Fire dampers
Type FV-EU
CE compliant according to
European regulations
With TROXNETCOM
as an option
H GE
TE
ET
HY
ISC
Extension piece
ST
EN
VD
I 6022
01/2015 DE/en
K4 1.1 1
Fire dampers
TOC
General information
FV-EU
Type
FV-EU
Variant
Page
General information
Correct use
Order code
Trim ring / Installation kit
Flexible connector
Limit switch
Installation details Solid walls
Installation details Solid ceiling slabs
Installation details Lightweight partition walls
Dimensions and weight
Specification text
Basic information and nomenclature
1.1 2
1.1 5
1.1 6
1.1 7
1.1 8
1.1 9
1.1 10
1.1 11
1.1 12
1.1 14
1.1 15
1.3 1
FV-EU
Product example
Description
Application
Fire protection valves of Type FV-EU,
with CE marking and declaration of
performance, for the isolation of duct
penetrations between fire compartments
in the event of a fire
To prevent the propagation of fire and smoke
through ductwork to adjacent designated
fire compartments
FV-EU
Classification
Class of performance to EN 13501-3,
up to EI 120 (ve, ho, i o) S
Variants
With fusible link
With fusible link and limit switch
Nominal sizes
100, 125, 160, 200 mm
L: 150 mm
Attachments
Limit switch for capturing the valve position
Accessories
Mortar-based installation
Trim ring, circular
Trim ring, square
K4 1.1 2
Special characteristics
Declaration of performance according to
Construction Products Regulation
Classification to EN 13501-3,
up to EI 120 (ve, ho, i o) S
Building inspectorate licence Z-56.4212-991,
non-combustible and non-hazardous to health
Complies with the requirements of EN 15650
Tested to EN 1366-2 for
fire resistance properties
Hygiene complies with VDI 6022
part 1 (07/2011), VDI 3803 (10/2002),
DIN 1946 part 4 (12/2008),
and EN 13779 (09/2007)
Corrosion protection according to EN 15650
in connection with EN 60068-2-52
Closed valve cone air leakage to EN 1751,
class 2
Low differential pressure
and sound power level
Any airflow direction
Construction features
Adjustment device for large
or small air volumes
Valve cone with bayonet fixing
01/2015 DE/en
Fire dampers
TOC
General information
Materials and surfaces
Installation subframe, spigot and valve disc
made of sheet steel
Installation subframe and spigot with
stove-enamelled finish, black
Exposed surface of valve disc powder-coated
RAL 9010
Valve cone made of special insulation material
Seal made of polyurethane
Attachments made of galvanised steel
Increased corrosion protection due to
powder-coated casing
Installation and commissioning
Install the fire damper according to the operating
and installation manual.
FV-EU
Maintenance
The functional reliability of the fire protection
valve must be tested at least every six months;
this has to be arranged by the owner of the
ventilation system; functional tests must be
carried out in compliance with the basic
maintenance principles stated in EN 13306
and DIN 31051. If two consecutive tests,
one 6 months after the other, are successful,
the next test can be conducted one year later.
Fire protection valves must be included
in the regular cleaning schedule
of the ventilation system
For details on maintenance and inspection,
refer to the installation and operating manual
Mortar-based installation:
In solid walls and ceiling slabs
In lightweight partition walls with metal support
structure and cladding on both sides
Standards and guidelines
Construction Products Regulation
EN 15650:
2010 Ventilation for buildings fire dampers
EN 1366-2-1999 Fire resistance tests for
service installations Fire dampers
EN 13501-3:2010 Fire classification of
construction products and building elements
EN 1751:1999 Ventilation for buildings
Air terminal devices
Technical data
01/2015 DE/en
Nominal sizes
Casing length
Release temperature
Operating temperature
Volume flow rate range
K4 1.1 3
Fire dampers
TOC
General information
Function
Construction
with fusible link
FV-EU
Functional description
In the event of a fire, fire protection valves shut
automatically to prevent the propagation of fire
and smoke through ductwork to adjacent
designated fire compartments.
In the event of a fire, the valve is triggered at 72 C
by a fusible link. The release mechanism is
accessible and can be tested from the outside.
Schematic illustration of the FV-EU with extension piece and limit switches
K4 1.1 4
01/2015 DE/en
Fire dampers
TOC
Correct use
FV-EU
Design information
Approved only for use in ventilation
and air conditioning sytems
Ducting must be installed in such a manner
that it does not impose any significant loads
on the fire protection valve in the event of a fire
For particular applications it is recommended
that flexible connectors are used to connect
rigid ducting to the unit
Correct use
Installation location
Construction
and building material
Minimum
Performance class
thickness
Mortar-based Dry mortarless
installation
installation
mm
EI TT (ve, ho, i o) S
Solid walls
Solid walls,
gross density 500 kg/m
100
EI 120 S
150
EI 120 S
100
EI 120 S
Lightweight
partition walls
with metal
support structure
and cladding
on both sides
N = Mortar-based installation
01/2015 DE/en
K4 1.1 5
Fire dampers
TOC
Order code
Order code
FV-EU
FV-EU
FV EU / DE / 160 / R / Z05
Type
FV-EU Fire protection valve
Country of destination
DE
Germany
Other destination countries upon request
Nominal size [mm]
100
125
160
200
Order examples
Accessories
No entry: none
R
Trim ring - circular
Trim ring - square
Q
Attachments
Z04 Z07
FV-EU
Make
Type
TROX
FV-EU / DE / 160
FV-EU with circular trim ring, extension piece and limit switch for indicating CLOSED
Make
Type
K4 1.1 6
TROX
FV-EU / DE / 160 / R / Z05
01/2015 DE/en
Accessories 1
TOC
/ R
/ Q
FV-EU
Application
For mortar-based installation
a trim ring may be used.
Accessories
Mortar-based installation
Order code
R
Q
D5
01/2015 DE/en
100
125
200
270
160
200
295
200
250
330
300
370
K4 1.1 7
Accessories 2
TOC
Flexible connector
Application
Ducting must be installed in such a manner
that it does not impose any significant loads
on the fire protection valve in the event of a fire
For information on how to limit such loads
please refer to the guideline regarding fire
protection requirements on ventilation systems
(Lftungsanlagen-Richtlinie, LAR)
As ducts may expand and walls may
become deformed in the event of a fire,
flexible connectors should be used when
connecting the unit to rigid ducting for
installation into lightweight partition walls
Flexible connectors should be installed
in such a way that they can compensate
both tension and compression
Flexible ducts can be used as an alternative
Flexible connectors
are to be ordered separately
Flexible connector
215
Description
FV-EU
~ 200*
K4 1.1 8
01/2015 DE/en
Attachments
TOC
Limit switch
Description
Limit switch
FV-EU
Application
Limit switches with volt-free contacts
enable the valve position indication
Up to the maximum switch rating,
relays or indicator lights for fire alarm
systems can be used
One limit switch each is required for damper
blade positions OPEN and CLOSED
Fire protection valves can be supplied with
one or two limit switches; the switches can
also be fitted later
Limit switches require an extension piece
/
/
/
/
Z04
Z05
Z06
Z07
Extension piece
Z04
Z05
Z06
Extension piece Z04 and limit switches for indicating CLOSED and OPEN
Z07
Technical data
Limit switch
Attachments
Wiring Examples
Order code
2 m/3 0.75 mm
IP 56
I with protective earth; III without protective earth
5A
30 V DC, 250 V AC
3 30 V DC
230 V AC/DC
N(-)
230 V
3 30 V DC
230 V AC/DC
L(+)
N(-)
GY
BN
BK
BK
01/2015 DE/en
L(+)
230 V
K4 1.1 9
Fire dampers
TOC
Installation location
In solid walls
Solid fire walls
Construction and building material
Concrete, aerated concrete or solid gypsum
wallboards to EN 12859 (without open spaces)
Minimum thickness 100 mm
Gross density 500 kg/m
Installation type
Mortar-based installation,
with perimeter mortar infill
Requirements
Minimum distance between
two fire protection valves: 200 mm
Minimum distance to load-bearing
structural elements: 75 mm
Installation information
An opening or a cut hole (circular or square)
of the nominal size plus 80 mm is required;
alternatively, the fire protection valve can be
concreted into the wall during construction
Completely close off gap s with one of the
following: mortar of group II, IIa, III or IIIa
according to DIN 1053; fire protection mortar
of group II or III or equivalent according to
EN 998-2 (classes M 2.5 to 10); fire protection
mortar of class M 2.5 to 10; gypsum mortar;
or, if necessary, concrete
An extension piece is required if the thickness
of the wall exceeds 115 mm
Fire protection valves must be installed,
connected and secured according to
the operating and installation manual.
Wall installation
Wall installation
W
A / A
In solid walls
FV-EU
W: 100 115 mm
Mortar, concrete or gypsum mortar
3 fixing tabs, one every 120
W > 115 mm
Mortar, concrete or gypsum mortar
3 fixing tabs, one every 120
Extension piece
K4 1.1 10
100
125
200
160
200
200
250
300
01/2015 DE/en
Fire dampers
TOC
FV-EU
Installation information
An opening or a cut hole (circular or square)
of the nominal size plus 80 mm is required;
alternatively, the fire protection valve
can be concreted into the ceiling slab
during construction
Completely close off gap s with one of
the following: mortar of group II, IIa, III or IIIa
according to DIN 1053; fire protection mortar
of group II or III or equivalent according to
EN 998-2 (classes M 2.5 to 10); fire protection
mortar of class M 2.5 to 10; gypsum mortar;
or, if necessary, concrete
Extension piece, if required
Installation location
In solid ceiling slabs
Construction and building material
Concrete or aerated concrete
Gross density 600 kg/m
Minimum thickness 150 mm
Installation type
Mortar-based installation,
with perimeter mortar infill
Requirements
Minimum distance to load-bearing
structural elements: 75 mm
Minimum distance between
two fire protection valves: 200 mm
s
D 150 mm
Mortar, concrete or gypsum mortar
3 fixing tabs, one every 120
Extension piece
D 150 mm
Mortar, concrete or gypsum mortar
3 fixing tabs, one every 120
Extension piece
01/2015 DE/en
100
125
200
160
200
200
250
300
K4 1.1 11
Fire dampers
TOC
Mortar-based
installation, with
perimeter mortar infill
Installation location
In lightweight partition walls with metal support
structure and cladding on both sides
Construction and building material
Metal support structure
Cladding on both sides
Installation type
Mortar-based installation,
with perimeter mortar infill
Requirements
Minimum distance to load-bearing
structural elements: 75 mm
Minimum distance between
two fire protection valves: 200 mm
Lightweight partition walls with a metal
support structure and cladding on both sides,
with European classification to EN 13501-3
or equivalent national classification
Cladding on both sides made of gypsum
bonded or cement bonded panel materials
Wall thickness W 100 mm
Additional layers of cladding
or double stud systems are approved
Installation details upon request
Mortar-based installation
Installation information
An opening or a cut hole of the nominal size
plus 80 mm is required
Completely close off gap s with one of
the following: mortar of group II, IIa, III or IIIa
according to DIN 1053; fire protection mortar
of group II or III or equivalent according to
EN 998-2 (classes M 2.5 to 10); fire protection
mortar of class M 2.5 to 10; gypsum mortar;
or, if necessary, concrete
An extension piece is required if the thickness
of the wall exceeds 115 mm
Fire protection valves must be installed,
connected and secured according to
the operating and installation manual.
D5
In lightweight
partition walls
with metal support
structure and cladding
on both sides
FV-EU
Mortar or plaster
Trim ring, circular or square
Screw fixing, by others, pitch circle = D5
3 fixing tabs, one every 120
K4 1.1 12
01/2015 DE/en
Fire dampers
TOC
FV-EU
A / A1
A / A1
625
01/2015 DE/en
100
125
200
270
160
200
295
200
250
330
300
370
K4 1.1 13
Fire dampers
TOC
D1
D2
A
D
Description
FV-EU
K4 1.1 14
100
125
98
164
158
1.7
160
123
189
183
2.2
200
158
224
218
3.0
198
264
258
4.0
01/2015 DE/en
Fire dampers
TOC
Specification text
Description
This specification text
describes the general
properties of the product.
Texts for variants can be
generated with our
Easy Product Finder
design programme.
Order options
Special characteristics
Declaration of performance according to
Construction Products Regulation
Classification to EN 13501-3,
up to EI 120 (ve, ho, i o) S
Building inspectorate licence Z-56.4212-991,
non-combustible and non-hazardous to health
Complies with the requirements of EN 15650
Tested to EN 1366-2 for
fire resistance properties
Hygiene complies with VDI 6022
part 1 (07/2011), VDI 3803 (10/2002),
DIN 1946 part 4 (12/2008),
and EN 13779 (09/2007)
Corrosion protection according to EN 15650
in connection with EN 60068-2-52
Closed valve cone air leakage to EN 1751,
class 2
Low differential pressure
and sound power level
Any airflow direction
Sizing data
______________________________ [m/h]
pst ______________________________ [Pa]
LWA Air-regenerated noise __________ [dB(A)]
Type
FV-EU Fire protection valve
Accessories
No entry: none
R
Trim ring - circular
Q
Trim ring - square
Country of destination
DE
Germany
Other destination countries upon request
Nominal size [mm]
100
125
160
200
01/2015 DE/en
FV-EU
Technical data
Nominal sizes: 100, 125, 160, 200 mm
Casing length:
150 mm, or 320 mm with extension piece
Release temperature: 72 C
Operating temperature: 10 to 50 C
Volume flow rate range: Extract air up to
350 m/h or supply air up to 400 m/h
Attachments
Z04 Z07
K4 1.1 15
TOC
1.3
X X Basic
Fire dampers
Basic information
and nomenclature
Product selection
Principal dimensions
Nomenclature
Colour codes according to IEC 60757
Sizing
01/2015 DE/en
K4 1.3 1
Fire dampers
TOC
Product selection
Fire dampers
Application
Type
FK-EU
Installation
location
Minimum
Construction/ thickness
building material
Mortarbased
installation
perimeter
part
-ially
FKS-EU
Dry
mortarless
installation
Fire
batt
Installation
kit
mm
In solid walls
In solid walls
with flexible gap
On the face
of solid walls
Adjacent to
solid walls
Remote from
solid walls
In solid ceiling
slabs
Walls/gross
density 500 kg/m
Walls/gross
density 500 kg/m
Walls/gross
density 500 kg/m
Walls/gross
density 500 kg/m
Walls/gross
density 500 kg/m
Ceiling slabs/gross
density 600 kg/m
Ceiling slabs/gross
density 600 kg/m
FKR-EU
MortarDry
MortarDry
based
mortarless
based
mortarless
installation installation installation installation
perimeter
Installation
kit
perimeter
Installation
kit
100
EI 90 S EI 90 S EI 120 S
EI 90 S
EI 120 S
EI 90 S
EI 120 S
100
EI 90 S
100
EI 90 S
100
EI 90 S
100
EI 90 S
125
EI 90 S
150
EI 90 S
EI 120 S
EI 90 S
EI 120 S
In
Ceiling slabs/gross
solid ceiling slabs,
125
EI 90 S
density 600 kg/m
with concrete base
Lightweight
partition walls
with metal support
Lightweight
100
EI 90 S
structure and
partition walls
cladding
on both sides
Lightweight
partition walls
with metal support
structure and
Lightweight
100
cladding
partition walls
on both sides,
flexible ceiling
joint
Fire walls
with metal support
structure and
Fire walls
115
EI 90 S
cladding
on both sides
Lightweight
partition walls
with metal support
Shaft walls
90
structure and
cladding
on one side
Lightweight
partition walls
without metal
Shaft walls
40 or 50
support structure
but with cladding
on one side
Tile ceilings, screw
suspended ceilings
materials
Metal ceilings
EI 120 S
EI 90 S
EI 90 S
EI 120 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
EI 90 S
K4 1.3 2
01/2015 DE/en
Fire dampers
TOC
Product selection
Fire dampers
Application
Type
FKRS-EU
Installation
location
Construction/
building material
Mortarbased
Minimum
installation
thickness
FV-EU
Dry
mortarless
installation
In solid walls
with flexible gap
On the face
of solid walls
Adjacent to
solid walls
Remote from
solid walls
In solid ceiling
slabs
In
solid ceiling slabs,
with concrete base
Lightweight
partition walls
with metal support
structure and
cladding
on both sides
Lightweight
partition walls
with metal support
structure and
cladding
on both sides,
flexible ceiling
joint
Fire walls
with metal support
structure and
cladding
on both sides
Lightweight
partition walls
with metal support
structure and
cladding
on one side
Lightweight
partition walls
without metal
support structure
but with cladding
on one side
FVZ-K30
KU-K30
Mortarbased
installation
Installation perikit
meter
Mortarbased
installation
Dry
mortarless
Installation installation
kit
perimeter
Fire
batt
100
EI 120 S
EI 120 S,
EI 90 S
EI 90 S
EI 120 S
K90
100
100
EI 90 S
EI 90 S
100
100
125
150
EI 120 S
EI 120 S,
EI 90 S
EI 90 S
EI 120 S
K90
Ceiling slabs/gross
density 600 kg/m
125
Lightweight
partition walls
100
EI 120 S,
EI 90 S
K90
Lightweight
partition walls
100
EI 90 S
Fire walls
115
EI 90 S
EI 90 S
K90
Shaft walls
90
EI 90 S
EI 90 S
Shaft walls
40 or 50
K30-U
K30-U
K30-U
K30-U
K30-U
K30-U
mm
In solid walls
KA-EU
Walls/gross
density 500 kg/m
Walls/gross
density 500 kg/m
Walls/gross
density 500 kg/m
Walls/gross
density 500 kg/m
Walls/gross
density 500 kg/m
Ceiling slabs/gross
density 600 kg/m
Ceiling slabs/gross
density 600 kg/m
EI 120 S, EI 120 S,
EI 120 S
EI 90 S
EI 90 S
01/2015 DE/en
K4 1.3 3
Fire dampers
TOC
Principal dimensions
Nomenclature
B [mm]
Width of the fire damper
H [mm]
Height of the fire damper
L [mm]
Length of the fire damper
pst [Pa]
Static differential pressure
LWA [dB(A)]
A-weighted sound power level
of air-regenerated noise
for the fire damper
v [m/s]
Airflow velocity based on
the upstream cross section (B H or diameter)
K
Correction value
A [m]
Free area
Sizing
with the help
of this catalogue
Colour
Code
black
brown
red
orange
yellow
green
blue
VT
GY
WH
PK
TQ
GNYE
Colour
violet
grey
white
pink
turquoise
green-yellow
K4 1.3 6