 18 kA
(400/415 V AC)
fixed thermal
1x In
fixed magnetic
> 10 x In

HDA 125Z

fixed thermal
1x In
fixed magnetic
> 10 x In

HDA 126U
adjustable thermal
0,63 - 0,8 - 1 x In
fixed magnetic
> 10 x In

MCCBs and switch disconnectors x160

Designation

In

Cat. ref.
1P

2P

3P

4P

16A
20A
25A
32A
40A
50A
63A
80A
100A
125A
160A

HNA 016Z
HNA 020Z
HNA 025Z
HNA 032Z
HNA 040Z
HNA 050Z
HNA 063Z
HNA 080Z
HNA 100Z
HNA 125Z
HNA 160Z

adjustable thermal
0,63 - 0,8 - 1 x In
fixed magnetic
> 10 x In

25A
40A
63A
80A
100A
125A
160A

HNA 025U
HNA 040U
HNA 063U
HNA 080U
HNA 100U
HNA 125U
HNA 160U

HNA 017Z
HNA 021Z
HNA 026Z
HNA 033Z
HNA 041Z
HNA 051Z
HNA 064Z
HNA 081Z
HNA 101Z
HNA 126Z
HNA 161Z
-

Switch disconnectors x160


suitable for
AC22A / AC 23A

125A
160A

HCA 125Z
HCA 160Z

MCCBs x160 40kA


breaking capacity
Ics : 20 kA
(400/415 V AC)
fixed thermal
1 x In
fixed magnetic
> 10 x In
HNA 160Z

HCA 126Z
HCA 161Z

Ue: 415 V AC
Icw (1s): 2 kA

Accessories for
MCCBS and switch disconnectors x160
Indication contacts
- 1 changeover switch (ON/OFF):
indicates the position of the MCCB is
open or closed.
- 1 changeover alarm contact:
indicates MCCB tripping.
coil connection
connection capacity:
0,75I flexible or rigid cables
Optional connection cables.
The cable capacity of the
terminals is 0,5 to 1,25 mm2.

HXA 021H

Shunt trip
remotes tripping of MCCBs or switch
disconnectors.
Operating voltage: 0,7 to 1,1 x Un
Under voltage release
allows the tripping of MCCBs or
switch disconnectors when voltage
level drop between 35 and 70% of
Un. Pick up voltage 0,85 x Un
Direct rotary handle
- padlockable

- equipped with front cover and


handle
- fixing without any additional screw.
Extended rotary handle
- IP 55
- supplied complete with shaft and
handle.

For technical data,


see pages 28 to 35.

Designation

Characteristics

Cat. ref.

Auxiliary contacts
AX
AL

1 changeover contact (ON/OFF)


250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC

HXA 021H

1 changeover alarm contact


250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC

HXA 024H

24 V DC

HXA 001H

48 V DC

HXA 002H

110 V AC

HXA 003H

220 - 240 V AC

HXA 004H

380 - 440 V AC

HXA 005H

24 V DC

HXA 011H

110 V AC

HXA 013H

220 - 240 V AC

HXA 014H

380 - 450 V AC

HXA 015H

Direct rotary handle

padlockable handle
max 6 mm

HXA 030H

Extended rotary handle

padlockable handle
max 8 mm

HXA 031H

Padlock

to mount on MCCB for


handle locking
for 3 padlock
max 8 mm

HXA 039H

HXA 024H
Shunt trip
SH

Undervoltage release
UV

HXA 014H

HXA 030H

10

Accessories for
MCCBS and switch disconnectors x160

Designation

Characteristics

Cat. ref.
3P

Extended connections

HYA 015H

Interphase barriers

Terminal cover

4P

set of 4 extended
connections

HYA 013H

HYA 013H

set of 3 or 4 spreaders

HYA 014H

HYA 015H

set of 3,
height: 50 mm

HYA 019H

HYA 019H

set of 3,
height: 97 mm

HYB 019H

HYB 019H

for extended connections

HYA 021H

HYA 022H

for spreaders

HYA 023H

HYA 024H

for collar terminal

HYA 027H

HYA 028H

HYA 033H

HYA 033H

HYA 021H

HYA 023H

HYA 027H

Din rail adaptor

11

MCCBs and free switch disconnectors x250


Moulded case circuit
breakers x250,
2 versions of trip unit:
- Z version: fixed thermal and
magnetic
- U version: adjustable thermal and
magnetic

integrated padlocking handle


4mm.

Switch disconnectors
allows tripping at distance using a
voltmetrical trip unit (optional)

Complies with IEC 60947-2

3P and 4P
Mechanical test button,
lockable settings,

Connection:
directly on copper cable terminal,
with end lug max. width: 25 mm
Connection capacity: 185 rigid
cables
Complies with IEC 60947-2

Designation

Designation

Complies with IEC 60947-3


AC 22/23A

For technical data,


see pages 36 to 44.

In

Cat. ref.
3P

MCCBs x250 25kA

4P

100A

HHB 100Z

HHB 101Z

125A

HHB 125Z

HHB 126Z

160A

HHB 160Z

HHB 161Z

200A

HHB 200Z

HHB 201Z

250A

HHB 250Z

HHB 251Z

100A

HNB 100Z

HNB 101Z

125A

HNB 125Z

HNB 126Z

160A

HNB 160Z

HNB 161Z

200A

HNB 200Z

HNB 201Z

250A

HNB 250Z

HNB 251Z

adjustable thermal
0,63 - 0,8 - 1x In
adjustable magnetic
6 - 8 - 10 - 13 x In (100 - 200A)
5 - 7 - 9 - 11 x In (250A)

100A

HNB 100U

HNB 101U

125A

HNB 125U

HNB 126U

160A

HNB 160U

HNB 161U

3P, 3 trip units


4P,
neutral setting: 0 or 100%

200A

HNB 200U

HNB 201U

250A

HNB 250U

HNB 251U

capacity suitable for


AC 22/23A

250A

HCB 250Z

HCB 251Z

breaking capacity
Icu : 25 kA
(400/415 V AC)
Ics: 20kA
fixed thermal
1 x In
fixed magnetic
10 x In

HNB 250Z
MCCBs x250 40kA

breaking capacity
Icu : 40 kA
(400/415 V AC)
Ics: 20 kA
fixed thermal
1 x In
fixed magnetic
10 x In

HNB 100U

Switch disconnectors x250

Icw (1s): 3,6 kA

12

Accessories for
MCCBS and switch disconnectors x250
Indication contacts
- 1 changeover switch (ON/OFF):
indicates the position of the MCCB is
open or closed.
- 1 changeover alarm contact:
indicates MCCB tripping.
coil connection
connection capacity:
0,75I flexible or rigid cables
Optional connection cables.
The cable capacity of the
terminals is 0,5 to 1,25 mm2.

HXA 021H

Shunt trip
remotes tripping of MCCBs or switch
disconnectors.
Operating voltage: 0,7 to 1,1 x Un
Under voltage release
allows the tripping of MCCBs or
switch disconnectors when voltage
level drop between 35 and 70% of
Un. Pick up voltage 0,85 x Un
Direct rotary handle
- padlockable

- equipped with front cover and


handle
- fixing without any additional screw.
Extended rotary handle
- IP 55
- supplied complete with shaft and
handle.

For technical data,


see pages 36 to 44.

Designation

Characteristics

Cat. ref.

Auxiliary contacts
AX
AL

1 changeover contact
250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC

HXA 021H

1 changeover alarm contact


250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC

HXA 024H

Shunt trip
SH

24 V DC
48 V DC
110 V AC
220 - 240 V AC
380 - 440 V AC

HXA 001H
HXA 002H
HXA 003H
HXA 004H
HXA 005H

Undervoltage release UV

24 V DC
110 V AC
220 - 240 V AC
380 - 450 V AC

HXA 011H
HXA 013H
HXA 014H
HXA 015H

Direct rotary handle

padlockable handle
max 6 mm

HXB 030H

Extended rotary handle

padlockable handle
max 8 mm

HXB 031H

Padlock

to mount on MCCBs for handle


locking
for 3 padlock
max 8 mm

HXA 039H

Motor operator

24 V DC
200 - 220V AC

HXB 040H
HXB 042H

HXA 024H

HXA 014H

13

Accessories for
MCCBS and switch disconnectors x250

Designation

Characteristics

Cat. ref.
3P

HYB 010H

4P

Interlocking

wire type

HXB 065H

HXB 065H

Collar terminal

4 aluminium / copper
conductors
150 rigid cables
120 flexible cables

HYA 001H

HYA 002H

Extended
connections

set of 4 pieces

HYB 010H

HYB 010H

spreaders

HYB 011H

HYB 012H

Interphase
barriers

set of 3,
height: 97 mm

HYB 019H

HYB 019H

Terminal cover

for extended connections

HYB 021H

HYB 022H

for spreaders

HYB 023H

HYB 024H

for rear connections short

HYB 025H

HYB 026H

for collar terminal

HYB 027H

HYB 028H

HYB 031H

HYB 032H

HYB 012H

HYB 022H

HYB 024H

Rear connection

HYB 031H

14

Designation

Characteristics

Cat.
ref.

Ring lug

compact lugs 35 8,5

HYA 088H

compact lugs 50 8,5

HYA 089H

compact lugs 70 8,5

HYA 090H

compact lugs 95 8,5

HYA 091H

compact lugs 120 8,5

HYB 092H

compact lugs 150 8,5

HYB 094H

MCCBs h250
Moulded case circuit
breakers h250
Thermal magnetic trip unit:
thermal adjustment: 0.63 to 1 In
magnetic adjustment: 6-8-10-13 x In

Designation

3P
Mechanical test button,
lockable settings,
Connection:
directly on copper cable terminal,
with end lug max. width: 25 mm

Complies with IEC 60947-2

Characteristics

In

For technical data,


see pages 45 to 51.

Cat. ref.
3P

MCCBs h250 25kA


TM

breaking capacity
Icu : 25 kA (400/415 V AC)
Ics: 19 kA

20-32A

HHG 032U

40-63A

HHG 063U

adjustable thermal
0.63 to 1 x In
adjustable magnetic
6 - 8 - 10 - 13 x In

63-100A

HHG 100U

80-125A

HHG 125U

100-160A

HHG 160U

125-200A

HHG 200U

160-250A

HHG 250U

breaking capacity
Icu : 50 kA (400/415 V AC)
Ics: 25 kA

40-63A

HNG 063U

63-100A

HNG 100U

adjustable thermal
0.63 to 1 x In
adjustable magnetic
6 - 8 - 10 - 13 x In

80-125A

HNG 125U

100-160A

HNG 160U

125-200A

HNG 200U

160-250A

HNG 250U

breaking capacity
Icu : 65 kA (400/415 V AC)
Ics: 36 kA

40-63A

HEG 063U

63-100A

HEG 100U

adjustable thermal
0.63 to 1 x In
adjustable magnetic
6 - 8 - 10 - 13 x In

80-125A

HEG 125U

100-160A

HEG 160U

125-200A

HEG 200U

160-250A

HEG 250U

HHG 250U

MCCBs h250 50kA


TM

MCCBs h250 65kA


TM

15

Accessories for MCCBS h250


Indication contacts
- 1 changeover switch (ON/OFF):
indicates the position of the MCCB is
open or closed.
- 1 changeover alarm contact:
indicates MCCB tripping.
coil connection
connection capacity:
0,75I flexible or rigid cables
Optional connection cables.
The cable capacity of the
terminals is 0,5 to 1,25 mm2.

HXC 021H

16

Under voltage release


allows the tripping of MCCBs or
switch disconnectors when voltage
level drop between 35 and 70% of
Un. Pick up voltage 0,85 x Un
Direct rotary handle
- padlockable

- equipped with front cover and


handle
- fixing without any additional screw.
Extended rotary handle
- IP 55
- supplied complete with shaft and
handle.

For technical data,


see pages 45 to 51.

Designation

Characteristics

Auxiliary contacts
AX
AL

1 changeover contact
250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC

HXC 021H

1 changeover alarm contact


250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC

HXC 024H

Cat. ref.

Shunt trip
SH

24 V DC
48 V DC
100 - 120 V AC
200 - 240 V AC
380 - 450 V AC

HXC 001H
HXC 002H
HXC 003H
HXC 004H
HXC 005H

Undervoltage release
UV

24 V DC
100 - 120 V AC
200 - 240 V AC
380 - 450 V AC

HXC 011H
HXC 013H
HXC 014H
HXC 015H

Direct rotary handle

padlockable handle
5 - 8 mm2 max

HXC 030H

Extended rotary handle

padlockable handle
5 - 8 mm2 max

HXC 031H

HXC 024H

HXC 004H

HXC 014H

Shunt trip
remotes tripping of MCCBs or switch
disconnectors.
Operating voltage: 0,7 to 1,1 x Un

Accessories for MCCBS h250

Designation

Characteristics

Cat. ref.

Padlock

to mount on MCCBs for


handle locking
for 3 padlock
max 5 mm

HXC 039H

Motor operator

24 V DC
200-220 V AC

HXC 040H
HXC 042H

Interlocking

wire type

HXC 065H

Collar terminal

copper

HYC 003H

Extended
connections

spreaders

HYC 011H

Terminal cover

for extended connections


for rear connections short
for collar terminal

HYC 021H
HYC 025H
HYC 027H

HXC 039H

HYC 011H

Rear connection

HYC 031H

HYC 031H

17

MCCBs and switch disconnectors h400-h630


Moulded case circuit breakers
h400, h630
2 versions of trip unit:
Thermal magnetic trip unit TM:
- thermal adjustment:
from 0.63 to 1 x In
- magnetic adjustment:
from 6 to 12 x In

adjustable:
2.5 to 10 x Ir (400A)
2.5 to 8 x Ir (630A)
- time delay: 0,1 - 0,2 s
3P & 4P (adjustable neutral 0 - 50% 100%).
Mechanical test button,
lockable settings

Switch disconnectors
allows tripping at distance using a
voltmetrical trip unit (optional)
Complies with IEC 60947-3
AC 23A / DC 22A

Electronic trip unit LSI:


- long delay ( thermal equivalent)
adjustable:
Ir = 0.4 to 1 x In
- short delay (magnetic equivalent)

Connection:
directly on copper cable terminal,
with end lug max. width: 30 mm
Complies with IEC 60947-2)

For technical data,


see pages 52 to 62.

Designation

Designation

In

Cat. ref.
3P

MCCBs h400 25kA


TM

breaking capacity
Icu : 25 kA (400/415 V AC)
Ics: 25 kA

4P

250A

HHD 250U -

400A

HHD 400U -

250A

HND 250U

HND 251U

400A

HND 400U

HND 401U

630A

HND 630U HND 631U

400A

HED 400U HED 401U

630A

HED 630U HED 631U

400A

HCD 400U HCD 401U

630A

HCD 630U HCD 631U

adjustable thermal
0.63 to 1 x In
adjustable magnetic
6 to 12 x In
3P
HHD 400U
MCCBs h400 50kA
TM

breaking capacity
Icu : 50 kA (400/415 V AC)
Ics: 50 kA
adjustable thermal
0.63 to 1 x In
adjustable magnetic
6 to 12 x In
3P

HND 630U

MCCBs h630 50kA


LSI

breaking capacity
Icu : 50 kA (400/415 V AC)
Ics: 50 kA
adjustable thermal
Ir = 0.4 to 1 x In
adjustable magnetic
2.5 to 8 x Ir
time delay: 0,1 - 0,2 s

MCCBs h630 70kA


LSI

breaking capacity
Icu : 70 kA (400/415 V AC)
Ics: 50 kA
adjustable thermal
Ir = 0.4 to 1 x In
adjustable magnetic
2.5 to 10 x Ir (400A)
2.5 to 8 x Ir (630A)
time delay: 0,1 - 0,2 s

Switch disconnectors

18

suitable for
AC 22A / AC 23A
Ue: 415 V AC
Icw (0,3s) = 5kA

Accessories for
MCCBS and switch disconnectors h400-h630
Indication contacts
- 1 changeover switch (ON/OFF):
indicates the position of the MCCB is
open or closed.
- 1 changeover alarm contact:
indicates MCCB tripping.
coil connection
connection capacity:
0,75I flexible or rigid cables
Optional connection cables.
The cable capacity of the
terminals is 0,5 to 1,25 mm2.

HXC 021H

Shunt trip
remotes tripping of MCCBs or switch
disconnectors.
Operating voltage: 0,7 to 1,1 x Un
Under voltage release
allows the tripping of MCCBs or
switch disconnectors when voltage
level drop between 35 and 70% of
Un. Pick up voltage 0,85 x Un
Direct rotary handle
- padlockable

- equipped with front cover and


handle
- fixing without any additional screw.
Extended rotary handle
- IP 55
- supplied complete with shaft and
handle.

For technical data,


see pages 52 to 62.

Designation

Characteristics

Cat.
ref.

Auxiliary contacts
AX
AL

1 changeover contact
250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC

HXC 021H

1 changeover alarm contact


250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC

HXC 024H

Shunt trip SH

24 V DC
48 V DC
100 - 120 V AC
200 - 240 V AC
380 - 450 V AC

HXC 001H
HXC 002H
HXC 003H
HXC 004H
HXC 005H

Undervoltage release
UV

24 V DC
100 - 120 V AC
200 - 240 V AC
380 - 450 V AC

HXC 011H
HXC 013H
HXC 014H
HXC 015H

Direct rotary handle

padlockable handle
max 6 mm

HXD 030H

Extended rotary handle

padlockable handle
max 8 mm

HXD 031H

Padlock

to mount on MCCBs for


handle locking
for 3 padlock
5 - 8 mm2 max

HXD 039H

HXC 024H

HXC 004H

HXC 014H

HXD 030H

HXD 039H

19

Accessories for
MCCBS and switch disconnectors h400-h630

Designation

Characteristics

In

Cat. ref.
3P

4P

Motor operator

24-48 V DC
100-240 V AC

HXD 040H
HXD 042H

HXD 040H
HXD 042H

Interlocking

wire type

HXD 065H

HXD 065H

Collar terminal

set of 3 or 4 terminals for copper


conductors 240

400A

HYD 003H

HYD 004H

Extended connections

set of 4 pieces

400A
630A

HYD 010H
HYD 013H

spreaders

400A
630A

HYD 011H
HYD 014H

HYD 012H
HYD 015H

HYD 021H
HYD 023H
HYD 025H
HYD 027H

HYD 022H
HYD 024H
HYD 026H
HYD 028H

HYD 031H
HYD 033H

HYD 032H
HYD 034H

HXD 042H

HYD 003H

HYD 015H

Terminal cover

for extended connections


for spreaders
for rear connections short
for collar terminal

HYD 022H
Rear connection

400A
630A

HYD 033H

20

Designation

Characteristics

Cat.
ref.

Ring lug

Compact lugs 120 10

HYD 093H

Compact lugs 150 10,5

HYD 095H

Compact lugs 185 10,5

HYD 096H

Compact lugs 185 12,8


with spreader
Compact lugs 240 12,8
with spreader

HYD 097H
HYD 098H

MCCBs and switch disconnectors h800-h1000


Moulded case circuit breakers
h1000
Electronic trip unit LSI:
- long delay (thermal equivalent)
adjustable:
Ir= 0,4 to 1 x In
- short delay (magnetic
equivalent) adjustable:
2,5 to 10 x Ir
- time delay: 0,1-0,2 s

3P & 4P (adjustable neutral 0 - 50% 100%).


Mechanical test button,
lockable settings.

Designation

Designation

Switch disconnectors
allows tripping at distance using a
voltmetrical trip unit (optional)
Complies with IEC 60947-3
AC 23A / DC 22A

Connection:
directly on copper cable terminal,
with end lug max. width: 50 mm

For technical data,


see pages 67 to 75.

Complies with IEC 60947-2

In

Cat. ref.
3P

MCCBs h1000 50kA


LSI

breaking capacity
Icu : 50 kA (400/415 V AC)
Ics: 50 kA

4P

800A

HNE 800U

HNE 801U

1000A

HNE 970U

HNE 971U

800A

HEE 800U

HEE 801U

1000A

HEE 970U

HEE 971U

800A

HCE 800H HCE 801H

1000A

HCE 970H HCE 971H

adjustable thermal
Ir = 0,4 to 1 x In
adjustable magnetic
2,5 to 10 x Ir
time delay: 0,1-0,2 s
neutral setting from 0-50 to
100%

HNE 970U
MCCBs h1000 70kA
LSI

breaking capacity
Icu : 70 kA (400/415 V AC)
Ics: 50 kA
adjustable thermal
Ir = 0,4 to 1 x In
adjustable magnetic
2,5 to 10 x Ir
time delay: 0,1-0,2 s
neutral setting from 0-50 to
100%

Switch disconnectors

suitable for
AC 22A / AC 23A
Ue : 415 V AC
Icw (0,3 s) = 10 kA

21

Accessories for
MCCBS and switch disconnectors h800-h1000
Indication contacts
- 1 changeover switch (ON/OFF):
indicates the position of the MCCB is
open or closed.
- 1 changeover alarm contact:
indicates MCCB tripping.

level drop between 35 and 70% of


Un. Pick up voltage 0,85 x Un

Shunt trip
remotes tripping of MCCBs or switch
disconnectors.
Operating voltage: 0,7 to 1,1 x Un

coil connection
connection capacity:
0,75I flexible or rigid cables
Optional connection cables.

Under voltage release


allows the tripping of MCCBs or
switch disconnectors when voltage

Designation

Characteristics

Auxiliary contacts

1 changeover contact
250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC

HXC 021H

1 changeover alarm contact


250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC

HXC 024H

24 V DC

HXC 001H

48 V DC

HXC 002H

100 - 120 V AC

HXC 003H

200 - 240 V AC

HXC 004H

380 - 450 V AC

HXC 005H

24 V DC

HXE 011H

110 - 120 V AC

HXE 013H

220 - 240 V AC

HXE 014H

380 - 415 V AC

HXE 015H

AX
AL

HXC 021H

The cable capacity of the


terminals is 0,5 to 1,25 mm2.

For technical data,


see pages 67 to 75.

Cat. ref.

HXC 024H

Shunt trip SH

HXC 004H

Undervoltage release
UV

HXE 014H

22

Accessories for
MCCBS and switch disconnectors h800-h1000
Direct rotary handle
- padlockable
- equipped with front cover and
handle
- fixing without any additional screw.

Extended rotary handle


- IP 55
- supplied complete with shaft and
handle.

Designation

Characteristics

For technical data,


see pages 67 to 75.

In

Cat. ref.
3P

HXD 039H

4P

Direct rotary handle

padlockable handle

HXE 030H

HXE 030H

Extended rotary handle

padlockable handle

HXE 031H

HXE 031H

Padlock

to mount on MCCB for


handle locking
for 3 padlock
max 8 mm

HXD 039H

HXD 039H

Motor operator

24 - 48V DC

HXE 040H

HXE 040H

100 - 240V AC

HXE 042H

HXE 042H

Interlocking

wire type

HXE 065H

HXE 065H

Terminal cover

for extended connections

HYE 021H

HYE 022H

for rear connections short

HYE 025H

HYE 026H

800A

HYE 031H

HYE 032H

1000A

HYE 033H

HYE 034H

Rear connection

HYE 031H

23

MCCBs and switch disconnectors h1250-h1600


Moulded case circuit breakers
h1600,
selection and protection
Electronic trip unit LSI
- Long delay (thermal equivalent)
adjustable:
Ir = 0,4 to 1 x In
- short delay (magnetic equivalent)
adjustable:
2,5 to 10 x Ir
- time delay: 0,1-0,2 s

3 pole, 3 trip units,


4 pole, 4 trip units,
adjustable neutral 0 - 50% - 100%

Switch disconnectors
allows tripping at distance using a
voltmetrical trip unit (optional)

Mechanical test button,


lockable settings.

Complies with IEC 60947-3


AC 23A / DC 22A

Connection:
directly on copper cable terminal,
with end lug max. width: 60 mm
For technical data,
see pages 72 to 77.

Complies with IEC 60947-2

Designation

Designation

In

Cat. ref.
3P

MCCBs h1600 50kA


LSI

breaking capacity
Icu : 50 kA (400/415 V AC)
Ics: 50 kA

4P

1250A

HNF 980U

HNF 981U

1600A

HNF 990U

HNF 991U

1250A

HEF 980U

HEF 981U

1600A

HEF 990U

HEF 991U

1250A

HCF 980U

HCF 981U

1600A

HCF 990U

HCF 991U

adjustable thermal
Ir = 0,4 to 1 x In
adjustable magnetic
2,5 to 10 x Ir
time delay: 0,1-0,2 s
neutral setting 0, 50, 100%

HNF 990U

MCCBs h1600 70kA


LSI

breaking capacity
Icu : 70 kA (400/415 V AC)
Ics: 50 kA
adjustable thermal
Ir = 0,4 to 1 x In
adjustable magnetic
2,5 to 10 x Ir
time delay: 0,1-0,2 s
neutral setting from 0, 50,
100%

Switch disconnectors

24

suitable for
AC 22A / AC 23A
Ue : 415 V AC
Icw (0,3 s) = 20 kA

Accessories for
MCCBS and switch disconnectors h1250-h1600
Indication contacts
- 1 changeover switch (ON/OFF):
indicates the position of the MCCB is
open or closed.
- 1 changeover alarm contact:
indicates MCCB tripping.
coil connection
connection capacity:
0,75I flexible or rigid cables
Optional connection cables.
The cable capacity of the
terminals is 0,5 to 1,25 mm2.

HXC 021H

Under voltage release


allows the tripping of MCCBs or
switch disconnectors when voltage
level drop between 35 and 70% of
Un. Pick up voltage 0,85 x Un
Direct rotary handle
- padlockable

- equipped with front cover and


handle
- fixing without any additional screw.
Extended rotary handle
- IP 55
- supplied complete with shaft and
handle.

For technical data,


see pages 72 to 77.

Designation

Characteristics

Cat. ref.

Auxiliary contacts
AX
AL

1 changeover contact
250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC

HXC 021H

1 changeover alarm contact


250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC

HXC 024H

Shunt trip
SH

24 V DC
48 V DC
100 - 120 V AC
200 - 240 V AC
380 - 450 V AC

HXC 001H
HXC 002H
HXC 003H
HXC 004H
HXC 005H

Undervoltage release
UV

24 V DC
110 - 120 V AC
220 - 240 V AC
380 - 415 V AC

HXE 011H
HXE 013H
HXE 014H
HXE 015H

Direct rotary handle

padlockable handle

HXF 030H

Extended rotary handle

padlockable handle

HXF 031H

Padlock

to mount on MCCB for


handle locking
for 3 padlock
max 8 mm

HXF 039H

Motor operator

24 V DC
200 - 230 V AC

HXF 040H
HXF 042H

HXC 024H

HXC 004H

HXC 014H

Shunt trip
remotes tripping of MCCBs or switch
disconnectors.
Operating voltage: 0,7 to 1,1 x Un

25

Technical information

MCCBs and switch disconnectors


x160

28

MCCBs and switch disconnectors


x250

36

MCCBs h250

45

MCCBs and switch disconnectors


h400-h630

52

MCCBs and switch disconnectors


h800-h1000

63

MCCBs and switch disconnectors


h1250-h1600

72

MCCBs, switch disconnectors


x160

MCCBs

HDA

HHA

HNA

PUSH TO TRIP

HCA

220/240V AC
IEC 60 947-2

380/415V AC
IEC 60 947-2

Icu

25 kA

18 kA

Ics

25 kA

18 kA

Icu

35 kA

25 kA

Ics

25 kA

20 kA

Icu

85 kA

40 kA

Ics

30 kA

20 kA

Icm

2,8 kA

Icw

2 kA - 1s

Magnetic and thermal settings

5,5

TRIP

Thermal adjustment from 0,63 to 1 x In


Magnetic adjustment fixed > 10 x In

28

In

15 - 50 A

63 - 80 A

100 - 125 A

160 A

Imag

600 A

1000 A

1500 A

1600 A

MCCBs, switch disconnectors


x160

Tripping curve
MCCB x160
10000

1000

The magnetic thereshold


tripping curves is mean
value. The tripping area is
Irm 20%.

Cold state

16A
15A

20A

25A

From warm state


(rated current)

125A, 50A
80A
75 A
100A, 40A
63A
60A
32A
30A

10

160A

Tripping time (sec)

100

0.1

0.01
1

10

xIn

29

MCCBs, switch disconnectors


x160

Thermal constraint curve (Let-through energy)


MCCB x160
10000

160A
125A
100A
75-80A
60-63A
50A
40A

HDA... up to 18kA
HHA... up to 25kA
HNA... up to 40kA

It (kAs)

1000

30-32A
15-16-20-25A

100

10
0,1

10

100

Iccp (kA)

Current limiting curve (Let-through pick current)


MCCB x160
100

0,25

0,3
160 A
125 A
100 A

80 A
75 A
60-63 A
50 A
40 A

30-32 A
15-16-20-25 A

0,5
10

0,7

Ip (kA)

0,8

0,9

HDA... up to 18kA
HHA... up to 25kA
HNA... up to 40kA

0.1
0,1

30

Iccp (kA)

10

100

MCCBs, switch disconnectors


x160

Dimensions
MCCB x160
A
B

96,1

45

130
114
C

11

25

25

A
(mm)

B
(mm)

C
(mm)

1P

24,8

25

111

2P

49,5

25

111

3P

74,5

25

111

4P

99,5

25

111

A
(mm)

B
(mm)

C
(mm)

1P

24,4

50

60,5

2P

49,5

50

60,5

3P

74,5

50

60,5

4P

99,5

50

60,5

A
(mm)

B
(mm)

C
(mm)

3P

106,5

50

60,5

4P

141,5

50

60,5

15
68

Terminal covers front connected (for straight bars)

230

Terminal cover for extended connections (spreaders)


C

31

MCCBs, switch disconnectors


x160
Terminal covers for collar terminal

C
A
(mm)

B
(mm)

C
(mm)

3P

74,5

60,5

4P

99,5

60,5

141

Connection
Connection with end lugs

16 mm
Max.

min. 6

max. 70

min. 6

max. 95

6,6 Nm

Interphase barriers

55

L
(mm)

32

HYA 019H

50

HYB 019H

97

MCCBs, switch disconnectors


x160

Extended connection: straight bars and spreaders

28

3P
28

3P
8

87
203 mm

203 mm

67

92

4P

25

25

122

25

4P

35

35

35

33

MCCBs, switch disconnectors


x160

Accessories
Direct rotary handle
127

74,5

53,7

45

101,8

48,5

Extended rotary handle


12

74,5

112

45

101,8

200

74,5
10

34

MCCBs, switch disconnectors


x160

Auxiliaries
Auxiliaries for MCCBs and tripping switches

5,5

TRIP
PUSH TO TRIP

Mounting combination for auxiliaries and releases

Auxiliary
Contact
contact
auxiliaire

4P
3P

AX

AX

Alarm
Signal
contact
dfaut

AL

AL

Shunt
trip

SH

SH / UV

UV

Undervoltage
release

35

MCCBs, switch disconnectors


x250

MCCBs

HHB

HNB

HCB

PUSH TO TRIP

220/240V AC
IEC 60 947-2

380/415V AC
IEC 60 947-2

Icu

35 kA

25 kA

Ics

25 kA

20 kA

Icu

85 kA

40 kA

Ics

40 kA

20 kA

Icm

9 kA

Icw

3,6 kA - 1s

Magnetic and thermal settings

TRIP

0,63
8

0,8
PUSH TO TRIP

10

13

l r (xIn)

l i (xIn)

Thermal adjustment from 0,63 to 1 x In


Magnetic adjustment from 6 to 13 x In (100 - 200A)
from 5 to 11 x In (250A)

36

MCCBs, switch disconnectors


x250
Tripping curve
MCCB x250

hour

3
2
1
40
30

minute

20
10
6
4
2
Cold start

1
40
30

Tripping Time

20
10
6
4
From warm state
(rated current)

0.6
0.4
0.2
0.1
0.06
0.04
0.02
0.01

8000

5000

4000

3000

2000

1500

1000

600

500

400

300

200

100
125

0.005
80

second

Percent Rated Current IN

37

MCCBs, switch disconnectors


x250

Thermal constraint curve (Let-through energy)


MCCB x250
9

10

250A

100A

Max. Let-through Energy (I2t) Characteristics

108

107

106

HHB... up to 25kA
HNB... up to 40kA

10

10

10

10

10

10

10

10

Current limiting curve (Let-through pick current)


MCCB x250
1000

Max. Let-through peak current (kA)

100

10

0.1

38

HHB... up to 25kA
HNB... up to 40kA

MCCBs, switch disconnectors


x250

Dimensions
MCCB x250
A
96 mm

35

45

165 mm
144 mm
C

35

A
(mm)

B
(mm)

C
(mm)

3P

104,5

35

126

4P

139,5

35

126

PUSH TO TRIP

22
68

Terminal covers front connected (for straight bars)

A
(mm)

B
(mm)

C
(mm)

3P

104,8

54,5

64

4P

139,8

54,5

64

PUSH TO TRIP

39

MCCBs, switch disconnectors


x250

Accessories
Terminal cover for extended connections (spreaders)
C

A
(mm)

B
(mm)

C
(mm)

3P

147,5

54,5

64

4P

196

54,5

64

PUSH TO TRIP

Terminal cover for rear connections


C

A
(mm)

B
(mm)

C
(mm)

3P

104,8

64

4P

139,4

64

A
(mm)

B
(mm)

C
(mm)

3P

104,8

28,5

64

4P

139,8

28,5

64

PUSH TO TRIP

Terminal covers for collar terminal


C

PUSH TO TRIP

40

MCCBs, switch disconnectors


x250

Connection
Extended connection and spreaders

PUSH TO TRIP

O TRIP

11

3P

3P
29,5

29,5

11

120
226

226

93

168

128

4P

35

35

4P

35

50

50

50

Rear connections
4P
3P

11

35

16

57

144 mm

35

11

35

PUSH TO TRIP

92

41

MCCBs, switch disconnectors


x250

Connection by collar

20 mm
Max.

min. 35

max. 150

min. 35

max. 185

25 Nm

85

Connection with end lugs

9 mm
Max.

25 mm
Max.

12,7 Nm

Interphase barriers

42

MCCBs, switch disconnectors


x250

Accessories
Rotary handle
116

PUSH TO TRIP

53,7

45

101,8

48,5

PUSH TO TRIP

104,5

12

Extended rotary handle


A

107,5

45

101,8

200

PUSH TO TRIP
PUSH TO TRIP

10

Motor operator
180

178

Rated operating voltage


Operating current (A)

310
331,5

Starting current (A)

24V DC
200-220V AC
24V DC
200-220V AC
24V DC
200-220V AC

Operating method
Operating time (s)

ON
OFF
RESET

Operating switch rating


Power supply required
Dielectric properties

24V DC
200-220V AC

ok
ok
18
4
26
8
direct drive
0,1
0,1
0,1
100V, 0.1A, opening
voltage 44V, current 4mA
300 VA minimum
1000 V AC
1500 V AC

43

MCCBs, switch disconnectors


x250
Auxiliaries
Auxiliaries for MCCBs and tripping switches

TRIP
PUSH TO TRIP

Mounting combination for auxiliaries and releases

Auxiliary
Contact
contact
auxiliaire

4P
3P

AX

AX

Alarm
Signal
contact
dfaut

44

AL

AL

SH

Shunt
Bobine
trip
mission

SH / UV

UV

Undervoltage
Bobine
release
minimum
de tension

MCCBs h250

MCCBs
Magnetic and thermal settings

220/240 V 380/415 V
AC
AC
(kA)
(kA)

0,8

0,63

HHG

HNG

HEG

Icu

35

25

Ics

27

19

Icu

35

50

Ics

65

25

Icu

85

65

Ics

85

36

8
10

Ir (x In)

Ii (x In)

Thermal adjustment from 0,63 to 1 x In


Magnetic adjustment from 6 to 10 x In (250A)
from 6 to 13 x In (160 and 200A)
from 6 to 12 x In (32, 63, 100 and 125A)

Tripping curve
MCCB h250 TM

hour

4
3
2
1
50
40
30
20

minute

COLD START
10
8
6
5
4
3
2
1
50
40
30
20

75% HOT START


time

10
8
6
5
4

second

3
2
1
0.8
0.6
0.5
0.4
0.3
0.2
0.1
0.08
0.06
0.05
0.04
0.03

7000
8000

6000

5000

4000

3000

2500

Adjustable setting range


of magnetic trip

2000

500

Hi

700
800
900
1000

In[%]

250

200

150

125

80
90
100

0.005

600

Lo

0.01

1500

0.02

45

MCCBs h250

Thermal constraint curve (Let-through energy)


MCCB h250
109

Max. Let-through Energy (I2t) (x A2sec)

108

107

106

105

HHGup to 25kA
HNGup to 50kA
HEGup to 65kA

Max. L et-thr ough E ner gy (I 2t) Char acter istics


TYPE
h250 HEG, HNG, HHG

10

103 1
10

2
103
104
10
Prospective circuit current in RMS sym. (A)

105

Current limiting curve (Let-through peak current)


MCCB h250

100

Max. Let-through peak current (kA)

0,25

0,3

160A
125A
100A

80A
75A
60-63A
50A
40A

30-32A
15-16-20-25A

0,5
10

0,7
0,8
0,9

0.1
0.1

46

HHGup to 25kA
HNGup to 50kA
HEGup to 65kA

10

100

MCCBs h250

Dimensions
MCCBs
A

90

3P

104,8

4P

139,8

45
102

165
144

A
(mm)

Accessories
Terminal covers front connected (for straight bars)
A

61

60

A
(mm)
104,8

4P

139,8

275

3P

7,5

Terminal cover for rear connections


A

61
A
(mm)
104,8

4P

139,8

170

3P

47

MCCBs h250

7,5

Terminal cover for collar terminal


61

A
(mm)
104,8

4P

139,8

170

3P

Connection
Extended connections and spreaders

29,5

11

120

Connection by collar

20 mm
Max.

48

mini

mini

35

35

max

max

150

185

MCCBs h250
Rear connections
4P
3P
35

35

16

57

144

11

35

11

92

Accessories
Direct rotary handle
A

160
92

3P

104,8

4P

139,8

72

101,8

A
(mm)

49

MCCBs h250

Extended rotary handle

23,8

143,5

101,8

200

22

A
(mm)
3P

104,8

4P

139,8

Motor operator
89,5

155

169,5

Rated operating voltage


Operating current (A)
Starting current (A)

24V DC
200-220V AC
24V DC
200-220V AC
24V DC
200-220V AC

Operating method
Operating time (s)

ON
OFF
RESET

Operating switch rating


Power supply required
Dielectric properties

50

24V DC
200-220V AC

ok
ok
18
4
26
8
direct drive
0,1
0,1
0,1
100V, 0.1A, opening
voltage 44V, current 4mA
300 VA minimum
1000 V AC
1500 V AC

MCCBs h250

Auxiliaries
Auxiliaries for MCCBs and free tripping switches

2
3

TRIP

Mounting combination for auxiliaries and releases

4P
3P
Auxiliary
contact

Shunt
trip

AX

SH

HXC 021 H
HXC 025 H

AL

Alarm
contact

HXC 024 H
HXC 026 H

AX

AL

SH / UV

UV

Undervoltage
release

51

MCCBs, switch disconnectors


h400 - h630

MCCBs
220/240 V 380/415 V 660/690 V
AC
AC
AC
(kA)
(kA)
(kA)
H400/H630 Icu
HND
Ics

Settings

B
A

Magnetic and thermal settings

TM
400 A

0,8

0,63

10
12

Ir (x In)

Thermal adjustment from 0,63 to 1 x In


Magnetic adjustment from 6 to 12 x In

52

8
1

Ii (x In)

85

50

20

85

50

15

H630
HED

Icu

100

70

20

Ics

85

50

15

H630
HCD

Icm _

Icw

5 kA-0,3 s _

MCCBs, switch disconnectors


h400 - h630

Electronic trip unit setting (LSI)


L - Long delay - protection against overloads: Ir and tr
settings
S - Short delay - protection against short circuits: Isd
and tsd settings
I - Instantaneous - max. instantaneous threshold (< 10
ms) in case of short circuit: 2,5 to 10 x Ir (400A) and
2,5 to 8 x Ir (630A).

Neutral settings:

2
B

1
0,8

0,85

Long delay current Ir setting

Characteristics

Ir (A)
0,9

4
0,95

0,63
0,4

Other curve characteristics setting (tr, Isd, tsd)

0,5

Neutral protection against overloads setting

2
100 %

50 %

ON
OFF

TEST IN

PICK UP

In A
250 A / 400 A
LSI

Ir (x In)

Adjustable IR
7
6
5
4
1

630 A

Long Time
Delay

Short Time
Delay

Ir (x In) tr (s)

isd (xlr)

0,4

OK

OK

0,5

OK

OK

0,63

OK

OK

0,8

OK

OK

0,85

OK

0,9

OK

OK

0,95

OK

OK

OK

OK

11s at 2 xlr

21s at 2 xlr

2,5

5,6,7
0.2S
0.1S

Characteristics
1,2
2.5

3
5

4
10 14 xIR

Neutral
protection

Short Time
Delay

tsd (s) li (xlr) Ir (x In) tr (s)

0,1

2
3

Inst Long Time


Delay

5
10

14
(max
13 x
In)

isd (xlr) tsd (s) li (xlr)

11s at 2 xlr

2,5

0,1

21s at 2 xlr
5

5 s at 6 xlr

10 s at 6 xlr

5 s at 6 xlr

19 s at 6 xlr

16 s at 6 xlr

29 s at 6 xlr

0,2

Inst

10 s at 6 xlr

14
(max
10 x
In)

8
0,2

0%
50%
100%

53

MCCBs, switch disconnectors


h400 - h630

Tripping curve

second

Tripping Time

minute

hour

MCCB h630 TM (400A)

Percent Rated Current IN

54

MCCBs, switch disconnectors


h400 - h630

Tripping curve
MCCB h630 LSI (250A and 400A)
3

hour

IR

Ip

1
40
30

tR

tp

Isd

20

tsd

minute

10

Ii

4
2
1
40
30

Tripping Time

20
10
6
4
2

second

1
0.6
0.4
0.2
0.1
0.06
0.04
0.02
0.01

8000

5000

4000

3000

2000

1500

1000

600

500

400

300

200

80

100
125

0.005

Percent Rated Current I R

Electronic trip unit setting (LSI)


MCCB h630 LSI (250A and 400A)
IR (A)
LTD Pick-up current

IR

Characteristics
Standard

xIn

0,4

0,5

0,63

0,8

0,9

0,95

No. 1

21

21

10

19

29

LTD

tR

(s)

11

STD

Isd

xIR

2,5

tsd

(s)

0,1

INST

Ii

xIR

14 (max : 13 x In)

IN

xIn

0 - 0,5 - 1

tN

(s)

tN=tR

200% x I R

Optional

600% x I R
5

10
0,2

55

MCCBs, switch disconnectors


h400 - h630

Tripping curve
MCCB h630 LSI (630A electronic)

3
hour

IR
Ip

1
40
30

tR

tp
Ig

20

Isd
tsd

minute

10

tg

Ii

4
2
1
40
30

Tripping Time

20
10
6
4
2

second

1
0.6
0.4
0.2
0.1
0.06
0.04
0.02
0.01

8000

5000

4000

3000

2000

1500

1000

600

500

400

300

200

80

100
125

0.005

Percent Rated Current IR

Electronic trip unit setting (LSI)


MCCB h630 LSI (630A electronic)
IR (A)
LTD Pick-up current

IR

Characteristics
Standard

LTD

tR

xIn

0,4

0,5

0,63

0,8

0,85

0,9

No. 1

(s)

21

21

10

16

11
200% x I R

STD

Optional

56

Isd

xIR

2,5

tsd

(s)

0,1

INST

Ii

xIR

14 (max : 13 x In)

IN

xIn

0 - 0,5 - 1

tN

(s)

tN=tR

600% x I R
5

8
0,2

0,95

MCCBs, switch disconnectors


h400 - h630

Thermal constraint curve (Let-through energy)


MCCB h630 (250A and 400A)

MCCB h630 (630A)

HNDup to 50kA
HEDup to 70kA

HNDup to 50kA
HEDup to 70kA

Current limiting curve (Let-through peak current)


MCCB h630 (250A and 400A)

HNDup to 50kA
HEDup to 70kA

MCCB h630 (630A)

HNDup to 50kA
HEDup to 70kA

57

MCCBs, switch disconnectors


h400 - h630

Dimensions
MCCBs
A

145

A
(mm)

B
(mm)

C
(mm)

3P

139,7

45

214

4P

184,7

45

214

45

102

260
228
C

45

32
97

Terminal covers front connected (for straight bars)

480

58

A
(mm)

B
(mm)

C
(mm)

D
(mm)

3P

180

126

94,5

93

4P

240

130

98

93

D
C

MCCBs, switch disconnectors


h400 - h630

Terminal covers for extended connections (spreaders)


A
(mm)

B
(mm)

C
(mm)

D
(mm)

3P

140

110

97

96

4P

185

114

99

98

Terminal covers for rear connections and collar terminal


A

C
D
B
(mm)

B
(mm)

C
(mm)

D
(mm)

3P

140

4,5

97

93

4P

185

4,5

97

93

B'
B

A
(mm)

Connection
Cable connection

1
13

25mm
Max.

Direct cable connection on terminal


Copper with conductor max. width: 25 mm

59

MCCBs, switch disconnectors


h400 - h630
Extended connection and spreaders

148
60

45

60

163
45 45

4P

30

14

14

30

349 mm

30

3P

4P
60

60
208

60

Rear connections

4P
3P
15

15

45

45

228 mm

45

56

15

6/8

96

Connection with end lugs

12
Max.

M 10

30 mm
Max.

60

MCCBs, switch disconnectors


h630

Accessories
Direct rotary handle
139,5

200

241,5
127

103

Extended rotary handle


139,5

180,5

23,8

241,5
127

200

27

Motor operator
139,5

220
123

Rated operating voltage


Operating current (A)

244
160

Starting current (A)

24-48V DC

ok

100-240V AC

ok

24-48V DC

4,3

100-240V AC

0,9

24-48V DC

9,8

100-240V AC

3,8

Operating method
Operating time (s)

spring charging
ON

0,1

OFF

1,5

RESET

1,5
100V, 0.1A, opening
voltage 48V, current 1mA

Operating switch rating


Power supply required
Dielectric properties

300 VA minimum
24-48V DC

1000 V AC

100-240V AC

1500 V AC

61

MCCBs, switch disconnectors


h400 - h630

Auxiliaries
Auxiliaries for MCCBs and free tripping switches

TRIP

Mounting combination for auxiliaries and releases

Shunt
Bobine
trip
mission

Auxiliary
Contact
contact
auxiliaire
AX

SH

AX

AL

SH / UV

Alarm
Signal
contact
dfaut
AL

62

UV

Undervoltage
Bobine
release
minimum
de tension

MCCBs, switch disconnectors


h800 - h1000

MCCBs

HN

HED

HCD

220/240 V
AC
(kA)

380/415 V
AC
(kA)

660/690 V
AC
(kA)

Icu

85

50

20

Ics

85

50

20

Icu

100

70

20

Ics

75

50

20

Icm

20

Icw

10 kA-0,3 s _

Electronic trip unit settings (LSI)


LSI
800/1000 A

2
B

1
Ir (A)
0,8

0,85

Characteristics
0,9

0,63
0,5
0,4

4
0,95

2
100 %

60 %

6
7

ON
OFF

PICK UP

TEST IN

L - Long delay - protection against overloads: Ir and tr settings


S - Short delay - protection against short circuits: Isd and tsd settings
I - Instantaneous - max. instantaneous threshold (< 10 ms) in case of
short circuit: 2,5 to 10 x Ir.

Adjustable IR
T

800 A
7
6
5
4
1
2

LSI

5,6,7
0.2S
0.1S

In A

1,2
2.5

3
5

4
10 14 xIR

Ir (x In)

Characteristics

LSI

Ir(A)

Im

0,4 - 1
In

2 - 10 Ir

0%
50%
100 %

Neutral
protection

1000 A

Long Time
Delay

Short Time
Delay

Ir (x In)

isd (xlr)

tr (s)

Inst

tsd (s)

Long Time
Delay

Short Time
Delay

li (xlr) Ir (x In) tr (s)

0,4

OK

OK

0,5

OK

OK

0,63

OK

OK

0,8

OK

OK

0,85

OK

0,9

OK

OK

0,95

OK

OK

OK

Inst

isd (xlr)

tsd (s)

li (xlr)

2,5

0,1

14
(max
10 x
In)

OK

11s at 2 xlr

21s at 2 xlr

2,5

0,1

5
10

14
(max
12 x
In)

11s at 2 xlr
21s at 2 xlr

5 s at 6 xlr

5 s at 6 xlr

10 s at 6 xlr

19 s at 6 xlr

16 s at 6 xlr

29 s at 6 xlr

0,2

10 s at 6 xlr

8
0,2

0%
50%
100%

63

MCCBs, switch disconnectors


h800 - h1000

Tripping curve
MCCB h1000 LSI (800A)

Electronic trip unit setting (LSI)


MCCBs 800A electronic
IR (A)
LTD Pick-up current

IR

Characteristics
Standard

LTD

tR

xIn

0,4

0,5

0,63

Optional

64

0,9

0,95

No. 1

(s)

21

21

10

16

11
200% x I R

STD

0,8

Isd

xIR

2,5

tsd

(s)

0,1

INST

Ii

xIR

14 (max : 10 x In)

NP

IN

xIn

0,8

tN

(s)

IN=tR

600% x I R
5

8
0,2

MCCBs, switch disconnectors


h800 - h1000

Tripping curve
MCCB h1000 LSI (1000A)

Electronic trip unit setting (LSI)


MCCBs 1000A electronic
IR (A)
LTD Pick-up current

IR

Characteristics
Standard

LTD

tR

xIn

0,4

0,5

0,63

0,8

0,9

0,95

No. 1

(s)

21

21

10

19

29

11
200% x I R

STD

Optional

600% x I R

Isd

xIR

2,5

10

tsd

(s)

0,1

INST

Ii

xIR

14 (max : 12 x In)

NP

IN

xIR

0,5 or 1 or NON (IN x 105% NT, IN x 120% T)

tN

(s)

IN=tR

0,2

65

MCCBs, switch disconnectors


h800 - h1000

Thermal constraint curve (Let-through energy)


MCCB h1000

Current limiting curve (Let-through peak current)


MCCB h1000

66

MCCBs, switch disconnectors


h800 - h1000

Dimensions
MCCBs
A
B

90

D
331
403

433
273

145

A
(mm)

B
(mm)

D
(mm)

3P

209,6

180

243

4P

279,6

250

243

A
(mm)

B
(mm)

C
(mm)

3P

215

130

99,5

4P

285

130

99,5

35
70

70

99,5

Terminal covers front connected (for straight bars)


C

534

534

67

MCCBs, switch disconnectors


h800 - h1000
Terminal covers for rear connections
C

A
(mm)

B
(mm)

C
(mm)

3P

206

18

102

4P

280

18

102

Connection
Extended connection

1
13

2
36
40

19

Direct cable connection on terminal


Copper with conductor max. width: 50 mm

68

MCCBs, switch disconnectors


h800 - h1000
Rear connections

90

58

12

58

12

122 mm

12

243,5 mm

288,5 mm

20 36

13

Connection with end lugs

19

69

MCCBs, switch disconnectors


h800 - h1000

Accessories
Direct rotary handle
115

200

127

103

Extended rotary handle


115
130

188
23,8

92

127

200

27

Motor operator
115
139,5

215

Rated operating
voltage

24-48V DC

ok

100-240V AC

ok

Operating method

spring charging

Power supply
required

300 VA minimum

160

118

24-48V DC

1000 V AC

100-240V AC

1500 V AC

Dielectric properties

70

MCCBs, switch disconnectors


h800 - h1000

Auxiliaries
Auxiliaries for MCCBs and free tripping switches

2
1
TRIP

Mounting combination for auxiliaries and releases


4P
3P

Auxiliary
contact
AX

SH

HXC 021 H
HXC 025 H

AX

AL

HXC 001 H
HXC 002 H
HXC 003 H
HXC 004 H
HXC 005 H

SH / UV

Alarm
contact
AL

HXC 024 H
HXC 026 H

Shunt
trip

UV

Undervoltage
HXC 011 H
release
HXC 012 H
HXC 013 H
HXC 014 H
HXC 015 H

71

MCCBs, switch disconnectors


h1250 - h1600

MCCBs

HNF

HEF

HCF

220/240 V
AC
(kA)

380/415 V
AC
(kA)

660/690 V
AC
(kA)

Icu

100

50

25

Ics

75

50

25

Icu

100

70

45

Ics

75

50

34

Icm

45 kA

Icw

20 kA-0,3 s

Electronic trip unit settings (LSI)

Ir (A)
0,8

0,9

Characteristics
0,95
1

0,63
0,5

3
2

0,4

ON

PICK UP

OFF

TEST IN

L - Long delay - protection against overloads: Ir and tr settings


S - Short delay - protection against short circuits: Isd and tsd settings
I - Instantaneous - max. instantaneous threshold (< 10 ms) in case of short
circuit: 2,5 to 10 x Ir.

In A
1250 - 1600 A
LSI

Ir (x In)

Characteristics

LSI

72

Ir(A)
0,4 - 1
In

Im
2,5 10 Ir

N
0%
50%
100 %

Neutral
protection

Long Time
Delay

Short Time Delay

Ir (x In)

isd (xlr)

tsd (s)

2,5

0,1

0,4

OK

0,5

OK

0,63

OK

0,8

OK

0,9

OK

0,95

OK

OK

tr (s)

11s at 2 xlr

21s at 2 xlr

5 s at 6 xlr

10 s at 6 xlr

19 s at 6 xlr

29 s at 6 xlr

0%
50%
100%

10
0,2

Inst
li (xlr)

14 (max 12 x
In)

MCCBs, switch disconnectors


h1250 - h1600

Tripping curve
MCCB h1600 LSI

hour

4
3
2
1
50
40
30

minute

20
10
8
6
5
4

1
50
40
30
20

time

10
8
6
5
4

second

3
2

1
0.8
0.6
0.5
0.4

4
5,6,7

0.3
0.2
0.1
0.08
0.06
0.05
0.04

1,2,3,4

0.03
0.02

7000
8000

6000

5000

4000

3000

2500

2000

1500

IR [%]

700
800
900
1000

600

500

250

200

150

80
90
100

0.005

125

0.01

Electronic trip unit setting (LSI)


MCCBs 1250A and 1600A electronic
IR (A)
LTD pick-up current

LTD
STD pick-up current

(S):

I1

0 x 0,8 - 0,85 - 0,9 - 0,95 - 1, no tripping till 105% of I1.


Tripping from 125%

(T1) I5 - 10 - 15 - 20 - 30 at I1 x 600% of the current (setting capacity */- 20%)

(A):

I2

I0 x 2 - 4 - 6 - 8 - 10 (setting capacity */- 15%)

(S):

T2

opening duration: 0,1 - 0,15 - 0,2 - 0,25 - 0,3


Total clering time is 50 ms. Initialisation time is 20ms before STD

INST

Ii

xIR

Adjustable from I0 x 3 to 12 (setting capacity */- 20%)

NP

IN

xIn

0,5 or 1 or NON (IN x 105% NT, IN x 120% T)

tN

(s)

IN=tR

STD

Optional

In x (0,4) 0,63 - 0,8 - 1


(A):

73

MCCBs, switch disconnectors


h1250 - h1600
Max. L et-thr ough E ner gy (I 2t) Char acter istics
HEF,
HNF
ThermalTYPE
constraint h1600
curve
(Let-through

energy)

MCCB h1600
g(

1010

Max. Let- through Energy (I2t) (x A2sec)

109

108

107

106

HNFup to 50kA
HEFup to 70kA

10

104 2
10

103
104
105
Prospective circuit current in RMS sym. (A)

106

Max. L et-thr
ough peak
cur r ent 3
Current limiting
curve
(Let-through
peak current)
MCCB h1600

h1600

TYPE

1000

Max. Let- through peak current (kA)

100

10

HNEup to 50kA
HEEup to 70kA

0.1
1

74

10

100

Prospective short- circuit current in RMS sym. (kA)

1000

MCCBs, switch disconnectors


h1250 - h1600

Dimensions
MCCBs
A
B

B
(mm)

3P

210

185

4P

280

255

70

95

476
541

570
370

11

70

A
(mm)

191

46
140

Connection
Connection with end lugs

19

75

MCCBs, switch disconnectors


h1250 - h1600

Accessories
Direct rotary handle

262

115
140

165

132

Extended rotary handle

258

115
140

128
23,8

165

200

27

Motor operator

210

24V DC

ok

200-230V AC

ok

Operating current (A)

200-230V AC

Starting current (A)

200-230V AC

3,2

260,5

Rated operating voltage


130

Operating method
173,5

Operating time (s)

spring charging
ON

0,06

OFF

RESET

Power supply required


Dielectric properties

76

300 VA minimum
24V DC

500 V AC

200-230V AC

1500 V AC

MCCBs, switch disconnectors


h1250 - h1600

Auxiliaries
Auxiliaries for MCCBs and free tripping switches

2
TRIP

Mounting combination for auxiliaries and releases


4P
3P

Auxiliary
contact
AX

SH

HXC 021 H
HXC 025 H

AX

AL

HXC 001 H
HXC 002 H
HXC 003 H
HXC 004 H
HXC 005 H

SH / UV

Alarm
contact
AL

HXC 024 H
HXC 026 H

Shunt
trip

UV

Undervoltage
HXC 011 H
release
HXC 012 H
HXC 013 H
HXC 014 H
HXC 015 H

77

Notes