Pressure testing
LS 133-02
Page 1 of 9
Contents
1
2
3
4
5
5.1
5.2
6
7
8
Scope ................................................................2
Scheduling of the pressure test.........................2
Test method ......................................................2
Requirements ....................................................2
Performance ......................................................3
Hydrostatic test .................................................3
Pneumatic test ..................................................4
Water quality .....................................................4
Exceptional cases .............................................5
Test results and test report ...............................5
Annex A
Annex B
Annex C
(normative) Performance of
pneumatic testing ....................................6
(normative) Safety areas for
pneumatic testing ....................................7
(normative) Temporary blinds for
pressure testing ......................................8
06
01.2013
GCQ / Henn
GCQ / Helmreich
05
07.2008
TM-Q / Henn
TAW / Rahofer
LEHQ-ENM1S /
Schmitt
TAW-N / Schmitt
Status
Issue
Date
Prepared
Checked
Approved
Linde AG
File name:
LS 133-02 (EN)
Issue 06/01.2013
LS 133-02
Page 2 of 9
Scope
This standard applies to the performance of pressure tests, i. e. hydrostatic or pneumatic tests of piping and
equipment on construction sites or pre-fabrication sites.
During pressure testing the leak tightness, the form/shape stability and the strength integrity of the test system
will be determined.
Project specific or component specific requirements from codes, regulations or specifications have preference
over the requirements of this standard.
Pressure testing shall be performed after completion of construction activities on the pressure-retaining wall and
after inspection and release by the inspection agency, but prior to applying painting, insulation, rubber coating,
brick-lining, metallic liners and similar coating to the inside and outside wall.
For piping a single-layer outside primer is admissible, provided that the consents of the purchaser, authority
resp. inspection agency exists.
For underground piping the area of the welding seams shall be accessible for inspection.
During the pressure test the number of personnel in the direct neighborhood shall be limited to a minimum
(e.g. testing after working hours).
Test method
The standard test method is hydrostatic testing, by using water as test fluid. The additional static load due to the
water weight of the systems to be tested, to supports, foundations, etc. shall be considered by taking
appropriate measures.
If in exceptional cases e.g. due to process reasons, the hydrostatic test is not suitable the pressure test may be
performed as pneumatic test, after consultation with the purchaser. Due to the risk potential occurring with
compressed gases precautions shall be taken for personnel protection. If applicable, the test shall be previously
agreed upon with the relevant industrial safety authorities and the inspection agency.
Generally, pressure testing shall be performed at room / ambient temperature. At low ambient temperature
(< 5 C), additional measures shall be agreed upon with the purchaser and the inspection agency.
If pressure vessels are subject to pressure testing on site, the instructions of the vessel manufacturer shall be
observed.
NOTE: Heat exchangers can be designed for differential pressure. This shall be considered during pressure
testing. Corresponding data are shown on the vessel nameplate.
Requirements
If components with longitudinal welds are installed, these welds shall be prior pressure-tested or 100%
nondestructively tested (shall apply to pneumatic test only)
Parts which are to be excluded from the pressure test (e.g. rupture discs, sensitive measuring
instruments, special components subject to a lower test pressure) shall be dismantled or isolated from the
system.
Documents specifying test method (test fluid), pressure test limits and test pressure shall be prior
approved by purchaser. (e.g. drawings with welding and testing plan or line/isometric list, isometric
drawing with defined pressure test circuits, etc.)
The static pressure of the water column shall be considered at large differences in height
Pre-condition for pressure testing are the accepted final inspection and compliance with specified scope
of examinations
Linde AG
File name:
LS 133-02 (EN)
Issue 06/01.2013
LS 133-02
Page 3 of 9
For pneumatic testing, radiographic examination of at least 10 % of all circumferential-welds and nozzle
welds > DN 100 (4 inches) shall be required. Nozzle welds which cannot be radiographed shall where
appropriate be ultrasonically tested resp. tested for surface cracks
Calibrated measuring instruments (pressure gauge, pressure transmitter) with measuring range
< 1.5 x test pressure shall be used; for pneumatic testing 2 independent measuring instruments with
remote reading or with reading from a protected area will be required, preferably with pressure recorder
Safety measures shall be observed against unintentional pressure increase due to heating of the test fluid
at rising ambient temperature. The pump shall be separated from the test system during testing
Sufficiently dimensioned parts for isolating the pressure chamber, such as blind flanges, line blinds, caps,
pressure devices (for temporary blinds refer to Annex C) shall be used
For hydrostatic testing the installation of vents and drains at high and low points will be required
Safety distances for test personnel and other involved persons according to Annex B for pneumatic
testing shall be observed
Pneumatic testing systems shall be kept small and large-size vessels shall be isolated, if possible.
Demarcation of a separate protection area and marking with "no access permitted" will be required
A responsible for supervision of the defined safety precautions and performance of the pressure testing
shall be nominated
Approval for the pneumatic testing by the authority and the purchaser shall be obtained
Performance
Test pressures and performance shall be acc. to the specified codes and standards.
NOTE: The factor for the calculation of the test pressure is not always constant. Calculated stress factors for the
design temperature (temperature correction factor) as specified in design and construction codes may have to
be considered.
5.1
Hydrostatic test
The test fluid shall be water according to Paragraph 6; the test pressure shall be applied at the
highest point
Securing of a dry outside surface (e.g. protection against rainy weather); in case of condensate, waiting
for temperature balance between test fluid and wall
Temperature control; pressurization only after reaching of the specified test temperature (= metal
temperature)
The pressure shall be increased slowly and continuously till reaching test pressure.
Visual examination of the walls after 15 min at the earliest and for piping with covered welds (under
reinforcing pads, etc.) after at least 30 min holding time at test pressure
Prior to draining: open vents, otherwise danger of bulging due to forming vacuum
After pressure testing immediate draining of water, removal of water residues, if any (e.g. by blowing) and
venting of the walls, otherwise danger of corrosion
Linde AG
File name:
LS 133-02 (EN)
5.2
Issue 06/01.2013
LS 133-02
Page 4 of 9
Pneumatic test
The test fluid shall be an oil-free and dry gas, air or nitrogen
Pressurization and pressure verification from a safe distance see Annex A and B
First leak test at 0.5 to 1.0 bar by visual examination of the welds and detachable connections after
application of foam-frothing agent
Increase pressure slowly and step-by-step till reaching test pressure; after a holding period of 10 min
each, visual examination and noise control from a safe distance
At test pressure (acc. Code) a holding time of at least 30 min (no access permitted during holding time
above max. allowable working pressure!)
If a safety valve is installed for protection against unintentional pressure increase (e.g. acc. to
ASME B31.3), the cross-section of the safety valve shall consider the required blow off volume
Access to the safety area only after decrease of the test pressure to the maximum allowable working
pressure. At this pressure inspect the piping for deformations and cracks. In the welding seam zone and
on all detachable connections a second leak test with frothing agents (bubble test) shall be performed
additionally
Exemption for Cold Boxes: Due to safety precautions the leak test on welds at maximum allowable
working pressure, with foam-frothing agents, shall be omitted. This leak test shall be carried out after
pressure release to 0.5 1.0 bar
Water quality
For the pressure test with liquid, clean (free from suspended substances) water of drinking water quality shall be
used. The admissible chloride content (including bromides, iodides) is specified in Table 1. The material data
given in Table 1 shall apply to all surfaces being in contact with water, i.e. also to metallic internals and
claddings. For constructions involving material combinations, the more stringent requirements each shall apply.
Table 1: Admissible chloride content of the water for pressure testing
Material group
1
Aluminium materials
10
Plastic materials
Linde AG
Chloride content
ppm = mg/l
< 250
< 150
< 50
no
limitation
File name:
LS 133-02 (EN)
Issue 06/01.2013
LS 133-02
Page 5 of 9
Exceptional cases
If, in exceptional cases, water is to be used with a chloride content exceeding the values of Table 1, namely
it shall be inhibited, e.g. with 1.5 % by weight of sodium carbonate or 0.5 % by weight of sodium nitrate.
Inhibition with lime solution or organic inhibitors needs the consent of the purchaser. For inhibition and additions
to water for obtaining a freezing point depression the local applicable regulations for water shall be observed.
At unknown or considerably variable water quality, the determination of the halides (chloride, bromide, iodide) is
required prior to each pressure testing, e.g. by means of "Aquaquant Chlorid" from Merck, Darmstadt.
If the proceeding acc. to this standard is not useful for an individual case, the details shall be agreed upon with
the purchaser and the inspection agency, e.g. for
The accepted pressure test shall be confirmed in a test report by the parties involved, by observing the specified
regulations, and by indicating the equipment tested, test method, test pressure, test period, test fluid, test results
and date and, where applicable, test temperature, pressure gauge No. with calibration certificate and pressure
recorder report.
At a not accepted pressure test, the purchaser shall be informed immediately. The further proceeding shall then
be agreed upon with the purchaser and the parties involved.
Linde AG
File name:
LS 133-02 (EN)
Issue 06/01.2013
LS 133-02
Page 6 of 9
Annex A
(normative)
Performance of pneumatic testing
SG
Pt
SG
1.0p
SG
0.9p
SG
0.8p
SG
0.7p
Pressure
SG
0.6p
SG
0.5p
th
D*)
0.5-1.0 bar
Start
End
Time
Linde AG
File name:
LS 133-02 (EN)
Issue 06/01.2013
LS 133-02
Page 7 of 9
Annex B
(normative)
Safety areas for pneumatic testing
For pressure vessels the safety distance shall be according Table B.1.
For piping the safety distance shall be in accordance with Table B.1 and upon consultation with the parties
involved.
Table B.1: Safety distances for vessels
Volume
m3
1
2
3
4
5
7
10
15
20
30
40
50
60
70
80
90
100
150
200
300
400
500
Pt=5
bar
Pt=10
bar
Pt=15
bar
2.1
2.9
3.6
4.1
4.6
5.4
6.5
7.9
9.2
11.2
13.0
14.5
15.9
17.2
18.3
19.5
20.5
25.1
29.0
35.5
41.0
45.9
3,3
4.7
5.7
6.6
7.4
8.8
10.5
12.8
14.8
18.2
21.0
23.5
25.7
27.7
29.7
31.5
33.2
40.6
46.9
57.4
66.3
74.2
4.3
6.1
7.4
8.6
9.6
11.4
13.6
16.6
19.2
23.5
27.2
30.4
33.3
35.9
38.4
40.7
42.9
52.6
60.7
74.4
85.9
96.0
Safety Distance
m
Pt=20
Pt=25
bar
bar
Pt=30
bar
Pt=35
bar
Pt=40
bar
5.1
7.2
8.9
10.2
11.5
13.6
16.2
19.8
22.9
28.1
32.4
36.2
39.7
42.9
45.8
48.6
51.2
62.7
72.4
88.7
102.5
114.5
6.5
9.2
11.3
13.0
14.6
17.3
20.6
25.3
29.2
35.7
41.3
46.1
50.5
54.6
58.3
61.9
65.2
79.9
92.2
113.0
130.5
145.8
7.1
10.1
12.4
14.3
16.0
18.9
22.6
27.6
31.9
39.1
45.1
50.5
55.3
59.7
63.8
67.7
71.4
87.4
100.9
123.6
142.7
159.6
7.7
10.9
13.4
15.4
17.2
20.4
24.4
29.9
34.5
42.2
48.8
54.5
59.7
64.5
69.0
73.1
77.1
94.4
109.0
133.5
154.2
172.4
5.9
8.3
10.1
11.7
13.1
15.5
18.5
22.7
26.2
32.1
37.0
41.4
45.4
49.0
52.4
55.6
58.6
71.7
82.8
101.4
117.1
131.0
Note:
The values shown in the table are based on the following formula acc. to Regels voor toestellen
onder druk "Rules for pressure vessels" T 0240:
l 1.51 V pt pt0.714
Linde AG
File name:
LS 133-02 (EN)
Issue 06/01.2013
LS 133-02
Page 8 of 9
Annex C
(normative)
Temporary blinds for pressure testing
C.1
General requirements
C.2
C.3
Temporary blinds shall be mounted centred and as a minimum cover the entire flange sealing surface. The
temporary blind shall not touch flange bolts after installation. Sealing surface of temporary blinds shall be flat,
smooth and free of scale and/or other irregularities.
Unless otherwise instructed by purchaser in writing, temporary blinds shall be removed directly after pressure
testing, after test systems were cleaned and dried.
Linde AG
File name:
LS 133-02 (EN)
Issue 06/01.2013
LS 133-02
Page 9 of 9
Table C.1: Thickness of temporary blinds for flanges considering minimum yield strength of 235 MPa
DN NPS
15
20
25
40
50
65
80
100
150
200
250
300
350
400
450
500
600
700
750
800
900
1000
1100
1200
1300
1400
1500
1600
1800
2000
0.5
0.75
1
1.5
2
2.5
3
4
6
8
10
12
14
16
18
20
24
28
30
32
36
40
44
48
52
56
60
64
72
80
Linde AG
5
1
1
1
2
2
2
3
3
4
5
6
7
8
9
11
12
14
16
16
18
20
22
24
26
28
30
32
35
39
43
10
1
2
2
2
3
3
3
4
6
7
9
10
12
13
15
16
19
22
23
25
28
31
34
37
40
43
46
49
55
61
15
2
2
2
3
3
4
4
5
7
8
10
12
14
16
18
20
23
27
28
30
34
38
41
45
48
52
56
59
67
74
20
2
2
2
3
4
4
5
6
8
10
12
14
16
18
21
23
27
31
32
35
39
43
47
52
56
60
64
69
77
86
25
2
2
3
3
4
5
5
6
9
11
13
16
18
20
23
25
30
34
36
39
44
48
53
58
62
67
72
77
86
96
30
2
3
3
4
4
5
6
7
10
12
15
17
20
22
25
28
33
37
40
43
48
53
58
63
68
73
79
84
94
105
35
2
3
3
4
5
6
6
7
10
13
16
18
21
24
27
30
35
40
43
46
51
57
62
68
74
79
85
91
102
113
40
2
3
3
4
5
6
7
8
11
14
17
20
23
26
29
32
38
43
46
49
55
61
67
73
79
85
91
97
109
121
45
2
3
3
4
5
6
7
8
11
14
18
21
24
27
31
34
40
46
48
52
58
65
71
77
84
90
96
103
115
128
50
3
3
4
5
5
6
7
9
12
15
19
22
24
29
32
36
42
48
51
55
61
68
75
81
88
95
101
108
122
135
55
3
3
4
5
6
7
8
9
12
16
19
23
27
30
34
37
44
51
53
57
64
71
78
85
92
99
106
113
128
142
60
3
3
4
5
6
7
8
10
13
17
20
24
28
31
35
39
46
53
56
60
67
75
82
89
96
104
111
118
133
148
65
3
3
4
5
6
7
8
10
14
18
21
25
29
33
37
41
48
55
58
62
70
78
85
93
100
108
116
123
139
70
3
4
4
5
6
8
9
10
14
18
22
26
30
34
38
42
50
57
60
65
73
80
88
96
104
112
120
128
144
75
3
4
4
6
6
8
9
11
15
19
23
27
31
35
39
44
52
59
62
67
75
83
91
99
108
116
124
132
149
80
3
4
4
6
7
8
9
11
15
19
23
28
32
36
41
45
53
61
64
69
78
86
94
103
111
120
128
137
130
4
5
6
7
9
10
11
14
19
24
30
35
41
46
52
57
68
77
82
88
99
109
120
131
142
135
4
5
6
7
9
11
12
14
20
25
30
36
42
47
53
58
69
79
83
90
101
112
122
133
144
140
4
5
6
8
9
11
12
14
20
26
31
36
42
48
54
59
70
80
85
91
102
114
124
136
147
145
4
5
6
8
9
11
12
14
20
26
31
37
43
49
55
60
72
82
86
93
104
116
127
138
150
150
4
5
6
8
9
11
13
15
21
26
32
38
44
49
56
61
73
83
88
95
106
118
129
140
155
4
5
6
8
9
11
13
15
21
27
32
38
44
50
56
62
74
84
89
96
108
119
131
143
160
4
5
6
8
9
11
13
15
21
27
33
39
45
51
57
63
75
86
91
98
110
121
133
145
165
4
5
6
8
9
11
13
15
21
27
33
39
46
52
58
64
76
87
92
99
111
123
135
147
170
4
5
6
8
9
11
13
16
22
27
34
40
47
53
59
65
77
88
94
101
113
125
137
150
175
4
5
6
8
10
12
14
16
22
28
34
41
47
53
60
66
79
90
95
102
115
127
139
File name:
180
4
5
6
8
10
12
14
16
23
28
35
41
48
54
61
67
80
91
96
104
116
129
141
185
4
6
7
9
10
12
14
17
23
29
35
42
49
55
62
68
81
92
98
105
118
130
143
190
5
6
7
9
10
12
14
17
23
30
36
42
49
56
62
69
82
93
99
106
119
132
145
195
5
6
7
9
10
13
14
17
24
30
36
43
50
56
63
70
83
95
100
108
121
134
147
200
5
6
7
9
10
13
14
17
24
30
37
43
50
57
64
71
84
96
101
109
122
136
149
LS 133-02 (EN)