FNC Fancoil-Applikationen
aus FC-10, FC-11, FC-12
(See separate document CM110385 for the FNC description of functions).
Fr RXB...
Page 21.1 21.1 22.1
FNC02
FNC03
FNC04
15
FNC05
21
FNC08
27
FNC10
31
FNC12
37
FNC18
43
FNC20
49
X
X
X
X
FC-11
X
FC-10
Application package
FC-12
Application
Related documents
CM110385
CM1Y9775
CM1Y9776
CM1Y9777
CM1Y9779
CA1N3804
CM110672en_03
30.11.2007
Building Technologies
2/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
FNC02
K NX
10385S10
Plant diagram
D3
YHC
Q1
T
Room controller.
Room unit with temp.
sensor.
B1 Return air sensor.
D1 Window switch.
D2 Presence detector.
D3 Changeover signal via KNX
bus.
Q1 Fan (1 ... 3 speeds).
YHC Heating/cooling valve.
B1
N1
R1
Operating diagrams
R1
D1
D2
N1
KNX
Y [%]
Change-over
H
100
10385D45
YHC
YHC
SpH
SpC
Change-over
Y
TR
SpH
SpC
H
C
YHC
Q14
Q24
Output signal.
Room temperature.
Effective heating setpoint.
Effective cooling setpoint.
Heating sequence.
Cooling sequence.
Heating/cooling valve.
Fan speed 1.
Fan speed 2.
Q34
Fan speed 3.
TR [C]
10385D34
Y
C
H
Q34
Q24
Q14
SpH
SpC
TR [C]
3/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Functions
Function
Brief description)
PI control.
Proportional control sequence, selectable:
Only heating sequence, only cooling sequence or changeover.
Control of thermal / electromechanic / motorized valve actuators (AC 24 V, PDM or
AC 24 V, 2-position / AC 24 V, 3-position).
Control of motorized KNX bus actuator valves.
Valve exercising feature.
1 ... 3-speed, automatic, or
Manual with room unit.
Room temperature sensor or
Return air sensor.
Comfort, Precomfort, Economy and Protection mode..
Change of operating mode via /Auto switch on room unit, presence detector,
window contact or central command.
Locally via room unit or centrally.
Presence detector.
Window switch.
Master/slave operation.
Boost heating, night cooling etc.
Free inputs/outputs.
Available with temperature sensor, setpoint adjuster,
button for
/Auto and fan speed control, and LCD display.
FNC02 is supplied with RXB21.1/FC-10.
Fan control.
Temperature measurement.
Room operating modes.
Setpoint shift.
General functions.
Room units.
Compatible controllers.
4/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
YHC.2 3)
Connection diagram
B1
D1
2)
D2
2)
Y2
Y1
KNX
YHC.1 3)
R1
10385A01
CE
CE
CE+
CP+
CP
N1
17 18
CE+
2
Y4
Y2
Q34
D3
RXB21.1
25 26 27 28
Y1
D2
19 19 21 21
10 11 12 13 14 15 16
Q24
Y3
Q14
GND
Q13
D1
N.C.
B1
QAX...
Q1
4)
AC 230 V
N
L
List of equipment
Ref.
N1
R1
B1
D1
D2
D3
Q1
YHC.1
YHC.2
2)
3)
4)
Note
Description
Room controller.
Room unit
Return air temperature sensor, room temperature sensor.
Window contact 2).
Presence detector 2).
Changeover signal via KNX bus.
1- or 3-speed fan 4).
Heating/cooling valve actuator, thermal, 2-point (PDM) control 3).
Heating/cooling valve actuator, motorized, 3-position control 3).
5/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Configuration
Menu
Parameters.
Values/Range
Basic setting
Communication
Communication mode
Receive timeout
Send heartbeat
Protection cooling setpoint
Economy cooling setpoint
Precomfort cooling setpoint
Comfort cooling setpoint
Comfort heating setpoint
Precomfort heating setpoint
Economy heating setpoint
Protection heating setpoint
Control sequence
S-mode.
60 min.
45 min.
40 C
35 C
28 C
24 C
21 C
19 C
15 C
12 C
Cooling only
Sequences
Off/On
Off
Off/On
Off
0 ... 360 s
150 s
Room unit
General functions.
Central functions
Master/slave
STP72E
0 ... 360 s
Fan speeds
External control
1-speed/2-speed/3-speed
Fan control.
Manual / Auto
Minimum on time.
1 ... 10 min
Temperature sensor B1
Room
Return air
Measured value only
No sensor
Periodic fan kick Comfort
0 ... 90 min (90min = Off)
Periodic fan kick Economy
0 ... 360 min (360min = Off)
Measured value correction
3 ... 3 K
Setpoint offset range
0 ... 10 K
Local Comfort mode
Enabled / Disabled
Room unit
Without LCD / with LCD
With LCD Display heating/cooling symbols
Enabled / Disabled
Temperature unit
C or F
Standard display
No display / Room
temperature / Setpoint
Setpoint display
Absolute / Relative
Digital input 1
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
Digital input 2
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
Temporary Comfort mode
0 ... 360 min
0s
3-speed
Auto
6 min
No sensor
90 min (Off)
360 min (Off)
0K
3K
Enabled
Without LCD
Enabled
C
Room temperature.
Relative
Free (bus = 1)
= Contact closed.
Free (bus = 1)
= Contact closed.
60 min
0 ... 90 min
5 min
0 ... 90 min
5 min
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Master or slave
Enabled
Enabled
Enabled
Enabled
Disabled
Master
6/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Ordering
The room controllers can be ordered preloaded with the application described here.
When ordering, specify the quantity, DESIGO RXB device name, type code and
application group.
Example
15
Note
RXB21.1/FC-10
The controllers are delivered with the basic settings shown above.
7/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
8/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
FNC03
K NX
10385S11
Plant diagram
YR
D3
D4
YHC
Q1
N1
R1
B1
D1
D2
D3
Room controller.
Room unit with temp.
sensor.
Return air sensor.
Window switch.
Presence detector.
Safety thermostat, electric
heating coil.
D4
Q1
YHC
YR
B1
R1
D1
D2
N1
KNX
Operating diagrams
Changeover = Heating.
Changeover = Cooling.
1-stage
ON
10385D30
10385D31
1K
ON
YR
YR
OFF
OFF
SpH
Y
TR
SpH
SpC
H
C
YHC
YR
Output signal.
Room temperature.
Effective heating setpoint.
Effective cooling setpoint.
Heating sequence.
Cooling sequence.
Heating/cooling valve.
Contactor or solid state
relay for electric heating
coil.
Mod.
ON
YHC
YHC
TR [C]
SpH
Y
10385D32
YR
100%
YHC
TR [C]
10385D33
YHC
YR
OFF
SpC
0%
SpH
TR [C]
SpH
SpC
TR [C]
9/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Change-over
10385D34
Y
TR
SpH
SpC
H
C
Q14
Q24
Output signal.
Room temperature.
Effective heating setpoint.
Effective cooling setpoint.
Heating sequence.
Cooling sequence.
Fan speed 1.
Fan speed 2.
Q34
Fan speed 3.
H
Q34
Q24
Q14
SpH
Functions
SpC
TR [C]
Function
Brief description)
PI control.
Proportional control sequence, selectable:
Only heating sequence, only cooling sequence or changeover.
Control of thermal / electromechanic / motorized valve actuators (AC 24 V, PDM /or
AC 24 V 2-position / AC 24 V 3-position).
Control of motorized KNX bus actuator valves.
Valve exercising feature.
2-position or proportional control.
Control: AC 24 V, 2-position or proportional.
1 ... 3-speed, automatic, or
Manual with room unit.
Room temperature sensor or
Return air sensor.
Comfort, Precomfort, Economy and Protection mode..
Change of operating mode via /Auto switch on room unit, presence detector,
window contact or central command.
Locally via room unit or centrally.
Presence detector.
Window switch.
Master/slave operation.
Boost heating, night cooling etc.
Free inputs/outputs.
Available with temperature sensor, setpoint adjuster,
/Auto and fan speed control, and LCD display.
button for
FNC03 is supplied with RXB22.1/FC-12.
Electric reheater.
Fan control.
Temperature measurement.
Room operating modes.
Setpoint shift.
General functions.
Room units.
Compatible controllers.
10/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
D3 2)
YHC.2 3)
B1
D1
2)
D2
2)
Y1
YHC.1
KNX
Y2
Connection diagram
3)
R1
CE
CE
CE+
4
CE+
CP+
N1
17 18
10385A02
Q34
CP
D4
RXB22.1
25 26 27 28
6)
YR
F1
22 23 24
Q24
Y2
13 14 15 16
Q14
Q13
Y1
GND
Q44
D1
19 19 21 21
6
D2
Q43
N.C.
N.C.
M
N
B1
AC 230 V
QAX...
Q1
4)
7)
N
L
Ref.
N1
R1
B1
D1
D2
D3
D4
Q1
YR
F1
YHC.1
YHC.2
List of equipment
Description
Room controller.
Room unit
Return air temperature sensor, room temperature sensor.
Window contact 2).
Presence detector 2).
Safety thermostat, electric heating coil.
Changeover signal via KNX bus.
1- ... 3-speed fan.
Electric reheater 6).
External fuse, max. 10 A 7).
Heating/cooling valve actuator, thermal, 2-point (PDM) control 3).
Heating/cooling valve actuator, motorized, 3-position control 3).
Note
11/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Configuration
Menu
Parameters.
Values/Range
Basic setting
Communication
Communication mode
Receive timeout
Send heartbeat
Protection cooling setpoint
Economy cooling setpoint
Precomfort cooling setpoint
Comfort cooling setpoint
Comfort heating setpoint
Precomfort heating setpoint
Economy heating setpoint
Protection heating setpoint
Control sequence
S-mode.
60 min.
45 min.
40 C
35 C
28 C
24 C
21 C
19 C
15 C
12 C
Cooling only
Sequences
Off/On
Off
Off/On
Off
0 ... 360 s
150 s
Room unit
General functions.
STP72E
0 ... 360 s
0s
1-stage
Mod.
Mod.
0 ... 6500 W
Off/On
Fan speeds
External control
1-speed/2-speed/3-speed
Fan control.
Manual / Auto
Minimum on time.
1 ... 10 min
Temperature sensor B1
Room
Return air
Measured value only
No sensor
Periodic fan kick Comfort
0 ... 90 min (90min = Off)
Periodic fan kick Economy
0 ... 360 min (360min = Off)
Fan overrun time
1 ... 10 min
Measured value correction
3 ... 3 K
Setpoint offset range
0 ... 10 K
Local Comfort mode
Enabled / Disabled
Room unit
Without LCD / with LCD
With LCD Display heating/cooling symbols
Enabled / Disabled
Temperature unit
C or F
Standard display
No display / Room
temperature / Setpoint
Setpoint display
Absolute / Relative
Digital input 1
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
Overtemp. = Contact open/closed
Digital input 2
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
Overtemp. = Contact open/closed
Temporary Comfort mode
0 ... 360 min
0W
Off
3-speed
Auto
6 min
No sensor
90 min (Off)
360 min (Off)
1 min
0K
3K
Enabled
Without LCD
Enabled
C
Room temperature.
Relative
Free (bus = 1)
= Contact closed.
Free (bus = 1)
= Contact closed.
60 min
0 ... 90 min
5 min
0 ... 90 min
5 min
12/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Menu
Parameters.
Values/Range
Basic setting
Central functions
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Master or slave
Enabled
Enabled
Enabled
Enabled
Disabled
Master
Master/slave
Ordering
The room controllers can be ordered preloaded with the application described here.
When ordering, specify the quantity, DESIGO RXB device name, type code and
application group.
Example
15
Note
RXB22.1/FC-12
The controllers are delivered with the basic settings shown above.
13/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
14/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
FNC04
K NX
10385S12
Plant diagram
YC
YH
Q1
T
N1
R1
B1
D1
D2
Q1
YH
YC
Room controller.
Room unit with temp.
sensor.
Return air sensor.
Window switch.
Presence detector.
Fan (1 3-speed).
Heating valve.
Cooling valve.
B1
D1
D2
N1
KNX
Operating diagrams
R1
Y [%]
H
YH
YC
SpH
SpC
10385D35
100
0
TR [C]
Output signal.
Room temperature.
Effective heating setpoint.
Effective cooling setpoint.
Heating sequence.
Cooling sequence.
Heating valve.
Cooling valve.
Fan speed 1.
Fan speed 2.
Q34
Fan speed 3.
H
Q34
Q24
10385D36
Y
TR
SpH
SpC
H
C
YH
YC
Q14
Q24
Q14
SpH
SpC
TR [C]
15/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Functions
Function
Brief description)
PI control.
Two proportional control sequences, heating and cooling.
Control of thermal / electromechanic / motorized valve actuators (AC 24 V, PDM /
AC 24 V, 2-position / AC 24 V, 3-position).
Control of motorized KNX bus actuator valves.
Valve exercising feature.
1 ... 3-speed, automatic, or
Manual with room unit.
Room temperature sensor or
Return air sensor.
Comfort, Precomfort, Economy and Protection mode..
Change of operating mode via /Auto switch on room unit, presence detector,
window contact or central command.
Locally via room unit or centrally.
Presence detector.
Window switch.
Master/slave operation.
Boost heating, night cooling etc.
Free inputs/outputs.
Available with temperature sensor, setpoint adjuster,
/Auto and fan speed control, and LCD display.
button for
FNC04 is supplied with RXB21.1/FC-10.
Fan control.
Temperature measurement.
Room operating modes.
Setpoint shift.
General functions.
Room units.
Compatible controllers.
16/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
B1
D1
2)
D2
2)
Y1
Y2
YC.2 3)
Y2
YH.2 3)
Y1
Connection diagram
3)
YH.1 YC.1 3)
KNX
R1
10385A03
RXB21.1
25 26 27 28
N1
CE
Y2
CE+
CP
Y1
17 18
Q34
D2
Y4
GND
Q24
N.C.
D1
19 19 21 21
10 11 12 13 14 15 16
Y3
Q14
Q13
CE
B1
CE+
CP+
QAX...
Q1
4)
AC 230 V
N
L
Ref.
N1
R1
B1
D1
D2
Q1
YH.1
YH.2
YC.1
YC.2
List of equipment
2)
3)
4)
Note
Description
Room controller.
Room unit
Return air temperature sensor, room temperature sensor.
Window contact 2).
Presence detector 2).
1- or 3-speed fan 4).
Heating valve actuator, thermal, 2-position (PDM) control 3).
Heating valve actuator, motorized, 3-position control 3).
Cooling valve actuator, thermal, 2-position (PDM) control 3).
Cooling valve actuator, motorized, 3-position control 3).
Type of operation (N/O or N/C) can be selected.
Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873).
Do not connect the fans in parallel (or use cut-off relays).
17/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Configuration
Menu
Parameters.
Values/Range
Basic setting
Communication
Communication mode
Receive timeout
Send heartbeat
Protection cooling setpoint
Economy cooling setpoint
Precomfort cooling setpoint
Comfort cooling setpoint
Comfort heating setpoint
Precomfort heating setpoint
Economy heating setpoint
Protection heating setpoint
Actuator type heat/cool valve
S-mode.
60 min.
45 min.
40 C
35 C
28 C
24 C
21 C
19 C
15 C
12 C
STP72E
Sequences
Off/On
Off
Off/On
Off
0 ... 360 s
150 s
Room unit
General functions.
Central functions
Master/slave
0 ... 360 s
Fan speeds
External control
1-speed/2-speed/3-speed
Fan control.
Manual / Auto
Minimum on time.
1 ... 10 min
Temperature sensor B1
Room
Return air
Measured value only
No sensor
Periodic fan kick Comfort
0 ... 90 min (90min = Off)
Periodic fan kick Economy
0 ... 360 min (360min = Off)
Measured value correction
3 ... 3 K
Setpoint offset range
0 ... 10 K
Local Comfort mode
Enabled / Disabled
Room unit
Without LCD / with LCD
With LCD Display heating/cooling symbols
Enabled / Disabled
Temperature unit
C or F
Standard display
No display / Room
temperature / Setpoint
Setpoint display
Absolute / Relative
Digital input 1
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
Digital input 2
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
Temporary Comfort mode
0 ... 360 min
0 ... 90 min
On-delay occupancy detector
0 ... 90 min
Off-delay presence detector
Heating demand signal
Enabled / Disabled
Cooling demand signal
Enabled / Disabled
Boost heating
Enabled / Disabled
Precooling, free cooling
Enabled / Disabled
Reset setpoint offset
Enabled / Disabled
Master/slave
Master or slave
0s
3-stufig
Auto
6 min
No sensor
90 min (Off)
360 min (Off)
0K
3K
Enabled
Without LCD
Enabled
C
Room temperature.
Relative
Free (bus = 1)
= Contact closed.
Free (bus = 1)
= Contact closed.
60 min
5 min
5 min
Enabled
Enabled
Enabled
Enabled
Disabled
Master
18/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Ordering
The room controllers can be ordered preloaded with the application described here.
When ordering, specify the quantity, DESIGO RXB device name, type code and
application group.
Example
15
Note
The controllers are delivered with the basic settings shown above.
19/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
20/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
FNC05
K NX
10385S13
Plant diagram
D3
YR
YC
YH
Q1
N1
R1
B1
D1
D2
D3
Q1
YH
YC
YR
Room controller.
Room unit with temp.
sensor.
Return air sensor.
Window switch.
Presence detector.
Safety thermostat electric
reheater.
Fan (1 3-speed).
Heating valve.
Cooling valve.
Electric reheater.
B1
R1
D1
D2
N1
KNX
21/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Operating diagrams
Application mode "Cooling" (3).
YC
OFF
SpC
SpH
TR [C]
YC
SpH
SpC
OFF
100%
YR
YH
OFF
TR [C]
Y
TR
SpH
SpC
H
C
Q14
Q24
Output signal.
Room temperature.
Effective heating setpoint.
Effective cooling setpoint.
Heating sequence.
Cooling sequence.
Heating/cooling valve.
Contactor or solid state relay for electric
heating coil.
Output signal.
Room temperature.
Effective heating setpoint.
Effective cooling setpoint.
Heating sequence.
Cooling sequence.
Fan speed 1.
Fan speed 2.
Q34
Fan speed 3.
TR [C]
Y
H
10385D39
YH
ON
SpC
YR
YC
0%
SpH
TR [C]
SpH
SpC
TR [C]
Y
C
H
Q34
Q24
10385D41
YR
YC
SpH
Y
H
10385D62
ON
YR
OFF
TR [C]
Mod.
YH
OFF
SpH
ON
10385D38
YH
ON
1K
YR
YR
10385D61
ON
Y
1K
10385D37
1-stage
Y
TR
SpH
SpC
H
C
YH
YR
10385D40
Q14
SpH
SpC
TR [C]
22/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Functions
Function
Brief description)
PI control.
Two proportional control sequences, heating and cooling.
Control of thermal / electromechanic valve actuators
(AC 24 V, PDM or AC 24 V, 2-position).
Control of motorized KNX bus actuator valves.
Valve exercising feature.
2-position or proportional control.
Control: AC 24 V, 2-position or proportional.
1 ... 3-speed
Automatic, or
Manual with room unit.
Room temperature sensor or
Return air sensor.
Comfort, Precomfort, Economy and Protection mode..
Change of operating mode via /Auto switch on room unit, presence detector,
window contact or central command.
Locally via room unit or centrally.
Presence detector.
Window switch.
Master/slave operation.
Boost heating, night cooling etc.
Free inputs/outputs.
Available with temperature sensor, setpoint adjuster,
/Auto and fan speed control, and LCD display.
button for
FNC05 is supplied with RXB22.1/FC-12.
Temperature measurement.
Room operating modes.
Setpoint shift.
General functions.
Room units.
Compatible controllers.
23/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
D3
Connection diagram
2)
KNX
B1
D1
2)
D2
2)
YH
3)
YC
3)
R1
10385A05
CE
CE+
CE
CE+
N1
6)
YR
2
CP
Q13
CP+
RXB22.1
25 26 27 28
22 23 24
17 18
Q34
Y2
13 14 15 16
Q24
Q14
Y1
Q44
D2
GND
19 19 21 21
Q43
N.C.
4
D1
N.C.
L
1
B1
QAX...
Q1
4)
7)
AC 230 V
F1
N
L
Ref.
N1
R1
B1
List of equipment
D1
D2
D3
Q1
YR
F1
YH,
YC
Description
Room controller.
Room unit
Return air temperature sensor,
room temperature sensor.
Window contact 2).
Presence detector 2).
Safety thermostat, electric heating coil.
1- ... 3-speed fan.
Electric reheater 6).
External fuse, max. 10 A 7).
Heating/cooling valve actuator, thermal, 2-point (PDM) control 3).
Note
24/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Configuration
Menu
Parameters.
Values/Range
Basic setting
Communication
Communication mode
Receive timeout
Send heartbeat
Protection cooling setpoint
Economy cooling setpoint
Precomfort cooling setpoint
Comfort cooling setpoint
Comfort heating setpoint
Precomfort heating setpoint
Economy heating setpoint
Protection heating setpoint
Actuator type heat/cool valve
S-mode.
60 min.
45 min.
40 C
35 C
28 C
24 C
21 C
19 C
15 C
12 C
STP72E
Sequences
Off/On
Off
Off/On
Off
0 ... 360 s
150 s
Room unit
General functions.
Central functions
Master/slave
0 ... 360 s
0s
1-stage
Mod.
Mod.
0 ... 6500 W
Off/On
Fan speeds
External control
1-speed/2-speed/3-speed
Fan control.
Manual / Auto
Minimum on time.
1 ... 10 min
Temperature sensor B1
Room
Return air
Measured value only
No sensor
Periodic fan kick Comfort
0 ... 90 min (90min = Off)
Periodic fan kick Economy
0 ... 360 min (360min =Off)
Fan overrun time
1 ... 10 min
Measured value correction
3 ... 3 K
Setpoint offset range
0 ... 10 K
Local Comfort mode
Enabled / Disabled
Room unit
Without LCD / with LCD
With LCD Display heating/cooling symbols
Enabled / Disabled
Temperature unit
C or F
Standard display
No display / Room
temperature / Setpoint
Setpoint display
Absolute / Relative
Digital input 1
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
Digital input 2
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
Temporary Comfort mode
0 ... 360 min
0W
Off
3-speed
Auto
6 min
No sensor
90 min (Off)
360 min (Off)
1 min
0K
3K
Enabled
Without LCD
Enabled
C
Room temperature.
Relative
Free (bus = 1)
= Contact closed.
Free (bus = 1)
= Contact closed.
60 min
0 ... 90 min
0 ... 90 min
5 min
5 min
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Master or slave
Enabled
Enabled
Enabled
Enabled
Disabled
Master
25/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Ordering
The room controllers can be ordered preloaded with the application described here.
When ordering, specify the quantity, DESIGO RXB device name, type code and
application group.
Example
15
Note
RXB22.1/FC-12
The controllers are delivered with the basic settings shown above.
26/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
K NX
10385S14
Plant diagram
B1
YC
YH
Q1
N1
R1
B1
D1
D2
Q1
YH
YC
Room controller.
Room unit with temp.
sensor.
Supply air temperature
sensor.
Window switch.
Presence detector.
Fan (1 3-speed).
Heating valve.
Cooling valve.
Operating diagrams
R1
D1
D2
N1
KNX
Y [%]
H
YH
YC
SpH
SpC
10385D42
100
Output signal.
Room temperature.
Effective heating setpoint.
Effective cooling setpoint.
Heating sequence.
Cooling sequence.
Heating valve.
Cooling valve.
Fan speed 1.
Fan speed 2.
Q34
Fan speed 3.
Y
C
H
Q34
Q24
10385D43
Y
TR
SpH
SpC
H
C
YH
YC
Q14
F1
TR [C]
Q14
SpH
SpC
TR [C]
27/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Functions
Function
Brief description)
Fan control.
Temperature measurement.
Room operating modes.
Setpoint shift.
General functions.
Room units.
Compatible controllers.
PI control.
Two proportional control sequences, heating and cooling.
Control of motorized valve actuators (AC 24 V, 3-position).
Control of motorized KNX bus actuator valves.
Room supply air cascade.
Valve exercising feature.
1 ... 3-speed, automatic, or
Manual with room unit.
Room temperature sensor and
Supply air temperature sensor.
Comfort, Precomfort, Economy and Protection mode..
Change of operating mode via /Auto switch on room unit, presence detector,
window contact or central command.
Locally via room unit or centrally.
Presence detector.
Window switch.
Master/slave operation.
Boost heating, night cooling etc.
Free inputs/outputs.
Available with temperature sensor, setpoint adjuster,
/Auto and fan speed control, and LCD display.
button for
FNC08 is supplied with RXB21.1/FC-10.
28/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
KNX
Connection diagram
QAX...
Y2
Q34
N1
17 18
RXB21.1
25 26 27 28
CE
Y4
CP
Q24
CE+
G
Q14
CP+
Y3
Q13
Y1
Y1
D2
19 19 21 21
Y2
10 11 12 13 14 15 16
Y1
N.C.
D1
5
GND
B1
R1
10385A06
YC 3)
CE
YH 3)
CE+
2)
Y2
D1 2) D2
B1
Q1
4)
AC 230 V
N
L
List of equipment
Ref.
N1
R1
B1
D1
D2
Q1
YH
YC
Description
Room controller.
Room unit
Supply air temperature sensor.
Window contact 2).
Presence detector 2).
1- or 3-speed fan 4).
Heating valve actuator, motorized,
3-position control 3).
Cooling valve actuator, motorized,
3-position control 3).
Note
29/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Configuration
Menu
Parameters.
Values/Range
Basic setting
Communication
Communication mode
Receive timeout
Send heartbeat
Protection cooling setpoint
Economy cooling setpoint
Precomfort cooling setpoint
Comfort cooling setpoint
Comfort heating setpoint
Precomfort heating setpoint
Economy heating setpoint
Protection heating setpoint
Maximum supply air temperature
Minimum supply air temperature
Actuator type heat/cool valve
S-mode.
60 min.
45 min.
40 C
35 C
28 C
24 C
21 C
19 C
15 C
12 C
35 C
16 C
SSP81...
Off/On
Off
0 ... 360 s
150 s
Other setpoints
Sequences
Room unit
General functions.
0 ... 360 s
Fan speeds
External control
1-speed/2-speed/3-speed
Fan control.
Manual / Auto
Minimum on time.
1 ... 10 min
Temperature sensor B1
Supply air (cascade)
Periodic fan kick Comfort
0 ... 90 min (90min = Off)
Periodic fan kick Economy
0 ... 360 min (360min = Off)
Measured value correction
3 ... 3 K
Setpoint offset range
0 ... 10 K
Local Comfort mode
Enabled / Disabled
Room unit
Without LCD / with LCD
With LCD Display heating/cooling symbols
Enabled / Disabled
Temperature unit
C or F
Standard display
No display / Room
temperature / Setpoint
Setpoint display
Absolute / Relative
Digital input 1
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
Digital input 2
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
Temporary Comfort mode
0 ... 360 min
Central functions
Master/slave
Off
0s
3-speed
Auto
6 min
Supply air (cascade)
90 min (Off)
360 min (Off)
0K
3K
Enabled
Without LCD
Enabled
C
Room temperature.
Relative
Free (bus = 1)
= Contact closed.
Free (bus = 1)
= Contact closed.
60 min
0 ... 90 min
5 min
0 ... 90 min
5 min
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Master or slave
Enabled
Enabled
Enabled
Enabled
Disabled
Master
Ordering
The room controllers can be ordered preloaded with the application described here.
When ordering, specify the quantity, DESIGO RXB device name, type code and
application group.
Example
15
Note
RXB21.1/FC-10
The controllers are delivered with the basic settings shown above.
30/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
FNC10
K NX
10385S19
Plant diagram
D3
YHC
N1
R1
Room controller.
Room unit with temp.
sensor.
B1 Return air sensor.
B2 Outside air temperature
sensor via KNX bus.
D1 Window switch.
D2 Presence detector.
D3 Changeover signal via KNX
bus.
D4 Safety thermostat, outside
air.
Q1 Fan (1 3-speed).
YHC Heating/cooling valve.
YM Outside air damper.
Operating diagrams
YM
Q1
D4
B2
B1
D1
R1
D2
N1
KNX
Y [%]
H
100
Y [%]
Change-over
C
100
YHC
SpH
Q34
Fan speed 3.
SpC
TR [C]
SpFr
SpEcm SpC
TO [C]
Change-over
Y
C
H
Q34
10385D46
Output signal.
Room temperature.
Outside air temperature.
Effective heating setpoint.
Effective cooling setpoint.
Economizer setpoint.
Risk of frost limit
Heating sequence.
Cooling sequence.
Heating/cooling valve.
Outside air damper.
Fan speed 1.
Fan speed 2.
min
0
Y
TR
TO
SpH
SpC
SpEcm
SpFr
H
C
YHC
YM
Q14
Q24
10385D44
10385D45
YM
YHC
Q24
Q14
SpH
SpC
TR [C]
31/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Functions
Function
Brief description)
PI control.
Proportional control sequence, selectable:
Only heating sequence, only cooling sequence or changeover.
Control of thermal or motorized valve actuators
(AC 24 V, PDM / AC 24 V, 2-position / AC 24 V, 3-position).
Control of motorized KNX bus actuator valves.
Valve exercising feature.
1 ... 3-speed, automatic, or
Manual with room unit.
Room temperature sensor or
Return air sensor.
Comfort, Precomfort, Economy and Protection mode..
Change of operating mode via /Auto switch on room unit, presence detector,
window contact or central command.
Locally via room unit or centrally.
Presence detector.
Window switch.
Master/slave operation.
Boost heating, night cooling.
Free inputs / outputs.
Available with temperature sensor, setpoint adjuster,
/Auto and fan speed control, and LCD display.
button for
FNC10 is supplied with RXB21.1/FC-11.
Fan control.
Temperature measurement.
Room operating modes.
Setpoint shift.
General functions.
Room units.
Compatible controllers.
32/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
2)
YHC.2
YM 3)
N1
10385A07
CP
Q34
B2
17 18
CE
Y2
Y4
Y2
Q24
D3
RXB21.1
25 26 27 28
Y1
D2
19 19 21 21
10 11 12 13 14 15 16
Y3
Q14
Q13
GND
Y1
Q23
Q24
6
N.C.
M
N
D1
B1
N
QAX...
CE+
R1
3)
YHC.1
CE
2)
D2
CE+
2)
KNX
CP+
D1
Y1
B1
3)
Y2
D4
Connection diagram
Q1
4)
AC 230 V
N
L
List of equipment
Ref.
N1
R1
B1
B2
D1
D2
D3
D4
Q1
YHC.1
YHC.2
YM
Description
Room controller.
Room unit
Return air temperature sensor,
room temperature sensor.
Outside air temperature sensor via KNX bus.
Window contact 2).
Presence detector 2).
Changeover signal via KNX bus.
Safety thermostat, outside air.
1- ... 3-speed fan 4).
Heating/cooling valve actuator, thermal, 2-point (PDM) control 3).
Heating/cooling valve actuator, motorized, 3-position control 3).
Damper actuator for outside air AC 24 V, 3-position 3).
2) Type of operation and allocation to inputs D1 and D2 can be selected. Identical devices must not be
connected to both inputs.
3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873).
4) Do not connect the fans in parallel (or use cut-off relays).
Note
33/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Configuration
Menu
Parameters.
Values/Range
Basic setting
Communication
Communication mode
Receive timeout
Send heartbeat
Protection cooling setpoint
Economy cooling setpoint
Precomfort cooling setpoint
Comfort cooling setpoint
Comfort heating setpoint
Precomfort heating setpoint
Economy heating setpoint
Protection heating setpoint
Risk of frost limit
Outside air supply
Outside temp min damper pos
Running time outside air damper
Minimum damper position
Control sequence
S-mode.
60 min.
45 min.
40 C
35 C
28 C
24 C
21 C
19 C
15 C
12 C
5 C
10 C ... 40C
0 ... 360 s
0 ... 100 %
Heating only
Cooling only
Changeover
STA71
SSA81
STA72E
SSB81
STE71
SSP81
STE72
SQS81
STP71
STP72E
Motorized 3rd devices
rd
Thermal 3 devices
Motorized bus
16 C
150 s
0%
Cooling only
0 ... 360 s
150 s
Other setpoints
Sequences
0 ... 360 s
Room unit
General functions.
Off/On
Off/On
Fan speeds
External control
1-speed/2-speed/3-speed
Fan control.
Manual / Auto
Minimum on time.
1 ... 10 min
Temperature sensor B1
Room
Return air
Measured value only
No sensor
Periodic fan kick Comfort
0 ... 90 min (90min = Off)
Periodic fan kick Economy
0 ... 360 min (360min = Off)
Measured value correction
3 ... 3 K
Setpoint offset range
0 ... 10 K
Local Comfort mode
Enabled / Disabled
Room unit
Without LCD / with LCD
With LCD Display heating/cooling symbols
Enabled / Disabled
Temperature unit
C or F
Standard display
No display / Room
temperature / Setpoint
Setpoint display
Absolute / Relative
Digital input 1
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
OT < Frost = Contact open/closed
Digital input 2
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
OT < Frost = Contact open/closed
Temporary Comfort mode
0 ... 360 min
STP72E
0s
Off
Off
3-speed
Auto
6 min
No sensor
90 min (Off)
360 min (Off)
0K
3K
Enabled
Without LCD
Enabled
C
Room temperature.
Relative
Free (bus = 1)
= Contact closed.
Free (bus = 1)
= Contact closed.
60 min
0 ... 90 min
5 min
0 ... 90 min
5 min
34/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Menu
Parameters.
Values/Range
Basic setting
Central functions
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Master or slave
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Master
Master/slave
Ordering
The room controllers can be ordered preloaded with the application described here.
When ordering, specify the quantity, DESIGO RXB device name, type code and
application group.
Example
15
Note
RXB21.1/FC-11
The controllers are delivered with the basic settings shown above.
35/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
36/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
FNC12
K NX
10385S20
Plant diagram
YC
YH
N1
R1
B1
B2
D1
D2
D3
Q1
YH
YC
YM
Room controller.
Room unit with temp.
sensor.
Return air sensor.
Outside air temperature
sensor via KNX bus.
Window switch.
Presence detector.
Safety thermostat, outside
air.
Fan (1 3-speed).
Heating valve.
Cooling valve.
Outside air damper.
Operating diagrams
Q1
YM D3
M
B2
B1
D1
R1
D2
N1
KNX
Y [%]
Y [%]
H
100
100
Q34
Fan speed 3.
10385D48
Output signal.
Room temperature.
Outside air temperature.
Effective heating setpoint.
Effective cooling setpoint.
Economizer setpoint.
Risk of frost limit
Heating sequence.
Cooling sequence.
Heating valve.
Cooling valve.
Outside air damper.
Fan speed 1.
Fan speed 2.
YC
min
0
SpH
SpC
TR [C]
SpFr
SpEcm SpC
TO [C]
Y
C
H
Q34
Q24
10385D49
Y
TR
TO
SpH
SpC
SpEcm
SpFr
H
C
YH
YC
YM
Q14
Q24
10385D47
YM
YH
Q14
SpH
SpC
TR [C]
37/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Brief description)
Fan control.
Temperature measurement.
Room operating modes.
Setpoint shift.
General functions.
Room units.
Compatible controllers.
PI control.
Two proportional control sequences, heating and cooling.
Control of thermal valve actuators (AC 24 V, PDM).
Control of motorized KNX bus actuator valves.
Outside air damper.
Valve exercising feature.
1 ... 3-speed automatic.
Manual with room unit.
Room temperature sensor or
Return air sensor.
Comfort, Precomfort, Economy and Protection mode..
Change of operating mode via /Auto switch on room unit, presence detector,
window contact or central command.
Locally via room unit or centrally.
Presence detector.
Window switch.
Master/slave operation.
Boost heating, night cooling.
Free inputs / outputs
Available with temperature sensor, setpoint adjuster,
button for
/Auto and fan speed control, and LCD display.
FNC12 is supplied with RXB21.1/FC-11.
38/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
D3 2)
Connection diagram
KNX
YM 3)
10385A08
CP
Q34
N1
17 18
CE
Y2
Y4
Y2
Q24
B2
RXB21.1
25 26 27 28
Y1
Y1
D2
19 19 21 21
10 11 12 13 14 15 16
Y3
Q14
GND
Q13
N.C.
M
N
D1
B1
N
QAX...
CE+
R1
3)
YC
CE
3)
YH
CE+
2)
CP+
D1 2) D2
B1
Q1
4)
AC 230 V
N
L
Ref.
N1
R1
B1
List of equipment
B2
D1
D2
D3
Q1
YH.1
YC.1
YM
Description
Room controller.
Room unit
Return air temperature sensor,
room temperature sensor.
Outside air temperature sensor via KNX bus.
Window contact 2).
Presence detector 2).
Safety thermostat, outside air.
1- ... 3-speed fan 4).
Heating valve, thermal, 2-position (PWM) control 3).
Cooling valve, thermal, 2-position (PWM) control 3).
Damper actuator for outside air AC 24 V, 3-position 3).
2) Type of operation and allocation to inputs D1 and D2 can be selected. Identical devices must not be
connected to both inputs.
3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873).
4) Do not connect the fans in parallel (or use cut-off relays).
Note
39/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Configuration
Menu
Parameters.
Values/Range
Basic setting
Communication
Communication mode
Receive timeout
Send heartbeat
Protection cooling setpoint
Economy cooling setpoint
Precomfort cooling setpoint
Comfort cooling setpoint
Comfort heating setpoint
Precomfort heating setpoint
Economy heating setpoint
Protection heating setpoint
Risk of frost limit
Outside air supply
Outside temp min damper pos
Running time outside air damper
Minimum damper position
Actuator type heat/cool valve
S-mode.
60 min.
45 min.
40 C
35 C
28 C
24 C
21 C
19 C
15 C
12 C
5 C
10 C ... 40C
0 ... 360 s
0 ... 100 %
16 C
150 s
0%
STA71
STA72E
STE71
STE72
STP71
STP72E
Thermal 3rd party devices
Motorized bus
0 ... 360 s
STP72E
Other setpoints
Sequences
0 ... 360 s
0s
Off/On
Off
Fan control.
Room unit
General functions.
Central functions
Master/slave
150 s
Motorized Offset
Off/On
External control
1-speed/2-speed/3-speed
Fan control.
Manual / Auto
Minimum on time.
1 ... 10 min
Temperature sensor B1
Room
Return air
Measured value only
No sensor
Periodic fan kick Comfort
0 ... 90 min (90min = Off)
Periodic fan kick Economy
0 ... 360 min (360min = Off)
Measured value correction
3 ... 3 K
Setpoint offset range
0 ... 10 K
Local Comfort mode
Enabled / Disabled
Room unit
Without LCD / with LCD
With LCD Display heating/cooling symbols
Enabled / Disabled
Temperature unit
C or F
Standard display
No display / Room
temperature / Setpoint
Setpoint display
Absolute / Relative
Digital input 1
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
OT < Frost = Contact open/closed
Digital input 2
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
OT < Frost = Contact open/closed
Temporary Comfort mode
0 ... 360 min
On-delay occupancy detector
0 ... 90 min
Off-delay presence detector
0 ... 90 min
Heating demand signal
Enabled / Disabled
Cooling demand signal
Enabled / Disabled
Boost heating
Enabled / Disabled
Precooling, free cooling
Enabled / Disabled
Rapid ventilation
Enabled / Disabled
Night purge
Enabled / Disabled
Reset setpoint offset
Enabled / Disabled
Master/slave
Master or slave
Fan speeds
Off
3-speed
Auto
6 min
No sensor
90 min (Off)
360 min (Off)
0K
3K
Enabled
Without LCD
Enabled
C
Room temperature.
Relative
Free (bus = 1)
= Contact closed.
Free (bus = 1)
= Contact closed.
60 min
5 min
5 min
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Master
40/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Ordering
The room controllers can be ordered preloaded with the application described here.
When ordering, specify the quantity, DESIGO RXB device name, type code and
application group.
Example
15
Note
RXB21.1/FC-11
The controllers are delivered with the basic settings shown above.
41/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
42/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
FNC18
K NX
Heating/cooling coil: heating only (with LTHW), cooling only (with CHW) or
changeover.
Changeover signal via KNX bus.
Outside air temperature sensor via KNX bus.
Heating with LTHW radiator.
Downdraft compensation
Modulating control of heating/cooling valve and radiator valve.
Automatic or manual fan control.
10385S21
Plant diagram
D3
YHC
Q1
B1 T
Operating diagrams
YH
R1
KNX
Y [%]
Change-over (Fan-Coil)
H
YHC
Heating sequence:
The heating coil in the fan coil system operates
in sequence with the radiator, i.e. the
heating/cooling valve is only operated after the
radiator valve is fully open (thermal valves are
operated in alternation, because fully open
here means 1 second ON / 1 second OFF).
YH
YHC
0
SpH
Change-over
SpC
Cooling sequence:
Control of heating/cooling valve.
TR [C]
Y
C
H
Q34
Q24
10385D51
Output signal.
Room temperature.
Effective heating setpoint.
Effective cooling setpoint.
Heating sequence.
Cooling sequence.
Heating valve (radiator).
Heating/cooling valve (fan
coil).
Q14 Fan speed 1.
Q24 Fan speed 2.
D2
100
Y
TR
SpH
SpC
H
C
YH
YHC
D1
N1
10385D50
Room controller.
Room unit with temp.
sensor.
B1 Return air sensor.
B2 Outside temp. via KNX bus.
D1 Window switch.
D2 Presence detector.
D3 Changeover signal via KNX
bus.
Q1 Fan (1 3-speed).
YH Heating valve (radiator).
YHC Heating/cooling valve (fan
coil).
B2
N1
R1
Q14
SpH
SpC
TR [C]
43/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Functions
Function
Two-pipe fan coil.
Fan control.
Temperature measurement.
Room operating modes.
Setpoint shift.
General functions.
Room units.
Compatible controllers.
44/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
YH.2 3)
YHC.2 3)
YHC.3
Y2
Y1
YH.3
Y2
Y1
Connection diagrams
KNX
D1 2) D2
B1
2)
YH.1
3)
YHC.1 3)
R1
QAX...
M
10385A09
CE+
RXB21.1
25 26 27 28
CE
17 18
CE
CP+
CE+
Y4
CP
Y2
Q34
Q24
Y1
D3
D2
19 19 21 21
10 11 12 13 14 15 16
Y3
Q14
Q13
5
GND
N.C.
B1
D1
B2
N1
Q1
4)
AC 230 V
N
L
Y1
YH
YH
YH
YH
YH
X
YH
X
X
Y2
YHC
YH
X
YH
YH
X
X
YHC
X
Y3
X
YHC
YHC
YHC
-YHC
-X
--
Y4
-YHC
YHC
--YHC
----
2) Type of operation and allocation to inputs D1 and D2 can be selected. Identical devices must not be
connected to both inputs.
3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873).
4) Do not connect the fans in parallel (or use cut-off relays).
45/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Ref.
N1
R1
B1
B2
D1
D2
D3
Q1
YH.1, YHC.1
List of equipment
YH.2, YHC.2
YH.3, YHC.3
Description
Room temperature controller.
Room unit
Return air temperature sensor, room temperature sensor.
Outside air temperature sensor via KNX bus.
Window contact 2).
Presence detector 2).
Changeover signal via KNX bus.
1 ... 3-speed fan 4).
Radiator valve, heating/cooling valve, thermal, 2-point control (PDM)
3)
.
Radiator valve, heating/cooling valve, motorized, 3-point control
(PDM) 3).
Radiator valve, heating/cooling valve, bus.
2) Type of operation and allocation to inputs D1 and D2 can be selected. Identical devices must not be
connected to both inputs.
3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873).
4) Do not connect the fans in parallel (or use cut-off relays).
Note
46/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Configuration
Menu
Parameters.
Values/Range
Basic setting
Communication
Communication mode
Receive timeout
Send heartbeat
Protection cooling setpoint
Economy cooling setpoint
Precomfort cooling setpoint
Comfort cooling setpoint
Comfort heating setpoint
Precomfort heating setpoint
Economy heating setpoint
Protection heating setpoint
Downdraft compensation
Outside temp 0% valve pos
Outside temp max valve pos
Maximum valve pos
Control sequence
S-mode.
60 min.
45 min.
40 C
35 C
28 C
24 C
21 C
19 C
15 C
12 C
30 ... 10C
30 ... 10C
0 ... 100%
0C
10C
100%
Heating only
Cooling only
Changeover
STA71
SSA81
STA72E
SSB81
STE71
SSP81
STE72
SQS81
STP71
STP72E
Motorized 3rd devices
rd
Thermal 3 devices
Motorized bus
Cooling only
STA71
STA72E
STE71
STA72E
Other setpoints
Sequences
150 s
0 ... 360 s
0s
Off/On
Off/On
Off
Off
Off/On
External control
1-speed/2-speed/3-speed
Manual / Auto
1 ... 10 min
Room
Return air
Measured value only
No sensor
0 ... 90 min (90min = Off)
0 ... 360 min (360min = Off)
3 ... 3 K
0 ... 10 K
Enabled / Disabled
Without LCD / with LCD
Enabled / Disabled
C or F
No display / Room
temperature / Setpoint
Absolute / Relative
Off
3-speed
Fan speeds
Fan control.
Minimum on time.
Temperature sensor B1
Room unit
STP71
SQS81
STP72E
Motorized 3rd devices
rd
Thermal 3 devices
Motorized bus
0 ... 360 s
Motorized Offset
Cooling coil outp bus valve
Heating surface outp bus valve
Fan control.
SSA81
SSB81
SSP81
STP72E
Auto
6 min
No sensor
90 min (Off)
360 min (Off)
0K
3K
Enabled
Without LCD
Enabled
C
Room temperature.
Relative
47/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Menu
Parameters.
General functions.
Digital input 1
Values/Range
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
Digital input 2
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
Temporary Comfort mode
0 ... 360 min
Central functions
Master/slave
Basic setting
Free (bus = 1)
= Contact closed.
Free (bus = 1)
= Contact closed.
60 min
0 ... 90 min
5 min
0 ... 90 min
5 min
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Master or slave
Enabled
Enabled
Enabled
Enabled
Disabled
Master
Ordering
The room controllers can be ordered preloaded with the application described here.
When ordering, specify the quantity, DESIGO RXB device name, type code and
application group.
Example
15
Note
RXB21.1/FC-11
The controllers are delivered with the basic settings shown above.
48/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
FNC20
K NX
10385S22
Plant diagram
YM
Q1
T
B1
N1
R1
B1
D1
D2
Q1
Room controller.
Room unit with temp.
sensor.
Return air sensor.
Window switch.
Presence detector.
Fan (1 3-speed).
YM
R1
D1
D2
N1
KNX
Operating diagrams
Y [%]
H
100
10385D52
YM
0
SpH
Output signal.
Room temperature.
Effective heating setpoint.
Effective cooling setpoint.
Heating sequence.
Cooling sequence.
Damper actuator.
Fan speed 1.
Fan speed 2.
Q34
Fan speed 3.
TR [C]
Y
C
H
Q34
Q24
10385D53
Y
TR
SpH
SpC
H
C
YM
Q14
Q24
SpC
Q14
SpH
SpC
TR [C]
49/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Function
Brief description)
Fan control.
Temperature measurement.
Room operating modes.
Setpoint shift.
General functions.
Room units.
Compatible controllers.
PI control.
Two proportional control sequences, heating and cooling.
Control of motorized damper actuators (AC 24 V, 3-position).
1 ... 3-speed, automatic, or
Manual with room unit.
Room temperature sensor or
Return air sensor.
Comfort, Precomfort, Economy and Protection mode..
Change of operating mode via /Auto switch on room unit, presence detector,
window contact or central command.
Locally via room unit or centrally.
Presence detector.
Window switch.
Master/slave operation.
Boost heating, night cooling etc.
Free inputs/outputs.
Available with temperature sensor, setpoint adjuster,
/Auto and fan speed control, and LCD display.
button for
FNC20 is supplied with RXB21.1/FC-10.
KNX
Connection diagram
D2
2)
YM
3)
R1
Y1
Y2
CE
N1
CE+
CP+
Q34
Q24
Q14
Q13
17 18
RXB21.1
25 26 27 28
D2
GND
19 19 21 21
10 11 12 13 14 15 16
Y4
CP
Y2
Y3
Y1
6
D1
N.C.
B1
QAX...
CE
2)
CE+
D1
B1
10385A10
Functions
Q1
AC 230 V
N
L
2)
3)
4)
50/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Ref.
N1
R1
B1
D1
D2
Q1
YM
List of equipment
2)
3)
4)
Note
Configuration
Menu
Description
Room controller.
Room unit
Return air temperature sensor, room temperature sensor.
Window contact 2).
Presence detector 2).
1- or 3-speed fan 4).
3-position damper actuator, AC 24 V 3).
Type of operation (N/O or N/C) can be selected.
Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873).
Do not connect the fans in parallel (or use cut-off relays).
Communication
Communication mode
Receive timeout
Send heartbeat
Room temperature setpoints
Protection cooling setpoint
Economy cooling setpoint
Precomfort cooling setpoint
Comfort cooling setpoint
Comfort heating setpoint
Precomfort heating setpoint
Economy heating setpoint
Protection heating setpoint
Sequences
Damper setting
Running time damper heating
Running time damper cooling
Switchover period H/C
LTE mode Heating outp bus valve
Cooling outp bus valve
Fan control.
Fan speeds
Fan control.
Minimum on time.
Temperature sensor B1
Room unit
Values/Range
Basic setting
S-mode.
60 min.
45 min.
40 C
35 C
28 C
24 C
21 C
19 C
15 C
12 C
0 300 sec
0 300 sec
0 300 sec
Off/On
150 sec
150 sec
0 sec
Off
Off/On
External control
1-speed/2-speed/3-speed
Manual / Auto
1 ... 10 min
Room
Return air
Measured value only
No sensor
0 ... 90 min (90min = Off)
0 ... 360 min (360min = Off)
3 ... 3 K
0 ... 10 K
Enabled / Disabled
Without LCD / with LCD
Enabled / Disabled
C or F
No display / Room
temperature / Setpoint
Absolute / Relative
Off
3-speed
Auto
6 min
No sensor
90 min (Off)
360 min (Off)
0K
3K
Enabled
Without LCD
Enabled
C
Room temperature.
Relative
51/52
Siemens
Building Technologies
CM110672en_03
30.11.2007
Menu
Parameters.
General functions.
Digital input 1
Values/Range
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
Digital input 2
Free (bus = 1)
= Contact open/closed
Occupancy: Occupied
= Contact open/closed
Window:
Window open
= Contact open/closed
Temporary Comfort mode
0 ... 360 min
Central functions
Master/slave
Basic setting
Free (bus = 1)
= Contact closed.
Free (bus = 1)
= Contact closed.
60 min
0 ... 90 min
5 min
0 ... 90 min
5 min
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Master or slave
Enabled
Enabled
Enabled
Enabled
Disabled
Master
Ordering
The room controllers can be ordered preloaded with the application described here.
When ordering, specify the quantity, DESIGO RXB device name, type code and
application group.
Example
15
Note
RXB21.1/FC-10
The controllers are delivered with the basic settings shown above.
52/52
Siemens
Building Technologies
CM110672en_03