Transformer substations in concrete
enclosures operated from the outside
1000 kVA
800 kVA
630 kVA
ABB
Table of contents
1.
2.
3.
List of figures
Fig. 01.
Fig. 02.
Fig. 03.
Fig. 04.
Fig. 05.
Fig. 06.
Exterior styles
Equipment placement
Equipment placement
Transformer installation
Cable bushings
KS...z joinery
....................... with
....................... with
....................... with
.......................... with
The substation is made as a complete, self-contained power device. It comprises a transformer, mediumvoltage switchgear and low-voltage switchboard, a measurement circuit on the medium-voltage or low-voltage
sides, cables and associated equipment; its a ready-to-use product to be placed directly in the desired location.
KS
substation designation
KS
3. Technical specifications
The substation, depending on the building type, is designed for the following equipment:
Building KS 19-28 z ( page 13)
medium-voltage switchgear: .....................
low-voltage RNTw type switchboard.......
transformer ..............................................
The supporting constructions as well as fixing and transporting fittings are metallically joined with building
reinforcement.
All metal components of the building are hot-zinc-coated.
Substation doors and ventilation grates are made of aluminium sheets and sections (or tinned steel), and painted
with polyester powder paints ( fig. 06). Ventilation doors are standard equipped with insect screens. The
door frame of the transformer room is equipped with protection railing hooks (for the upper voltage connector
transformer type), and with hooks for safety nets (for the transformers with traditional ceramic insulators).
The building roof is made of B45 type concrete ( page 18), and is fitted with threaded transportation sockets
(with PVC plugs the plugs and lifting slings for roof removal are delivered with the substation as standard).
Equipment can be installed inside the substation after removal of the roof.
The transport fittings are approved for permissible loads.
The building contain medium-voltage, low-voltage, and transformer compartments.
The medium-voltage switchgear and low-voltage switchboards are accessed after opening service doors,
separate for the medium- and low-voltage sections. The transformer is accessed after opening the transformer
room ventilation door.
The medium-voltage and low-voltage cables are passed into the building base through type P50 (P70) ( fig.
05) cable bushings or HD cable bushings.
The KS 19-28 z contains 9 type P50 (p70) cable bushings as standard for the dry medium-voltage cables,
and the low-voltage cables are run directly from the ground.
In the KS 22-30 z buildings and KS 25-36 z buildings, the medium-voltage cables, and the low-voltage cables
are run through the P70 cable bushings.
The substation building internal walls and roof are painted with white waterproof acrylic paints; the walls, base
floor and substation building floor are multi-layer painted with sealing paints. The external walls structural
plaster finish and the roof are painted with sealing paints according to the RAL colour palette.
The base trim and the roof are painted from the outside with sealing paints in the substation door colour.
The standard substation external finish is shown in fig. 01.
2800 mm
2950 mm
1740 mm
650 mm
2390 mm
6500 kg
7500 kg
9500 kg
5.35 m2
............................................................................... 3000 mm
.............................................................................. 3150 mm
................................................................................ 2200 mm
............................................................................... 2350 mm
3600 mm
3750 mm
length:
substation building........................................................................
substation roof..............................................................................
height above the ground...........................................................................
base foundation depth (including surface) ..................................................
total building height.................................................................................
substation building weight.......................................................................
equipped substation weight (without transformer)............................................
substation weight with the transformer (up to 1000 kVA) ..........................
building area.............................................................................................
2500 mm
2650 mm
1800 mm
700 mm
3320 mm
10500 kg
12000 kg
14800 kg
9 m2
IP 43
20 J
2500 N/m2
10
B
120 min
3660 MJ/ m2
2890 MJ/ m2
2165 MJ/ m2
10 to 15 m *)
The transformer substation can be located adjacent to a building, with a solid wall (no openings) towards the
building, if the distance to the window and door openings is more than 1.1 m, and the horizontal and vertical
distances from rooms with permanent presence of people is higher than 2.8 m.
KS 19-28 z
KS 22-30 z
KS 25-36 z
KS 25-36 z
(1000 kVA)
certificate no.550
certificate no.569
certificate no.569
attestation no. 021/2002
certificate no.596
..................................................................
17.5kV or 24 kV
400 V
660 V
990 A (1440 A)
1250 A (1600 A)
400 A (630 A)
40 kA
16 kA
0.5 sec
Transformer data:
transformer type
..................................................................
connector-type
(or insulators with terminal lug)
3.3.1. Standards:
EN 61330 : Prefabricated transformer high-voltage/low-voltage stations
EN 60298 : 2000 AC switchgears in metal enclosures for voltages above 1 kV.
IEC 439-1+AC : 1994 Low-voltage switchgear and controlgear. Requirements for fully and partially
tested sets.
IEC 1641 : 1996 Technical Report. Enclosed low-voltage switchgear and controlgear assemblies. Guide
for testing under conditions of arcing due to internal fault.
IEC 529 (1989) Protection provided by enclosures (IP code).
3.4.
Medium-voltage switchgears ( page 19, and the SafeRing and SafePlus catalogue)
3.5.
Low-voltage switchboard
( pages 20-22)
3.6.
Transformers
The transformer inside the substation building is standing on shock absorbing cushions, and fixed to the hooks
provided in the buildings transformer room. ( fig. 04).
The transformer is connected with the medium-voltage switchgear using three single-phase cables 1 x 50 (70)
mm2, in cross-linked polyethylene insulation for up to 20 kV voltage (one per phase). The cables from the
medium-voltage switchgear side are terminated with elbow jack heads e.g. type EASW 20/250 (type and kind of
head on the medium-voltage switchgear side is defined in the switchgear assembly and operation documentation).
10
The substation installation site must guarantee a driveway and a manoeuvre field for
a crane and truck carrying the substation.
health and safety regulations must be observed at all times
the substations must be set up by cranes with lifting capacity of more than 50%
higher than the substation weight
use only the lifting slings and traverses designed for the KS... substations
The depth of the substation foundation trench can be obtained as the total depth of the trench plus surface
thickness, as given in the infrastructure design.
KS 19-28 z ................................... total of 650 mm
KS 22-30 z ................................... total of 700 mm
KS 25-36 z ................................... total of 700 mm
After setting up the substation, the transportation holes should be secured with PVC plugs (supplied with the
substation).
5. Environmental protection
The KS...z substations do not create any ecological threat. Buildings, doors, and all associated structures are
made of environmentally friendly materials. The building base contains a leak-proof oil pit that prevents the
transformer oil permeation into soil, and ground waters through the building base.
We guarantee assistance in scrapping of accidentally damaged equipment.
(e.g.. switchgears with SF6 gas).
11
6. Warranty
The manufacturer gives a limited warranty for transformer substations, equipped as ordered, for a period of
minimum 24 months excluding other vendors equipment, which is covered by a 12-month warranty.
The manufacturer accepts no liability for damages and faults resulting from incorrect operation and usage, lack
of maintenance or improperly performed engineering works.
We guarantee assistance in choosing and commissioning of the substation, training of personnel, delivery of
spares and consumables.
7. Documentation acceptance
The KS... series transformer substations are accompanied by type
documentation
During the preparation of the transformer substation documentation, apart from the legal and formal steps
related to substation architecture and location, the following should be done:
substation electrical diagram co-ordination and design, based on technical conditions issued by the relevant
Power Distribution Company
co-ordination with the Power Distribution Administration the way and type of electric power measurements,
and design of the measuring circuit (if applicable)
design of the external distribution networks
design of the substation earthing, using natural earthings, based on soil resistivity measurements
planning of the substation assembly procedure, with regard to transportation conditions
8.
Ordering a substation
When ordering a substation, the following should be defined:
type of substation (building)
operating voltage of the medium-voltage side
type and number of bays in the medium-voltage switchgear
configuration of the RNTw low-voltage switchboard
additional equipment of the RNTw low-voltage switchboard
transformer type, rated power, and voltages of the lower and upper-voltage sides
types of cables supplying power in the medium-voltage line bays
transformer cable connections (connectors and insulators)
substation exterior colour and contents of the warning labels ( page 18)
12
KS 19-28 z
building width
building length
building height above ground
depth of building foundation
Protection degree
building weight less equipment
630 kVA
1900 mm
2800 mm
1700 mm
650 mm
IP 43
~6500 kg
fig.s 02 and 03
Materials
building
roof
joinery
the building walls are finished with structural plasters in the ordered
colour (standard sand RAL 1015)
1900
ventilation door
exhaust grate
6
7
medium-voltage compartment
low-voltage compartment
2
8
2800
service door
1700
building roof
10
5
650
substation building
2350
6
1
10 transformer room
13
KS 22-30 z
630 kVA
building width
building length
building height above ground
depth of building foundation
protection degree
building weight less equipment
3000 mm
2200 mm
1800 mm
700mm
IP 43
8000 kg
Materials
building
roof
joinery
the building walls are finished with structural plasters in the ordered
colour (standard sand RAL 1015)
the building walls are finished with structural plasters in the ordered
colour (standard sand RAL 1015)
the building roof is covered with sealing paints (standard brown
RAL 8016 or ash RAL 7032)
joinery is painted with powder paints in the roof colour
2200
ventilation door
exhaust grate
medium-voltage compartment
low-voltage compartment
transformer room
1350
service door
3000
1800
building roof
5
700
substation building
2550
6
1
800
8
375
14
KS 25-36 z
1000 kVA
3600 mm
2500 mm
1800 mm
700 mm
IP 43
10500 kg
building width
building length
building height above ground
depth of building foundation
protection degree
building weight less equipment
Materials
building
roof
joinery
the building walls are finished with structural plasters in the ordered
colour (standard sand RAL 1015)
2500
substation building
cable bushings
medium-voltage compartment
low-voltage compartment
transformer room
2000
exhaust grate
3600
ventilation door
9
1800
service door
5
700
building roof
2550
7
2
6
1
800
375
15
KS 25-36 z
lants
ower p
p
l
il
m
d
for win
1250 kVA
General specifications
building width
building length
building height above ground
depth of building foundation
protection degree
building weight less equipment
3600 mm
2500 mm
1800 mm
700 mm
IP 43
11000 kg
Materials
building
joinery
reinforced concrete
aluminium (or aluzinc)
the building walls are finished with structural plasters in the ordered
colour (standard sand RAL 1015)
the building roof is covered with sealing paints (standard brown
RAL 8016 or ash RAL 7032)
joinery is painted with powder paints in the roof colour
2500
4
2000
3600
2550
1800
substation building
building roof
service door
ventilation door
exhaust grate
700
5
6
1
800
cable bushings
transformer room
16
2 KS 22-30 z
2 KS 25-36 z
500
breakstone
2 KS 19-28 z
17
building roofs :
KS 19-28 z
KS 22-30 z
KS 25-36 z
and
2 x KS 19-28 z
2 x KS 22-30 z
2 x KS 25-36 z
2
Flat, double slope, reinforced
concrete, 5% pitch
1
2
Drainpipes and decorative roofs are provided for the KS... z type substations
company logo
substation type
substation number
ground level
MV/LV TRANSFORMER
MV/LV TRANSFORMER
18
ventilation door 1
ventilation door 2
MV SWITCHGEAR
LV SWITCHGEAR
The MV switchgear transformer bays are equipped with a circuit breaker or a fuse. In the switchgear equipped
with the isolation switch (200 A), the transformer is protected by a combination of a high-power isolation switch, and highvoltage HRC fuse links type CEF. The isolation switch rated current in the transformer bay is limited by the fuse link rated
current (see table below).
Detailed information on switchgear design and operation is given in installation and operation documentation of
the MV switchgears.
Note: the UniSwitch, SafePlus and traditional, air insulated switchgears allow
free choice of configuration of medium-voltage side bays
Phase order
Each bay in the MV switchgear (SF ) is standard equipped with neon lamp voltage indicators, and with test sockets for
setting phase of the medium-voltage cables (in each phase).
Phasing devices are fitted on clients request.
6
SafeRing
SafePlus
17.5 and 24 kV
17.5 and 24 kV
transformer bay:
- with fuse
- without fuse
2
number of bays
(mm)
(mm)
750
750
(mm)
1345
1345
15 kV
transformer power
fuse
transformer power
fuse
100 kVA
10 A
100 kVA
10 A
160 kVA
16 A
160 kVA
16 A
250 kVA
25 A
250 kVA
16 A
400 kVA
25 A
400 kVA
25 A
630 kVA
40A
630 kVA
40 A
1000 kVA
63 A
1000 kVA
50 A
upper voltage
20 kV
19
RNTz switchboards
Cu 60 x 10
(Cu 80 x 10)
Example
Internal load
Compensation
16 A
D01
Cu 40 x 10
(Cu 60 x 10)
RB-00
16 A
D01
220 V/16 A
PV
D01
V
PK measurement
1250 A (1600 A)
D01
standard colour
Cu 50 x 10
(Cu 80 x 10)
RBL-2
IP 20
L
RBL-2
40 kA
protection degree
RBL-2
10
RBL-2
16 kA
RBL-2
Stand-by
660 V
Stand-by
PR measurement
RBL-2
230 / 400 V
RBL-2
rated voltage
RAL 7032
Cu 40 x 10
(Cu 60 x 10)
PEN
RNTz - 10
RNTz - 12
V
A
600
20
V
A
1000
1380
RNTz - 6
1200
280
RBL-2
RNTz switchboards
continue.
Example:
Busbars
2 feeder:
L1
L2
L3
PEN
SOCOMEC
1250 A
przekadniki
baterii kondensatorw
L1
L2
2
L3
PEN
21
RNTz switchboards
continue.
PR, PK - measurements
TT-3
TT-2
WILK
WILK
WILK
WILK
WILK
WILK
650
500
450
650
550
TP-2
TP-3
WILK
WILK
WILK
750
WILK
WILK
850
700
zegar
zegar
zegar
zegar
Transformer power
100 kVA
160 kVA
250 kVA
400 kVA
630 kVA
Capacitor power *
2 (2.5) kVAr
2.5 (3) kVAr
3 (5) kVAr
5 (7.5) kVAr
7.5 (10) kVAr
22
Transformers
Oil type
manufacturer
ABB
power
(kVA)
160
250
400
630
1000
(mm)
950
990
1085
1180
1890
(mm)
780
720
900
1020
1105
(mm)
1230
1340
1445
1570
2040
23
The medium-voltage switchgears in SF6 insulation permit connection of dry or oil cables.
Cable heads
SF6 insulated switchgears
head manufacturer
line bays incomer cables
transformer bay cables to the transformer
F&G
EUROMOLD
RAYCHEM
RICS
EASW 20/250
K 158 LR
RSES
F&G
EUROMOLD
RAYCHEM
EAVI 20; TI 24
ITK; OTK
IXSU; OXSU
EAVI 20; TI 24
ITK; OTK
IXSU; OXSU
F&G
EUROMOLD
RAYCHEM
EAVI 20; TI 24
ITK; OTK
IXSU; OXSU
K 158 LR
RSES
transformers
head manufacturer
with traditional connectors (insulators)
with jack connectors
24
Substation earthing
Safety earthing:
FeZn 50x4 mm
KS 19-28 z
KS 22-30 z
KS 25-36 z
Earthing busbar
FeZn 50x4 mm
PEN
PE
FeZn 50x4 mm
FeZn 50x4 mm
LV switchboard
Substation structure
Division
Transformer
MV cable
MV switchgear
PE
25
16 T crane
1900
1700
traverse
9,5 T
breakstone
650
ground level
2300
150
cable
2300
3500
4400
cable
do not oversize the foundation slab
cable runs
Substation placement
(with equipment)
KS 22-30 z
16 T crane
(25 T in case of difficulties)
3000
2200
1850
traverse
12,5 T
3300
150
700
ground level
breakstone
4600
2500
3800
KS 25-36 z
Substation placement
(with equipment)
16 T crane
(25 T in case of difficulties)
3600
2500
1850
trawers
15 T
26
150
700
ground level
breakstone
3900
2800
5300
4200
Transformer substation
KS 19-28 z
KS 22-30 z
KS 25-36 z
Substation equipment options - standard
substation building
MV switchgear:
LV switchboard
transformer
Equipment placement
MV/LV transformer
ventilation door
exhaust grate
1
6
5
2
4
8
3
7
V
A
kVAr
4
V
kWh
4
V
kVAr
ST
kWh
fig.
8.1
27
with fuse...
kV
I>
3x1YHKXS 50 cable
EASW 20/250 heads
Earthing busbar
kV
Transformer
MV switchgear
LV switchboard
Structures
Other
Compensation
A
kVAr
Internal load
16 A
D01
16 A
D01
SIRCO
6A
D01
Energy counter
Qsn
PR :
Qnn
60W
60W
PV
V
3
A/5A
220 V/16 A
6A
D01
RNTz
L1, L2, L3 400/230 V, 50 Hz
PK :
Cu 50 (80) x 10
A/5A
Cu 40 (60) x 10
PEN
RBL-2
RBL-2
RBL-2
RBL-2
RBL-2
RBL-2
RBL-2
RBL-2
Stand-by
10
Stand-by
PEN
28
8.2
Transformer substation
KS 19-28 z
KS 22-30 z
KS 25-36 z
Substation equipment options with medium-voltage side measurement
substation building:
MV switchgear:
LV switchboard
transformer
2a
MV/LV transformer
ventilation door
exhaust grate
7
6
1
6
2a
8
2
3
7
fig.
9.1
29
2-bay switchgear with fuse (SafeRing) in the transformer bay + medium-voltage measurement bay
L1, L2, L3
in SF6 insulation
17.5 (24) kV
IMZ
UMZ
3
EAVI 20 heads
TP board
3xYHKXS 50 cable
3x1YHKXS 50 cable
EASW 20/250 heads
Earthing busbar
kVA
1
Transformer
MV switchgear
LV switchboard
Other
Structures
kV
2
Compensation
4x2YKXS 240 cable
kVAr
RB-00
Internal load
16 A
D01
16 A
D01
SIRCO
Qsn
Qnn
60W
60W
6A
D01
PV
220 V/16 A
3
PEN
L1,L2,L3
RBL-2
RBL-2
RBL-2
RBL-2
RBL-2
RBL-2
RBL-2
Stand-by
Stand-by
10
Cu 50 (80) x 10
Cu 40 (60) x 10
RBL-2
RNTz
A
Test energy counter
PK :
A/5A
PEN
additional equipment
fig.
30
9.2
Two-transformer substation
2KS 19-28 z
2KS 22-30 z
2KS 25-36 z
Substation equipment options example of two-transformer substation
substation building
2x
MV switchgear:
e.g.
2 x SafeRing or SafePlus
LV switchboard
e.g.
transformer
e.g.
2 x 630 kVA
7
1
MV/LV transformer
ventilation door
ventilation grate
exhaust grate
1
6
5
2
4
9
3
8
8
6
1
6
5
2
4
9
3
7
fig.
10.1
31
kV
I>
I>
Earthing busbar
3x1YHKXS 50 cable
3x1YHKXS 50 cable
T2
Transformer
kV
kVA
MV switchgear
kVA
Other
kV
Transformer
MV switchgear
LV switchboard
Structures
Other
LV switchboard
T1
Structures
Earthing busbar
Compensation
kVAr
kVAr
SIRCO
SIRCO
Internal load
MP:
A/5A
A
6A
D01
PR:
Cu 40 (60) x 10
PEN
A/5A
RNTz
L1, L2, L3 400/230 V, 50 Hz
RBL-2
RBL-2
10
RBL-2
RBL-2
PEN
PEN
PEN
L1,L2,L3
L1,L2,L3
2RBL-3
RBL-2
RBL-2
RBL-2
RBL-2
RBL-2
Cu 50 (80) x 10
Cu 50 (80) x 10
6
RBL-2
RBL-2
RBL-2
RBL-2
A/5A
7
RBL-2
RBL-2
PR:
RNTz
L1, L2, L3 400/230 V, 50 Hz
8
PV
V
3
6A
D01
Energy counter
6A
D01
MP:
A/5A
10
6A
D01
PV
RBL-2
kV
Cu 40 (60) x 10
32
10.2
Exterior 1
MV/LV transformer
Identification label
MV Switchgear
Exterior 2
ROOF
grey or brown colour
WALLS
sand colourr
METAL FITTINGS
grey or brown colour
Exterior 2
TRIM
grey or brown colour
ROOF
grey or brown colour
WALLS
sand colourr
METAL FITTINGS
grey or brown colour
TRIM
grey or brown colour
Exterior 4
MV Switchgear
MV/LV transformer
Exterior
fig. 01
33
Service door
Ventilation door
KS 19-28 z substation
fig. 02
Equipment placement
34
KS 19-28 z substation
980
Exhaust grate
300
995
Equipment placement
1415
fig. 03
35
Version 1
Version 2
W1 vibration damper
(with level adjustment)
NOTES:
1.Transformer installation is performed after substation roof removal.
2.The transformer is placed directly in the oil pit:
- on vibration dampers (version 1), or
- on shock absorbing cushions (version 2)
Version3
Transformer
mounting strips
Transformer installation
Fig. 04
36
Version 1
P50 cable bushing ( 50 mm)
Version 2
P70 cable bushing (7
Thermo-shrink tube
0 mm)
Thermo-shrink tube
Version 3
HD125 (150)
Cable bushings
Thermo-shrink tube
fig. 05
37
Service door
Technical specifications:
1.Material aluminium or aluzinc sheet
2.Anti-rust coating polyester powder paint
3.Ingress protection IP43
Ventilation door
fig. 06
38
Insect screen