3.1.
peralatan switchgear di lokasi Pembangkit seperti yang ditunjukan pada Single Line
Diagram (SLD) PLTM Cikebo terlampir adalah sebagai berikut :
1.
Turbin.
1
2.
Meter
56,5
Generator.
1
2
3
4
5
6
7
3.
Standar
Rated output
Power
Rated Current
Power factor
Tegangan
Frekwensi
IS 4722 / IEC60034
2 x 2822
2 x 3320
304,25
0,85
6,3
50
kW
kVA
Amp
kV
Hz
Main Trasformer
1
2
3
4
5
6
7
8
9
10
Type
Kapasitas
Frekwensi
Tegangan Primer
Tegangan Sekunder
Type of Tap Changer
Taping Range
Impedansi
Neutral Grounding Resistor
Accessories
MVA
Hz
kV
kV
%
Ohm
-
the conservator
- Tap position indicator (Local )
- Bi-directional wheels with
suitable locking arrangement.
- HV neutral CTs for REF
protection.
- Rating & Diagram Plate
Anodised Aluminium
- Earthing Terminals
- Lifting Lugs
- Radiators
- Silicagel Breather
- Pressure relief valve.
- Bottom drain Filter Valve
- Top Filter Valve
4.
Auxiliary Trasformer
1
2
3
4
5
6
7
8
9
Type
Kapasitas
Frekwensi
Tegangan Primer
Tegangan Sekunder
Type of Tap Changer
Taping Range
Impedansi
Accessories
kVA
Hz
kV
kV
%
-
5.
Peralatan Switchgear
Type
Tegangan
Rated Voltage
Rated Frquency
Tingkat Tegangan Isolasi
Arus Nominal
Arus Pemutus Hubung
Singkat untuk 1 detik
Tegangan Kontrol
kV
kV
Hz
kV
Amp
3 phase
6,3
7,2
50
125
630
kA
25
V DC
110 Volt
1
2
3
Type
Rasio Arus (Primer/sekunder)
Class
Amp
Type
Tegangan Primer
Tegangan Sekuder
kV
V
5.2. Swichgear 20 kV
5..2.1 Busbar 20 kV
1
Standard
2
Type of designation (tempat
pemasangan dan konfigurasi
busbar)
3
Rated voltage (Ur)
4
Rated lightning impuls
withstand voltage (Up)
5
Rated power frequency
withstand voltage (Ud)
6
Rated frequency
7
Rated normal current
8
Rated short-time withstand
current ( I k )
9
Rated duration of short circuit
10
Rated peak withstand current
(Ip)
11
Degrees of protection (IP)
12
Insulation medium
13
Material Busbar system
14
Number of phase busbar
5.2.2 Circuit Breaker 20 KV Indoor
1
Standard
2
Type of designation
3
Operation duty minimum
4
Rated voltage
5
Rated nominal current
6
Rated lightning impuls
withstand voltage
7
Breaking capacity
10
Making capacity
11
Rated frequency
12
Interrupting medium
13
Mechanism type
14
Mechanical endurance
15
Opening time
IEC 62271-200
Indoor metal clad and single
busbar
kV
24
kV
125
kV
50
Hz
A
50
1250
kA
25
sec.
kA
2,5 x I k
Minimum IP 4X
Air
Copper with heatshrink
3
kV
A
IEC 602271-100
Withdrawable or truck-mounted
O - 0.3s - CO - 180s CO
24
630
kV
125
kA
kA
Hz
25
2,5 x I k
50
SF6 or Vacuum
motor spring
M2 (10.000 times)
60
ms
16
17
5.2.3
1
2
3
4
5
6
7
8
9
10
5.2.4
1
2
3
4
7
8
9
10
5.2.5
Closing time
Supply voltage :
- Control voltage
- Tripping and closing Coils
- Motor voltage
Current Transformer 20 kV
Standard
Type of design
Nominal voltage
Rated voltage (Ur)
Rated Frequency (Fr)
Rated short time thermal
current (Ith)
Rated duration of short circuit
Dynamic withstand current
(Idyn)
Ratio, class, rated output :
- ratio
a) for protectio
- class
- burden
b) for metering :
- class
- Instrument security factor
Insulation temperature class
(resin)
20 KV Voltage Transformer
Standard
Type of design
Rated voltage (Ur)
Minimum Rated voltage
factor
Rated Frequency
Ratio, class, rated output :
a) for metering
- ratio
- class
- burden
b) for protection
- ratio
- class
Rated lightning impulse
withstand voltage (Up)
Power frequency withstand
voltage (Ud)
Protection Relay
ms
110
Vdc
Vdc
Vdc
110
110
110
kV
kV
Hz
IEC 60044-1
Post Type, single phase, indoor
20
24
50
kA
12,5
kA
2,5 x Ith
150-400/1-1-1
VA
5P20
20
0,2
FS 10
minimum class E
kV
IEC 60044-2
Indoor
24
1,2 Cont and 1,9 - 30 s
Hz
50
V
VA
20.000:3 / 110:3
0.2
30
V
-
20.000:3 / 110:3
3P
kV
125
kV
50
1
2
3
5.2.6
Type
5.2.7. Energy Meter
1
Type
2
3
Class of meter
Rated input :
- current from 20 kV
measurement
- voltage from 20 kV VT
Quantity to be measured &
recorded :
Banana plug
Digital kWh & kVARh meter,
3P 4W
0.2s
A
1 or 5
110:3
7
8
9
10
5.2.8
1
2
3
Quantity to be measured :
minutes
- voltage (kV)
- phase current (A)
- power factor
- frequency (Hz)
1, 5, 10, 15, 20, 30
and 60
Minimum 3
Vdc
110 10%
C
%RH
0 - 50
20 - 90
Modem completed with optical
wire port or RS485 or RJ45
Digital, 3P 4W
0.2
A
1 or 5
4
5
6
7
8
5.3.
1
2
3
4
5
- voltage from 20 kV VT
Sampling rate
Rated operating conditions :
- rated supply voltage
- temperature range
- humidity range
Display
Mounting position
Design of case
V
cyc/sec
110/3
3 or more
Vdc
C
%RH
110 10%
0 50
20 90
LCD
Flush
Square
kV
kV
kA
20
16,8 - 24
10
Tidak lebih dari 2,7
kV
125
V
V
A
kA
600
400
160
10
kV
2,5
Tegangan Isolasi
Tegangan Operasi
Arus Nominal
Ketahanan Arus Sesaat
untuk 1 detik
Penguji Tegangan Dielektrik
Type
Tegangan Isolasi
Tegangan Operasi
V
V
ACB 4P
600
400
Arus Nominal
160
kA
10
6.
6.1
Generator Protection
6.2
Transformer Protection
6.3
6.4
Synchronization
6.5
6.6
7
7.1
AC/DC System
Storage Batery
Type
Jumlah Sel
Tegangan Nominal
Tegangan Maksimum
7.2
Battery Charger
7.3
7.4
Type
AC Input Voltage
Maksimum Teg Ouput DC
Rated DC Output Current
DC Panel
One Set Bus
Incoming MCB
OutGoing MCB
Metering
Uninteruptable Power Supply
(UPS)
Type
Cooling System