Introduction
Trench is a recognized world leader in the
design and manufacture of high voltage
equipment for application on electric
utility and high energy industrial systems.
As part of Trench's product scope, the
Company produces a diversified range of
Instrument Transformers which are installed
on 69-800 kV electrical systems.
Instrument Transformers include:
Voltage (Potential) Transformers
(both inductive and capacitive
type), Current Transformers and
Combined Instrument Transformers
(voltage and current transformer in
one unit).
Voltage Transformers must convert
transmission class voltages to standardized low and easily measurable
values, which will be used for metering, protection and control of
the high voltage system. As such,
the need for accurate and reliable
voltage transformation is essential.
Fig. 1
Type UT5D-350,
two bushing voltage
transformer
Features
Fig. 2
Sectioned view of a typical
UT5 voltage transformer
VoltageTransformer
Catalog Numbering System
Type
Suffix
UT5-550 - 115
System Voltage
Nominal system voltage (in kV)
BIL Rating
Basic lightning impulse insulation level (in kV)
Voltage transformer catalog numbers consist of a type
(number) followed by a suffix.
The TYPE number consists of the transformer Series designation followed by the BIL Rating (in kV). In this example,
UT5-550.
Series
UT5
Voltage
Transformer
Selection
(60 Hz)
Series
UT5
UT5H
UT5D
(TwoBushing)
UT5H
UT5D
BIL
(kV)
System
Voltage
(kV)
Rated
Primary
(Volts)
Voltage Ratio (1
Both
Secondaries
Rated
Secondary
(Volts) (3
Accuracy
and Burden
Rating
Burden
Rating
(VA)
Catalog
Number
150
200
250
350
350
550
650
750
900
1050
25
34.5
46
60
69
115
138
161
230
230
14400
20125
27600
34500
40250
69000
80500
92000
138000
138000
120/200:1
175/300:1
240/400:1
300/500:1
350/600:1
600/1000:1
700/1200:1
800/1400:1
1200/2000:1
1200/2000:1
120/72
115/67.08
115/69
115/69
115/67.08
115/69
115/67.08
115/65.71
115/69
115/69
0.3Z
0.3ZZ
0.3ZZ
0.3ZZ (2)
0.3ZZ
0.3ZZ
0.3ZZ
0.3ZZ
0.3ZZ
0.3ZZ
4000
5000
5000
4500
5000
7000
6000
7500
7500
7500
UT5-150-25
UT5-200-35
UT5-250-46
UT5-350-60
UT5-350-69
UT5-550-115
UT5-650-138
UT5-750-161
UT5-900-230
UT5-1050-230
150
200
250
350
350
550
650
750
900
1050
25
34.5
46
60
69
115
138
161
230
230
14400
20125
27600
34500
40250
69000
80500
92000
138000
138000
120/200:1
175/300:1
240/400:
300/500:1
350/600:1
600/1000:1
700/1200:1
800/1400:1
1200/2000:1
1200/2000:1
120/72
115/67.08
115/69
115/69
115/67.08
115/69
115/67.08
115/65.71
115/69
115/69
0.15Y
0.15Y
0.15Y
0.15Y
0.15Y
0.15Y
0.15Y
0.15Y
0.15Y
0.15Y
4000
5000
5000
4500
5000
7000
6000
7500
7500
7500
UT5H-150-25
UT5H-200-35
UT5H-250-46
UT5H-350-60
UT5H-350-69
UT5H-550-115
UT5H-650-138
UT5H-750-161
UT5H-900-230
UT5H-1050-230
200
200
34.5
34.5
34500
20125
520/300:1
300/175:1
66.4/115
67.08/115
0.3ZZ
0.3Z
5000
5000
UT5D-200-35
UT5D-200-35
250
250
46
46
46000
27600
693/400:1
400/240:1
66.4/115
69/115
0.3ZZ
0.3Z
6000
6000
UT5D-250-46
UT5D-250-46
350
350
69
69
69000
40250
1039/600:1
600/350:1
66.4/115
67.08/115
0.3ZZ
0.3Z
6000
6000
UT5D-350-69
UT5D-350-69
1) Voltage transformers are single-bushing ANSI C57.13 group 3 for connection phase-to-ground on solidly grounded Wye systems
(except for Type UT5D, which is ANSI C57.13 group 2 with secondary and tertiary ratings as shown).
2) 0.6 ZZ on tap of secondary and tertiary windings.
3) For voltage transformers with three secondaries, consult factory.
4) Contact factory for CSA standard ratings and 50 Hz application
Accuracy Selection
Series
UT5
UT5H (3)
UT5D
Accuracy Rating
90% through 110%
of Nominal Voltage
0.3%
0.15% (4)
0.3%
0,W,X,M,Y,Z,ZZ (2)
0,W,X,M,Y
0,W,X,M,Y,Z,ZZ (5)
1) The accuracy rating is based on the sum of the burdens on both windings not
exceeding the values listed above.
2) On the UT5-150-25, the burden rating is 0, W, X, M, Y and Z.
3) Contact factory for additional information on Hi-ACC High Accuracy transformers.
4) The 0.15% parallelogram is constructed using the same principles as the 0.3% parallelogram in accordance with ANSI Standard C57.13, except the maximum phase angle
and ratio correction factors of the 0.15% parallelogram are half those of the 0.3%
parallelogram.
5) The listed burden rating is for line-to-line application only. Burdens for line-to-ground
application, within the 0.3% accuracy rating, are 0,W,X,M,Y,and Z.
Series
UT5
UT5H
UT5D
(Two-bushing)
BIL
(kV)
Nominal
System Voltage
(kV)
Creepage
Distance
In./mm
Strike
Distance
In./mm
Rated
Primary
(Volts)
Induced
Voltage
(kV)
150
200
250
350
350
550
650
750
900
1050
25
34.5
46
60
69
115
138
161
230
230
34/864
34/864
52/1321
52/1321
52/1321
92/2337
112/2845
169/4293
169/4293
214/5436
13/330
13/330
24/610
24/610
24/610
40/1016
48/1219
65/1651
65/1651
84/2134
14400
20125
27600
34500
40250
69000
80500
92000
138000
138000
50
70
95
140
140
230
275
325
395
460
150
200
250
350
350
550
650
750
900
1050
25
34.5
46
60
69
115
138
161
230
230
34/864
34/864
52/1321
52/1321
52/1321
92/2337
112/2845
169/4293
169/4293
214/5436
13/330
13/330
24/610
24/610
24/610
40/1016
48/1219
65/1651
65/1651
84/2134
14400
20125
27600
34500
40250
69000
80500
92000
138000
138000
50
70
95
140
140
230
275
325
395
460
200
250
350
34.5
46
69
34/864
52/1321
52/1321
13/330
24/610
24/610
34500/20125
46000/27600
69000/40250
70
95
140
Series
Type
BIL(kV)
150
200
250
350
UT5 and
UT5H
550
650
750
900
1050
52.81
(1341)
52.81
(1341)
63.68
(1617)
63.68
(1617)
85.31
(2167)
93.37
(2372)
119.38
(3032)
119.38
(3032)
137.81
(3526)
52.19
(1326)
52.19
(1326)
63.06
(1602)
63.06
(1602)
84.69
(2151)
92.75
(2356)
118.75
(3016)
118.75
(3016)
137.19
(3510)
13.40
(340)
13.40
(340)
24.21
(615)
24.21
(615)
40.34
(1025)
48.34
(1228)
65.28
(1658)
65.28
(1658)
83.65
(2123)
14.00
(356)
14.00
(356)
14.00
(356)
14.00
(356)
19.50
(3035)
19.50
(3035)
24.63
(626)
24.63
(626)
24.63
(626)
20.75
(527)
20.75
(527)
20.75
(527)
20.75
(527)
22.25
(564)
22.25
(565)
27.50
(699)
27.50
(699)
27.50
(699)
20.36
(517)
20.36
(517)
20.36
(517)
20.36
(517)
23.00
(584)
23.00
(584)
28.12
(714)
28.12
(714)
28.12
(714)
23.50
(597)
23.50
(597)
23.50
(597)
23.50
(597)
25.00
(635)
25.00
(635)
30.25
(768)
30.25
(768)
30.25
(768)
16.56
(421)
16.56
(421)
16.56
(421)
16.56
(421)
19.00
(483)
19.00
(483)
25.00
(635)
25.00
(635)
25.00
(635)
Type
Series BIL(kV)
200
58
(1473)
UT5D 250 67.88
(1724)
350 67.88
(1724)
18
45.4
19.7 48.3
34
370
(457) (1153) (500) (1227) (860) (168)
18
54.4
28.7 58.2
52
420
(457) (1382) (729) (1478) (1321) (191)
18
54.4
28.7 58.2
52
420
(457) (1382) (729) (1478) (1321) (191)
18
(68)
20
(76)
20
(76)
Standard Equipment
Aluminum flat pad primary
terminal and ground terminal
Trench Limited
Coil Product Division
71 Maybrook Drive, Scarborough
Ontario, Canada M1V 4B6
Phone (416) 298-8108
Fax
(416) 298-2209
E-Mail sales@ca.trenchgroup.com
www.trenchgroup.com
Trench Limited
Instrument Transformer Division
390 Midwest Road, Scarborough
Ontario, Canada M1P 3B5
Phone (416) 751-8570
Fax
(416) 751-6952
E-Mail sales@ca.trenchgroup.com
Trench France S.A.
16, rue du Gnral Cassagnou
B.P. 70
F - 68302 St-Louis Cedex/France
Phone +33.3.89 70 23 23
Fax
+33.3.89 67 26 63
E-Mail sales@trench-france.com
Trench Germany GmbH
Nrnberger Strasse 199
96050 Bamberg/Germany
Phone +49.951.1803-0
Fax
+49.951.1803-224
E-Mail sales@trench.de
Trench Switzerland AG
Lehenmattstrasse 353
CH - 4028 Basel/Switzerland
Phone +41.61.315 51 11
Fax
+41.61.315 59 00
E-Mail sales@trench.ch
Subject to change without notice
04.2000
E 211.41