In the negative flexure regions, shear connectors shall be provided where the
longitudinal reinforcement is considered to be a part of the composite section.
Otherwise, shear connectors need not be provided in negative flexure regions, but
additional connectors shall be placed in the region of the points of permanent load
contraflexure.
n AC =
(1)
(2)
Ar f sr
Zr
nZ r
Vsr
Zr = d2 5.5 d2/2;
P
Qr
n=
(a)
where
Pp = min . of
Fp = Pp
0.85 f cbs t s
(LRFD Eq. 6.10.10.4.2 - 2)
Lp
R
P = PT2 + FT2
where
PT = Pp + Pn
Pn = min . of
0.45 f cbs t s
(b)
Ln
R
Shear Resistance, Qn
Qn
= 0.5 Asc
f c Ec Asc Fu
Qn
f c Ec
S6.10.7.4.1
S6.10.7.4.1a
A B C
7/8"
6"
3"
8"
5"
(Typ.)
14"
5-2
S6.10.7.4.1a
Heightstud = 6.0 in
Diameterstud = 0.875 in
Heightstud
Diameterstud
= 6.86
OK
n Zr I
Vsr Q
5-3
S6.10.7.4.1b
I = 66340.3 in
S6.10.3.1.1b
Q = 1195.8 in
Zr = d
5.5 d
2
N = 82125000
S6.10.7.4.2
(see Design Step 3.14 at location
of maximum positive flexure)
d = 0.48
Therefore,
p =
n Zr I
Vsr Q
Zr = 2.11 K
p = 10.04 in
5-4
= 2.11
S6.6.1.2.5
I = 130196.1 in
SC6.10.7.4.1b
Q = 1807.4 in
Zr = 2.11 K
p =
n Zr I
Vsr Q
S6.10.7.4.2
(see previous computation)
p = 13.07 in
5-5
S6.10.7.4.1b
OK
p 6d
d = 0.875 in
6 d = 5.25 in
OK
S6.10.7.4.1c
Stud shear connectors must not be closer than 4.0 stud diameters
center-to-center transverse to the longitudinal axis of the supporting
member.
4 d = 3.50 in
Spacingtransverse = 5.0 in
OK
In addition, the clear distance between the edge of the top flange and
the edge of the nearest shear connector must not be less than 1.0
inch.
Distanceclear =
14in
d
(see Figure 5-1)
5in
2
2
Distanceclear = 1.56 in
OK
The clear depth of concrete cover over the tops of the shear
connectors should not be less than 2.0 inches, and shear connectors
should penetrate at least 2.0 inches into the deck. Based on the
shear connector penetration information presented in Table 5-1, both
of these requirements are satisfied.
5-6
S6.10.7.4.1d
For the strength limit state, the factored resistance of the shear
connectors, Qr, is computed as follows:
S6.10.7.4.4
Qr = sc Qn
S6.10.7.4.4a
sc = 0.85
S6.5.4.2
S6.10.7.4.4c
Asc =
d
4
Asc = 0.601 in
S5.4.2.1
Ec = 3834 ksi
S5.4.2.4
Fu = 60.0 ksi
S6.4.4
Qn = 36.06 K
Qr = sc Qn
Therefore,
Qr = 30.65 K
S6.10.7.4.4a
Vh
Qr
The total horizontal shear force, Vh, between the point of maximum
positive moment and each adjacent point of 0.0 moment is equal to
the lesser of the following:
Vh = 0.85 f' c b ts
or
Vh = Fyw D tw + Fyt bt tt + Fyc bf tf
5-7
S6.10.7.4.4b
where
b = 103.0 in
ts = 8.0 in
Fyw = 50 ksi
D = 54 in
tw = 0.50 in
Fyt = 50 ksi
bt = 14 in
tt = 0.875 in
Fyc = 50 ksi
bf = 14 in
tf = 0.625 in
S5.4.2.1
STable 6.4.1-1
STable 6.4.1-1
STable 6.4.1-1
Vh = 2400 K
Vh
Qr
n = 78.3
The distance between the end of the girder and the location of
maximum positive moment is approximately equal to:
L = 48.0 ft
L = 35.6 ft
5-8
S6.10.7.4.4a
n = 3
L 12
in
ft
L = 35.6 ft
p = 10 in
n = 128.2
OK
S6.10.7.4.4b
Vh = Ar Fyr
2
where
Ar = 12.772 in
Fyr = 60 ksi
Vh = Ar Fyr
Vh = 766 K
Therefore, the number of shear connectors provided between each
adjacent point of 0.0 moment and the centerline of an interior
support must not be less than the following:
Vh
n =
Qr
n = 25.0
The distance between the point of dead load contraflexure and the
centerline of the interior support is approximately equal to:
L = 120 ft 83.6 ft
L = 36.4 ft
Using a pitch of 10 inches, as previously computed for the fatigue
limit state, the number of shear connectors provided is as follows:
n = 3
L 12
n = 131.0
in
ft
p = 10 in
OK
5-9
S6.10.7.4.4a
Therefore, using a pitch of 10 inches for each row, with three stud
shear connectors per row, throughout the entire length of the girder
satisfies both the fatigue limit state requirements of S6.10.7.4.1 and
S6.10.7.4.2 and the strength limit state requirements of S6.10.7.4.4.
Therefore, use a shear stud spacing as illustrated in the following
figure.
Symmetrical about CL Pier
144 Spaces @ 10" = 120'-0"
(3 Stud Shear Connectors Per Row)
CL Bearing Abutment
CL Pier
5-10
S6.10.8.2.1