Fire dampers

Type FV-EU

CE compliant according to
European regulations

Fire protection valves for supply and extract air


Circular fire protection valve for the isolation of duct penetrations between
fire compartments; suitable for supply air and extract air systems.
They also satisfy ventilation requirements
Nominal sizes 100, 125, 160, 200 mm
For installation in walls and ceilings
Low differential pressure and sound power level
Integration into the central BMS with TROXNETCOM

With TROXNETCOM
as an option

H GE

Trim ring, circular or square

TE

ET

HY

ISC

Extension piece

ST

EN

Optional equipment and accessories


Electric limit switch

VD

I 6022

Tested to VDI 6022

01/2015 DE/en

K4 1.1 1

Fire dampers

TOC

General information

FV-EU

Type

FV-EU

Variant

Page
General information
Correct use
Order code
Trim ring / Installation kit
Flexible connector
Limit switch
Installation details Solid walls
Installation details Solid ceiling slabs
Installation details Lightweight partition walls
Dimensions and weight
Specification text
Basic information and nomenclature

1.1 2
1.1 5
1.1 6
1.1 7
1.1 8
1.1 9
1.1 10
1.1 11
1.1 12
1.1 14
1.1 15
1.3 1

FV-EU

Product example

Description

Application
Fire protection valves of Type FV-EU,
with CE marking and declaration of
performance, for the isolation of duct
penetrations between fire compartments
in the event of a fire
To prevent the propagation of fire and smoke
through ductwork to adjacent designated
fire compartments

FV-EU

Classification
Class of performance to EN 13501-3,
up to EI 120 (ve, ho, i o) S

For detailed information


on attachments
see Chapter K4 1.2.

Variants
With fusible link
With fusible link and limit switch
Nominal sizes
100, 125, 160, 200 mm
L: 150 mm
Attachments
Limit switch for capturing the valve position
Accessories
Mortar-based installation
Trim ring, circular
Trim ring, square

K4 1.1 2

Special characteristics
Declaration of performance according to
Construction Products Regulation
Classification to EN 13501-3,
up to EI 120 (ve, ho, i o) S
Building inspectorate licence Z-56.4212-991,
non-combustible and non-hazardous to health
Complies with the requirements of EN 15650
Tested to EN 1366-2 for
fire resistance properties
Hygiene complies with VDI 6022
part 1 (07/2011), VDI 3803 (10/2002),
DIN 1946 part 4 (12/2008),
and EN 13779 (09/2007)
Corrosion protection according to EN 15650
in connection with EN 60068-2-52
Closed valve cone air leakage to EN 1751,
class 2
Low differential pressure
and sound power level
Any airflow direction
Construction features
Adjustment device for large
or small air volumes
Valve cone with bayonet fixing

01/2015 DE/en

Fire dampers

TOC

General information
Materials and surfaces
Installation subframe, spigot and valve disc
made of sheet steel
Installation subframe and spigot with
stove-enamelled finish, black
Exposed surface of valve disc powder-coated
RAL 9010
Valve cone made of special insulation material
Seal made of polyurethane
Attachments made of galvanised steel
Increased corrosion protection due to
powder-coated casing
Installation and commissioning
Install the fire damper according to the operating
and installation manual.

FV-EU
Maintenance
The functional reliability of the fire protection
valve must be tested at least every six months;
this has to be arranged by the owner of the
ventilation system; functional tests must be
carried out in compliance with the basic
maintenance principles stated in EN 13306
and DIN 31051. If two consecutive tests,
one 6 months after the other, are successful,
the next test can be conducted one year later.
Fire protection valves must be included
in the regular cleaning schedule
of the ventilation system
For details on maintenance and inspection,
refer to the installation and operating manual

Mortar-based installation:
In solid walls and ceiling slabs
In lightweight partition walls with metal support
structure and cladding on both sides
Standards and guidelines
Construction Products Regulation
EN 15650:
2010 Ventilation for buildings fire dampers
EN 1366-2-1999 Fire resistance tests for
service installations Fire dampers
EN 13501-3:2010 Fire classification of
construction products and building elements
EN 1751:1999 Ventilation for buildings
Air terminal devices

Technical data

01/2015 DE/en

Nominal sizes
Casing length
Release temperature
Operating temperature
Volume flow rate range

100, 125, 160, 200 mm


150 mm (320 mm with extension)
72 C
0 50 C
Extract air up to 350 m/h or supply air up to 400 m/h

K4 1.1 3

Fire dampers

TOC

General information

Function
Construction
with fusible link

FV-EU

Functional description
In the event of a fire, fire protection valves shut
automatically to prevent the propagation of fire
and smoke through ductwork to adjacent
designated fire compartments.
In the event of a fire, the valve is triggered at 72 C
by a fusible link. The release mechanism is
accessible and can be tested from the outside.
Schematic illustration of the FV-EU with extension piece and limit switches

Installation subframe (subframe


and fixing material are supplied separate)
Spigot
Valve cone
Flat springs
Fusible link 72 C
Spring (for closure)
Seal

K4 1.1 4

Valve disc with seal


Adjustment device (position 1:
large air volume; position 2: small air volume)
Bayonet fixing
Extension piece
Sheet metal cover
Limit switch, indicating OPEN
Limit switch, indicating CLOSED

01/2015 DE/en

Fire dampers

TOC

Correct use

FV-EU
Design information
Approved only for use in ventilation
and air conditioning sytems
Ducting must be installed in such a manner
that it does not impose any significant loads
on the fire protection valve in the event of a fire
For particular applications it is recommended
that flexible connectors are used to connect
rigid ducting to the unit

Correct use
Installation location

Construction
and building material

Minimum
Performance class
thickness
Mortar-based Dry mortarless
installation
installation
mm
EI TT (ve, ho, i o) S

Solid walls
Solid walls,
gross density 500 kg/m

100

EI 120 S

Solid ceiling slabs,


gross density 600 kg/m

150

EI 120 S

Lightweight partition walls

100

EI 120 S

Solid ceiling slabs

Lightweight
partition walls
with metal
support structure
and cladding
on both sides

N = Mortar-based installation

01/2015 DE/en

K4 1.1 5

Fire dampers

TOC

Order code

Order code

FV-EU
FV-EU

FV EU / DE / 160 / R / Z05

Type
FV-EU Fire protection valve
Country of destination
DE
Germany
Other destination countries upon request
Nominal size [mm]
100
125
160
200
Order examples

Accessories
No entry: none
R
Trim ring - circular
Trim ring - square
Q
Attachments
Z04 Z07

FV-EU
Make
Type

TROX
FV-EU / DE / 160

FV-EU with circular trim ring, extension piece and limit switch for indicating CLOSED
Make
Type

K4 1.1 6

TROX
FV-EU / DE / 160 / R / Z05

01/2015 DE/en

Accessories 1

TOC

Trim ring / Installation kit


Description

/ R
/ Q

Order code detail

FV-EU

Application
For mortar-based installation
a trim ring may be used.

Materials and surfaces


Trim ring, circular or square,
made of galvanised sheet steel,
powder-coated RAL 9010

Accessories
Mortar-based installation

Dry mortarless installation

Trim ring, circular


Trim ring, square

Order code

R
Q

FV-EU with trim ring (mortar-based installation)

D5





Trim ring, circular or square


Screw fixing, by others, pitch circle = D5
Nominal size
A / A
D5

01/2015 DE/en

100

Solid wall or lightweight partition wall

125
200
270

160
200
295

200
250
330

300
370

K4 1.1 7

Accessories 2

TOC

Flexible connector
Application
Ducting must be installed in such a manner
that it does not impose any significant loads
on the fire protection valve in the event of a fire
For information on how to limit such loads
please refer to the guideline regarding fire
protection requirements on ventilation systems
(Lftungsanlagen-Richtlinie, LAR)
As ducts may expand and walls may
become deformed in the event of a fire,
flexible connectors should be used when
connecting the unit to rigid ducting for
installation into lightweight partition walls
Flexible connectors should be installed
in such a way that they can compensate
both tension and compression
Flexible ducts can be used as an alternative
Flexible connectors
are to be ordered separately

Materials and surfaces


Flexible connectors made of
fibre-reinforced plastic
Fire resistance properties to 4102; B2

Flexible connector
215

Description

FV-EU

~ 200*

* flexible length 100 mm when installed

K4 1.1 8

01/2015 DE/en

Attachments

TOC

Limit switch
Description

Limit switch

FV-EU
Application
Limit switches with volt-free contacts
enable the valve position indication
Up to the maximum switch rating,
relays or indicator lights for fire alarm
systems can be used
One limit switch each is required for damper
blade positions OPEN and CLOSED
Fire protection valves can be supplied with
one or two limit switches; the switches can
also be fitted later
Limit switches require an extension piece

For detailed information


on limit switches
see Chapter 1.2

/
/
/
/

Z04
Z05
Z06
Z07

Extension piece

Z04

Extension piece Z04 and limit switch for indicating CLOSED

Z05

Extension piece Z04 and limit switch for indicating OPEN

Z06

Order code detail

Extension piece Z04 and limit switches for indicating CLOSED and OPEN

Z07

Technical data

Limit switch

Attachments

Connecting cable length/cross section


Protection level
IEC protection class
Maximum switching current
Maximum switching voltage

Wiring Examples

Order code

2 m/3 0.75 mm
IP 56
I with protective earth; III without protective earth
5A
30 V DC, 250 V AC

CLOSED or OPEN position reached


limit switch is actuated

CLOSED or OPEN position not reached


limit switch is not actuated

3 30 V DC
230 V AC/DC
N(-)
230 V

3 30 V DC
230 V AC/DC

L(+)

N(-)

GY

BN
BK

BK

Indicator light or relay,


to be provided by others
NO contact:
grey/black

01/2015 DE/en

L(+)

230 V

Indicator light or relay,


to be provided by others
NC contact:
brown/black

K4 1.1 9

Fire dampers

TOC

Installation details Solid walls


Mortar-based
installation, with
perimeter mortar infill

Installation location
In solid walls
Solid fire walls
Construction and building material
Concrete, aerated concrete or solid gypsum
wallboards to EN 12859 (without open spaces)
Minimum thickness 100 mm
Gross density 500 kg/m
Installation type
Mortar-based installation,
with perimeter mortar infill
Requirements
Minimum distance between
two fire protection valves: 200 mm
Minimum distance to load-bearing
structural elements: 75 mm

Installation information
An opening or a cut hole (circular or square)
of the nominal size plus 80 mm is required;
alternatively, the fire protection valve can be
concreted into the wall during construction
Completely close off gap s with one of the
following: mortar of group II, IIa, III or IIIa
according to DIN 1053; fire protection mortar
of group II or III or equivalent according to
EN 998-2 (classes M 2.5 to 10); fire protection
mortar of class M 2.5 to 10; gypsum mortar;
or, if necessary, concrete
An extension piece is required if the thickness
of the wall exceeds 115 mm
Fire protection valves must be installed,
connected and secured according to
the operating and installation manual.

Wall installation

Wall installation
W

A / A

In solid walls

FV-EU

W: 100 115 mm
Mortar, concrete or gypsum mortar
3 fixing tabs, one every 120

W > 115 mm
Mortar, concrete or gypsum mortar
3 fixing tabs, one every 120
Extension piece

Dimensions of installation opening [mm]


Nominal size
A/A

K4 1.1 10

100

125
200

160
200

200
250

300

01/2015 DE/en

Fire dampers

TOC

Installation details Solid ceiling slabs


In solid ceiling slabs
Mortar-based
installation, with
perimeter mortar infill

FV-EU
Installation information
An opening or a cut hole (circular or square)
of the nominal size plus 80 mm is required;
alternatively, the fire protection valve
can be concreted into the ceiling slab
during construction
Completely close off gap s with one of
the following: mortar of group II, IIa, III or IIIa
according to DIN 1053; fire protection mortar
of group II or III or equivalent according to
EN 998-2 (classes M 2.5 to 10); fire protection
mortar of class M 2.5 to 10; gypsum mortar;
or, if necessary, concrete
Extension piece, if required

Installation location
In solid ceiling slabs
Construction and building material
Concrete or aerated concrete
Gross density 600 kg/m
Minimum thickness 150 mm
Installation type
Mortar-based installation,
with perimeter mortar infill
Requirements
Minimum distance to load-bearing
structural elements: 75 mm
Minimum distance between
two fire protection valves: 200 mm

Fire protection valves must be installed,


connected and secured according to
the operating and installation manual.

Ceiling slab installation, upright

Ceiling slab installation, suspended


s



D 150 mm
Mortar, concrete or gypsum mortar
3 fixing tabs, one every 120
Extension piece

D 150 mm
Mortar, concrete or gypsum mortar
3 fixing tabs, one every 120
Extension piece

Dimensions of installation opening [mm]


Nominal size
A/A

01/2015 DE/en

100

125
200

160
200

200
250

300

K4 1.1 11

Fire dampers

TOC

Installation details Lightweight partition walls

Mortar-based
installation, with
perimeter mortar infill

Installation location
In lightweight partition walls with metal support
structure and cladding on both sides
Construction and building material
Metal support structure
Cladding on both sides
Installation type
Mortar-based installation,
with perimeter mortar infill
Requirements
Minimum distance to load-bearing
structural elements: 75 mm
Minimum distance between
two fire protection valves: 200 mm
Lightweight partition walls with a metal
support structure and cladding on both sides,
with European classification to EN 13501-3
or equivalent national classification
Cladding on both sides made of gypsum
bonded or cement bonded panel materials
Wall thickness W 100 mm
Additional layers of cladding
or double stud systems are approved
Installation details upon request
Mortar-based installation

Installation information
An opening or a cut hole of the nominal size
plus 80 mm is required
Completely close off gap s with one of
the following: mortar of group II, IIa, III or IIIa
according to DIN 1053; fire protection mortar
of group II or III or equivalent according to
EN 998-2 (classes M 2.5 to 10); fire protection
mortar of class M 2.5 to 10; gypsum mortar;
or, if necessary, concrete
An extension piece is required if the thickness
of the wall exceeds 115 mm
Fire protection valves must be installed,
connected and secured according to
the operating and installation manual.

Metal support structure, examples



D5

In lightweight
partition walls
with metal support
structure and cladding
on both sides

FV-EU



Mortar or plaster
Trim ring, circular or square
Screw fixing, by others, pitch circle = D5
3 fixing tabs, one every 120

K4 1.1 12

01/2015 DE/en

Fire dampers

TOC

Installation details Lightweight partition walls

FV-EU

Metal support structure, examples

A / A1

A / A1

625

Dimensions of installation opening [mm]


Nominal size
A
D5

01/2015 DE/en

100

125
200
270

160
200
295

200
250
330

300
370

K4 1.1 13

Fire dampers

TOC

Dimensions and weight


FV-EU with extension piece and limit switch

D1

D2

A
D

FV-EU with fusible link


L ~ 320

Description

FV-EU

Dimensions [mm] / Weight [kg]


Nominal size
D
D1
D2
Weight

K4 1.1 14

100

125
98
164
158
1.7

160
123
189
183
2.2

200
158
224
218
3.0

198
264
258
4.0

01/2015 DE/en

Fire dampers

TOC

Specification text
Description
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.

Order options

Fire protection valve for the isolation of duct


penetrations between fire compartments.
For use in supply air and extract air systems;
with two-stage adjustment device for adjusting
the air volume.
Ready-for-operation unit,
which includes a fire-resistant valve cone
and a release mechanism.
Tested for fire resistance properties to EN 1366-2,
with CE marking and declaration
of performance according to
the Construction Products Regulation.
For mortar-based installation into solid walls
and ceiling slabs, and into lightweight partition
walls with metal support structure and cladding
on both sides.
Casing length of 150 mm,
or 320 mm with extension piece
For the connection to ducts made of
non-combustible or combustible materials.
Thermal release at 72 C.

Materials and surfaces


Installation subframe, spigot and valve disc
made of sheet steel
Installation subframe and spigot with
stove-enamelled finish, black
Exposed surface of valve disc powder-coated
RAL 9010
Valve cone made of special insulation material
Seal made of polyurethane
Attachments made of galvanised steel
Increased corrosion protection due to
powder-coated casing

Special characteristics
Declaration of performance according to
Construction Products Regulation
Classification to EN 13501-3,
up to EI 120 (ve, ho, i o) S
Building inspectorate licence Z-56.4212-991,
non-combustible and non-hazardous to health
Complies with the requirements of EN 15650
Tested to EN 1366-2 for
fire resistance properties
Hygiene complies with VDI 6022
part 1 (07/2011), VDI 3803 (10/2002),
DIN 1946 part 4 (12/2008),
and EN 13779 (09/2007)
Corrosion protection according to EN 15650
in connection with EN 60068-2-52
Closed valve cone air leakage to EN 1751,
class 2
Low differential pressure
and sound power level
Any airflow direction

Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LWA Air-regenerated noise __________ [dB(A)]

Type
FV-EU Fire protection valve

Accessories
No entry: none
R
Trim ring - circular
Q
Trim ring - square

Country of destination
DE
Germany
Other destination countries upon request
Nominal size [mm]
100
125
160
200

01/2015 DE/en

FV-EU

Technical data
Nominal sizes: 100, 125, 160, 200 mm
Casing length:
150 mm, or 320 mm with extension piece
Release temperature: 72 C
Operating temperature: 10 to 50 C
Volume flow rate range: Extract air up to
350 m/h or supply air up to 400 m/h

Attachments
Z04 Z07

K4 1.1 15

TOC

1.3

X X Basic

information and nomenclaturetestregistrierung

Fire dampers

Basic information
and nomenclature

Product selection
Principal dimensions
Nomenclature
Colour codes according to IEC 60757
Sizing

01/2015 DE/en

K4 1.3 1

Fire dampers

TOC

Basic information and nomenclature

Product selection
Fire dampers
Application

Type
FK-EU

Installation
location

Minimum
Construction/ thickness
building material

Mortarbased
installation
perimeter

part
-ially

FKS-EU

Dry
mortarless
installation
Fire
batt

Installation
kit

mm
In solid walls
In solid walls
with flexible gap
On the face
of solid walls
Adjacent to
solid walls
Remote from
solid walls
In solid ceiling
slabs

Walls/gross
density 500 kg/m
Walls/gross
density 500 kg/m
Walls/gross
density 500 kg/m
Walls/gross
density 500 kg/m
Walls/gross
density 500 kg/m
Ceiling slabs/gross
density 600 kg/m
Ceiling slabs/gross
density 600 kg/m

FKR-EU

MortarDry
MortarDry
based
mortarless
based
mortarless
installation installation installation installation
perimeter

Installation
kit

perimeter

Installation
kit

Fire resistance class

100

EI 90 S EI 90 S EI 120 S

EI 90 S

EI 120 S

EI 90 S

EI 120 S

100

EI 90 S

100

EI 90 S

100

EI 90 S

100

EI 90 S

125

EI 90 S

150

EI 90 S

EI 120 S

EI 90 S

EI 120 S

In
Ceiling slabs/gross
solid ceiling slabs,
125
EI 90 S
density 600 kg/m
with concrete base
Lightweight
partition walls
with metal support
Lightweight
100
EI 90 S
structure and
partition walls
cladding
on both sides
Lightweight
partition walls
with metal support
structure and
Lightweight
100

cladding
partition walls
on both sides,
flexible ceiling
joint
Fire walls
with metal support
structure and
Fire walls
115
EI 90 S
cladding
on both sides
Lightweight
partition walls
with metal support
Shaft walls
90

structure and
cladding
on one side
Lightweight
partition walls
without metal
Shaft walls
40 or 50

support structure
but with cladding
on one side
Tile ceilings, screw

fixed and primed


In self supporting
Lay-in ceiling tiles
fire-resistant
made of panel

suspended ceilings
materials
Metal ceilings

EI 120 S

EI 90 S

EI 90 S

EI 120 S

EI 90 S

EI 90 S

EI 90 S

EI 90 S

EI 90 S

EI 90 S

EI 90 S

EI 90 S

EI 90 S

EI 90 S

EI 90 S

EI 90 S

EI 90 S

EI 90 S

EI 90 S

EI 90 S

EI 90 S

EI 90 S

EI 90 S

Not for FK-EU as air transfer damper


Installation kit for the selected installation situation
For DN 100 to 200 in lightweight partition wall with metal support structure and mineral wool
50 only for FKR-EU
Additional mineral wool

K4 1.3 2

01/2015 DE/en

Fire dampers

TOC

Basic information and nomenclature

Product selection

Fire dampers
Application

Type
FKRS-EU

Installation
location

Construction/
building material

Mortarbased
Minimum
installation
thickness

FV-EU

Dry
mortarless
installation

In solid walls
with flexible gap
On the face
of solid walls
Adjacent to
solid walls
Remote from
solid walls
In solid ceiling
slabs
In
solid ceiling slabs,
with concrete base
Lightweight
partition walls
with metal support
structure and
cladding
on both sides
Lightweight
partition walls
with metal support
structure and
cladding
on both sides,
flexible ceiling
joint
Fire walls
with metal support
structure and
cladding
on both sides
Lightweight
partition walls
with metal support
structure and
cladding
on one side
Lightweight
partition walls
without metal
support structure
but with cladding
on one side

FVZ-K30

KU-K30

Mortarbased
installation

Installation perikit
meter

Mortarbased
installation

Dry
mortarless
Installation installation
kit

perimeter

Fire
batt

100

EI 120 S

EI 120 S,
EI 90 S

EI 90 S

EI 120 S

K90

100

100

EI 90 S

EI 90 S

100

100

125

150

EI 120 S

EI 120 S,
EI 90 S

EI 90 S

EI 120 S

K90

Ceiling slabs/gross
density 600 kg/m

125

Lightweight
partition walls

100

EI 120 S,
EI 90 S

K90

Lightweight
partition walls

100

EI 90 S

Fire walls

115

EI 90 S

EI 90 S

K90

Shaft walls

90

EI 90 S

EI 90 S

Shaft walls

40 or 50

K30-U

K30-U

K30-U

K30-U

K30-U

K30-U

mm
In solid walls

KA-EU

Walls/gross
density 500 kg/m
Walls/gross
density 500 kg/m
Walls/gross
density 500 kg/m
Walls/gross
density 500 kg/m
Walls/gross
density 500 kg/m
Ceiling slabs/gross
density 600 kg/m
Ceiling slabs/gross
density 600 kg/m

Tile ceilings, screwfixed and primed


In self supporting
fire-resistant
Lay-in ceiling tiles made
suspended ceilings
of panel materials
Metal ceilings

Fire resistance class

EI 120 S, EI 120 S,
EI 120 S
EI 90 S
EI 90 S

Not for FK-EU as air transfer damper


Installation kit for the selected installation situation
For DN 100 to 200 in lightweight partition wall with metal support structure and mineral wool
50 only for FKR-EU
Additional mineral wool

01/2015 DE/en

K4 1.3 3

Fire dampers

TOC

Basic information and nomenclature

Principal dimensions

Nomenclature

Rectangular fire dampers

Circular fire dampers

B [mm]
Width of the fire damper

Nominal size [mm]


Diameter of the fire damper

H [mm]
Height of the fire damper

L [mm]
Length of the fire damper

[m/h] and [l/s]


Volume flow rate

pst [Pa]
Static differential pressure

LWA [dB(A)]
A-weighted sound power level
of air-regenerated noise
for the fire damper

v [m/s]
Airflow velocity based on
the upstream cross section (B H or diameter)
K
Correction value

A [m]
Free area

Resistance coefficient (fully ducted)


Wiring

Colour codes according to IEC 60757


Code
BK
BN
RD
OG
YE
GN
BU

Sizing
with the help
of this catalogue

Colour codes according to IEC 60757

Colour

Code
black
brown
red
orange
yellow
green
blue

VT
GY
WH
PK
TQ
GNYE

Colour
violet
grey
white
pink
turquoise
green-yellow

This catalogue provides convenient quick sizing


tables for fire dampers.
The volume flow rates for all available dimensions
and nominal sizes are provided based on a
particular differential pressure.
Sizing data for other volume flow rates and
differential pressures can be determined quickly
and precisely using the Easy Product Finder
design programme.

Easy Product Finder

The Easy Product Finder


allows you to size
products using your
project-specific data.
You will find
the Easy Product Finder
on our website.

K4 1.3 6

01/2015 DE/en