Professional Documents
Culture Documents
INT69 SU2
Application
The INT69 SU2 Diagnosis motor protector is a further development of the
reliable KRIWAN compressor protection unit INT69 SU2 with additional
flexibly reacting protection functions for extending the service life of a
refrigeration system. Of added value is the comprehensive diagnosis with
data memory for quickly determining the cause in case of a malfunction.
The INT69 SU2 Diagnose automatically saves operational and error data
in a nonvolatile memory. This data can be retrieved on a PC as needed
and analysed for diagnosis. The full scope of the diagnosis is achieved
by using KRIWAN-specific AMS sensors. The data recorded includes the
operating times in each temperature range of the motor winding.
Functional description
INT69 SU2
DP
S1 M2 M1
Technical specifications
K1
C
F1
LP
HP
Supply
Wiring diagram
76.5
72.1
81.5
4.7
15.9
T2
30.8
3.84
T1
S2
64.8
S1
M2 M1
5.85
35
Dimensions in mm
Supply voltage
- Dual voltage
or
- AC24V
Permitted ambient temperature
Temperature sensor
- Type
- R25,total
- Rtrip, static
- Rreset
Time delay
Short circuit monitoring system
Typically <30
PTC
Reset of running time
Power interruption/mains failure for
approx. 5s
Relay contact
max. 240V ~ 2.5A C300
min. 24V ~ 20mA
Mechanical service life
Approx. 1 million switching cycles
Interface
Diagnose port (DP)
Protection class acc. to
IP00
EN 60529
Connection type
6.3mm flat connection
Housing material
PA glass-fibre-reinforced
Mounting
Screw mounted
Dimensions [mm]
81.5x76.5x35 (LxWxH)
Weight
Approx. 200 g
Check base
IEC/EN 60335/60730
EN 61000-6-2, EN 61000-6-3
EN 61010-1
Overvoltage category II
Pollution level 2
Approval
UL file no. 75899, VDE reg. no. C400
Order data
INT69 SU2 Diagnose dual voltage
INT69 SU2 Diagnose AC24V
22 A 622
31 A 622
Accessories on request
Technical changes reserved
KRIWAN Industrie-Elektronik GmbH Allmand 11 D-74670 Forchtenberg phone ++49-7947-822-0 fax ++49-7947-1288 e-mail: info@kriwan.com home: www.kriwan.com
Product group A
T2 T1 S2
Edition: 710.00394.0
INT69 SU2
Diagnose