Professional Documents
Culture Documents
Applied Energy
journal homepage: www.elsevier.com/locate/apenergy
a r t i c l e
i n f o
Article history:
Received 14 August 2008
Received in revised form 3 December 2008
Accepted 9 December 2008
Available online 14 January 2009
Keywords:
Energy analysis
Exergy analysis
Space heating
Efciency
a b s t r a c t
In the present study, energy and exergy analyses are presented for the whole process of space heating in
buildings. This study is based on a pre-design analysis tool, which has been produced during ongoing
work for the International Energy Agency (IEA) formed within the Energy Conservation in Buildings
and Community Systems Programme (ECBCSP) Annex 37. Throughout this paper, in all of the calculations
such as heat losses and gains were taken according to Turkish Standards Institution TSE, which is in
accordance with the European Standard TS EN ISO 13789. In the analysis, heating load is taken account
but cooling load is neglected and the calculations presented here are done using steady state conditions.
The analysis is applied to an ofce in Izmir with a volume of 720 m3 and a net oor area of 240 m2 as an
example of application. Indoor and exterior air temperatures are 20 C and 0 C, respectively. It is
assumed that the ofce is heated by a liquid natural gas (LNG) red conventional boiler, an LNG condensing boiler and an external airair heat pump. With this study, energy and exergy ows are investigated.
Energy and exergy losses in the whole system are quantied and illustrated. The highest efciency values
in terms of energy and exergy were found to be 80.9% for external airair heat pump and 8.69% for LNG
condensing boiler, respectively.
2008 Elsevier Ltd. All rights reserved.
1. Introduction
In general, energy consumption can be examined under four
main sectors such as industrial, building (residential), transportation and agriculture. In many countries, the energy required for
space heating in buildings has the highest share of all which his
about 40% of total energy consumed in the residential sector [1].
Thus, energy consumption in buildings is quite high and must be
carefully considered.
Calculations for all kinds of energy utilization, including heating/cooling loads of rooms in buildings and temperature distributions, are based on energy balances. This is done in reference to
the rst law of thermodynamics, which states that energy is conserved in every device and process and energy can neither be destroyed nor consumed [2]. There are many studies in the
literature dealing with energy analysis in buildings. Gratia and
Herde [3] studied design of low-energy ofce buildings. Pfafferott
and Herkel [4] evaluated statistical simulation of user behaviour
in low-energy ofce buildings. Yang et al. [5] investigated energy
performance of building envelopes in different climate zones in
China. Sjgren et al. [6] studied on monthly consumption data registered by the property holders for over 100 multifamily buildings
in Sweden. They used an approach, based on the energy signature
method, which was developed for evaluating the energy perfor* Corresponding author. Tel./fax: +90 232 3888562.
E-mail address: abdullah.yildiz@ege.edu.tr (A. Yildiz).
0306-2619/$ - see front matter 2008 Elsevier Ltd. All rights reserved.
doi:10.1016/j.apenergy.2008.12.010
1940
Nomenclature
A
b
Cp
COP
E_
_
Ex
f
F
g
I
l
N
nd
area (m2)
temperature factor ()
specic heat (kJ/kg K)
coefcient of performance ()
energy rate (W)
exergy rate (W)
approximation factor ()
factor ()
total transmittance ()
radiation intensity (W/m2)
length (m)
percentage of equipment resistance
air exchange rate (ach/h)
Subscripts
aux
auxiliary energy requirement
circ
circulation
const
constant
dis,D
distribution system
dt
design temperature
e
external surrounding, equipment
E,emis
emission system
env
environment
ew
external wall
ex
extra
f
window frame, parameter
G,Ge
generation
gp
generator position
h
heat
heat
heater
i
inside surrounding, surface, counting variable
in
input, inlet
ins
insulation
j
counting variable
l
lighting
no
number ()
P
power (W)
p
specic power, pressure (W/m2, N/m2)
_
m
mass ow (kg/s)
R
T
U
V
Greek symbols
Q_
heat transfer rate (kW)
g
energy or rst law efciency ()
q
density (kg/m3)
w
exergy or second law efciency ()
D
difference
loss
thermal losses
max
maximum
N
netto
no
effect of non-orthogonal radiation
o
occupants
p
primary energy
prim
primary energy
q
quality
ref
reference
renew
from renewable source
ret
return
S
solar, supply and storage
s
source, surface
sh
shading effects
T
transmission
td
temperature drop
tot
total
V
ventilation
w
window
o
reference
Abbreviations
ECBCS
Energy Conservation in Buildings and Community Systems Programme
IEA
International Energy Agency
LNG
liquid natural gas
TSE
Turkish Standard Institution
performance of residential heating systems with separate mechanical ventilation. Chengqin et al. [24] studied principles of exergy
analysis in HVAC and evaluation of evaporative cooling schemes.
In these studies, external wall of buildings were taken as
boundary conditions and energy and exergy analyses were calculated for buildings. But, in the actual analysis, energy and exergy
analyses must be calculated in all of the systems from the primary
energy transformation till the building envelope including the
envelope. Firstly, Schmidt [25] presented a detailed report for the
design of low exergy buildings and gave an example of energy
and exergy analyses of an ofce heated by liqueed natural gas
red high temperature boiler from power plant till building envelope. Balta et al. [26] studied a heating system from the power
plant through to the building envelope and used a ground source
heat pump with a COP of 2.32 as the heating system.
In the literature, only one system such as LNG red high temperature boiler or ground source is analyzed. In this study, exergy
and energy analyses for three different heating systems that are in
_
wide use in Izmir
namely (i) liquid natural gas (LNG) red conventional boiler, (ii) LNG condensing boiler and (iii) an external airair
heat pump are conducted from the power plant through to the
building envelope. The methodology which used in this study
based on a pre-design analysis tool, which has been produced during ongoing work for the International Energy Agency (IEA) formed
within the Energy Conservation in Buildings and Community Systems Programme (ECBCSP) Annex 37. Throughout this paper, design temperatures such as indoor and outdoor temperatures
which are used in calculation of heat losses and gains were taken
according to Turkish Standards Institution TSE, which is in accordance with the European Standard TS EN ISO 13789. Analysis is applied to an ofce which has a dimension of 15 m 16 m 3 m.
Heating load is taken into account but cooling load is neglected.
In these analyses, the systems energy and exergy losses and efciencies were calculated and compared. Further, the best system
is proposed.
Q_ T
1941
X
U i Ai 1 b T i T e
1942
Fig. 2. Energy demand in buildings for different applications from source to sink [25].
Q_ V C P q V nd 1 gV T i T e
Q_ S
X
Is;j 1 F f Aw;j g j F sh F no
where Q_ s (W) is the solar gain, Is,j (W/m ) is the solar radiation and
is given for different orientations. As it can be seen from Fig. 1, the
2
ofce has a single window facing the south. For Izmir, the average
value of Is,j in the south orientation can be taken as 44 W/m2 [29].
Ff is the window frame fraction, Aw,j (m2) is the total window area.
gj is the total energy transmittance of the glazing and can be estimated to be 0.75 for double glazing. Fsh is the possible shading effects of other surrounding buildings and the Fno correction for
non-orthogonal radiation on the windowpanes and both of them
can be estimated to be 0.9 for most cases [15,27].
The internal gain is specied by two groups. One group is the
heat gain of occupants, i.e. people staying inside the room, and
the other is the heat gain from equipment, like computers, printers,
or other appliances, like television sets. In this study, it is assumed
that there are 15 people, 15 computers, one refrigerator, one photocopy machine, one television and bulbs with a total power of
200 W in the ofce. Q_ 00i;o is set to 80 W per occupant and with the
number of present occupants, noo; the gain from occupants can
be estimated from Eq. (4). Q_ 00i;e is the gain caused by each equipment. Then, the internal gain caused by equipments can be estimated by Eq. (5). Heat gains per equipment are given Table 1
1943
02
Table 1
Heat gains per equipment [30].
T heat
Equipment
Computer
Refrigerator
Photocopy machine
Television
75
150
200
75
m
X
where Tin and Tret are inlet and return temperatures of the emission
systems and their values are given in Table 2.
Using this temperature, a new quality factor at the heater surface is dened
i1
T ret T i
F q;heat 1
Q_ 00i;e ni eo
T0
T heat
10
All heat ows, heat losses via the envelope, and internal gains,
occurring inside the ofce have to be summed up to create the following energy balance which refers to the rst law of
thermodynamics:
(Heat demand) = (sum of heat losses) (sum of heat gains)
Q_ h Q_ T Q_ v Q_ S Q_ i;o Q_ i;e
F q;room 1
3
1
T
T
1
ret
in
5 TiA
@4
2
ln T in T i
T0
Ti
where T0 and Ti are the reference temperature and room temperature and they are taken as 0 C and 20 C, respectively.
Then, the exergy load, i.e. the exergy demand of the room to be
satised by the following system:
_ room F q;room Q_ h
Ex
_ heat F q;heat Q_ h
Ex
11
Q_ loss;E Q_ h
gE
1
12
Paux;E paux;E Q_ h
13
where paux,E is the specic power for heat energy emission systems
and is given in Table 2.
The exergy demand of the heat energy emission system is derived as given in Eq. (14)
_ emis
DEx
Q_ h Q_ loss;E
T in
T in T ret T o ln
T in T ret
T ret
14
_ emis Ex
_ emis
_ heat DEx
Ex
15
Table 2
Characteristic data of heat emission systems [31].
Heat emission system
90
70
35
70
55
25
0.95
0.95
0.95
0
0
0.81
1944
Table 3
Values of parameters of fi [31].
Criteria
Possible choices
Parameter fi
1.00
0.90
Insulation (fins)
No insulation
Bad insulation
Good insulation
0.70
0.90
1.00
Low
Mid
High
1.00
0.95
0.90
<35 C
<50 C
others
Low
Mid
High
0.98
0.99
1.00
<5 K
<10 K
others
16
_ gcirc
paux;D Dp m=
17
where gcirc can be taken as 0.27 [25]. Pressure drop in the distribution system is calculated from
Dp 1 N R lmax AN pex
18
_
m
3
m
s
1
0:0036
1:163 DT dis
19
Q_ loss;D Q_ h Q_ loss;E
gD
1
20
Paux;D
paux;D Q_ h Q_ loss;E
21
Comments
mean design temperature Tdis and the return temperature is the design temperature minus the temperature drop DTdis
_ dis
DEx
T dis
Q_ loss;D
T dis T o ln
DT dis
T dis DT dis
22
_ dis Ex
_ dis
_ emis DEx
Ex
23
1
Q_ Ge Q_ h Q_ loss;E Q_ loss;D Q_ loss;S 1 F S
24
gG
25
_ Ge Q_ Ge F q;S
Ex
26
Table 4
Values of characteristics for heating systems [31].
Heating system
Thermal
efciency/COP
Quality factor of
source, Fq,s ()
Primary energy
factor, FP ()
LNG condensing
boiler
LNG conventional
boiler
External airair
heat pump
0.95
90
1.8
20
0.95
1.3
0.80
70
1.8
20
0.95
1.3
3.20
80
10
1.0
3.0
1945
30
0.63
0.09
0.41
0.32
0.00
0.00
0.5
0.41
0.00
6.07
6.07
6.07
1.45
0.52
0.41
0.32
0.00
0.00
0.93
0.41
0.00
6.07
6.07
6.07
1.19
0.38
0.41
0.79
0.41
0.00
6.07
6.07
6.07
0.32
0.00
0.00
0.00
0.22
0.00
1.12
1.35
1.13
7.51
6.39
0.00
0.14
0.00
0.38
2.52
2.38
6.77
6.39
0.00
0.14
2.12
1.98
6.76
6.39
0.00
0.37
0.96
5.01
1.35
7.51
5.38
1.69
2.52
6.77
4.53
2.12
6.76
0.39
0.00
5.00
7.5
2.31
7.5
2.5
0.00
2.81
0.00
2.79
10.71
7.90
11.25
8.46
0.00
2.44
0.00
2.39
Total energy
rate (kW)
Relative energy
loss (kW)
Relative exergy
loss (kW)
Total energy
rate (kW)
Component
Table 5
Total energy/exergy ow and energy/exergy losses rate of the system components.
29
9.09
6.65
Relative energy
loss (kW)
In this study, when external airair heat pump is used for heat
generation Frenew is taken as 2.20. If a boiler is used as heating system, Frenew is equal to zero.
Quality factor of energy source Fq,s needed for exergy analysis
are specied for energy source in the primary energy conversion
and its value is given in Table 4. Finally, total exergy load for building is calculated from
Total exergy
rate (kW)
Relative exergy
loss (kW)
28
Total exergy
rate (kW)
where Fp is the primary energy factor and is given in Table 4. Auxiliary energy used in the generation as electricity needed for driving
pump is effective in the part of heat generation. This effect is given
by auxiliary energy factor Paux,G. The typical maximum supply temperature of the boiler Ts,max is needed to check the consistency of the
overall system design. Pl and PV are specic power of specic lighting and specic ventilation, respectively, in Eq. (27) and they are taken as zero in this study. Values of characteristics for systems of
heat production are given in Table 4. Fp,electricity is primary energy
factor for electricity and it can taken as three [25].
If the generation utilizes a renewable energy source or extracts
heat from the environment, as heat pumps do, the additional
renewable energy load is
Total energy
rate (kW)
27
Total exergy
rate (kW)
F p;electricity
Relative energy
loss (kW)
9.54
7.15
The overall energy and exergy loads of the building are expressed in the required primary energy and exergy inputs. For
the fossil or non-renewable part of the primary energy, the result is
Input
After power
plant
After heating
system
After storage
After
distribution
After emission
After room
After envelope
Relative exergy
loss (kW)
0.00
5.19
1946
31
volume and the net oor are of the ofce are 720 m3 and 240 m2,
respectively. Indoor and exterior air temperatures are 20 C and
0 C, respectively, which are reference temperatures of TSE for
Izmir.
The transmission and ventilation are calculated to be 3.33 kW
and 7.23 kW, respectively, using Eqs. (1) and (2). Solar and internal
heat gains are found to be 0.275 kW and 4.22 kW, respectively,
using Eqs. (35). According to these data, heat demand of the ofce
is calculated to be 6.07 kW from Eq. (6).
The graphical presentations of the calculated results are shown
in Figs. 46, which indicate where losses occur. In Fig. 4, the useable ow of energy and exergy through the space heating process
from source to sink is presented. The largest input energy of system occurs when the LNG conventional boiler is used and its value
is 11.25 kW. The lowest input energy of system occurs when the
external airair heat pump is used and its value is 7.5 kW. As a
1947
buildings. The advantages of the analyses and the difference between energy and exergy analyses are demonstrated.
We can extract some concluding remarks from this study as
follows:
(a) While a part of energy leaves from building envelope, some
of it still remains. However, all of the exergy is consumed in
the building envelope.
(b) When the external airair heat pump is used as the heating
system, input energy to the generation system is 2.50 kW
but output energy is 7.51 kW. Therefore, the added renewable environmental heat is 5.01 kW.
(c) The largest exergy loss occurred during the combustion process when the boilers are used as the heating systems, but
when the external airair heat pump is used as the heating
system, the largest exergy loss occurred in the primary
energy transformation.
(d) Total energy efciencies of systems using LNG condensing
boiler, LNG conventional boiler and external airair heat
pump (energy demand room/total energy input) are calculated to be 63.6%, 53.9% and 80.9%, respectively.
(e) Total exergy efciencies of systems using LNG condensing
boiler, LNG conventional boiler and external airair heat
pump (exergy demand room/total exergy input) are calculated to be 8.69%, 8.68% and 6.66%, respectively.
(f) The best system in respect of environmental aspects is the
system with the heat pump. There is no combustion in this
system and the lowest input energy to power plant is in this
system.
(g) For the optimum system choice not only the environmental
aspects but also economical aspects must be taken into
account.
(h) The exergy load and auxiliary energy demand of each system
is affected by its subsystem characteristics such as heat
emission, distribution and heat generation subsystem characteristics. These values are given in Tables 24.
(i) For the future studies, an ergonomic analysis, which is a
combination of energy and economic analyses, and exergonomic analysis, which is a combination of exergy and economic analyses are recommended.
1948
References
[1] Bolattrk A. Determination of optimum insulation thickness for building walls
with respect to various fuels and climate zones in Turkey. Appl Therm Eng
2006;26(11,12):13019.
[2] Moran MJ, Shapiro HN. Fundamentals of engineering thermodynamics. 3rd
ed. New York: John Wiley and Sons; 1998.
[3] Gratia E, Herde AD. Design of low energy ofce buildings. Energy Build
2003;35:47391.
[4] Pfafferott J, Herkel S. Statistical simulation of user behaviour in low-energy
ofce buildings. Sol Energy 2007;81:67682.
[5] Yang L, Lam JC, Tsang CL. Energy performance of building envelopes in
different climate zones in China. Appl Energy 2008;85(9):80017.
[6] Sjgren JU, Andersson S, Olofsson T. An approach to evaluate the energy
performance of buildings based on incomplete monthly data. Energy Build
2007;39:94553.
[7] Chowdhury AA, Rasul MG, Khan MMK. Thermal-comfort analysis and
simulation for various low-energy cooling-technologies applied to an ofce
building in a subtropical climate. Appl Energy 2008;85:44962.
[8] Lam JC, Wan KKW, Tsang CL, Yang L. Building energy efciency in different
climates. Energy Convers Manage 2008;49(8):235466.
[9] Durmayaz A, Kadoglu M. Heating energy requirements and fuel consumptions
in the biggest city centers of Turkey. Energy Convers Manage
2003;44:117792.
[10] Chandel SS, Aggarwal RK. Performance evaluation of a passive solar building in
Western Himalayas. Renew Energy 2008;33(10):216673.
[11] Filipin C, Beascochea A. Performance assessment of low-energy buildings in
central Argentina. Energy Build 2007;39:54657.
[12] Persson M, Roos A, Wall M. Inuence of window size on the energy balance of
low energy houses. Energy Build 2006;38:1818.
[13] Eskin N, Trkmen H. Analysis of annual heating and cooling energy
requirements for ofce buildings in different climates in Turkey. Energy
Build 2008;40:76373.
[14] Rey FJ, Velasco E, Varela F. Building energy analysis (BEA): a methodology to
assess building energy labelling. Energy Build 2007;39:70916.
[15] Wittchen KB, Aggerholm S. Calculation of building heating demand in EPIQR.
Energy Build 2000;31:13741.
[16] Prager C, Khl M, Heck M, Herkel S. The inuence of the IR reection of painted
facades on the energy balance of a building. Energy Build 2006;38:136979.
[17] Feng Y. Thermal design standards for energy efciency of residential buildings
in hot summer/cold winter zones. Energy Build 2004;36:130912.
[18] Meester BD, Dewulf J, Verbeke S, Janssens A, Langenhove HV. Exergetic lifecycle assessment (ELCA) for resource consumption evaluation in the built
environment. Build Environ 2009;44(1):117.
[19] Gong G, Zeng W, Chang S, He J, Li K. Scheme-selection optimization of cooling
and heating sources based on exergy analysis. Appl Therm Eng
2007;27:94250.
[20] Shukuya M, Komuro D. Exergyentropy process of passive solar heating and
global environmental systems. Sol Energy 1996;58(13):2532.
[21] Saito M, Shukuya M. The human body consumes exergy for thermal comfort.
LowEx News 2001;2:67.
[22] Franconi EM, Brandemuehl MJ. Second law study of HVAC distribution system
performance. ASHRAE Trans 1999;10(1):123746.
[23] Zmeureanu R, Wu XY. Energy and exergy performance of residential heating
systems with separate mechanical ventilation. Energy 2007;32:18795.
[24] Chengqin R, Nianping L, Guangfa T. Principles of exergy analysis in HVAC and
evaluation of evaporative cooling schemes. Build Environ 2002;37:104555.
[25] Schmidt D. Design of low exergy buildings-method and a pre-design tool. Int J
Low Energy Sustain Build 2003;3:147.
[26] Balta MT, Yildiz Kalinci Y, Hepbasli A. Evaluating a low exergy heating system
from the power plant through the heat pump to the building envelope.
Energy Build 2008;40(10):17991804.
[27] TS EN ISO 13789. Thermal performance of buildings transmission heat loss
coefcient calculation method. Turkish Standard Institution; 2000 [in
Turkish].
[28] TS 825. Thermal insulation in building. Turkish Standard Institution; 1998 [in
Turkish].
[29] Tamer S. Air conditioning and ventilation. Meteksan (AS
); 1990 [in Turkish].
[30] Kreider JF, Curtiss PS, Rabl A. Heating and cooling of buildings design for
efciency. Mc-Graw Hill; 2002.
[31] Zirngibl J, Francois C. Exergy analysis tool, various contributions. Internal
working documents IEA Annex 37. Paris, France: CSTB; 2002.
[32] Dincer
I,
Rosen
MA.
Energy
environment
and
sustainable
development. Elsevier Ltd.; 1988.