Professional Documents
Culture Documents
MECHANICAL SERVICES
Plumbing
Division 22
Mechanical Services
Contents
00 1
DIVISION 22
Plumbing
Section 22 05 00
Section 22 05 16
Section 22 05 19
Section 22 05 23
Section 22 05 48
Section 22 05 53
Section 22 05 73
Section 22 05 76
Section 22 07 16
Section 22 07 19
Section 22 10 00
Section33 50 00
00 2
GENERAL
General Requirements
Scope of Work
Quality Assurance
Submittals
Protection of Pipe Materials
Identification
PRODUCTS
Piping Materials
Pipe Services
Fittings
Mechanical Couplings and Fittings.
Flanges
Unions
Valves General
Hangers and Riser Supports
Inserts and Supports
Sump Covers and Frames
Valve Tags and Charts
Nameplates
Sleeves
Thermometers
Gauges
Flow Meters
Wiring and Electric Motors and Motor Starters
EXECUTION
Installation
Pump and Equipment Connections
Drains
Pipe Installation
Piping system Joints
Control Components
Dirt Accumulation Under Control Valves
Hangers
Anchors
Air vents
Expansion Joints
Installation of Temperature Gauges
Installation of Pressure Gauges
Installation of Flow Measuring Gauges
Protection
Rigging of Equipment
Concrete
Metals
Cutting and Patching
Identification of Equipment and Piping
Flashing
Inserts, Sleeves and Escutcheons
Access Doors
Excavation and Backfill
Painting
22 05 00 1
3.26
3.27
PART 1
GENERAL
1.01
GENERAL REQUIREMENTS
A.
B.
C.
It is the Contractors responsibility to be fully aware of and comply with all of the
requirements of the above listed documents.
1.02
SCOPE OF WORK
A.
This section is a Plumbing Basic Materials and Methods section and is to be read as a part
of any other section of the specification making reference to pipe, tube and fittings,
hangers and supports, and electrical equipment.
B.
Provide all necessary materials, labour, equipment, tools, appliances, services, hoisting,
scaffolding, supports and supervision to provide complete piped services to all plumbing
systems, installed in accordance with the Divisions 21, 22, 23 and 25 of the
specifications.
C.
Types of pipe, tube and fittings specified in this section include the following:
1. Piping Materials
a. Steel Pipe.
b. Copper Tube.
c. Polyvinyl Chloride (PVC).
d. Acrylonitrile Butadiene Styrene (ABS).
e. High Density Polyethylene (HDPE).
2. Pipe/Tube Fittings
a. Fittings for Steel pipe.
b. Fittings for Copper Tube.
22 05 00 2
B.
Regulatory Requirements
1. Welding
a. Certify welding procedures, welders and operators for shop and project site welding
of piping work in accordance with Lloyds Standard Class 2, ANSI B31.1 using
procedures stated under Part 3 Execution section of the specification.
b. Certify welding of pipework using the Standard Procedure Specifications by and
welders tested under supervision of, Lloyds of London UK or the National Certified
pipe Welding Bureau (NCPWB) or in accordance with procedures stated under Part 3
Execution section of the specification.
2. Brazing
a. Certify brazing procedures, braziers and operators in accordance with BS 1723 and
BS 1724 or ANSI B31.5 paragraph 527.5 for shop project site brazing of pipework.
b. Welders not certified, or welders failing tests will not be permitted to work on this
project. Any work performed by non-authorized welders will be rejected and work
replaced by welders holding valid test certificate at Contractors expense. Submit
qualification certificates for the Engineers review and record.
1.04
SUBMITTALS
A.
B.
C.
a.
b.
c.
d.
e.
f.
22 05 00 3
g. Identification Materials.
D.
E.
Samples
1. Submit samples of identification materials together with schedule of application.
F.
Pipe Schedule
1. Submit piping schedule showing manufacturer, pipe or tube weight, wall thickness, fitting
type and joint type for each piping system
G.
Welding Certification
1. Submit welders certification for all welders proposed for pipework/support welding on
the project. Submit reports for the welding of the piping works as required by the
Engineer.
H.
Brazing Certification
1. Submit welders certification for all welders proposed for pipework/support welding on
the project. Submit reports for the welding of the piping works as required by the
Engineer.
1.05
A.
Provide factory applied plastic and caps on each length of pipe and tube. Maintain end
caps through shipping, delivery, storage, and placing in position to prevent pipe end
damage and to eliminate the ingress of dirt and moisture.
B.
Store pipe and tube indoors on purpose made racks, to protect from weather. Where
it is necessary to store outdoors provide purpose made racks to elevate pipe and tube
above grade and enclose the whole with durable weatherproof covering.
C.
Protect flanges and fittings from damage by dirt and moisture by inside storage or by
packaging in durable waterproof wrapping.
1.06
IDENTIFICATION
A.
All pipe work insulated and un-insulated in mechanical plant areas, service voids, service
ducts, false ceilings and exposed in corridors and on roofs shall be provided with colour
coded bands and names at 5m intervals, change of direction or physical space to indicate
the service, together with directional arrows to indicate direction of flow. The
identification shall be provided in accordance with the requirements specified in section
22 05 53.
B.
Identification colour coded bands and nomenclatures shall be in accordance with BS1710
or other approved International Pipework Colour Coding and Identification Standard and
may take the form of self adhesive plastic tapes.
C.
D.
PART 2
PRODUCTS
22 05 00 4
2.01
A.
PIPING MATERIALS
General
1. Provide pipe and tube of type, joint type, grade, size and weight (wall thickness, SDR or
class) indicated for each service. Where type, grade or class is not indicated, request
proper selection from the Engineer.
B.
C.
Copper tubing
1. Material specifications to be Hard Drawn ASTM B.88 Type M, or BS2871, Table X.
D.
Stainless Steel
1. Stainless Steel Cr-Ni-MO to DIN 1008, BS 316S33.
E.
Red brass
1. ASTM B43, seamless, annealed, 85 percent copper IPS.
F.
G.
H.
2.02
PIPE SERVICES
22 05 00 5
A.
2.
b.
Internal drainage: HDPE to DIN 19535 with but weld (electro fusion weld
shall be used wherever but weld is not possible).
weld (electro
weld
Buried in foundation drainage: HDPE to DIN 19535 (fittings shall be electro fusion
weld and but weld fittings are not permitted).
22 05 00 6
6.
Buried in foundation storm drainage: HDPE to DIN 19535 with electro weld shall be
used and but weld is not permitted).
Irrigation Water:
2.03
A.
FITTINGS
General
1. Provide factory-fabricated fittings of type, materials, grades, class and pressure ratings
indicated for each service and pipe size. Provide sizes and types matching pipe, tube,
valves or equipment connection in each case.
2. For Stainless Steel Pipe:
Stainless Steel press-fittings Cr- Ni-MO steel BS 316 S 33 BS 320 S31.
3. For Steel pipe:
a. To 50mm (2):
1) Steel: Socket weld ends, ANSI B16.11 or BS1965.
2) Steel: Screwed, ANSI B16.4, or BS1740.
3) Malleable irons: ANSI B16.3, or BS143 and 1256, threaded.
a) 150 lb wsp.
b) 300 lb wsp, where noted.
b. 65mm (2 1/2) and larger welded:
1) Butt welded, same weight as piping.
2) ANSI B16.9 or BS1965.
3) ANSI B16.28 or BS1965 for short radius elbows rated to connecting pipe.
c. Branch connections:
1) Equal to main and to 2 pipes sized smaller: weld tees.
2) Three or more pipe size smaller than main, but 65mm (2 1/2) and larger: Bonney
weld-o-lets.
22 05 00 7
A.
General
1. Mechanical couplings:
a. Malleable iron, Grade II for following working pressures:
Up to 150mm (6) IPS-6900 kPa (1000 psi)
200 to 300mm (8 to 12) IPS- 5520 kPa (800 psi).
b. Grooved type or steel shoulder ends.
c. Gaskets: Synthetic rubber ASTM D-735, Grade R 615 BZ.
2. Bolts: Oval neck track type, ASTM A183:
a. Mechanical Couplings to be similar to Victaulic Style 77.
3. Grooved End Fittings:
a. Grooved type, ductile iron as specified or equal British Standard for couplings to
250mm (10), steel ASTM A536, rated 2070 kPa (300 psi) working pressure.
b. Companion pipe
recommendations.
4.
grooving:
As
per
coupling
and
fitting
manufacturers
22 05 00 8
e. Solvent weld using cleanse purple primer and industrial grade cement.
7. For ABS (Sanitary Drainage)
a. Class C solvent weld to BS.5392 Part 1.
b. Gaskets and 0 rings on sockets to be of EPDM.
c. Flanges to BS4504.
8.
Dielectric Couplings
a. To join pipes of dissimilar materials.
b. Use insulating coupling.
c. Dielectric coupling to be similar to Victaulic Style 47 when connecting dissimilar
metals in liquid systems.
2.05
A.
FLANGES
For steel pipe: of matching quality, grade and thickness.
1. Welded: Welding neck, slip-on, socket welded, ANSI B16.5. or BS10 slip-on flanges:
Back welded.
a. 150 lb wsp.
b. 300 lb wsp.
c. 300 lb ring groove for high pressure service.
2. Screwed:
a. Standard cast iron: ANSI B16.1 or BS10.
b. Extra heavy cast iron: ANSI B16.1
c. Match Connecting flange
1) For Class
2) For Facing
B.
C.
Flange gaskets:
1. One-piece ring type 1.6mm (1/16) thick.
2. Suitable for temperature, pressure and service of system.
D.
22 05 00 9
2.06
A.
UNIONS
For steel pipe:
1. Malleable iron 300 lb wsp.
a. Ground jacket seat: Brass-to-iron, black or galvanized to match piping.
b. A.A.R. malleable iron 300 lb wsp.
c. Forged steel, 2000, 3000 lb wsp class, bronze-to-steel or steel-to-steel seats, where
noted or required for service.
B.
2.07
A.
VALVES GENERAL
In addition to valves, cocks and strainers etc., shown on drawings, the Contractor shall
include for the installation of sufficient valves, cocks and strainers at appropriate
locations to enable the system to operate to the satisfaction of the Consultant.
No asbestos containing materials shall be employed in any valve.
Valves shall bear the BSI Kitemark or equivalent denoting Quality System, accreditation
and compliance with British Standards and where no Kitemark scheme exists, valves shall
be manufactured under an approved BS5750 Quality System. All valves should be from
one source (one manufacturer).
Generally, all valves of the same type shall be of the same manufacturer. All gate, globe,
angle, swing check and butterfly valves as a group shall be of the same manufacturer.
All castings shall be clean close grained metal free from rough projections. Unless
otherwise specified valves of 50mm nominal bore and under shall have female ends
screwed to BS 21 and valves 65mm nominal bore and over shall have flanged ends.
22 05 00 10
Special care must be exercised in the installation of screwed valves to avoid straining
their bodies, and preventing the gate or seat from closing tight. The wrench shall always
be applied to the side being attached to the pipe. When attaching pipe to a valve already
in place, a second wrench shall be used to hold the valve while the pipe is being
tightened. A pipe shall not be screwed so far into a valve as to damage the seat.
Flanged valves shall have matching flanges manufactured in accordance with BS4504.
Composite flanges to BS4504 should be used when butterfly or other 'inside bolt circle'
valves are installed in copper pipe work systems.
All valves which contain copper alloy shall be gunmetal or capable of withstanding
dezincification.
All valves on potable water services shall be approved by the Local water authority and
WRc.
In lieu of gate valves, butterfly valves can be used for size 65mm and above.
Valves for plumbing services are specified in the Section 22 05 23.
2.08
A.
B.
Provide adjustable Clevis type equal to Grinnell Fig. 65 for pipe sizes up to and
including 65mm (2 1/2). For pipe sizes 75mm (3) and over, provide adjustable Clevis
type equal to Grinnell Fig. 260. Use rod sizes as recommended by the manufacturer.
C.
On copper piping, provide copper plated type hanger or separate piping from hanger with
an approved insulating tape or plastic coating.
D.
Provide oversized hangers to pass over insulation on all insulated piping. Refer to the
Contract Documents.
22 05 00 11
E.
Riser supports: Provide anchors and supports, complete with spring isolators where
shown, or indicated on the riser diagrams. Refer to the Contract Documents for anchor
and support requirements.
F.
The Contractor shall provide full details the proposed supports, anchors, guides and
hangers and the shop drawing and submit the same for approval.
G.
The Contractor shall submit all relevant calculation for the design of the proposed
supports, anchors, guides and hangers.
2.09
A.
B.
Supports from building construction: Inserts, beam clamps, steel fishplates (in concrete
fill only), cantilever brackets or other means. Submit for review.
C.
D.
In mechanical equipment rooms: Install inserts in two way grid pattern, minimum 1.2m
(4ft.) on centres.
E.
Fasteners:
1. Expansion cases and concrete fasteners:
SLUGIN SERIES 6800-1.
2.11
A.
22 05 00 12
Charts:
1. Submit a valve tag chart for domestic water, fuel oil, chilled water, and fire water
indicating the following data for each valve:
a.
b.
c.
d.
e.
Valve number.
System.
Type .
Size
Location.
2. Mount charts on walnut grained wood plague with clear plastic laminations covering
diagrams. Wood plague with gold paint bevelled edge. Permanently fastened in each
Mechanical equipment room, using 4 brass screws.
2.12
NAMEPLATES
A.
Engraved black lamicoid sheet with white lettering in both Arabic and English languages.
B.
Inscriptions to indicate equipment nomenclature such as pump P1, Chiller No. 1 etc.
C.
Provide for:
1.
2.
3.
4.
5.
6.
7.
8.
9.
2.13
A.
2.14
A.
Gauges.
Meters.
Instruments.
Pilot lamps.
Control devices.
Motor controllers.
Equipment mounted on panels.
Transmitters.
All equipment including but not limited to calorifiers, pumps, pressure vessels etc.
SLEEVES
Piping: Machine cut schedule 40 (medium wall) steel pipe or medium cast iron.
THERMOMETERS
Thermometers:
1. Case: 225 mm (9) die cast aluminium with metallic blue black finish with adjustable
angle.
Lulu hypermarket at western region
Date: 31st March 2015 Rev. 00
22 05 00 13
2. Window: Clear acrylic plastic and double strength glass held in place with removable
stainless steel cap.
3. Tube: Lens front red appearing mercury tubing.
4. Scale: White background with jet black embossed figures and markings. Range -5 to
50oC with 1oC scale increment between 0 oC to 15oC.
5. Stem: Aluminum with socket connections. Stem length to suite application.
6. Bulb Chamber: Bulb chamber tapered to fit matched taper in the sockets.
7. Model: Trerice BX91 for water.
Trerice BX99 for air.
Or equivalent.
B.
Separable Sockets:
1. Material: Brass
2. Socket Length: To suit application for duct and pipe installations. Contractor to select
gauge with correct socket length for each particular location and application.
3. Manufacturer: Same as the proposed thermometer.
2.15
A.
GAUGES
Pressure Gauges
1. Case: 110mm (4 1/2) size black fibreglass reinforced polypropylene.
2. Liquid Fill: Glycerin.
3. Dial: White background with jet black embossed figures and graduations.
4. Pointer: Micro adjustable red pointer for indication of set pressure limit.
5. Window: Acrylic plastic with O ring seal for weather proof service.
6. Movements: Brass with bronze bushings.
7. Bourdon Tube: Phosphor bronze.
8. Safety: Blow out back.
9. Diaphragm Seal: For temperature compensation.
10. Socket: Brass 50mm (1/2) N.P.T.
11. Ranges: 0 - 2000 kPa (0 - 300 psig).
0 - 700 kPa (0 - 100 psig).
0 - 350 kPa (0 - 50 psig).
12. Accuracy: 1/2% of range.
13. Model: Trerice No. 450 LFB or equivalent.
22 05 00 14
14. The Contractor shall select gauges with a suitable range and graduations for each location
and application in accordance with the pressure at the particular point of installation
B.
Magnetic wafer type level gauges for domestic water pumps accumulator.
C.
Gauge Accessories.
1. Pressure snubbers: Porous bronze coil and brass body.
2. Gauge cock: Brass, T handle, union connection, 1/4.
2.16
FLOW METERS
A.
B.
C.
D.
2.17
A.
B.
Provide motor and systems control wiring between starter panels and control components
and meet all requirements stipulated for similar wiring and controls as specified in
Division 26.
C.
Provide wiring of items supplied by equipment manufacturers such as low water cut-offs,
anti vibration lock-outs, flow switches, thermostats, sump pump alternators, level
controllers, water treatment equipment and control wiring between starters and control
panels, etc.
D.
All motors of equipment intended to operate under fire condition or installed in non-air
conditioned space shall be rated at 50oC (122oF) ambient temperatures.
All motors of equipment not intended to operate under fire condition and installed in air
conditioned space shall be rated at 40oC (104oC) ambient temperature.
E.
F.
Variable speed motors of 1/2 HP and over: Provide thermistor over temperature
protection for each winding, wired in series, with leads terminated in the motor junction
box. Provide for installation by Division 16, a motor tripping device, Westinghouse Type
3 UN7 or approved equal, c/w latching relay, pilot light & one auxiliary set of alarm
contacts.
G.
Provide motor starters, for motorized mechanical equipment, in general as per Division
26.
22 05 00 15
1. Unless otherwise noted, starters for 3 phase motors: combination, quick-make and
quick-break disconnects with full voltage, non-reversing magnetic contactors for
across-the-line service within the limits of starting currents specified in item 2. below.
Provide full protection of each phase by means of one overload relay per phase, reset
button shall be in front of panel. Under-voltage protection: starter coil to disengage on
85 percent of rated voltage unless otherwise noted. Provide accessories as follows:
TEST-OFF-ON switches, START-STOP pushbuttons, pilot lights, control
transformers, auxiliary contacts etc., as indicated on the motor control schedule. Provide
three phase ammeters with selector switch, voltmeters with selector switch, earth fault
and phase failure protection.
2. The maximum starting currents of electric motors shall be as listed hereunder:
Three Phase up to 3 HP five times F.L.C.
3 HP to 35 HP two times F.L.C.
35 HP and above 1.5 times F.L.C.
Starting equipment to limit the current may consist of:
Star-Delta Starters
Resistance Starters
Auto-Transformer Starters
Other approved current limiting devices.
3. Motor control centres and equipment starters: Provide enclosure as specified in Section
26 24 19. Starters installed in control centre, as above, and complete with load wiring and
control wiring terminal boards and all required provisions for electric line and load
side power connections. Starter shall be of the drawer type, withdrawable in the OFF
position.
4. Unless otherwise noted starters for single phase motors: 240 volt, thermal overload
protected manual starting switches with ON/OFF toggle switch, LED pilot light, earth
leakage protection, three phase ammeters with selector switch and a surface or flush
mounting IP54 enclosure to suit application. If automatic or remote operation is required
provide magnetic starters as specified above for 3 phase motors, single phase motors to be
with non-automatic circuit breakers.
5. Disconnects: Heavy duty IP54 (min.), front operated with handle suitable for padlocking
in the OFF position and arranged so enclosure cover cannot be opened while the handle
is in the ON position. Operating mechanisms: quick-break positive acting with
visible blades ad line terminal shield. Fusible units: complete with fuse clips and suitable
for H.R.C. fuses unless otherwise noted. Equip each unit with solderless lugs and front
cover nameplate identifying the catalogue number and electrical characteristics.
Enclosures for disconnects mounted indoors: IP54. Enclosures for disconnects mounted
outdoors: IP65. Ampere rating, number of poles and fuse requirements: as indicated in
the contract documents. Provide a disconnect switch for every motor.
6. Fuses (unless otherwise indicated) English Electric Ltd., or approved equal, Form 1,
Class J H.R.C. for constant running equipment and Bussman Class J High Interrupting
capacity time delay type for equipment that cycles ON and OFF.
7. All mechanical equipment having integral starters, and control panels shall incorporate, in
addition to the provisions of the Motor Control Centers and starters, earth leakage
sensors, local audio/visual alarm, and output signals for BMS monitoring in accordance
with Section 25 00 00.
Lulu hypermarket at western region
Date: 31st March 2015 Rev. 00
22 05 00 16
8. All starters, control panels and Motor Control Centers shall be equipped with a door
interlocked power disconnect per circuit and be factory assembled and tested.
9. All starters, control panels and motor control centers shall be provided with a lamp test
facility.
PART 3
EXECUTION
3.01
INSTALLATION
A.
Install equipment, pipes, tubes and fittings in a workmanlike manner to present a neat
appearance and to function properly to the acceptance of the Engineer. Install ducts and
pipes parallel and perpendicular to building planes. Install piping concealed in chases,
behind furring, or above ceiling. Install exposed systems grouped to present a neat
appearance to the approval of the Engineer. Comply with manufacturers installation
instructions.
B.
C.
Install all equipment and apparatus regarding wiring, maintenance, adjustment or eventual
replacement with due allowance therefore.
D.
Install control devices to guarantee proper sensing. Shield elements from direct radiation
and avoid placing them behind obstructions.
E.
Include in the work all requirements of manufacturers shown on the shop drawings.
F.
Install all ceiling mounted components in accordance with the Architects reflected ceiling
drawings. Installation to be inspected and approved as acceptable by the Engineer.
G.
Leave space clear and install all work to accommodate future materials and/or equipment
as indicated and to accommodate equipment and/or materials supplied by other trades.
Verify spaces in which work is to be installed. Install pipe runs etc., to maintain
maximum headroom and clearances and to conserve space in shaft and ceiling spaces.
H.
Confirm on the site the exact location of outlets and fixtures. Confirm location of outlets
for equipment supplied by other trades.
I.
Seal all protrusions through fire rated enclosures to maintain the integrity of the fire
enclosure.
3.02
A.
3.03
A.
Pipe all discharge from relief valves, equipment and condensate drains, strainers and
chemical pot feeders to the nearest floor drain or suitable receptacle.
B.
Provide 20mm (3/4) ball valves with hose ends, caps and chains at strainers, all low
points, at pumps, coils and at each piece of equipment.
22 05 00 17
C.
Provide deep seal traps (150mm trap seal) on all air handling equipment condensate
drains and floor drains.
D.
Contractor shall provide and install temporary cover plates over all floor drains and roof
drains to prevent accumulation or disposal of debris during construction All cover plates
to be removed at time of acceptance by the Engineer.
3.04
PIPE INSTALLATION
A.
Install all piping in the best workmanlike manner in accordance with the best practices of
the trade. Tundishes to be provided on all drains that collect drainpipes from equipment,
drain lines etc.
B.
The piping shown on the drawings is diagrammatic for clearness in indicating the general
run and connections and may or may not be, in all instances, shown in its true position.
Take responsibility for the proper erection of systems of piping in every respect suitable
for the work intended and as described in the specifications.
C.
D.
Install piping to avoid any interference with the installation or removal of equipment,
other piping, ducts etc.
E.
Place all valves and specialties to permit easy operation and access, and regulate and
adjust all packing glands on completion of the work.
F.
Install systems so that they can be thoroughly drained and all air eliminated. Provide
drain cocks at all low points in the systems and air vents at all high points. Indicate
accordingly on the shop drawings.
G.
During welding or soldering procedures, provide a fire retardant cloth, mat or blanket to
protect the structure, and adequate fire protection equipment at all locations where work
is being done. Close off shaft or confine areas with a fire retardant mat or cloth to prevent
sparks or pieces of hot metal from falling down the shaft or area way.
H.
Provide sufficient isolation valves in the installations to allow isolation of all floors, on
each riser, to each apartment or specific zones etc for the purposes of maintenance.
Provide adequate drain cocks between isolation valves to drain the isolated part of the
system for the purpose of maintenance. Indicate all isolation valves on the shop
drawings.
I.
Provide quick fill points for the purpose of quick fill of the water supply system or
sections of the systems on completion of maintenance. Quick fill points shall be provided
in the plant rooms and top of water risers. The Contractor shall indicate the proposed
quick fill points on the shop drawings.
J.
Provide drain points to the water system for the purpose of drain of the system or sections
of the systems on completion of maintenance. Drain points shall be provided in the plant
rooms, bottom of the water risers. The Contractor shall indicate the proposed drain points
on the shop drawings.
K.
Provide long turn pipe fittings having wall thickness no less than pipe wall thickness.
Provide line size tees, and where branch linens are more than two sizes smaller than the
main, weld-o-lets may be used.
L.
Where steel piping is required to be buried use pre-insulated pipes or apply two prime
coats of saturated hydrocarbon paste with inert filler and passivating agents as a primer
and adhesive for wrapping with a petroleum impregnated nylon carrier tape to engineer
22 05 00 18
approval. Applications to be made after assembly and testing of pipe work. Paste and
tape to be similar to that manufactured by Denso of Canada Ltd., 33 Commander Blvd.,
Agincourt (Toronto) Ontario, Canada. Tel : 416 291 7756.
M.
Where it is necessary to offset piping to avoid obstructions, use 45 degree rather than 90
degree elbows.
N.
Provide suitable cleanouts on every other change in direction and slope all condensate
drip drains.
3.05
A.
Provide joints of the type indicated for each pipe work system.
B.
Pipe work shall be threaded in accordance with ANSI B21, threads shall be cut full and
clean using sharp dies.
Threaded ends shall be reamed to remove burrs and restore full inside diameter. Apply
pipe jointing compound, or pipe joint tape PTFE or Teflon where recommended by
pipe/fitting manufacturer, on male threads at each joint and tighten joint to leave not more
than three threads exposed.
C.
D.
The Contractor shall avoid the excessive use of jointing material and PTEE/Teflon shall
not be used above 65mm pipe diameter.
E.
Braze copper tube and fittings where indicated in accordance with ANSI B31.
F.
Silver brazing will be the jointing of two closely adjacent prepared surfaces with melting
brazing alloy drawn by capillary action over the complete surfaces to be jointed. The
flame gas will be either oxy-acetylene, oxy-propane or oxy-butane.
G.
Solder copper tube and fitting joints in accordance with recognized industry practice. Cut
tube ends square, ream to full inside diameter and clean both outside of tube end and
inside of fitting. Apply suitable flux, as recommended by tube/fitting manufacturer, to
joint areas of both tube and fittings. Insert tube full depth into fitting and apply molten
solder in a manner which will draw solder by capillary action over the complete surfaces
to be jointed. Excess solder and flux to be wiped from joint.
H.
22 05 00 19
22 05 00 20
13. Any weld, whether radio-graphically tested or not which are considered by the Engineer
to be faulty, either in whole or in part, or which have failed under hydraulic or other tests
so designated by the Engineer, will be removed and replaced by the Contractor.
14. The faculty part of a weld may be removed by flame gouging, chipping or grinding.
Otherwise, the Engineer may instruct that the portion of the works containing the fault
weld be cut out and replaced by the welding-in of a new section of pipe or member.
15. Electrodes will be tropicalized as required suitable for the type of weld. Pipe and
preparation for butt welding will be machine beveled. Oxygen cutting will be permitted.
All oxide will be removed after cutting and the cut to be made smooth and true by filing
or grinding.
16. The correct alignment and welding gap shall be carefully maintained throughout the
welding using mechanical jigs, or tack welding and/or welded-on bridging pieces.
17. Where tack welds are used in the joint, they will be to the same finishes and thicknesses
as the initial root run. All extremities of tack welds will be dressed to provide fusion with
the initial root run of weld.
18. All scale, rust, paint and any other substance detrimental to the weld will be removed
from the tack weld before the initial root run fusion is commenced.
19. External weld reinforcement will not be less than 10% nor greater than 20% of the pipe
wall or material thickness and will be symmetrical above the centre line of the weld joint.
20. No hump or crater will be permitted in weld runs where welds have stopped and
recommenced. The penetration bead of the weld in pipe joints will not exceed 1.6mm
penetration.
21. The deposited weld metal will be free from cracks, slag, cavities, undercutting and other
faults. The external appearance of all welds will be clean and regular, with all slag
removed by hammer, chisel and/or wire brush.
22. Should any of the welders work ( as defined by the Engineer) be found to be faulty
during radiographic tests, then that welder shall be removed from site and all other welds
undertaken by that welder shall be checked by radiographic means and replaced as
necessary at the expense of the contractor.
23. The extra radiography involved shall not be part of the 2% inspection previously
stipulated.
I.
Flanged pipe joints shall be made using purpose made mild steel, cast iron, wrought iron
screwed or welded flanges, compatible with the pipe work material used.
J.
Steel flanges shall be raised face type except when bolted to flat faced cast iron flanges on
equipment, in which case they shall be flat faced.
K.
Bolting for services shall be hexagon head bolts and heavy hexagonal nuts. Nuts and
bolts shall be tightened beyond finger tightness with an indicating torque wrench to
ensure equal tension on all bolts. Tighten bolts such that those 180 degrees apart or
directly opposite are torqued up in sequence.
L.
Gaskets for insertion between flanges shall be purpose made, full face diameter, of
approved non-toxic composition material not less than 3mm thick before compression.
M.
Caulking of any joints screwed, flanged, welded or otherwise will not be permitted.
22 05 00 21
N.
Victaulic Joints:
1. Ensure that grooved pipes are in compliance with the current Victaulic specifications and
recommendations.
2. Ensure that the A dimension, i.e. the area from the pipe end to the front edge of the
groove is free from identations, scores, seams, projections or roll marks.
3. Use only lubricants which are non-toxic and non-injurious to the gasket material.
4. Upon completion of assembly, the bolt pads of each coupling must be fully drawn
together, except for HP-70 couplings in sizes to 100mm (4).
3.06
A.
3.07
A.
3.08
CONTROL COMPONENTS
Mount all pipe line devices supplied by the specialist Building Management System SubContractor such as flow switches, valves, separable wells for temperature controllers and
sensors.
DIRT ACCUMULATION UNDER CONTROL VALVES
The Contractor shall verify at the end of 6 (six) months from start of operation that dirt
has not accumulated under the seats of automatic control valves. Such material collected
under valve set shall be removed and if seat is damaged it shall be replaced by Contractor
at no additional cost to the Employer.
HANGERS
A.
Hanger rods shall not be attached to beams without approval of the Engineer. Explosive
actuated tools are not permitted.
B.
The following table will determine the spacing between support points for all piping on
this installation.
C.
Nominal
Pipe Size
mm
in
Copper
Tubing Steel
m ft m
Plastic
PVC
ft
m
ft
12 ( .5 )
20 ( .75)
25 (1 )
32 (1.25)
38 (1.5 )
50 (2 )
64 (2.5 )
76 (3 )
100 (4 )
150 (6 )
200 (8 )
250 (10 )
300 (12 )
350 (14 )
400 (16 )
450 (18 )
1.22
1.83
1.83
1.83
1.83
3.05
3.05
3.05
3.05
3.05
3.05
3.05
4.88
4.88
5.18
5.18
1.50
1.83
2.13
2.74
2.74
3.05
3.05
3.66
4.57
5.18
5.79
6.70
7.00
7.62
8.23
8.53
.91
.91
.91
1.22
1.22
1.22
1.50
1.50
1.50
1.83
2.13
2.13
2.44
2.44
2.74
2.74
( 4)
( 6)
( 6)
( 6)
( 6)
(10)
(10)
(10)
(10)
(10)
(10)
(10)
(16)
(16)
(17)
(17)
(5)
(6)
(7)
(9)
(10)
(10)
(11)
(12)
(15)
(17)
(19)
(22)
(23)
(25)
(27)
(28)
(3)
(3)
(3)
(4)
(4)
(4)
(5)
(5)
(5)
(6)
(7)
(7)
(8)
(8)
(9)
(9)
Where services supported by hangers are vulnerable to vibration, hangers shall be of the
spring isolation type.
22 05 00 22
D.
3.09
Equipment, piping, and ductwork shall be hung independently of each other and
independently of other trades equipment or fixtures.
Furthermore, this Contractor shall ensure that other trades do not hang their systems from
hangers provided under this Section, unless mutually agreed between trades and approved
by the Engineer.
ANCHORS
A.
Anchors shall be supplied and installed as necessary to ensure pipe work expansion does
not cause any damage to the pipe work installation, adjacent services or the building
fabric.
B.
C.
D.
E.
Details of proposed anchors and imposed loads, complete with supporting calculations
shall be provided for approval by the structural and mechanical engineers.
F.
On steel pipe work, the pipe shall be welded to anchors with heavy steel straps.
G.
On copper pipe work, the pipe shall be welded to anchors with heavy copper pipes.
H.
For plastic pipe work systems they shall be in accordance with the pipe manufacturers
recommendations.
I.
J.
Cold draw on expansion joints shall not be applied until the anchors are rigid and trim.
K.
Provide full details of all anchors on the shop drawings and submit the same for approval.
3.10
AIR VENTS
A.
Provide air vents on water piping at all high points in the system and at each piece of
equipment and in locations where air may be trapped. Provide shut off cocks to
automatic air vents.
B.
Provide automatic air vents on piping mains except where a possibility from water
damage would occur, in which case, use manual vents.
C.
3.11
EXPANSION JOINTS
A.
Install expansion joints and compensatory where indicated on drawings and in accordance
with manufacturers instructions especially in regard to proper length, anchoring and
guiding, pre-compression, removal of spacers and testing.
B.
Install expansion joints on all pipe work passing over building expansion joints.
3.12
A.
22 05 00 23
1. Install temperature gauges in vertical upright position, and tilted so as to be easily read by
observer standing on floor.
B.
Locations
1. Install in the following locations, and elsewhere as indicated on drawings:
a. At inlet and outlet of each heat exchanger.
b. At inlet and outlet of each water heater calorifier .
C.
Thermometer Wells
Install in piping tee where indicated, in vertical upright position. Fill well with oil or
graphite, secure cap.
3.13
A.
B.
Locations
1. Install in the following locations, and elsewhere as indicated on drawings:
a. At suction and discharge of each pump.
b. At water service outlet.
c. At the outlet of the domestic water booster set.
d. Fountain system, irrigation system.
C.
3.14
3.15
PROTECTION
A.
Cover openings in equipment and cover equipment where damage may occur from
weather to finish. Cover temporary openings in ducts and pipes with polythene sheets,
until final connection is made. Cover all items cast into concrete floors or walls such as
floor drains, cleanouts, etc., prior to pour, with heavy plastic tape or duct tape.
Cover and seal, with polythene sheeting, all equipment, coils and motors in place during
to prevent entry of dust, paint and debris.
B.
Damaged items of works due to lack of proper protection shall be replaced at the
discretion of the Engineer and at no additional cost to the Employer.
3.16
RIGGING OF EQUIPMENT
22 05 00 24
A.
Provide all rigging, hoisting and handling of equipment as necessary in order to place
each piece of equipment in its designated area within the building.
B.
Direct this work by qualified people normally engaged in rigging, hoisting and handling
of equipment.
3.17
CONCRETE
A.
B.
Provide in good time, all inserts, sump frames, anchors etc., required to be built into
forming for mechanical services.
3.18
A.
3.19
A.
3.20
METALS
Steel construction such as pipe and duct hanger supports, vertical column supports
required solely for the work of mechanical trades and not shown on architectural or
structural drawings to be provided by Division 21, 22 & 23 to the acceptance of the
Engineer.
CUTTING AND PATCHING
Inform other trades in time concerning required openings. In work already finished the
Contractor will perform all cutting and patching at the expense of Division 21, 22 & 23.
Obtain the approval of the Engineer before doing any work.
IDENTIFICATION OF EQUIPMENT AND PIPING
A.
Identify all automatic control devices, pumps, fans etc., with plates fixed to equipment
using Pop rivets or sheet metal screws.
B.
C.
Identify the following piping as to service and direction of flow using stencils and black
lettering behind each access door, in each room and/or every 5m (16.4 ft.).
a.
b.
c.
d.
e.
f.
g.
h.
3.21
FLASHING
A.
Flash all mechanical parts passing through or built into an outside wall, or a waterproof
floor.
B.
Provide copper flashing for sleeves passing through exterior walls or water proof floors.
C.
Provide counter flashing on stacks, ducts and pipes passing through roofs to fit over
flashing or curb.
22 05 00 25
3.22
A.
Provide for setting by applicable Division all sleeves required for piping and access
openings in walls, floors and roofs, as indicated in Contract Documents.
B.
Place inserts only in portion of the main structure and not in any finishing material.
C.
Supply and locate all inserts, holes, anchor bolts and sleeves in advance of time when
walls, floors and roof are to be erected.
D.
F.
3.23
ACCESS DOORS
A.
Access doors shall be provided under applicable Division for the particular type of
construction in which access is to be provided. Coordinate with General Contractor.
B.
Access doors are required in walls and ceilings to provide access to all fire dampers,
motorized dampers, duct mounted coils, smoke detectors, fan inlets and outlets, valves,
strainers, gauges, meters, flow switch, etc. where indicated on the Architectural drawings.
3.24
A.
Do all excavation, bedding, backfill and related work required for mechanical work in
accordance with requirements of applicable Division except as varied by this article.
B.
22 05 00 26
C.
In firm undisturbed soil, lay pipes directly on the soil and shape soil to fit the lower 1/3
segment of all pipes and pipe bells. Ensure even bearing along the barrels.
D.
In rock and shale excavate 150mm (6) below and a minimum of 200mm (8) to either
side of the pipe. Over excavation to be filled back with a bedding of 10mm (3/8)
crushed stone or granular A gravel.
E.
Prepare new bedding under the pipe in unstable soil, in fill, and in all cases where pipe
bedding has been removed in earlier excavation, particularly near perimeter walls of
buildings, at manholes and catch basins. Compact to maximum possible density and
support the pipe by 200mm (8) thick concrete cradle, spanning full length between firm
supports. Install reinforcing steel in cradle and construct piers every 2400mm (8 ft.) or
closer, down to solid load bearing strata. Provide a minimum of one pier per length of
pipe. Use the same method where pipes cross.
F.
Where excavation is necessary in proximity to and below the level of any footing, bed
with 14,000 kPa (2000 psi) concrete to the level of the highest adjacent footing.
Proximity is determined by the angle of repose as established by the Engineer.
G.
Provide support over at least the bottom one third segment of the pipe in all bedding
methods.
H.
Do not open trench ahead of pipe laying and bedding more than weather will permit.
Break up rocks and boulders and remove these by drilling and wedging. Do not use
blasting unless specifically approved by the Engineer.
I.
Do all backfilling in 150mm (6) layers with clean selected materials acceptable to the
Engineer.
Backfill excess excavation and compact to the following standard Proctor percentage:
Sodded Area
Under Paving
Under Floor Slabs
J.
3.25
85%
95%
100%
A.
Provide all exposed ferrous metal work on equipment with at least one factory prime coat,
or paint one prime coat on job. Clean up or wire brush all equipment, etc., before
painting. Finish painting in accordance with the applicable Section 09 90 00.
B.
Co-ordinate with the applicable Division subcontractor and provide all required assistance
in identifying all piping circuits requiring colour coding.
C.
For Factory finishes, repaint or refinish surfaces damaged during shipment, erection or
construction work.
3.26
A.
22 05 00 27
3. During fabrication and assembly, slag and weld splatter shall be removed from both
internal and external pipe joints by peening, chipping and wire brushing.
4. Degrease, in the presence of the Employer and the Engineer, chilled water piping using
procedures and chemicals to be provided water treatment specialist as referenced in
Section 22 32 00.
5. Notify the Engineer prior to post erection cleaning in sufficient time to allow witnessing
by the engineer. Obtain agreement from the Engineer concerning cleaning procedures
and scheduling. The Contractor shall arrange for proper disposal of cleaning and flushing
fluids.
6. Prior to blowing or flushing of erected pipe systems, the contractor shall disconnect all
instrumentation and equipment, open wide all valves, and be certain all strainer screens
are in place.
B.
Water Flush
1. Pipe components shall be flushed with clean water until all particulate matter is removed
from the pipe system and flushing water discharged from the system is clean.
2. Minimum velocities of 4.0m/s shall be maintained at all points.
3. Flow shall be in the same direction as when in normal operation.
4. Discharge shall be from low points of lines, ends of headers and as otherwise required to
flush the entire system.
5. After flushing, any residual water shall be drained and/or blown out prior to testing.
Water flush shall apply to the following systems:
a. Potable water-hot, chilled cold and cold.
b. Water feature piping.
6. Flushing bypasses shall be provided on plate heat exchangers, filtration equipment and
pressure reducing valve assemblies.
7. During flushing all filtration equipment and pressure reducing valve assemblies shall be
bypassed.
8. The Contractor shall provide all necessary temporary pipe work for the purposes of
flushing the system.
9. The Contractor shall submit a Method Statement for the proposed flushing of the systems.
10. The domestic water system shall be disinfected.
3.27
A.
All tests shall be performed as specified in the individual sections of Division 21, 22 & 23
in the presence of the Engineer and such other parties as may have legal jurisdiction.
B.
All defective work shall be promptly repaired or replaced and tests repeated until
approved by the Engineer.
22 05 00 28
C.
Any damage resulting from the tests shall be repaired and/or damaged materials replaced
at the Contractors expense.
D.
The Engineer and all other having legal jurisdiction shall be notified at least 48 hours in
advance to allow witnessing when a test is to be performed.
E.
Tests shall be performed and approval of tests obtained in writing prior to backfilling,
insulation, painting or concealing in any manner.
F.
Records shall be prepared and retained for each system or section of system tested. Test
reports shall be signed by the Engineer and transmitted in triplicate to the Engineer. The
Contractor shall furnish additional copies as required to all persons having legal
jurisdiction.
G.
Test reports shall include, but not necessarily be limited to, the following:
1. Identification of piping system or section tested.
2. Date of test and date of Engineers signature.
3. Testing medium, test equipment description (sketch if necessary) and description of test
procedure.
4. Test pressure, duration of test and recorded pressure drop,.
H.
Test shall be observed after the pipe and contents have stabilized at the ambient
temperature and the source of test pressure has been shut off.
I.
Pressure tests in general shall apply to piping only with all equipment, traps, relief valves
and instruments blocked off or disconnected.
J.
In no case shall piping or any component be subjected to pressures exceeding their rating.
K.
All system valves within the section being tested shall be open.
L.
M.
All pipework systems shall be tested at 1.5 times the system working pressure. Unless
otherwise indicated.
N.
Gauges used for pressure testing shall be checked and calibrated against a dead weight
tester at least once per month and certified correct over the range of the gauge, to the
Engineers approval.
O.
Gauges used for testing shall have a minimum dial diameter of 120mm and scale
divisions equal to or less than the maximum allowable pressure drop.
P.
Q.
The pressure shall be gradually raised to the value given and the source then blocked off.
The pressure shall not drop more than the amount indicated during the corresponding
minimum time interval.
R.
If an audible or visible leak is detected during testing, this shall be cause to disapprove the
test, even though the maximum allowable pressure drop has not been exceeded.
22 05 00 29
S.
T.
Upon successful completion and approval of the tests, the piping shall be relieved of
pressure, drained and put into normal operation, except for potable water, which shall be
sterilized before placing in service.
U.
V.
After cleaning and testing, all open pipelines and valves shall be capped or plugged with
purpose made polythene closures, unless otherwise specified.
END OF SECTION
22 05 00 30
PART 2
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
PART 3
3.1
GENERAL
Section Includes
Related Sections And Divisions
References
Submittals
Regulatory Requirements
Extra materials
PRODUCTS
Flexible Pipe Connectors-Steel Piping
Flexible Pipe Connectors-Copper Piping
Expansion Joints-Stainless Steel Bellows Type
Expansion Joints-External Ring Controlled Stainless Steel Bellows Type
Expansion Joints-Single Sphere, Below Compensator
Expansion Joints-Two Ply Bronze Bellows Type
Expansion Joints-Low Pressure Compensator with Two Ply Bronze Bellows
Expansion Joints-Steel with Two Packed Sliding Sleeve
Expansion Joints-Copper with packed Sliding Sleeve
EXECUTION
Installation
22 05 16 1
PART 1
GENERAL
1.1
SECTION INCLUDES
A.
B.
C.
1.2
B.
C.
1.3
1.4
A.
B.
SUBMITTALS
A. Product Data:
1. Flexible Pipe Connectors: Indicate maximum temperature and pressure rating, face-toface
length, live length, hose wall thickness, hose convolutions per foot (meter) and per
assembly, fundamental frequency of assembly, braid structure, and total number of
wires in braid.
2. Expansion Joints: Indicate maximum temperature and pressure rating, and maximum
expansion compensation.
B. Samples: Submit two low pressure compensators 3/4 inch (20 mm) in size.
C. Design Data: Indicate selection calculations.
D. Manufacturer's Instructions: Indicate manufacturer's installation instructions, special
procedures, and external controls.
E. Project Record Documents: Record installed locations of flexible pipe connectors,
expansion joints, anchors, and guides.
F. Maintenance Data: Include adjustment instructions.
1.5
REGULATORY REQUIREMENTS
A. Conform to UL requirements.
1.6
EXTRA MATERIALS
A. Supply two sets of packing for each packed expansion joint.
PART 2
PRODUCTS
22 05 16 2
2.1
2.2
2.3
2.4
EXPANSION JOINTS - EXTERNAL RING CONTROLLED STAINLESS STEEL
BELLOWS TYPE
A. Pressure Rating: 125 psi and 400 degrees F (862 kPa and 204 degrees C).
B. Maximum Compression: 15/16 inch (24 mm).
C. Maximum Extension: 5/16 inch (8 mm).
D. Maximum Offset: 1/8 inch (3 mm).
E. Joint: Flanged.
F. Size: Use pipe sized units.
G. Accessories: Internal flow liner.
H. Application: Steel piping over 2 inches (50 mm).
2.5
22 05 16 3
B. Pressure Rating, Sizes 3/4 Inch to 2 Inch (20 mm to 50 mm): 150 psi and 210 degrees F
(1040 kPa and 99 degrees C).
C. Pressure Rating, Sizes 1-1/2 Inch to 12 Inch (32 mm to 300 mm): 150 psi and 250
degrees F (1040 kPa and 121 degrees C).
D. Pressure Rating, Sizes 14 Inch to 24 Inch (350 mm to 600 mm): 105 psi and 250 degrees
F (725 kPa and 121 degrees C).
E. Maximum Compression: 1/2 inch (13 mm).
F. Maximum Elongation: 3/8 inch (10 mm).
G. Maximum Offset: 3/8 inch (10 mm).
H. Maximum Angular Movement: 15 degrees.
I.
2.6
2.7
EXPANSION JOINTS - LOW PRESSURE COMPENSATOR WITH TWO-PLY BRONZE
BELLOWS
A. Working Pressure: 75 psi (510 kPa).
B. Maximum Temperatures: 250 degrees F (121 degrees C).
C. Maximum Compression: 1/2 inch (12.7 mm).
D. Maximum Extension: 5/32 inch (4.0 mm).
E. Joint: Soldered.
F. Size: Use pipe sized units.
G. Application: Copper or steel piping 3 inches (75 mm) and under.
2.8
2.9
22 05 16 4
PART 3
EXECUTION
3.1
INSTALLATION
A. Install in accordance with manufacturer's instructions.
B. Install in accordance with EJMA (Expansion Joint Manufacturers Association) Standards.
C. Install flexible pipe connectors on pipes connected to vibration isolated equipment.
Provide line size flexible connectors.
D. Install flexible connectors at right angles to displacement. Install one end immediately
adjacent to isolated equipment and anchor other end. Install in horizontal plane unless
indicated otherwise.
E. Anchor pipe to building structure where indicated. Provide pipe guides so movement is
directed along axis of pipe only. Erect piping such that strain and weight is not on cast
connections or apparatus.
F. Provide support and equipment required to control expansion and contraction of piping.
Provide loops, pipe offsets, and swing joints, or expansion joints where required.
G. Substitute grooved piping for vibration isolated equipment instead of flexible connectors.
Grooved piping need not be anchored.
END OF SECTION
22 05 16 5
PART 2
2.1
2.2
2.3
2.4
2.5
PART 3
3.1
3.2
GENERAL
Summary
Quality Assurance
Submittals
PRODUCTS
Pressure Gauges
Pressure Gauge Taps
Pressure/Temperature Test Plugs
Stem Type Thermometers
Water Flow Meter
EXECUTION
Installation
Application
2259 1
PART 1
1.1
GENERAL
SUMMARY
A.
1.2
This Section includes flow meters, pressure gauges and pressure gauge taps,
thermometers and thermometer wells, static pressure and filter gauges.
QUALITY ASSURANCE
A.
Reference Standards:
1. American National Standards Institute (ANSI).
1.3
SUBMITTALS
A.
Submit with shop drawings list, which indicates use, operating range, total range and
location.
PART 2
PRODUCTS
2.1
PRESSURE GAUGES
A.
114mm diameter in metal case, glycerin filled phosphor bronze bourdon tube, rotary
brass movement, brass socket and 1 percent mid-scale accuracy with front
recalibration adjustment, black figures on white background. Provide brass needle or
gate valve.
B.
Pressure Ranges
Types of Service
Air and water
2.2
Pressure Range
0 to 690 kPa
2.3
2.4
Provide pressure or temperature test plugs. Taps shall be Petes Plug, 15mm NPT,
brass with Nordel core, Model 710. In addition, the Contractor shall supply the
Employer with six 125mm stem pocked testing thermometers.
229mm scale adjustable angle, 0.5 degrees C scale division, mercury-free lens, front
tube, cast aluminum case, brass separable socket or flange with perforated stem, and
80mm extension necks on insulated piping.
B.
2259 2
silicon and be complete with caps and chains. Thermometers and thermometer wells
shall have the following insertion lengths:
1. Located in Horizontal Piping and Vertical Piping below 1.8 meters:
a. 65mm, 100mm and 125mm Pipe
b. 125mm, 150mm and 200mm Pipe
2. Locate in Vertical Piping above 1.8meters:
a. 125mm, 80mm, 100mm & 150mm Pipe
b. 200mm, 200mm Pipe and above
C.
2.5
Scale ranges may be slightly greater than shown to meet manufacturers standard.
Require ranges in degrees Celsius.
1. Chilled Water -18 40 deg C
2. Heat Recovery -18 40 deg C
3. Heating Water 0 115 deg C
WATER FLOW METERS
A.
B.
Materials
1. Sensor housing: powder-coated die-cast aluminum
2. Measuring tube: stainless steel with polyurethane liner.
3. Flange: Class 150 ANSI B16.5 CS A105
Design Requirements:
Sensor and Transmitter: NEMA 4X certified.
Compact version (transmitter and sensor form a mechanical unit).
Calibration: 3-Point. 0.5%
Sensor:
a. Electromagnetic flow measurement
b. Flanged connections
c. Bi-directional flow measurement capability
d. No pressure loss through sensor
e. Maximum flow measurement: 167 IGPM
f. Maximum fluid velocity: +80C
g. Maximum fluid temperature: +50C
h. Maximum process pressure: 40 bar
5. Measuring Tube:
a. Internal diameter: 79mm
b. Pressure rating: ANSI Class 150
6. Transmitter:
a. Key operation, two-line, non-illuminated display
7. Power Supply:
a. Hook meter to available power supply.
b. Include on instrument power display option.
1.
2.
3.
4.
PART 3
3.1
EXECUTION
INSTALLATION
A.
B.
Provide 1 pressure gauge per pump installing taps before strainers and on suction and
discharge of pump. Pipe to gauge.
C.
2259 3
D.
E.
3.2
APPLICATION
A.
B.
C.
Pumps
Piping risers and distribution
PRV stations
Pressure Vessels
Expansion tanks
Stem-Type Thermometers
1. Expansion Tank
D.
Pressure/Temperature Taps
1. All automatic control and pressure reducing valves on inlets and outlets.
2. Pump inlets and outlets.
END OF SECTION
2259 4
PART 2
2.1
2.2
PART 3
3.1
3.2
GENERAL
Section Includes
References
Submittals
Quality Assurance
Delivery, storage, And Protection
Extra materials
PRODUCTS
Valves-Plumbing Services
Mixing Valves
EXECUTION
Preparation
Installation
22 05 23 1
PART 1
GENERAL
1.1
SECTION INCLUDES
A.
.
1.2
REFERENCES
A.
1.3
A.
Product Data: Provide manufacturers catalogue information. Indicate valve data and
ratings.
B.
Shop Drawings: Indicate valve and pipe materials used, jointing methods, supports, floor
and wall penetration seals. Indicate installation, layout, weights, mounting and support
details, and piping connections.
C.
Project Record Documents: Record actual locations of components and tag numbering.
D.
Operation and Maintenance Data: Include installation instructions and spare parts lists.
1.4
QUALITY ASSURANCE
A.
The manufacturer must have at least ten years of experience in the design and manufacture
of specific equipment being supplied.
B.
Qualifications
1. Execute work of this section only by skilled tradesmen employed by a qualified
approved Plumbing Contractor and regularly engaged in the installation of plumbing
equipment.
C.
D.
Valves: Provide manufacturer's name, size and pressure rating marked on valve body.
E.
Products Requiring Electrical Connection: Listed and classified as suitable for the
purpose
specified and indicated.
1.5
1.6
EXTRA MATERIALS
A. Provide two valve stem packings for each size and type of valve installed.
PART 2
PRODUCTS
2.1
VALVES-PLUMBING SERVICES
A.
General
22 05 23 2
The Contractor shall include for the installation of sufficient valves, cocks and strainer at
appropriate locations to enable the system to operate to the satisfaction of the Consultant.
No asbestos containing materials shall be employed in any valve.
Valves shall bear the BSI Kitemark or equivalent denoting Quality System, accreditation
and compliance with British Standards and where no Kitemark scheme exists, valves shall
be manufactured under an approved BS5750 Quality System. All valves should be from
one source (one manufacturer).
Generally, all valves of the same type shall be of the same manufacturer. All gate, globe,
angle, swing check and butterfly valves as a group shall be of the same manufacturer.
All castings shall be clean close grained metal free from rough projections. Unless
otherwise specified valves of 50mm nominal bore and under shall have female ends
screwed to BS 21 and valves 65mm nominal bore and over shall have flanged ends.
Special care must be exercised in the installation of screwed valves to avoid straining
their bodies, and preventing the gate or seat from closing tight. The wrench shall always
be applied to the side being attached to the pipe. When attaching pipe to a valve already
in place, a second wrench shall be used to hold the valve while the pipe is being
tightened. A pipe shall not be screwed so far into a valve as to damage the seat.
Flanged valves shall have matching flanges manufactured in accordance with BS4504.
Composite flanges to BS4504 should be used when butterfly or other 'inside bolt circle'
valves are installed in copper pipe work systems.
All valves which contain copper alloy shall be gunmetal or capable of withstanding
dezincification.
All valves on potable water services shall be approved by the Local Water Supply
Authority and WRc.
Butterfly valves shall be used for size 65mm and above.
B.
Isolating Valves
For sizes up to and including 50mm shall be bronze to BS5154, MSS SP-80, Class 150,
PN 16 (or bronze ball valve PN 25 for working pressure in excess to 1,333 kPa). Valves
shall be complete with position indicator and locking device, asbestos free gland
packing, with non-rising stem, threaded bonnet, WRc approved or equivalent, one piece
wedge and BS21 taper thread (ISO 7). Valves shall be kitemarked or equivalent.
For sizes 65mm and above shall be WRc approved ductile iron butterfly valve to BS
5155 and BS EN 593 PN 16 (or ductile iron BS PN25/ANSI300 for working pressure
In excess to 1,333 kPa). Ductile iron body epoxy coated fully lugged stainless steel disc
EPDM liner. Valves sizes up to DN250 shall have regulating lever. Valves DN 250 and
larger shall be supplied with fully enclosed gear operator and memory stop.
C.
Regulating Valves
Sizes up to and including 50mm valves shall be of the DZR variable orifice double
regulating, to BS7350 PN 16 (or bronze PN25 for working pressure in excess to 1,333
kPa), non-rising stem, screwed bonnet, parabolic regulating disc, double regulating
(memory stop) device, supplied with two test points. The end connections shall be
threaded to BS21 (taper), (parallel) and NPT. Valves shall be kitemarked or equivalent.
Sizes 65mm and above, shall be ductile iron variable orifice double regulating valve, to
22 05 23 3
BS7350 PN 16 (or ductile iron PN25 for working pressure in excess to 1,333 kPa). and
shall be with non-rising stem, bolted bonnet, double regulating (memory stop) device,
end connections flanged to BS4504/ ANSI 150. Valves shall be kitemarked or
equivalent.
D.
Strainers
Strainers, in addition to where shown on drawings shall be fitted upstream of all major
items of plant.
Sizes up to and including 50mm shall be bronze (BS1400 LG2) "Y" type strainer PN16
(or bronze PN25 for working pressure in excess to 1,333 kPa). WRc approved or
equivalent, with 304 perforated stainless steel 40 mesh screen. Strainer shall be with
screwed cap and BS21 taper threaded (ISO7).
Sizes 65mm and above, shall be cast iron to BS1452 Gr 220, PN 16 (or cast iron PN25
for working pressure in excess to 1,333 kPa) and shall be flanged to BS4504 PN 16/
ANSI Class 125 150.
Standards screens:
For Sizes 50-80mm, Hole Dia. 1.2mm.
For Sizes 100-450, Hole Dia. 3.0mm.
E.
F.
22 05 23 4
Each valve shall be equipped with brass readout valves readings integral check valve to
facilitate taking differential pressure with across the orifice for accurate system balance.
As an alternative to the triple duty valve, the use of check valve, shut-off valve and
balancing valve as specified is also acceptable.
G.
Suction diffusers
Furnish and install as indicated on drawings an angle pattern flow straightening fitting
equipped with a combination diffuser-strainer-orifice cylinder, flow straightening vanes,
start-up strainer, permanent magnet and adjustable support foot.
The combination diffuser-strainer-orifice shall be designed to withstand pressure
differential equal to the system pump shut off head and shall be with a free area equal to
five times the cross section area of the pump suction opening.
The length straight pattern valve designed to perform the functions of a non slam check
valve, throttling valve, shut-off valve and calibrated balancing valve.
The valve shall be fitted with a bronze seat, replaceable bronze disc EPDM seat insert,
stainless steel stem, and chatter preventing stainless steel spring.
The valve design shall permit repacking under full system pressure. Each valve shall be
equipped with brass readout valves readings integral check valve to facilitate taking
differential pressure with across the orifice for accurate system balance.
The flow-straightening fitting shall be of cast iron construction with flanged system and
flanged pump connections.
The fitting shall have a carbon steel combination diffuser-strainer-orifice cylinder with
3/16 diameter perforations to protect the system pump.
The full-length carbon steel flow straightening vanes shall provide non-turbulent flow to
the suction side of the system pump.
The magnet shall be positioned in the flow of stream to protect the pump seal (s).
The start-up strainer shall be of 16-mesh bronze, and the adjustable support foot shall
eliminate pipe strain at the flow fitting/pump connection. All internal components shall
be replaceable.
Verify that the nominal pressure of the selected suction diffuser is not less than 1.5 time
the static head on the valve.
As an alternative to the suction diffuser, the use of strainer and shut-off valve is
acceptable.
H.
Float Valves
Float valves shall be installed as indicated on drawings to provide consistent level control
in reserve supply water storage tanks. The valve shall meet the requirements of the
water Byelaws for air gaps and shall be constructed throughout in WRc approved or
equivalent materials and shall prevent back siphonage. Inlet flow shall be coaxial with the
piston movement, to ensure high discharge capacity and smooth, quiet operation. The
valve shall have O ring piston seals, resilient seated disk, dezincification resistant
bronze body and disk components. All floats shall be manufactured in copper to BS2870
and fabricated using WRc approved solder and shall be hydraulically tested to ensure
22 05 23 5
buoyancy and constructed in accordance with BS 1968. Bronze equilibrium float valves
up to 3" and above shall be flanged end BS4504 PN 16.
I.
J.
Flow Measurement
For the purpose of the flow and temperature measurement and the proportional balancing
of water distribution system, the sub-contractor shall provide a digital (microprocessor)
flow measurement test set and shall be suitable for portable or bench mounted use.
K.
Air Vents
Air bottles shall be made from pipeline size tubing each approximately 230mm long fitted
with a cop and 8mm size air cock. They shall be fitted out equal tees. Where an air bottle
is fixed out of each an 8mm copper extension tube shall be run from the cap to within
1.5m of the floor in a position agreed with the Consultant terminating with an 8mm
needle seated key-operating air cock.
Automatic air vents shall have gunmetal or brass bodies, nonferrous or stainless steel floats
and guides and non-corrodible valves and seats. Each automatic air vent shall have an
integral lock
shield valve. Air release pipes shall be run to discharge at a visible
position agreed with the Consultant. The air release pipe work shall be 8mm nominal
bore soft copper which shall be clipped neatly to the structure.
Automatic air vents shall be installed at all high points of pipe headers, pipe risers,
pressure vessels and water heating units.
L. Temperature and Pressure Gauges
Gauges shall be the Bourdon pattern having 100mm diameter dials with black enameled
steel case and dust proof, chromium plated bezel. Gauges shall have indicating black
pointed and loose red index pointer. Pressure gauges shall be installed in pipe work or
equipment using mild steel connector pipes incorporating 10mm diameter copper alloy
cocks with union tailpieces. Pipe work connections shall be 15mm or 10mm nominal bore
with welding or screwed sockets.
Temperature or thermometer pockets shall be stainless steel or nonferrous metal with
15mm nominal bore screwed heads and a packet length giving a 75mm immersion depth.
Pockets shall be screwed into 15mm nominal bore mild steel sockets welded to the pipe
work. All pockets shall be filled with suitable heat conductive graphite oil.
Pockets in pipe work up to 80mm nominal bore shall be installed in bends. Where
pockets are installed in pipe work 32mm nominal bore and below the pipe work shall be
locally increased in cross-sectional area to accommodate the pockets.
Pockets in pipe work 100mm nominal bore and above shall be installed direct into pipe
work. Thermometers shall be linear scaled, filled system type, gas filled unless otherwise
indicated and in full accordance with BS5235.
22 05 23 6
22 05 23 7
two ball stop valves for isolating the control system form the main valve.
14. Valves shall be operationally and hydrostatically tested prior to shipping and shall
carry one year limited warranty against failure due to defects in workmanship or
materials.
15. The basis valves shall be constructed of cast iron ASTM A 126/B, rated for 125 Class
with ANSI flanged connections. Valves shall be capable of operating from 0 to 80oC
ambient.
16. Valves shall be capable of reducing the line pressure as scheduled on the drawing.
P. Air Separator
1. Separator shall be tangential type with line size inlet and outlet connections
2. Separator shall be welded steel with red oxide paint finish, constructed, tested and
labeled in accordance with Section VII of the ASME Boiler and Pressure Vessel
Code for a working pressure of 862kPa.
3. Separator shall be complete with drain connection and air venting fitting.
4. Separator shall have a removable stainless steel strainer with 4.76mm diameter
perforations with a free area of not less than five times the connecting pipe cross
sectional area.
Q. Vacuum Breakers
1. Provide threaded vacuum breakers with ball, spring, O ring flexible seat and screen.
2. Ball shall be 440 stainless steel and seat shall be EPR.
3. Spring shall be 316 stainless steel, screen and cap shall be 304 stainless steel and
threaded collar shall be 416 stainless steel.
4. Brass body.
5. Vacuum breakers shall be equal to Johnson Service VB 126 BR - P-S-E.
R. Hose Bibs
1. Bronze or red brass, replaceable hexagonal disc, hose thread spout, Crane cat. No.58
S.
T. All flanged valves shall be epoxy coated both internally and externally in order to prevent
corrosion and pitting.
22 05 23 8
U. All valves for the domestic water system shall be approved for use on potable water
systems.Valves shall be WRc approved or equivalent.
V.
2.2
The pressure rating of all valves shall be selected to match the pressure in the system
at the location the valve is to be installed.
MIXING VALVES (Not Used)
PART 3
EXECUTION
3.1
PREPARATION
A. Remove scale and foreign material, from inside and outside, before assembly.
B. Prepare valve connections to pipes and equipment with flanges or unions.
3.2
INSTALLATION
22 05 23 9
A. Install valves with stems upright or horizontal, not inverted. Remove protective coatings
prior to Installation.
B. Provide gate valves for shut-off or isolating service.
C. Provide drain valves at main shut-off valves, low points of piping and apparatus.
END OF SECTION
22 05 23 10
SECTION 22 05 48- VIBRATION AND SESMIC CONTROLS FOR PLUMBING PIPING AND
EQUIPMENT
PART 1
1.1
1.2
1.3
1.4
1.5
PART 2
2.1
2.2
2.3
PART 3
3.1
3.2
3.1
GENERAL
Section Includes
Related Sections and Divisions
Submittals
Quality Assurance
Delivery, Storage, and Protection
PRODUCTS
Inertia Bases
Vibration Isolators
Seismic Restraints
EXECUTION
Installation
Field Quality Control
Schedules
22 05 48 1
PART 1
GENERAL
1.1
SECTION INCLUDES
A.
B.
C.
Inertia bases.
Vibration isolators.
Seismic restraints.
1.2
Cast-in-Place Concrete.
Division 23, Section 23 05 48.
Other sections in the Divisions 21, 22, 23 and 25.
1.3
SUBMITTALS
A.
each.
Product Data: Provide schedule of vibration isolator type with location and load on
B.
Shop Drawings: Indicate inertia bases and locate vibration isolators, with static and
dynamic load on each. Indicate seismic control measures.
C.
1.4
QUALITY ASSURANCE
A
The manufacturer must have at least ten years of experience in the design and
manufacture of specific equipment being supplied.
1.5
Deliver and store vibration and seismic controls in shipping containers, with labeling
in place.
PART 2
PRODUCTS
2.1
INERTIA BASES
A.
Structural Bases:
1. Construction: Welded structural steel with gusseted brackets, to support equipment and
motor, with motor slide rails.
2. Design: Sufficiently rigid to prevent misalignment or undue stress on machine, and to
transmit design loads to isolators and snubbers.
B.
22 05 48 2
2.2
VIBRATION ISOLATORS
A.
C.
1. Type : Closed spring mount with top and bottom housing separated with neoprene
rubber stabilizers.
2. Springs: Minimum horizontal stiffness equal to 75 percent vertical stiffness, with
working
deflection between 0.3 and 0.6 of maximum deflection. Color code springs for load
carrying capacity.
3. Housings: Incorporate neoprene isolation pad meeting requirements for neoprene pad
isolators, and neoprene side stabilizers with minimum 0.25 inch (7 mm) clearance.
4. For Exterior and Humid Areas: Hot dipped galvanized housings and neoprene coated
springs.
D.
E.
Spring Hanger:
22 05 48 3
G. Rubber Mount or Hanger: Molded rubber designed for 0.4 inch (10 mm) deflection with
threaded insert.
H. Glass Fiber Pads: Neoprene jacketed pre-compressed molded glass fiber.
I.
Seismic Snubbers:
1. Type: Non-directional and double acting unit consisting of interlocking steel members
restrained by neoprene elements.
2. Elements: Replaceable neoprene, minimum of 0.75 inch (18 mm) thick with minimum
1/8 inch (3 mm) air gap.
3. Capacity: 4 times load assigned to mount groupings at 0.4 inch (10 mm) deflection.
4. Attachment Points and Fasteners: Capable of withstanding 3 times rated load capacity of
seismic snubber.
J.
Roof Mounting Curb: 14 inches (350 mm) high with rigid steel lower section containing
adjustable spring pockets with restrained spring isolators, steel upper section to support
rooftop equipment, and continuous elastomeric membrane extending from upper section
for counter-flashing over roofing. Provide acoustical package consisting of interior
perimeter angles and cross members to support up to two layers of gypsum board.
SEISMIC RESTRAINTS
Refer to Division 23, Section 23 05 48.
PART 3
EXECUTION
3.1
INSTALLATION
A.
B.
22 05 48 4
C.
D.
E.
F.
G.
2. Set concrete inertia bases for 2 inches (50 mm) clearance between housekeeping pad and
base.
3. Adjust equipment level.
On closed spring isolators, adjust so side stabilizers are clear under normal operating
conditions.
Prior to making piping connections to equipment with operating weights substantially
different from installed weights, block up equipment with temporary shims to final
height. When full load is applied, adjust isolators to load to allow shim removal.
Provide pairs of horizontal limit springs on fans with more than 6.0 inches WC (1.5 kPa)
static pressure, and on hanger supported, horizontally mounted axial fans.
Provide seismic snubbers for all equipment, piping, and ductwork mounted on isolators.
Each inertia base shall have minimum of four seismic snubbers located close to isolators.
Snub equipment designated for post-disaster use to 0.05 inch (1.5 mm) maximum
clearance. Other snubbers shall have clearance between 0.15 inch (4 mm) and 0.25 inch
(7 mm).
Support piping connections to equipment mounted on isolators using isolators or resilient
hangers for scheduled distance.
1. Up to 4 Inches (100 mm) Pipe Size: First three points of support.
2. 5 to 8 Inches (125 to 200 mm) Pipe Size: First four points of support.
3. 10 inches (250 mm) Pipe Size and Over: First six points of support.
4. Select three hangers closest to vibration source for minimum 1.0 inch (25 mm) static
deflection or static deflection of isolated equipment. Select remaining isolators for
minimum 1.0 inch (25 mm) static deflection or 1/2 static deflection of isolated equipment.
3.2
Inspect isolated equipment after installation and submit report. Include static deflections.
3.3
SCHEDULES
A.
.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
1 Inch (25 mm) Pipe Size: Isolate 120 diameters from equipment.
2 Inch (50 mm) Pipe Size: Isolate 90 diameters from equipment.
3 Inch (80 mm) Pipe Size: Isolate 80 diameters from equipment.
4 Inch (100 mm) Pipe Size: Isolate 75 diameters from equipment.
6 Inch (150 mm) Pipe Size: Isolate 60 diameters from equipment.
8 Inch (200 mm) Pipe Size: Isolate 60 diameters from equipment.
10 Inch (250 mm) Pipe Size: Isolate 54 diameters from equipment.
12 Inch (300 mm) Pipe Size: Isolate 50 diameters from equipment.
16 Inch (400 mm) Pipe Size: Isolate 45 diameters from equipment.
24 Inch (600 mm) Pipe Size: Isolate 38 diameters from equipment.
END OF SECTION
22 05 48 5
PART 2
2.1
2.2
2.3
2.3
2.4
PART 3
3.1
3.2
GENERAL
Section Includes
Related Sections and Divisions
References
Submittals
PRODUCTS
Nameplates
Tags
Stencils
Pipe Markers
Ceiling Tacks
EXECUTION
Preparation
Installation
22 05 53 1
PART 1
GENERAL
1.1
SECTION INCLUDES
A.
B.
C.
D.
Nameplates.
Tags.
Stencils.
Pipe Markers.
1.2
1.3
REFERENCES
A.
Society of
ASME A13.1 - Scheme for the Identification of Piping Systems; The American
Mechanical Engineers; 1996 (Reaffirmed 2002).
1.4
SUBMITTALS
A.
List: Submit list of wording, symbols, letter size, and color coding for mechanical
identification.
Chart and Schedule: Submit valve chart and schedule, including valve tag number,
location, function, and valve manufacturer's name and model number.
Product Data: Provide manufacturers catalog literature for each product required.
Samples: Submit labels in approved size.
Manufacturer's Installation Instructions: Indicate special procedures, and installation.
Project Record Documents: Record actual locations of tagged valves.
B.
C.
D.
E.
F.
PART 2
PRODUCTS
2.2
NAMEPLATES
A.
2.3
A.
B.
C.
2.4
Plastic Tags: Laminated three-layer plastic with engraved black letters on light
contrasting background color. Tag size minimum 1-1/2 inch (40 mm) diameter.
Metal Tags: Brass with stamped letters; tag size minimum 1-1/2 inch (40 mm)
diameter with smooth edges.
Chart: Typewritten letter size list in anodized aluminum frame.
STENCILS
A.
long
color field, 3/4 inch (20 mm) high letters.
Lulu hypermarket at western region
Date: 31st March 2015 Rev. 00
22 05 53 2
3. 2-1/2 to 6 inch (65-150 mm) Outside Diameter of Insulation or Pipe: 12 inch (300 mm)
long color field, 1-1/4 inch (30 mm) high letters.
4. 8 to 10 inch (200-250 mm) Outside Diameter of Insulation or Pipe: 24 inch (600 mm)
long
color field, 2-1/2 inch (65 mm) high letters.
5. Over 10 inch (250 mm) Outside Diameter of Insulation or Pipe: 32 inch (800 mm) long
color field, 3-1/2 inch (90 mm) high letters.
6. Ductwork and Equipment: 2-1/2 inch (65 mm) high letters.
B.
2.5
PIPE MARKERS
A.
B.
Plastic Pipe Markers: Factory fabricated, flexible, semi- rigid plastic, preformed to
fit around pipe or pipe covering; minimum information indicating flow direction arrow
and identification of fluid being conveyed.
C.
Plastic Tape Pipe Markers: Flexible, vinyl film tape with pressure sensitive adhesive
backing and printed markings.
D.
Underground Plastic Pipe Markers: Bright colored continuously printed plastic ribbon
tape, minimum 6 inches (150 mm) wide by 4 mil (0.10 mm) thick, manufactured for
direct burial service.
2.6
CEILING TACKS
A.
Description: Steel with 3/4 inch (20 mm) diameter color coded head.
B.
PART 3
EXECUTION
3.1
PREPARATION
A.
B.
3.2
A.
B.
C.
D.
22 05 53 3
E.
Install plastic tape pipe markers complete around pipe in accordance with manufacturer's
instructions.
F.
Install underground plastic pipe markers 6 to 8 inches (150 to 200 mm) below finished
grade, directly above buried pipe.
G.
Identify pumps, heat transfer equipment, tanks, and water treatment devices with plastic
nameplates. Small devices, such as in-line pumps, may be identified with tags.
H.
Identify control panels and major control components outside panels with plastic
nameplates.
I.
J.
K.
L.
Identify piping, concealed or exposed, with plastic pipe markers. Use tags on piping 3/4
inch (20
mm) diameter and smaller. Identify service, flow direction, and pressure.
Install in clear view and align with axis of piping. Locate identification not to exceed 20
feet (6 m) on straight runs including risers and drops, adjacent to each valve and Tee, at
each side of penetration of structure or enclosure, and at each obstruction.
M.
Provide ceiling tacks to locate valves or dampers above T-bar type panel ceilings.
Locate in corner of panel closest to equipment.
END OF SECTION
22 05 53 4
GENERAL
Section Includes
References
Submittals
Quality Assurance
Delivery, Storage, and Protection
PRODUCTS
Drainage Manholes, Catch Basins and Gully-Traps
EXECUTION
Preparation
Installation
22 05 73 1
PART 1
GENERAL
1.1
SECTION INCLUDES
A.
1.2
A.
1.3
Fully compliant with the requirements and approvals of the local authorities having
jurisdiction.
SUBMITTALS
A.
B.
Shop Drawings: Indicate materials used, construction details, supports, water proof
details . Indicate installation, layout, and piping connections.
C.
Project Record Documents: Record actual locations of components and tag numbering.
D.
Operation and Maintenance Data: Include installation instructions and spare parts lists.
1.4
QUALITY ASSURANCE
The manufacturer must have at least ten years of experience in the design and
manufacture of specific equipment being supplied.
Qualifications
A.
B.
jurisdiction.
C.
1.5
Provide manufacturer's name, size and manufacturing standard marked on the product
body.
DELIVERY, STORAGE, AND PROTECTION
A.
B.
PART 2
PRODUCTS
22 05 73 2
PART 3
EXECUTION
3.1
PREPARATION
A.
3.2
INSTALLATION
A.
Install manholes, catch basins and gully-traps to the approval of the local Drainage
Department.
B.
C.
Where it is necessary to install manholes and gully-traps in a finished area, the covers
shall have equal finish of the adjacent area.
Manholes, gully-traps and catch basins shall be so installed that there is a clearance of not
less than 450mm for the purpose of rodding and cleaning.
END OF SECTION
22 05 73 3
PART 3
3.1
3.2
GENERAL
Section Includes
References
Submittals
Quality Assurance
Delivery, storage, and Protection
PRODUCTS
Cleanouts-Plumbing Services
EXECUTION
Preparation
Installation
22 05 75 1
PART 1
GENERAL
1.1
SECTION INCLUDES
A.
1.2
REFERENCES
A.
1.3
SUBMITTALS
A.
B.
Shop Drawings: Indicate cleanout materials used, jointing methods, supports, floor
and wall penetration seals. Indicate installation, layout, weights, mounting and support
details, and piping connections.
C.
Project Record Documents: Record actual locations of components and tag numbering.
D.
Operation and Maintenance Data: Include installation instructions and spare parts lists.
1.4
QUALITY ASSURANCE
The manufacturer must have at least ten years of experience in the design and
manufacture of specific equipment being supplied.
Qualifications
A.
B.
C.
Cleanouts: Provide manufacturer's name, size and pressure rating marked on valve body.
D.
Products Requiring Electrical Connection: Listed and classified as suitable for the
purpose
specified and indicated.
1.5
B.
C.
PART 2
PRODUCTS
CLEANOUTS-PLUMBING SERVICES
All concealed cleanouts shall have easy access for cleaning and inspection. Where concealed
cleanouts have no direct access and installed in furred ceiling spaces, cleanouts shall extend up
through floor slab above and the Engineer shall give specific approval to its location in the above
floor space.
Lulu hypermarket at western region
Date: 31st March 2015 Rev. 00
22 05 75 2
Cleanouts in terrazzo, tile or carpeted floors shall be complete with nickel bronze frame and square or
round full opening nickel bronze access cover having terrazzo, tile or carpet recesses to permit in
setting of the applicable flooring or floor covering material. Flat top cleanouts without recesses will
not be acceptable.
Cleanouts in concrete floors shall be complete with polished bronze frame and scoriated nickel bronze
tractor duty cover and internal brass or bronze plug.
Cleanouts in floors with a waterproof membrane shall be similar to the cleanouts specified above but
with a flashing clamp device for attaching to the waterproof membrane below finished floor level.
Cleanouts at the base of each vertical stack and rain water leader shall be either Daisy or Barrett type.
Cleanouts extending through walls in finished areas shall have stainless steel covering plates to permit
access to cleanout plugs.
Cleanouts in ceiling spaces shall be proprietary screwed type as supplied by the HDPE piping
manufacturer.
PART 3
EXECUTION
3.1
PREPARATION
A.
Remove scale and foreign material, from inside and outside, before assembly.
B.
3.2
INSTALLATION
A.
Cleanouts shall be installed at each change of direction of drainage pipes inside the
building and, and where indicated on the drawings. Cleanouts shall be not more than 10m
apart in horizontal lines. A cleanout shall be provided at or near the foot of each vertical
waste or soil stack.
B.
Cleanouts without direct access on concealed piping shall be extended through and
terminate flush with finished wall or floor. Pits or chases may be left in the wall or floor,
provided they are of sufficient size to permit removal of the cleanout plug and proper
cleaning of the system.
C.
Where it is necessary to conceal a cleanout plug, a heavy duty stainless steel covering
plate shall be provided, which will permit ready access to the plug.
D.
E.
Cleanouts shall be of the same nominal size as the pipes up to 100mm pipe diameter and
not less than 100mm for larger piping.
F.
Cleanouts shall be so installed that there is a clearance of not less than 450mm for the
purpose of rodding and cleaning.
END OF SECTION
22 05 75 3
PART 2
2.1
2.2
2.3
2.4
2.5
2.6
PART 3
3.1
3.2
3.3
GENERAL
Section Includes
Related Sections and Divisions
References
Submittals
Quality Assurance
Delivery, Storage, and protection
Environmental requirements
PRODUCTS
Requirements of all products of this section
Glass Fiber, Flexible
Glass Fiber, Rigid
Cellular Glass
Hydrous Calcium Silicate
Flexible Elastomeric Cellular Insulation
EXECUTION
Examination
Installation
Schedules
22 07 16 1
PART 1
GENERAL
1.1
SECTION INCLUDES
A.
B.
C.
1.2
Equipment insulation.
Covering.
Breeching insulation.
RELATED SECTIONS AND DIVISIONS
A.
B.
1.3
A.
B.
ASTM B 209 - Standard Specification for Aluminum and Aluminum-Alloy Sheet and
Plate; 2004.
C.
ASTM B 209M - Standard Specification for Aluminum and Aluminum-Alloy Sheet and
Plate (Metric); 2004.
D.
ASTM C 177 - Standard Test Method for Steady-State Heat Flux Measurements and
Thermal Transmission Properties by Means of the Guarded-Hot-Plate Apparatus; 2004.
E.
2000.
ASTM C 195 - Standard Specification for Mineral Fiber Thermal Insulating Cement;
F.
G.
ASTM C 518 - Standard Test Method for Steady-State Thermal Transmission Properties
by Means of the Heat Flow Meter Apparatus; 2004.
H.
ASTM C 533 - Standard Specification for Calcium Silicate Block and Pipe Thermal
Insulation; 2004.
I.
J.
ASTM C 552 - Standard Specification for Cellular Glass Thermal Insulation; 2003.
K.
ASTM C 553 - Specification for Mineral Fiber Blanket Thermal Insulation for
Commercial and
Industrial Applications; 2002.
L.
ASTM C 592 - Standard Specification for Mineral Fiber Blanket Insulation and BlanketType Pipe Insulation (Metal-Mesh Covered) (Industrial Type); 2004.
M.
ASTM C 612 - Standard Specification for Mineral Fiber Block and Board Thermal
Insulation; 2004.
N.
O.
ASTM E 96/E 96M - Standard Test Methods for Water Vapor Transmission of Materials;
2005.
22 07 16 2
P.
Q.
UL 723 - Standard for Test for Surface Burning Characteristics of Building Materials;
Underwriters Laboratories Inc.; 2003.
1.4
SUBMITTALS
A.
B.
Samples: Submit two samples of any representative size illustrating each insulation
type.
C.
1.5
materials
QUALITY ASSURANCE
A.
B.
1.6
B.
Protect insulation from weather and construction traffic, dirt, water, chemical, and
mechanical damage, by storing in original wrapping.
1.7
ENVIRONMENTAL REQUIREMENTS
A.
B.
Maintain temperature during and after installation for minimum period of 24 hours.
PART 2
PRODUCTS
2.1
2.2
A.
22 07 16 3
B.
Vapor Barrier Jacket: Kraft paper reinforced with glass fiber yarn and bonded to
aluminized film.
1. Moisture Vapor Permeability: 0.02 perm inch (0.029 ng/Pa s m), when tested in
accordance with ASTM E 96/E 96M.
2. Secure with self-sealing longitudinal laps and butt strips.
3. Secure with outward clinch expanding staples and vapor barrier mastic.
C.
Tie Wire: 0.048 inch (1.22 mm) stainless steel with twisted ends on maximum 12 inch
(300 mm) centers.
D.
E.
2.3
.
3. Maximum Water Vapor Sorption: 5.0 percent by weight.
4. Maximum Density: 8.0 lb/cu ft (128 kg/cu m).
B.
Kraft paper reinforced with glass fiber yarn and bonded to aluminized film.
2. Moisture Vapor Permeability: 0.02 perm inch (0.029 ng/Pa s m), when tested in
accordance with ASTM E 96/E 96M.
3. Secure with self-sealing longitudinal laps and butt strips.
C.
4. Secure with outward clinch expanding staples and vapor barrier mastic.
Facing: 1 inch (25 mm) galvanized steel hexagonal wire mesh stitched on one face of
insulation.
D.
2.4
CELLULAR GLASS
A.
2.5
22 07 16 4
A.
'K' ('Ksi') Value: 0.40 at 300 degrees F (0.057 at 148 degrees C), when tested in
accordance with ASTM C 177 or C518.
2. Maximum Service Temperature: 1200 degrees F (649 degrees C).
3. Density: 15 lb/cu ft (249 kg/cu m).
B.
Tie Wire: 0.048 inches (1.22 mm) stainless steel with twisted ends on maximum 12 inch
(300 mm) centers.
C.
2.6
B.
insulation.
PART 3 EXECUTION
3.1
EXAMINATION
A. Verify that equipment has been tested before applying insulation materials.
B. Verify that surfaces are clean and dry, with foreign material removed.
3.2
INSTALLATION
A. Install in accordance with manufacturer's instructions.
B. Factory Insulated Equipment: Do not insulate.
C. Exposed Equipment: Locate insulation and cover seams in least visible locations.
D. Apply insulation close to equipment by grooving, scoring, and beveling insulation. Fasten
insulation to equipment with studs, pins, clips, adhesive, wires, or bands.
E. Fill joints, cracks, seams, and depressions with bedding compound to form smooth surface.
On cold equipment, use vapor barrier cement.
F. Insulated equipment containing fluids below ambient temperature: Insulate entire system.
G. Fiber glass insulated equipment containing fluids below ambient temperature: Provide vapor
barrier jackets, factory-applied or field-applied. Finish with glass cloth and vapor barrier
adhesive.
H. For hot equipment containing fluids 140 degrees F (60 degrees C) or less, do not insulate
flanges and unions, but bevel and seal ends of insulation.
For hot equipment containing fluids over 140 degrees F (60 degrees C), insulate flanges and
unions with removable sections and jackets.
22 07 16 5
J. Fiber glass insulated equipment containing fluids above ambient temperature: Provide
standard jackets, with or without vapor barrier, factory-applied or field-applied. Finish with
glass cloth and adhesive.
K. Inserts and Shields:
1.
2.
3.
4.
O. Cover glass fiber insulation with metal mesh and finish with heavy coat of insulating cement
aluminum jacket.
P. Nameplates and ASME Stamps: Bevel and seal insulation around; do not insulate over.
Q. Equipment Requiring Access for Maintenance, Repair, or Cleaning: Install insulation so it
can be easily removed and replaced without damage.
3.3
SCHEDULES
A. Heating Systems:
1. Pump Bodies
(Flexible fiber glass blanket c/w min. 25mm thick and 72 Kg/m3 density and vapor seal)
2. Flue Gas Breeching (Calcium Silicate c/w min. 100mm thick and stainless steel cladding)
3. Stacks to Roof
(Calcium Silicate c/w min. 100mm thick and stainless steel cladding)
B. Cooling Systems:
1. Pump Bodies: (Flexible fiber glass blanket c/w min. 25mm thick and 72 Kg/m3 density and
vapor seal)
2. Air Separators:
3. Expansion Tanks:
4. Chiller Cold Surfaces (Not Factory Insulated):
5. Chiller Hot Surfaces (Not Factory Insulated):
22 07 16 6
END OF SECTION
22 07 16 7
PART 1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
PART 2
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10
PART 3
3.1
3.2
3.3
GENERAL
Section Includes
Related Sections and Divisions
References
Submittals
Quality Assurance
Delivery, Storage, and Protection
Environmental Requirements
PRODUCTS
Requirements of all products of this section
Glass Fiber
Cellular Glass
Expanded Polystyrene
Expanded Perlite
Hydrous Calcium Silicate
Polyisocuynurate Cellular Plastic
Polyethylene
Flexible Elastomeric Cellular Insulation
Jackets
EXECUTION
Examination
Installation
Schedules
22 07 19 1
PART 1
1.1
GENERAL
SECTION INCLUDES
A. Piping insulation.
B. Jacket Accessories.
1.2
B.
1.3
REFERENCES
A.
B.
ASTM B 209 - Standard Specification for Aluminum and Aluminum-Alloy Sheet and
Plate; 2004.
C.
ASTM B 209M - Standard Specification for Aluminum and Aluminum-Alloy Sheet and
Plate (Metric); 2004.
D.
ASTM C 177 - Standard Test Method for Steady-State Heat Flux Measurements and
Thermal Transmission Properties by Means of the Guarded-Hot-Plate Apparatus; 2004.
E.
ASTM C 195 - Standard Specification for Mineral Fiber Thermal Insulating Cement;
2000.
F.
G.
ASTM C 518 - Standard Test Method for Steady-State Thermal Transmission Properties
by Means of the Heat Flow Meter Apparatus; 2004.
H.
ASTM C 533 - Standard Specification for Calcium Silicate Block and Pipe Thermal
Insulation; 2004.
I.
J.
K.
ASTM C 552 - Standard Specification for Cellular Glass Thermal Insulation; 2003.
L.
ASTM C 578 - Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation;
2005a.
M.
ASTM C 585 - Standard Practice for Inner and Outer Diameters of Rigid Thermal
Insulation for Nominal Sizes of Pipe and Tubing (NPS System); 1990 (Reapproved
2004).
N.
22 07 19 2
O.
ASTM C 610 - Standard Specification for Molded Expanded Perlite Block and Pipe
Thermal Insulation; 2005.
P.
ASTM C 795 - Standard Specification for Thermal Insulation for Use in Contact with
Austenitic Stainless Steel; 2003.
Q.
R.
ASTM D 2842 - Standard Test Method for Water Absorption of Rigid Cellular Plastics;
2001.
S.
T.
ASTM E 96/E 96M - Standard Test Methods for Water Vapor Transmission of Materials;
2005.
U.
V.
UL 723 - Standard for Test for Surface Burning Characteristics of Building Materials;
Underwriters Laboratories Inc.; 2003.
1.4
or
SUBMITTALS
A.
B.
Samples: Submit two samples of any representative size illustrating each insulation type.
C.
1.5
materials
QUALITY ASSURANCE
A.
B.
1.6
B.
Protect insulation from weather and construction traffic, dirt, water, chemical, and
mechanical damage, by storing in original wrapping.
1.7
ENVIRONMENTAL REQUIREMENTS
A.
22 07 19 3
B.
Maintain temperature during and after installation for minimum period of 24 hours.
PART 2
PRODUCTS
2.1
2.2
A.
B.
Insulation: ASTM C 547 and ASTM C 795; semi-rigid, noncombustible, end grain
adhered to jacket.
1. 'K' ('Ksi') value: ASTM C 177, 0.24 at 75 degrees F (0.035 at 24 degrees C).
2. Maximum service temperature: 650 degrees F (343 degrees C).
3. Maximum moisture absorption: 0.2 percent by volume.
C.
Vapor Barrier Jacket: White Kraft paper with glass fiber yarn, bonded to aluminized film;
moisture vapor transmission when tested in accordance with ASTM E 96/E 96M of 0.02
perm-inches (0.029 ng/Pa s m).
D.
Tie Wire: 0.048 inch (1.22 mm) stainless steel with twisted ends on maximum 12 inch
(300 mm) centers.
E.
F.
G.
H.
2.3
I.
Outdoor Vapor Barrier Mastic: Vinyl emulsion type acrylic or mastic, compatible with
insulation, black color.
J.
Outdoor Breather Mastic: Vinyl emulsion type acrylic or mastic, compatible with
insulation, black color.
K.
22 07 19 4
A.
2.4
EXPANDED POLYSTYRENE
A.
2.5
EXPANDED PERLITE
A.
2.6
Insulation: ASTM C 533 and ASTM C 795; rigid molded, asbestos free, gold color.
1. 'K' ('Ksi') value: ASTM C 177 and C518; 0.40 at 300 degrees F (0.057 at 149 degrees
C), when tested in accordance with ASTM C 177 or ASTM C 518.
2. Maximum service temperature: 1200 degrees F (649 degrees C).
3. Density: 15 lb/cu ft (240 kg/cu m).
B.
Tie Wire: 0.048 inch (1.22 mm) stainless steel with twisted ends on maximum 12 inch
(300 mm) centers.
C.
2.7
2.8
POLYETHYLENE
A.
1.
2.
3.
4.
5.
22 07 19 5
B.
Elastomeric Foam Adhesive: Air dried, contact adhesive, compatible with insulation.
2.10
A.
JACKETS
PVC Plastic.
1. Jacket: One piece molded type fitting covers and sheet material, off-white color.
a. Minimum Service Temperature: 0 degrees F (-18 degrees C).
b. Maximum Service Temperature: 150 degrees F (66 degrees C).
c. Moisture Vapor Permeability: 0.002 perm inch (0.0029 ng/Pa s m), maximum,
when tested in accordance with ASTM E 96/E 96M.
d. Thickness: 10 mil (0.25 mm).
e. Connections: Brush on welding adhesive.
2. Covering Adhesive Mastic: Compatible with insulation.
B.
ABS Plastic
1. Jacket: One piece molded type fitting covers and sheet material, off-white color.
a. Minimum Service Temperature: -40 degrees F (-40 degrees C).
b. Maximum Service Temperature of 180 degrees F (82 degrees C).
c. Moisture Vapor Permeability: 0.012 perm inch (0.018 ng/Pa s m), when
tested in accordance with ASTM E 96/E 96M.
d. Thickness: 30 mil (0.76 mm).
e. Connections: Brush on welding adhesive.
C.
Canvas Jacket: UL listed 6 oz/sq yd (220 g/sq m) plain weave cotton fabric treated with
dilute fire retardant lagging adhesive.Lagging Adhesive: Compatible with insulation.
D.
PART 3
EXECUTION
22 07 19 6
3.1
EXAMINATION
A.
Verify that piping has been tested before applying insulation materials.
B.
Verify that surfaces are clean and dry, with foreign material removed.
3.2
INSTALLATION
A.
B.
C.
Exposed Piping: Locate insulation and cover seams in least visible locations.
D.
Insulated pipes conveying fluids below ambient temperature: Insulate entire system
including fittings, valves, unions, flanges, strainers, flexible connections, pump bodies,
and expansion joints.
E.
Insulate fittings, joints, and valves with molded insulation of like material and thickness
as adjacent pipe. Finish with glass cloth and vapor barrier adhesive or PVC fitting
covers.
F.
For hot piping conveying fluids 140 degrees F (60 degrees C) or less, do not insulate
flanges and unions at equipment, but bevel and seal ends of insulation.
G.
For hot piping conveying fluids over 140 degrees F (60 degrees C), insulate flanges and
unions at equipment.
H.
I.
J. Continue insulation through walls, sleeves, pipe hangers, and other pipe penetrations. Finish
at supports, protrusions, and interruptions. At fire separations, refer to Section 07 8400.
22 07 19 7
K. Pipe Exposed in Mechanical Equipment Rooms or Finished Spaces (less than 10 feet
meters) above finished floor): Finish with canvas jacket sized for finish painting.
(3
L. Exterior Applications: Provide vapor barrier jacket. Insulate fittings, joints, and valves with
insulation of like material and thickness as adjoining pipe, and finish with glass mesh
reinforced vapor barrier cement. Cover with aluminum jacket with seams located on
bottom side of horizontal piping.
M. Buried Piping: Provide factory fabricated assembly with inner all-purpose service jacket
with
self-sealing lap, and asphalt impregnated open mesh glass fabric, with one mil (0.025 mm)
thick aluminum foil sandwiched between three layers of bituminous compound; outer surface
faced with a polyester film.
N. Heat Traced Piping: Insulate fittings, joints, and valves with insulation of like material,
thickness, and finish as adjoining pipe. Size large enough to enclose pipe and heat
tracer. Cover with aluminum jacket with seams located on bottom side of horizontal piping.
3.3
SCHEDULES
A. Heating Systems:
1. Heating Water Supply and Return
B. Cooling Systems:
1. Chilled Water.
22 07 19 8
E.
Other Systems (Very high temperature hot piped services from 233o to 650oC) including:
1. Engine Exhaust Piping
2. Piping Exposed to Freezing with Heat Tracing:
Fittings
Thickness up to 100 mm
100 mm
100 mm
Thickness over
100 mm
125 mm
F.
Vapor Seal
No
Aluminum Jacketing
Yes
125 mm
No
Yes
22 07 19 9
1. All Soil, Waste and Rain Water pipes and fittings above habitable areas shall be
acoustically treated.
Schedule of Acoustic Insulation for Drainage Pipe work Systems
Insulation type Fiberglass batting. Thickness - 25mm
.Vapor barrier Type KNM 100 ALQ-1 Kinetics Noise Control Inc. or approved equal.
The decoupling layer shall be of type KFA Kinetics Noise Control Inc. or approved equal.
END OF SECTION
22 07 19 10