SPESIFIKASI PERALATAN MEKANIKAL DAN ELEKTRIKAL PLTM CIKEBO.

3.1.

Spesifikasi Peralatan Pembangkit


Spesifikasi peralatan Mekanikal dan Elektrikal PLTM Cikebo termasuk

peralatan switchgear di lokasi Pembangkit seperti yang ditunjukan pada Single Line
Diagram (SLD) PLTM Cikebo terlampir adalah sebagai berikut :
1.

Turbin.
1

2.

Rated Net Head

Meter

56,5

Generator.
1
2
3
4
5
6
7

3.

Standar
Rated output
Power
Rated Current
Power factor
Tegangan
Frekwensi

IS 4722 / IEC60034
2 x 2822
2 x 3320
304,25
0,85
6,3
50

kW
kVA
Amp
kV
Hz

Main Trasformer
1
2
3
4
5
6
7
8
9
10

Type
Kapasitas
Frekwensi
Tegangan Primer
Tegangan Sekunder
Type of Tap Changer
Taping Range
Impedansi
Neutral Grounding Resistor
Accessories

MVA
Hz
kV
kV

%
Ohm
-

3 phase, ONAN, Outdoor


2 x 4,0
50
6,3
20
ON Load Tap Changer
+10 %/- 25 % @ of 5 % steps
+/- 7
Resistor 12 Ohm or 40 Ohm
Double float type buchholz
having alarm and trip contacts
Dial type (150 mm) oil
temperature indicator
with alarm and trip contacts
and maximum
reading pointer with resetting
device
Dial type (150 mm) winding
temperature indicator (WTI)
with alarm, cooler control and
trip contacts and maximum
reading pointer with resetting
device
Magnetic oil level gauge, with
alarm contact.
Flexible oil resistant air bag in

the conservator
- Tap position indicator (Local )
- Bi-directional wheels with
suitable locking arrangement.
- HV neutral CTs for REF
protection.
- Rating & Diagram Plate
Anodised Aluminium
- Earthing Terminals
- Lifting Lugs
- Radiators
- Silicagel Breather
- Pressure relief valve.
- Bottom drain Filter Valve
- Top Filter Valve
4.

Auxiliary Trasformer
1
2
3
4
5
6
7
8
9

Type
Kapasitas
Frekwensi
Tegangan Primer
Tegangan Sekunder
Type of Tap Changer
Taping Range
Impedansi
Accessories

kVA
Hz
kV
kV

%
-

5.

3 phase, ONAN, Indoor


100
50
6,3
0,4
OFF Load tap changer
+/- 5 % @ of 2.5 % steps
+/- 4
Pressure Gauge
Dial untuk Thermometer
Oil Level Gauge
Temperature switch (High and
Low)
Hand Hole

Peralatan Switchgear

5.1. Switchgear 6,3 kV


5.1.1. Disconector Switch (DS)
1
2
3
4
5
6
7
8

Type
Tegangan
Rated Voltage
Rated Frquency
Tingkat Tegangan Isolasi
Arus Nominal
Arus Pemutus Hubung
Singkat untuk 1 detik
Tegangan Kontrol

5.1.2. Transformator Arus (CT)

kV
kV
Hz
kV
Amp

3 phase
6,3
7,2
50
125
630

kA

25

V DC

110 Volt

1
2
3

Type
Rasio Arus (Primer/sekunder)
Class

Amp

1 phase, Epoxy Resin


400/1-1
Metering 0,2
Proteksi 5P20

5.1.3. Transformator Tegangan (PT)


1
2
3

Type
Tegangan Primer
Tegangan Sekuder

kV
V

1 phase, Epoxy Resin


6,6/V3
110/V3

5.2. Swichgear 20 kV
5..2.1 Busbar 20 kV
1
Standard
2
Type of designation (tempat
pemasangan dan konfigurasi
busbar)
3
Rated voltage (Ur)
4
Rated lightning impuls
withstand voltage (Up)
5
Rated power frequency
withstand voltage (Ud)
6
Rated frequency
7
Rated normal current
8
Rated short-time withstand
current ( I k )
9
Rated duration of short circuit
10
Rated peak withstand current
(Ip)
11
Degrees of protection (IP)
12
Insulation medium
13
Material Busbar system
14
Number of phase busbar
5.2.2 Circuit Breaker 20 KV Indoor
1
Standard
2
Type of designation
3
Operation duty minimum
4
Rated voltage
5
Rated nominal current
6
Rated lightning impuls
withstand voltage
7
Breaking capacity
10
Making capacity
11
Rated frequency
12
Interrupting medium
13
Mechanism type
14
Mechanical endurance
15
Opening time

IEC 62271-200
Indoor metal clad and single
busbar
kV

24

kV

125

kV

50

Hz
A

50
1250

kA

25

sec.

kA

2,5 x I k
Minimum IP 4X
Air
Copper with heatshrink
3

kV
A

IEC 602271-100
Withdrawable or truck-mounted
O - 0.3s - CO - 180s CO
24
630

kV

125

kA
kA
Hz

25
2,5 x I k
50
SF6 or Vacuum
motor spring
M2 (10.000 times)
60

ms

16
17

5.2.3
1
2
3
4
5
6
7
8
9

10
5.2.4
1
2
3
4
7
8

9
10

5.2.5

Closing time
Supply voltage :
- Control voltage
- Tripping and closing Coils
- Motor voltage
Current Transformer 20 kV
Standard
Type of design
Nominal voltage
Rated voltage (Ur)
Rated Frequency (Fr)
Rated short time thermal
current (Ith)
Rated duration of short circuit
Dynamic withstand current
(Idyn)
Ratio, class, rated output :
- ratio
a) for protectio
- class
- burden
b) for metering :
- class
- Instrument security factor
Insulation temperature class
(resin)
20 KV Voltage Transformer
Standard
Type of design
Rated voltage (Ur)
Minimum Rated voltage
factor
Rated Frequency
Ratio, class, rated output :
a) for metering
- ratio
- class
- burden
b) for protection
- ratio
- class
Rated lightning impulse
withstand voltage (Up)
Power frequency withstand
voltage (Ud)
Protection Relay

ms

110

Vdc
Vdc
Vdc

110
110
110

kV
kV
Hz

IEC 60044-1
Post Type, single phase, indoor
20
24
50

kA

12,5

kA

2,5 x Ith

150-400/1-1-1

VA

5P20
20

0,2
FS 10
minimum class E

kV

IEC 60044-2
Indoor
24
1,2 Cont and 1,9 - 30 s

Hz

50

V
VA

20.000:3 / 110:3
0.2
30

V
-

20.000:3 / 110:3
3P

kV

125

kV

50

1
2
3
5.2.6

Three-phase over current and


Earth Fault
Directional relay
Under voltage relay

Three-phase over current and


Earth Fault (51S, 51G)
Directional relay (67)
Under voltage relay (27)

Test Plug for Protection


Relay and Metering

Type
5.2.7. Energy Meter
1

Type

2
3

Class of meter
Rated input :
- current from 20 kV
measurement
- voltage from 20 kV VT
Quantity to be measured &
recorded :

Banana plug
Digital kWh & kVARh meter,
3P 4W
0.2s
A

1 or 5

110:3

- sending Wh & Watt


- receiving Wh & Watt
- sending VARh & VAR
- receiving VARh & VAR
- sending VAh & VA
- receiving VAh & VA
6

7
8
9

10
5.2.8
1
2
3

Quantity to be measured :

Energy recording interval


(programmable)
Tariff calculation mode
functions
Rated operating conditions :
- rated auxiliary supply
voltage
- temperature range
- humidity range
Port communication comply
to IEC 61850
Watt Meter (include Var,
Ampere and Volt meter)
Type
Class of accuracy
Rated input :
- current from 20 kV
measurement

minutes

- voltage (kV)
- phase current (A)
- power factor
- frequency (Hz)
1, 5, 10, 15, 20, 30
and 60
Minimum 3

Vdc

110 10%

C
%RH

0 - 50
20 - 90
Modem completed with optical
wire port or RS485 or RJ45

Digital, 3P 4W
0.2
A

1 or 5

4
5

6
7
8
5.3.
1
2
3
4
5

- voltage from 20 kV VT
Sampling rate
Rated operating conditions :
- rated supply voltage
- temperature range
- humidity range
Display
Mounting position
Design of case

V
cyc/sec

110/3
3 or more

Vdc
C
%RH

110 10%
0 50
20 90
LCD
Flush
Square

kV
kV
kA

20
16,8 - 24
10
Tidak lebih dari 2,7

kV

125

V
V
A
kA

600
400
160
10

kV

2,5

Lightning Arrester (LA)


Tegangan
Rated Voltage
Arus pengisian Normal
Tingkat Tegangan Residu
(RVL)
Tingkat Tegangan Isolasi

5.4. Switchgear 0,4 kV


5.4.1. Busbar 0,4 kV
1
2
3
4
5

Tegangan Isolasi
Tegangan Operasi
Arus Nominal
Ketahanan Arus Sesaat
untuk 1 detik
Penguji Tegangan Dielektrik

5.4.2. Pemutus Beban


1
2
3

Type
Tegangan Isolasi
Tegangan Operasi

V
V

ACB 4P
600
400

Arus Nominal

160

Arus Pemutus Hubung


Singkat

kA

10

6.

Protection, Kontrol dan Sistem Metering

6.1

Generator Protection

6.2

Transformer Protection

6.3

Outgoing Line Protection

6.4

Synchronization

6.5

Automatic Voltage Regulation


(AVR)

6.6

400 V Protection and


Metering

7
7.1

AC/DC System
Storage Batery
Type
Jumlah Sel
Tegangan Nominal
Tegangan Maksimum

7.2

Battery Charger

Stator earth fault protection (64 S)


Under/Over voltage protection (27/59)
Voltage controled over current prot (51 V)
Negative phase sequence protection (46)
Loss of excitation protection (40)
Reverse power protection (32P)
Over/Under Frequency (81O/U)
Generator diferential protection (87G)
Stator Thermal Protection (49)
Generator Ground Fault protection (59N)
Over Excitation Protection (240
Unbalance Voltage Protection (47)
Digital Metering Sistem (DMS)
(A,kV,Hz,kW,kVars,kWh dan kVArh)
Bucholz Trip Realay (63)
Transformer Diferential Relay (87GT)
Inst/IDMT Over current protection (51)
Inst/IDMT Neutral Over current protection
(51N)
Digital Metering Sistem (DMS)
(A,kV,Hz,kW,kVars,kWh dan kVArh)
Oil Temperatur Indicator (OTI)
Winding Temperatur Indicator (WTI)
Inst/IDMT Over current protection (51)
Inst/IDMT Neutral Over current protection
(51N)
Under/Over Voltage Protection (27/59)
Digital Metering Sistem (DMS)
(A,kV,Hz,kW,kVars,kWh dan kVArh)
Check Synchronization Relay (25)
Double Frequecy Meter (DFM)
Double Voltage Meter (DVM)
DC Field Curret (AF)
DC Field Voltage (VF)
Line Voltage (VG)
Stator Current (IG)
Voltage Balance Relay (60)
Over Current Protection (51)
Earth Fault Protection (51N)
Voltmeter (V)
Digital Metering Sistem (DMS) (A,kV,kW)

Nickel Cadmium Alkaline


86 sel
110 V, 150 A, 5 jam Discharge
121 V

7.3

7.4

Type
AC Input Voltage
Maksimum Teg Ouput DC
Rated DC Output Current
DC Panel
One Set Bus
Incoming MCB
OutGoing MCB
Metering
Uninteruptable Power Supply
(UPS)
Type
Cooling System

Thyristor, suitable for 3 phase 340 V AC


3 phase 380/400 V AC
121V DC
50 A
110 V DC, Max 121 V DC
110 V DC, 63 Amp
110 V DC
Volt, Amp

Single phase, 220 V, 50 Hz, 0,8 Laging to


1,0 PF
Natural Air Ventilated