You are on page 1of 17

TENDER DOCUMENT

TENDER No.: NRO/CON/MANIKTALA-PG-HVAC/492


FOR

HVAC SYSTEM FOR


EMPLOYEES STATE INSURANCE (ESI)
HOSPITAL AND PG COLLEGE AT MANIKTALA, KOLKATA

VOLUME III
PRICE BID

ENGINEERING PROJECTS (INDIA) LIMITED


(A GOVT. OF INDIA ENTERPRISE)

Core-3, Scope Complex, 7, Institutional Area,


Lodhi Road, New Delhi-110003
TEL NO: 011-24361666, 24366226 FAX NO. 011- 24363426

Name Of Work :

HVAC System for Employees State Insurance (ESI) Hospital and PG College of Maniktala,Kolkata

NIT:
PRICE SCHEDULE
SI. No.

DESCRIPTION

HVAC System

ESTIMATED COST
(Rs.)
3

TO BE QUOTED BY TENDERER
Amount ( -) Below / (+) Above
5= (3 x 4 )
In words
In figures
In words

% (-) Below / (+) Above


4
In figures

7,29,77,607

TENDER VALUE

Total Amount( Rs.)


3+5

Project :HVAC System for ESI Hospital and PG College at Maniktala -West Bengal
Bill of Quantities (BOQ) of the HVAC works :
Sr.No.

Description

Qty

Unit

Rate

Nos.

6500000

Amount

AIR COOLED SCREW TYPE WATER CHILLING MACHINES :


1

Supply,installation,testing and commissioning of 290 TR


actual cooling capacity water chilling machines each
comprising of screw compressors,motors,autotransformers,
starters,air cooled condensers with fans,insulated chillers
,flow switch,vibration isolators,integral refrigerant piping and
wiring accessories as per specifications,automatic capacity
safety,controls centralised microprocessor control panel and
all mounted on a steel frame.
Motor shall be suitable for 415V10%V,3ph/50Hz AC power
supply.Starting current of the compressor shall not exceed
2 times the full load current.
chilled water temperatures will be as given below.
a. Chilled Water IN to chilling machine:54 Deg F(12.2 Deg C)
b. Chilled Water OUT from Chilling Machine :44 Deg F(6.7 Deg C)
c Fouling Factor : 0.0005
Cost of chiller card for conection to BMS shall be included.
The refrigerant used shall be ozone friendly - R-134 A .Initial
charge of refrigerant and oil shall be supplied with the chilling
machine. Air In temperature to condenser is 37.8DB/28.3WB.
The maximum IKW/TR at actual conditions shall not exceed 1.26
(compressor s+ condenser fans + heaters)
Water Chilling Machine as described above and in
the specifications and complete in all respects.

26000000

Chilled water and Hot water Pumps :


2

Supply,installation,testing and commissioning


of end suction split casing type water pump sets
factory mounted on a common base with electric
motor for recirculation of water for the central
air-conditioning system.All pumps shall be aligned.
The pump motor shall be suitable for 415_+10% V,
50cycles, 3 phase power supply.The qouted rates
shall be inclusive of insulation and cladding.

ESIC Hospital and PGI at Maniktala

Project :HVAC System for ESI Hospital and PG College at Maniktala -West Bengal
Bill of Quantities (BOQ) of the HVAC works :
Pump performance characteristics shall be as
follows as per drawings and specifications.
a) Chilled water Primary Pumps
system :
Water flow Rate : 700 US GPM
Head
: 18 m
( Including one standby)
b) Chilled water secondary Pumps with VFDs
system :
Water flow Rate : 700 US GPM
Head
: 18 m
( Including one standby)
c) Hot Water Pumps for winter Heating :
Water Flow Rate : 300 US GPM
Head
: 24 m
( Including one standby)

Nos.

160000

640000

Nos.

280000

1120000

Nos.

153000

459000

No

445000

890000

Hot Water Generators :


3

Supply,installation,testing and commissioning of electrical


Hot water Generator equipped with sufficient no.of flanges
and electric immersion heaters.The pressure Vessel shall
be constructed as per ASME standards and insulated on all
sides with 2 layers of 50 mm thick fiberglass with 28 guage
Aluminium cladding as per specifications. The hot water
generator shall be equipped with all automatic and safety
controls such as manual reset , high temperature water
outlet,step controller and recycling relay,on/off switch type
thermostat,pilot light, low water cut off and other controls
as per manufacturers recommendations.All basic controls
and terminals shall be located in an integral control cabinet
factory wired and tested. The hot water generator shall be
suitable for 41510%volts/50 cycles,3phase power supply
The entire hot water generator shall be factory assembled
and tested requiring only connection to services of 300 KW
Water in - 110 Deg
Water out - 120 Deg
Floor Mounted AHUs :

ESIC Hospital and PGI at Maniktala

Project :HVAC System for ESI Hospital and PG College at Maniktala -West Bengal
Bill of Quantities (BOQ) of the HVAC works :
4

a)
b)
c)
d)
e)
f)
g)
h)
I)
j)
k)
l)
m)
n)

Supply,installation,testing and commissioning of sheet metal


sectionalised construction draw thru type in Double skin construction
with thermal break profile.Each Air Hndling Units shall be with filter
section with prefilters and microvee filters,chilled water cooling
coil of copper tube & Al.Fins construction,squirrel cage induction
motor,centrifugal fan, mixing chamber for connecting the outside
fresh air to AHUs,belt drive and vibration isolators.Coil size shall be
selected for a max.face velocity of 500 FPM and
static shall be 50 mm.Motor shall be suitable for
415 V/3ph/50Hz AC supply. Air moving capacities
shall be as follows as per drawings and specifications.
22,700 cfm with 4 row cooling coil
19,000 cfm with 4 row cooling coil
18,200 cfm with 4 row cooling coil
16,500 cfm with 4 row cooling coil
15,700 cfm with 4 row cooling coil
15,500 cfm with 4 row cooling coil
14,750 cfm with 4 row cooling coil
14,000 cfm with 4 row cooling coil
13,500 cfm with 4 row cooling coil
13,000 cfm with 4 row cooling coil
12,700 cfm with 4 row cooling coil
12,250 cfm with 4 row cooling coil
12,000 cfm with 4 row cooling coil
11,150 cfm with 4 row cooling coil
(All AHUs shall be with thermal break profile)
Ceiling Suspended TFA Units :

Supply,installation,testing and commissioning of sheet


metal construction draw thru type Air Handling Units in Double
Skin construction. Each Air Hndling Units shall be with filter
section with prefilters ,chilled water cooling coils of copper
tube & Al.Fins construction,squirrel cage induction motor
centrifugal fan, belt drive and vibration isolators.Coil size shall
be selected for a maximum face velocity of 500 FPM and
static shall be 40 mm.Motor shall be suitable for 415V/3ph/50hz
Air moving capacities shall be as given below as per drawings and
specifications.
a) 2,200 cfm with 6 row cooling coil
b) 1,750 cfm with 6 row cooling coil

2
1
2
2
1
1
1
1
3
1
1
1
1
1

No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.

650000
630000
630000
520000
500000
500000
500000
475000
475000
425000
425000
400000
400000
360000

1300000
630000
1260000
1040000
500000
500000
500000
475000
1425000
425000
425000
400000
400000
360000

1
1

No.
No.

75000
60000

75000
60000

ESIC Hospital and PGI at Maniktala

Project :HVAC System for ESI Hospital and PG College at Maniktala -West Bengal
Bill of Quantities (BOQ) of the HVAC works :
(All AHUs shall be with thermal break profile)
Ceiling Suspended AHUs for OTs:
6

a)
b)
c)
d)
7

Supply,installation,testing and commissioning of sheet metal


construction draw thru type AHUs in double skin construction
Each AHU shall have filter section with prefilters, microvee filters
,HEPA filters,3# 3KW strip heaters,mixing chamber,chilled water cooling
coil of copper tube & Al.Fins construction,squirrel cage induction
motor,centrifugal fan,belt drive,vibration isolators etc.Coil size of the
of these air handling units shall be selected for a maximum face
velocity of 500 FPM and static pressure shall be 125 mm WG
The air moving capacities shall be as detailed below.These units
shall be in accordance with drawings and specifications.
2,400 cfm with 6 row cooling coil
2,200 cfm with 6 row cooling coil
2,000 cfm with 6 row cooling coil
1,000 cfm with 6 row cooling coil
(All AHUs shall be with thermal break profile)
Supply,installation,testing and commissioning of Heat exchanger
units(HRV) in double skin construction,constructed out of extruded
Aluminium section frame with puf insulated panels,blowers,plate
to plate type Aluminium heat exchanger and filters.The unit will
have two separate passages one for supply of fresh air and the other
for exhaust of cool air from the rooms after the revovery of energy.
Efficiency of these heat exchangers shall be 60-65%.The plate
to plate heat exchanger shall be rigid thermally bonded seamless
Aluminium channels separated by extruded aluminium spacers of
the 2000 cmh capacity.The unit shall be complete with its panels.
as per drawings and specifications.(For Operation Theatres only)

1
1
9
1

No.
No.
No.
No.

175000
163000
150000
110000

175000
163000
1350000
110000

11

Nos.

155000

1705000

R.O.
R.O.

No.
No.

22000
28000

0
0

Fan Coil Units :


8

Supply,installation,testing and commissioning of


horizontal hide away type fan coil unit complete
with fan ,fan motor,cooling coil,filters, 2-way motarised
with snap acting thermostat and ball valve set etc.and
complete as per specifications and drawings of below capacities.
a) 1.5 TR (600 cfm)
b) 2.0 TR (800 cfm)

ESIC Hospital and PGI at Maniktala

Project :HVAC System for ESI Hospital and PG College at Maniktala -West Bengal
Bill of Quantities (BOQ) of the HVAC works :
Hydronic Type chilled water Cassette Units :
9

a)
b)
c)
d)

Supply,installation,testing and commissioning of hydronic type


chilled water cassette units complete with fan, fan motor,decorative
grilles/panel,drain pump,cooling coil,filters, 2-way motarised
valve with snap acting thermostat and ball valve set etc.and complete
as per specifications and drawings of below capacities.
1.00 TR (630 cmh)
1.62 TR (1000 cmh)
1.98 TR (1250 cmh)
2.50 TR (1600 cmh)

29
37
15
1

No.
No.
No.
No.

30000
40000
45000
50000

870000
1480000
675000
50000

2
2
8

Nos
Nos
Nos

130000
90000
70000

260000
180000
560000

5
13
3
1
1

No.
Nos.
Nos.
Nos.
Nos.

20000
14000
14500
13000
11000

100000
182000
43500
13000
11000

Pressurisation Fan sections :


10

Supply,installation,testing and commissioning


of DIDW centrifugal fan section with motor,drives
set mounting frame,GI sheet casing of 16 Guage
complete as per specifications and drawings of
below capacities for staircase pressurisation.
a) 15000 cfm at 15 mm static
b) 8000 cfm at 15 mm static
b) 6000 cfm at 15 mm static
Ducted Inline Type Exhaust fans :

11

a)
b)
c)
d)
e)

Supply,installation,testing and commissioning of ducted


Inline type exhaust fans complete with motor ,fan,
exhaust Louvers as per drawings and specifications.
of following sizes :
1000 cfm at 20mm static
800 cfm at 20 mm static
900 cfm at 20 mm static
450 cfm at 20 mm static
250 cfm at 20 mm static
Propeller Type Exhaust fans :

12

Supply,installation,testing and commissioning of propeller


type free discharge exhaust fans complete with motor ,
fan ,exhaust Louvers as per drawings and specifications.

ESIC Hospital and PGI at Maniktala

Project :HVAC System for ESI Hospital and PG College at Maniktala -West Bengal
Bill of Quantities (BOQ) of the HVAC works :
of following sizes :
a) 225 mm dia (free discharge)
13 Supply,installation,testing and commissioning
of decorative High Wall type split units complete
with indoor and outdoor units,refrigerant pipes
with insulation, stablisers,ms frame for outdoor
units interconnecting all wiring,cabling and
complete in all respects as per drawings and
specifications. (2 TR cooling capacity)
14 Supply,installation,testing and commissioning
of decorative High Wall type split units complete
with indoor and outdoor units,refrigerant pipes
with insulation, stablisers,ms frame for outdoor
units interconnecting all wiring,cabling and
complete in all respects as per drawings and
specifications.(1.5 TR cooling capacity)

15

No.

3267

49005

R.O.

Nos.

41440

R.O.

Nos.

36720

Main A/C Panel


15 Supply,installation,testing and commissioning of the
following integrated, cubicle type dead front, extensible
sheet steel control panels,anchoring the panel to the
foundation.The panel shall be suitable for 690 Volts/
3PH/50Hz. Quoted price shall include rubber mats etc.The
Panel shall have separate compartment for Bus bar and cable
alleys.The following components and accessories shall
be mounted within each control panel.
a)
I)

ii)
iii)
iv)

v)

INCOMING FROM PANEL


One No. 2000 Amps Electrically operated draw out type 4 pole
Air Circuit Breaker (ACB) with 6 NO & 6 NC contacts
1 set
and complete with the following :
0-500 Volts digital type voltmeter with selector
switch
1 set
0-2000 Amps digital type ammetre with 2000/5
Amps CTs and selector switches.
1 set
Over voltage tripping mechanism for persistent voltage
exceeding 110% of the rated voltage for more than five
minutes.
1 set
CT operated overcurrent and earth fault relay (IDMT) with

ESIC Hospital and PGI at Maniktala

Project :HVAC System for ESI Hospital and PG College at Maniktala -West Bengal
Bill of Quantities (BOQ) of the HVAC works :
vi)
b)

ii)

iii)

iv)

vii)

f)
g)

CTs, 1600/5A, SP 10 protection class 15 VA burden.


1 set
Phase indicating Lamps with toggle switches & control fuses
1 set
BUS BARS :
Aluminium bus bar with heat shrikable sleaves rated at 2000
amps for three phase and neutral phase.Bus bar shall have
maximum current density of 1 amp per sq.mm and the neutral
phase bus bar of not less than 50% capacity.
2 sets
OUTGOINGS FROM BUSBAR :
4 nos. 1000 Amps. motorised TP MCCB (50KA) with neutral link
and 6 NO & 6 NC auxilliary contacts on outgoing feeders
for 290 TR air cooled chilling unit compressor motors. The
compartment shall shall contain CT operated ammeter of
0-1000 Amps range with selector switch and indicating lamps
with fuse and toggle switch for ON and TRIP status of motor.
4 Nos.125 Amps TP MCCB (35 KA) with neutral link outgoing
feeders for chilled water primary pumps .The compartment shall contain star delta starter with single phase
preventor and CT operated ammeter of 0-150 Amps.range with
for ON and TRIP status of motor.
4 Nos.125 Amps TP MCCB (35 KA) with neutral link outgoing
feeders for chilled water secondary pumps.the compartment shall contain star delta starter with single phase
preventor and CT operated ammeter of 0-150 Amps.range with
for ON and TRIP status of motor.
3 Nos.63 Amps TP MCCB (35 KA) with neutral link outgoing
feeders for hot water pumps.The compartment
shall contain star delta starter with single phase preventor
and CT operated ammeter of 0-63 Amps.range with for ON
and TRIP status of motor.
2 nos. 800 Amps. motorised TP MCCB (50KA) with neutral link
and 6 NO & 6 NC auxilliary contacts on outgoing feeders
for 300 KW Hot water Generator as per the details . The
compartment shall shall contain CT operated ammeter of
0-800 Amps range with selector switch and indicating lamps
Necessary cable alleys of all equipment shall be included.
All switch gears/controls gears shall be of motor duty rating.
Auto/Manual stop change over switch to each equipment
and necessary potential free contacts.

1 set

2800000

2800000

Control Panel in Air Handling Unit Rooms :

ESIC Hospital and PGI at Maniktala

Project :HVAC System for ESI Hospital and PG College at Maniktala -West Bengal
Bill of Quantities (BOQ) of the HVAC works :
16

I)
ii)
iii)
iv)
v)
vi)
vii)

viii)
ix)
x)
a)
b)
c)
d)
e)

Supply,installation,testing and commissioning of the following


cubicle type openable front ,sheet steel wall mounted control
panels sleeve type Al. bus bar including anchoring into
the wall.These panels shall be complete in all respects
as per the drawings and the specifications.
The panel shall include the following accessories :
MCCB as per rating given below.
Terminal block for power distribution.
Single Phase Preventor.
Phase indicating lights and indicating lights for ON/TRIP
status
Digital type Ammeter and suitable size CT and selector
switche.
Time delay relay for automatic restart of AHUs motors.
Auto/Manual stop selector switch shall be provided in each
AHU Panel.The same should provide potential free contact
for position monitoring to BMS system.
All starters shall have suitable potential free contacts
Wiring for microswitch for stopping the fan when fire
dampers closes.
Bypass starter for BMS (AHUs VFDs)
The number of AHU panel shall be as detailed below :
63 amps TPN MCCB with 1 No.2.0 HP DOL Starter for AHU
fan motor and & 16 Amps.
63 amps TPN MCCB with 1 No.3.0 HP DOL Starter for AHU
fan motor and & 16 Amps.
63 amps TPN MCCB with 1 No.10 HP Star Delta Starter for AHU
fan motor and & 16 Amps.
63 amps TPN MCCB with 1 No.12.5 HP Star Delta Starter for AHU
fan motor and & 16 Amps.
63 amps TPN MCCB with 1 No.15 HP Star Delta Starter for AHU
fan motor and & 16 Amps.

sets

20000

20000

12

sets

25000

300000

14

sets

45000

630000

sets

45000

90000

sets

45000

90000

Control Panel for ventilation and pressurisation fans :


17

Supply,installation,testing and commissioning of the following


cubicle type openable front ,sheet steel wall mounted control
panels sleeve type Al. bus bar including anchoring into
the wall.These panels shall be complete in all respects

ESIC Hospital and PGI at Maniktala

Project :HVAC System for ESI Hospital and PG College at Maniktala -West Bengal
Bill of Quantities (BOQ) of the HVAC works :

I)
ii)
iii)
iv)
v)
vi)
vii)
viii)
a)
b)

as per the drawings and the specifications.


The panels shall include the following accessories :
MCCB as per rating given below.
Terminal block for power distribution.
Single Phase Preventor.
Phase indicating lights and indicating lights for ON/TRIP
status
Digital type Ammeter and suitable size CT and selector
switche.
Time delay relay for automatic restart of Fan motors.
Auto/Manual stop selector switch shall be provided in each
Fan Panel
All starters shall have suitable potential free contacts
The number of El. Panels shall be as detailed below :
32 amps TPN MCCB with 1 No. 5.0 HP DOL Starter
63 amps TPN MCCB with 1 No. 10 HP DOL Starter

10
2

sets
sets

25000
45000

250000
90000

200
75
125
30
400
550
150
70
55
100
500
100

RM
RM
RM
RM
RM
RM
RM
RM
RM
RM
RM
RM

4200
3500
2150
1902
1648
958
807
684
571
513
462
300

840000
262500
268750
57060
659200
526900
121050
47880
31405
51300
231000
30000

Chilled Water Piping :


18

a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
k)
l)

Supply,installation,testing and commissioning of "C"class mild


steel Chilled water piping with all necessary fittings like flanges
,supports,bends, tees,reducers,sockets & TF quality Expanded
polystyrene(EPS) insulation & 28 guage Al.cladding as per the
thickness and densities as mentioned in the drawings and the
specifications.
300 mm dia
200 mm dia.
150 mm dia.
125 mm dia.
100 mm dia.
80 mm dia
65 mm dia
50 mm dia.
40 mm dia.
32 mm dia.
25 mm dia.
20 mm dia.
Chilled Water Circuit /hot water lines Valves :

ESIC Hospital and PGI at Maniktala

Project :HVAC System for ESI Hospital and PG College at Maniktala -West Bengal
Bill of Quantities (BOQ) of the HVAC works :
19

a)

b)

c)

c)

d)

e)
f)

Supply,installation,testing and commissioning


of following type of valves as per drawings and
specifications for the chilled/hot water circuit with
all fittings and insulations and 28 guage Al.cladding.
Butterfly Valves
300 mm dia
150 mm dia
125 mm dia.
100 mm dia.
80 mm dia.
65 mm dia.
50 mm dia
40 mm dia
Ball valve for CS AHUs
32 mm dia.
25 mm dia.
Balancing Valve
150 mm dia
125 mm dia.
100 mm dia
80 mm dia.
65 mm dia.
50 mm dia
40 mm dia
32 mm dia.
25 mm dia.
Check Valve
150 mm dia.
100 mm dia.
Y-Strainers
80 mm dia.
65 mm dia.
32 mm dia
40 mm dia
25 mm dia
Pot Strainer
300 mm dia
Flexible pipe Connection
150 mm dia
125 mm dia.

10

7
30
4
10
28
10
R.O.
R.O.

Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos

25000
4619
2572
2109
1576
1452
1274
1159

175000
138570
10288
21090
44128
14520
0
0

28
2

Nos
Nos

1400
956

39200
1912

6
R.O.
2
14
5
R.O.
R.O.
14
1

Nos
Nos.
Nos.
Nos.
Nos.
Nos.
Nos.
Nos.
Nos.

32000
11957
8744
5407
3182
2279
1622
1200
950

192000
0
17488
75698
15910
0
0
16800
950

8
3

Nos
Nos

7500
3000

60000
9000

15
5
15
R.O.
11

Nos
Nos
Nos
Nos
Nos

4171
3553
3090
2626
1500

62565
17765
46350
0
16500

No

140000

24
R.O.

Nos
Nos

12000
10041

140000
0
288000
0

ESIC Hospital and PGI at Maniktala

Project :HVAC System for ESI Hospital and PG College at Maniktala -West Bengal
Bill of Quantities (BOQ) of the HVAC works :
100 mm dia.
80 mm dia.
65 mm dia.
32 mm dia
25 mm dia
g) Water Flow Switch

10
28
10
28
2
4

Nos
Nos
Nos
Nos
Nos
Nos

7724
6488
4943
3399
2400
5057

77240
181664
49430
95172
4800
20228

R.O
14
5
14
1

Nos
Nos
Nos
Nos
Nos

77445
52263
46675
15000
8500

0
731682
233375
210000
8500

115

Nos.

4300

494500

90
105

Nos
Nos

707
637

63630
66885

2-Way Motorised Valves :


20

a)
b)
c)
d)
e)

Supply,installation,testing and commissioning of following Globe type


UL/CE Approved 2-way motorised valves for AHUs with status
feedback for the chilled water and hot water circuit with actuators,
linkage, control wiring and all fittings and insulation and
28 Guage Al.cladding as per drawings and specifications.
100 mm dia.pipe size
80 mm dia.pipe size
65 mm dia. pipe size
32 mm dia.pipe size
25 mm dia.pipe size
AHUs Thermostats :

21

Supply,installation,testing and commissioning of


proportional type cooling and heating thermostats for the
various Air Handling Units complet with required control
wiring/installation kit etc. as per drawings and specifications

22

Supply,installation,testing and commissioning


of following Thermameters and pressure guage
as per drawings and specifications for the
Chilled/hot water circuit complete with syphon
and fitttings
a) Pressure guage
b) Thermometer
Expansion Tank :

23

Supply,installation,testing and commissioning


of 1000 litres capacity expansion tank fabricated
from 3mm MS sheet and having 19 mm thick nitrile

11

ESIC Hospital and PGI at Maniktala

Project :HVAC System for ESI Hospital and PG College at Maniktala -West Bengal
Bill of Quantities (BOQ) of the HVAC works :
rubber foam insulation covered with 28 Ga Aluminium
sheet with man hole cover, drain ,overflow,quick
fill,water supply connections,valves and complete
in all respects as per drawings and specification
1000mm X 1000mm X 1000 mm

No

35000

70000

R.O.
75
300
75
50
350

Rmt
Rmt
Rmt
Rmt
Rmt
Rmt

900
700
600
500
400
300

0
52500
180000
37500
20000
105000

Supply,installation,testing and commissioning


of Air Vents 15 mm dia.

75

Nos

1400

105000

Supply,installation,testing and commissioning


of 1" dia Ball valves for drain with fittings etc.

150

Nos

956

143400

3450
2300
800
400

M2
M2
M2
M2

690
790
930
1065

2380500
1817000
744000
426000

Drain Piping :
24

a)
b)
c)
d)
e)
f)
25

26

Supply,installation,testing and commissioning


of "B" class GI drain piping complete with fitting
etc & nitrile foam insulation with sealing tapes &
28 G Aluminium cladding complete as per drawings &
specifications of below sizes.
80 mm dia.
65 mm dia.
50 mm dia.
40 mm dia.
32 mm dia.
25 mm dia.

Rectangular Ductwork :
27

a)
b)
c)
d)

Supply,installation,testing and commissioning


of rectangular sheet metal ductwork complete with supports,
dampers/splitters/vanes/fasteners/nuts/washers and all
ancilliary items as per specifications and drawings of the
following guauges / thickness.:
24 Gauge
22 Guage
20 Guage
18 Guage
XPE Insulation :

12

ESIC Hospital and PGI at Maniktala

Project :HVAC System for ESI Hospital and PG College at Maniktala -West Bengal
Bill of Quantities (BOQ) of the HVAC works :
28

Supply,installation,testing and commissioning of


expanded polyethylene insulation on ducts complete
as per the drawings and specifications of following sizes.
a) 9 mm thickness

6300

M2

461

2904300

1200

M2

381

457200

M2

8249

32996

110

M2

6477

712470

78

M2

12342

962676

20

M2

8000

160000

M2

7500

45000

15

M2

4400

66000

Duct Accoustic Lining :


29

Supply,installation,testing and commissioning


of 25 mm thick & 32 kg/m3 density fiberglass
insulation boards fixed on GI frame & covered with 26
guage perforated Aluminium sheet with nuts,bolts and
complete as per drawings and specifications
for the accoustic lining of a/c ducts.
Grilles/Diffusers/Louvers/VCDs/FDs :

30

31

32

33

34

35

36

Supply,installation,testing and commissioning


of Supply air grilles with dampers in extruded
Aluminium construction and powder coated
finish as per specifications and drawings.
Supply,installation,testing and commissioning
of Return air grilles without dampers in extruded
Aluminium construction and powder coated
finish as per specifications and drawings
Supply,installation,testing and commissioning
of Supply air Diffusers with dampers in extruded
Aluminium construction and powder coated
finish as per specifications and drawings.
Supply,installation,testing and commissioning
of Return air Diffusers without dampers in extruded
Aluminium construction and powder coated
finish as per specifications and drawings.
Supply,installation,testing and commissioning
of MS powder coated grilles with dampers,louvers
and filters for Fresh air intake.
Supply,installation,testing and commissioning of
GI construction Volume control Dampers lever
operated type as per specifications and drawings
Supply,installation,testing and commissioning of
motorised combined smoke and fire dampers complete with

13

ESIC Hospital and PGI at Maniktala

Project :HVAC System for ESI Hospital and PG College at Maniktala -West Bengal
Bill of Quantities (BOQ) of the HVAC works :

37

38

39

control panel interconnecting wiring at locations shown in the


drawings and as per specifications
AHU Room Accoustic Lining :
Supply,installation,testing and commissioning of
accoustic lining on all side walls of each AHU Rooms with
fiberglass ,tissue paper and 24 guage perforated aluminium sheet.
The Fibreglass insulation shall be 50 mm X 32Kg/m3 of
board tyoe and shall be fixed on GI Frame as per the
drawings and the specifications.
Supply,installation,testing and commissioning of
of powder coated extruded aluminium air transfer grilles with
rear side frame as per drawings and specifications
Supply,installation,testing and commissioning of
flexible duct connections constructed of fire resistance
flexible double canvas sleeve as per the drawings and
specifications.

25

M2

25000

625000

1500

M2

786

1179000

M2

6100

18300

30

M2

3400

102000

200
200
75
85
150
450
400

RM
RM
RM
RM
RM
RM
RM

4000
2000
700
600
500
400
300

800000
400000
52500
51000
75000
180000
120000

Power Cabling :
40

a)
b)
c)
d)
e)
f)
g)

Supply,installation,testing and commissioning of


PVC insulated sheathed 1.1 KV grade armoured
Al. Power cables from various panels upto their
respective equipment on MS painted perforated trays
with appropriate clamps/fixing arrangements as per
specifications and drawings.
3.5 C X 400 mm2 Aluminium Cable
3.5 C X 240 mm2 Aluminium Cable
3 C X 25 mm2 Aluminium Cable
3 C X 16 mm2 Aluminium Cable
3 C X 10 mm2 Aluminium Cable
3 C X 6 mm2 Aluminium Cable
3 C X 4 mm2 Aluminium Cable
Control Cabling :

41

Supply,installation,testing and commissioning of


PVC insulated sheathed 1.1 KV grade armoured
Copper control cables for various equipment
through walls/ceilings with appropriate clamps
/ fixing arrangements and complete with termination

14

ESIC Hospital and PGI at Maniktala

Project :HVAC System for ESI Hospital and PG College at Maniktala -West Bengal
Bill of Quantities (BOQ) of the HVAC works :
as per specifications and drawings.
a) 2C X 1.5 mm2

200

RM

150

125
350
250

RM
RM
RM

95
25
17
Grand Total

30000

Earthing :
42

Supply,installation,testing and commissioning of


double earthing continuity conductor of GSS from
Panels to respective equipment as per drawings
and specifications.
a) 25 mm X 3 mm strip
b) 6 SWG wire
c) 8 SWG wire

15

11875
8750
4250
72977607

ESIC Hospital and PGI at Maniktala

You might also like