SWITCH ON- Input block

B
2

I
7

1. Switch On the input breaker (A)


2. Check Input Mains (2)
3. Precharge; phase R SCRs partialization (B)
4. Chek Rectifier Voltage at the end of precharge (67)

5. Switch On SCRs of phases R, S and T (B)


6. Switch On rectifier (F)
7. Switch On Battery Chargers, after about
60seconds (H-I)

MASK CONTROL
Tolerance
plus
Max Voltage
Max input value

Mask
Mask

2.5V

Vin/Vout

AC signal

Mask Offset

Disable time at
zero crossing

T
Max Voltage
Tolerance minus

Input_Mask_Min_Level
Input_Mask_Max_Level
Point_Out_Of_Msk
65%
Max diference of input rectifier phase current:
Setting parameters in ASSIST:

-load>12,5% nom
-Switch-off rectifier after 100ms

2. SWITCH ON- Output block

L
9

11
7

1.
2.
3.
4.
5.

Check rectifier Voltage (6-7)


Switch On Inverter (L)
Check Inverter Voltage (9)
Switch On Contactor (M)
Check Output Voltage (11)

3. MAINS FAULT

B C
2

H
F

G
I

1. Check Mains Voltage (2)


2.
3.
4.
5.

6. Switch On Rectifier (F), with changing of


working method,from Rectifier to Boost
Switch Off Input SCRs (B) and Rectifier
7. Switch Off Battery Charger (H-I)
Check Battery Voltage (6-3 and 7-4)
8. Wait of 23ms
Wait of 2ms
9. Switch On 4th Leg (G)
Switch On battery SCRs (C and/or D) depending if 10. Force battery operation for at least 10sec.
Battery Voltage is OK.

4. BATTERY OPERATION; Negative battery block fault

3
6

C
F
D
4

1.
2.
3.
4.
5.

Check Battery Voltage (6-3 and 7-4)


Switch Off negative battery SCRs (D)
Switch Off Rectifier (F)
Wait of 2ms
Switch On Rectifier (F), with changing of working
method (F).

5. BATTERY TO MAINS COMMUTATION

B C
2

H
F

1.
2.
3.
4.
5.
6.

Check Mains Voltage (2)


Switch Off Battery SCRs (C-D)
Switch OFF Rectifier (F)
Wait 2ms
Switch On input SCRs
Switch On Rectifier (F), with changing of working
method (F), from Boost to Rectifier

7. Switch Off 4th Leg (G)


8. Wait 22ms
9. Switch On Battery Charger (H-I)

6. INVERTER TO AUX. MAINS COMMUTATION


(Inrush current)

L
1

O
M

11

1.
2.
3.
4.
5.
6.

Check Output Voltage (11)


Switch Off Inverter (L)
Check Auxiliary Mains (1)
Switch On By-Pass SCRs (O)
Wait 100ms
Switch Off Contactor

7. Forcing By-Pass state for 2sec (O)

7. AUXILIARY MAINS TO INVERTER COMMUTATION

O
9

1. Switch On Inverter (L)


2. Wait 7 ms, than Check Inverter Voltage (9)
3. Variation of Inverter Voltage Vinv=Vmains+10V
(L)
4. Check syncronism Inverter/Mains
5. Wait 1 sec, than Switch On contactor ((M)
6. Overlap Mains/Inverter of XX ms

7. Switch Off Auxiliary Mains SCRs(O)


8. Default Inverter Voltage (L)

AUXILIARY MAINS TO INVERTER COMMUTATION

Cde
K1
Contactor
CMD

Typique
12ms

0
10ms

Fermeture
K1
Contactordeclosing
(puissance)

15ms

0
Cde
thyristors
By-Pass
CMD
by-pass

Cde Elvation
tension onduleur

Mains following CMD

0
-1s
-20ms
0

+22ms
+20ms

+25ms
+32ms

Mask Enable

8. ECO-MODE: Auxiliary Mains fault

L
9

11

1.
2.
3.
4.
5.

Check Output Voltage (11)


Switch OFF Auxiliary Mains SCRs (O)
Switch On Inverter (L)
Wait 7 ms, than Check Inverter Voltage (9)
Switch On contactor ((M)

9. NORMAL MODE TO ECO MODE COMMUTATION

L
1

1. On Mimic Panel, set Eco-Mode command


(Operator)
2. Check Aux. Mains Voltage (1)
3. Switch Off Inverter (L)
4. Switch On Aux. Mains SCRs (O)
5. Wait 100ms
6. Switch Off Inverter Contactor

10. MANUAL BY-PASS

L
1

1. On Mimic Panel, set Eco-Mode command


(Operator)
2. Check Aux. Mains Voltage (1)
3. Switch Off Inverter (L)

4. Switch On Aux. Mains SCRs (O)

5. Wait 100ms
6. Switch Off Inverter Contactor (M)
7. Move the Output Breaker (N) in position 2
(operator); in any case, the micro-switch of
Output Breaker (N) force the Inverter to Mains
commutation.

11. TRIES
In case of fault or very critical external conditions, the UPS change logic to stop the appropriate power block.
Sometimes is allowed to UPS to do some tries to restart; the main cases are:
PROBLEM

Precharge failure
Max Vboost
Min Vboost
Inverter to Aux. Mains commutation
Inverter Starting failure

N OF TRIES
3
3
3
5
3

12. INVERTER AND RECTIFIER FREQUENCY


Inverter and Rectifier dont run with fix PWM frequency.
This fact permit to UPS to work in very strong and critical conditions, presents in same moment, keeping
reduced the losses of IGBT and its juntion temperature.
With low load the PWM increase reducing noise.
PWM frequency is always the same both for Inverter and Rectifier, even if the threshold of commutations are
different. The worse case (Inverter or Rectifier) force the lower frequency.
PWM frequency depends by:
-Inverter/Rectifier Current
-Heat sink temperature
-Rectifier operation: Mains voltage value, one or two battery blocks.
PWM frequency:
-15kHz
-12,5kHz
-10kHz
-8kHz
In nominal condition of input mains, at 35C, the link between load and frequency is the following (exept for
40kVA):
PWM frequency
15kHz
12,5kHz
10kHz
8kHz

Histeresys:10%

% Load R
070
70120
120150
>150

% Load RCD
060
60100
100125
>125