Professional Documents
Culture Documents
11/13/2014
03:43PM
1. General Details:
Air System Name ...................................................................................... PB-18
Equipment Type ........................................................ Packaged Rooftop Units
Air System Type ........................................................................ Dual Duct CAV
Number of zones ............................................................................................... 2
2. System Components:
Ventilation Air Data:
Airflow Control .................................................... Constant Ventilation Airflow
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Unocc. Damper Position ......................................................................... Closed
Damper Leak Rate ............................................................................................ 0 %
Outdoor Air CO2 Level .................................................................................. 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................... 14.4 C
Coil Bypass Factor ..................................................................................... 0.100
Cooling Source ........................................................................... Air-Cooled DX
Schedule ............................................................................... JFMAMJJASOND
Capacity Control ........................................... Constant Temperature - Fan On
Central Heating Data:
Supply Temperature ..................................................................................... 24.0 C
Heating Source .................................................................. Electric Resistance
Schedule ............................................................................... JFMAMJJASOND
Capacity Control ........................................... Constant Temperature - Fan On
Supply Fan Data:
Fan Type ................................................................................. Forward Curved
Configuration ...................................................................................... Blow-thru
Fan Performance .......................................................................................... 700 Pa
Overall Efficiency ............................................................................................ 65 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................. 2 %
Duct Leakage .................................................................................................... 3 %
Return Duct or Plenum Data:
Return Air Via ............................................................................. Ducted Return
3. Zone Components:
Space Assignments:
Zone 1: Zone 1-LER
SUBSTATTION_PB_18
Zone 2: Zone 2-LIR
SUBSTATTION_PB_18_LIR
x1
x1
Zone
Cooling T-Stat
Occ.
(C)
Cooling T-Stat
Unocc.
(C)
Heating T-Stat
Occ.
(C)
Diversity
Factor
(%)
Direct
Exhaust
Airflow
(L/s)
Direct Exhaust
Fan
(kW)
24.0
27.0
21.1
15.6
1.70
100
0.0
0.0
24.0
27.0
19.0
15.6
1.70
100
0.0
0.0
Terminal Type
CAV mix box
CAV mix box
Min. Airflow
Fan Performance Fan Efficiency
6.00 ACH
6.00 ACH
Design Supply
Temperature
-
Page 1 of 2
11/13/2014
03:43PM
C
L/s
L/s
C
Zone
Supply Airflow
(L/s)
Reheat Coil
(kW)
4313.6
628.7
5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load ......................................................................... 102.0
Design OAT .................................................................................................. 35.0
Equipment Sizing ............................................................................. Auto-Sized
Capacity Oversizing Factor ............................................................................... 0
ARI Performance Rating .............................................................................. 2.96
Conventional Cutoff OAT ............................................................................. 12.8
Low Temperature Operation ................................................................ Not used
kW
C
%
EER
C
Page 2 of 2