You are on page 1of 3

InfoMile Solutions

Client:
Project:
Job Title:
Building:

S.V.POWER PVT LTD


500 TPH CFBC BOILER
Design of Footing
COMPRESSOR BUILDING

Reference

Grade of Concrete
Grade of Steel
Unit Weight of Soil
Safe Bearing Capacity of soil, SBC
Depth of Pedestal
Width of Pedestal
Length of Pedestal above footing
Length of Footing
Width of Footing
Area of Footing
Depth of Footing
Effective Cover to Steel
Effective depth
Moment of inertia about x,

15.09.2008
AKV
Rev:

Description of Problem

X
Z

Date:
Done by:
Checked by:

Values Units
M25
Fe500

Moment of inertia about z,


Weight of soil above footing
Weight of Footing
GOVERNING LOAD CASES
NORMAL LOADS(DL+IL)
Pi
Mxi
Mzi
DL+IL+EQX
Pii
Mxii
Mzii
DL+IL+EQZ
Piii
Mxiii
Mziii

fck
fy

lpz
bpx
hp
Lz
Bx
A
D
cc
d
Zxx
Zzz
Ws
Wf

NORMAL LOADS(DL+IL)
Pi/A
Mxi/Zxx
Mzi/Zzz

25.00
500.00
18.00
600.00
0.60
0.30
2.70
1.50
1.20
1.80
0.40
0.06
0.34
0.45

MPa
MPa
kN
kN/m2
m
m
m
m
m
m2
m
m
m
m3
0.36 m3
78.73 kN
18.00 kN

369.82 kN
8.53 kNm
5.88 kNm
392.16 kN
7.94 kNm
36.04 kNm
388.82 kN
8.02 kNm
30.50 kNm

259.20 kN/m2
18.96 kN/m2
16.33 kN/m2

Pmaxi
Pmini
SINCE Pmaxi<SBC, SIZE PROVIDED IS SAFE
DL+IL+EQX
Pii/A
Mxii/Zxx
Mzii/Zzz

294.49 kN/m2
223.91 kN/m2

Pmaxii
Pminii
SINCE Pmaxii<1.25SBC, SIZE PROVIDED IS SAFE

389.35 kN/m2
153.86 kN/m2

DL+IL+EQZ
Piii/A
Mxiii/Zxx
Mziii/Zzz
Pmaxiii
Pminiii
SINCE Pmaxiii<1.25SBC, SIZE PROVIDED IS SAFE

file:///var/www/apps/conversion/tmp/scratch_2/268362260.xls

271.61 kN/m2
17.64 kN/m2
100.10 kN/m2

269.75 kN/m2
17.82 kN/m2
84.73 kN/m2
372.30 kN/m2
167.20 kN/m2

InfoMile Solutions
Client:
Project:
Job Title:
Building:

S.V.POWER PVT LTD


500 TPH CFBC BOILER
Design of Footing
COMPRESSOR BUILDING

Reference

Date:
Done by:
Checked by:

15.09.2008
AKV
Rev:

Description of Problem

Values Units
371.71

Mx
X
Mz
Z

311.65
1.50

0.6
0.30

1.20
171.50

251.93

287.57

274.21

SP16, Design aids to


IS:456-2000

cl. 26.3.3.b.1 & 2 of


IS:456-2000

SP16, Design aids to


IS:456-2000

Cl. 26.3.3.b.1 & 2 of


IS:456-2000

Table 19 of IS:456-2000

Moments at the face of Pedestal:


Moment about X-direction
Mxu/bd2
(Mxu = 1.5*Mx)
Percent of Steel required
Area of steel required/m
Provided Diameter of bar # 12
Spacing required
Check for max. spacing
Provide #12mm bars @ 200mm
Moment about Z-direction
Mzu/bd2
(Mzu = 1.5*Mz)
Percent of Steelrequired
Area of steel required/m
Provided Diameter of bar # 12
Spacing required
Check for max. spacing
Provide #12mm bars @ 200mm
Check for Shear:
Pr. at d diatance from face
284.30
Shear For both directions
29.49
Maximum Shear Force
v = Vu/bd
(Vu = 1.5*V)
Available steel Area
Percent of steel provided
For the above % of steel
Design Shear strength

Since c > v, Safe One Way Shear

file:///var/www/apps/conversion/tmp/scratch_2/268362260.xls

Mx
pt
Ast

Mz
pt
Ast

kN/m2
kN
V
v

35.61 kNm
0.46 MPa
0.12 %
408.00 mm2
4.00
250.00 mm
250.00 mm

28.67
0.37
0.12
408.00
4.00
250.00
250.00

kNm
MPa
%
mm2

357.03
33.07
33.07
0.15
565.49
0.17

kN/m2
kN
kN
MPa
mm2
%

mm
mm

0.35 MPa

InfoMile Solutions
Client:
Project:
Job Title:
Building:

S.V.POWER PVT LTD


500 TPH CFBC BOILER
Design of Footing
COMPRESSOR BUILDING

Reference

Date:
Done by:
Checked by:

Rev:

Description of Problem
Punching Shear
Punching Resistance
Punching resistance is

15.09.2008
AKV
0

Values Units
>

895.33 kN
392.16 kN

Hence Safe in Punching Shear


Cl. 26.5.2.1 of IS:456-2000

Shrinkage reinforcement at top:


Minimum Area of steel
Provided Diameter of bar # 10
Spacing required
Provide #10mm bars @ 250mm
Final Results:
Provide Size of the Footing: 1200 x 1500 x 400mm
Bottom Main reinforcement about X-Direction:
Provide #12mm bars @ 200 c/c
Bottom Main reinforcementabout Z-Direction:
Provide #12mm bars @ 200 c/c
Shrinkage reinforcement at top:
Provide #10mm bars @ 250 c/c

file:///var/www/apps/conversion/tmp/scratch_2/268362260.xls

408.00 mm2
78.54 mm2
192.50 mm

You might also like