Annexure-II

Technical Data Sheet to be compulsorily filled by Vendor


- 200KW Solar Panel, Roof top Grid Tie
Sr.
Speicification
No
A. Site Condition
1 Maximum ambient temperature
2 Minimum ambient temperature
3 Design ambient temperature
4 Relative humidity max/min
5 Altitude above MSL
6 Environment
7 Location

2
3
4

1
2
3
4
5
6
7
8
9

1
2

IOCL Requirement

40 Deg C
9 Deg C
40.0 Deg C
96 % / 50%
54 m
Humid & corrosive
03 Bldg. (Inside refinery Terrace of EWS , CSB &
Outside refinery-Admn building
of Block A & B
* Vendor to make site survey
before submitting the tender to
analyze the scope.

B. SPV power plant


Rated Output

To be mentioned by Vendor (To


meet total 200KW = (100 +100)
KW
To be mentioned by Vendor
No. of PV Modules
No. of series module in one array To be mentioned by Vendor

No. of arrays in parallel To be mentioned by Vendor


combination
C. SPV Module
To be mentioned by Vendor
PV cell type
To be mentioned by Vendor
Make of SPV cell
To be mentioned by Vendor
Make of SPV Module
Maximum Power Rating of one To be mentioned by Vendor
module
To be mentioned by Vendor
Rated Current of module
To be mentioned by Vendor
Rated Voltage of module
Short Circuit Current of module To be mentioned by Vendor
Open Circuit Voltage of module To be mentioned by Vendor
Sample I-V curve Submitted (Yes To be mentioned by Vendor
/ No)
D. Mounting Arrangement
Roof-mounted
Mounting type
Surface azimuth angle of PV To be mentioned by Vendor
Module

Page 1 of 4

Vendor Reply/ Confirm

Tilt angle(slope) of PV Module

To be mentioned by Vendor

E. DC Combiner Box / Array Junction Box


1
2
3

To be mentioned by Vendor
Enclosure
Necessary Fuse Protection & Yes
Surge Protection.
IEC 60 695-2-11- UL Subject 94
Fire Protection
(Glow wire test )

4
5

Degree of protection
mechanical load
Rated Insulated Voltage

6
7

Dielectric strength
Type Test

against IK 08 (5 Joule)
DC 1000V
4.65 KV DC
In accordance to IEC 60364-712

F. Power Conditioning Unit (PCU) / Inverter


1

Nomianl output power at site Total 200 KW = 2*100KW


(Note: To be Installed on the
based on the site conditions
terrace of 3 no. Bldg to meet total
200KW output power overall)

3
4

To be mentioned by Vendor
Nominal Output array voltage
*shall be suitable for the MPPT
range of PCU
DC Array Input Operating (-20% to +15%) of the DC Array
input voltage
Voltage
MPPT Based Solar Charge
Type of solar charge controller
Controller

MOSFET/IGBT based
Switching device
Continuous
inverter
Output
Rating (KVA)
Pure Sine Wave Output
7 Output Wave Form
< 3% @ nominal power
8 Total Harmonic distortion
3 ph, 415 10 %
9 Output Voltage
50Hz 3%
10 Output Frequency
> 0.9
11 Power Factor
> 90% at nominal voltage &
12 PCU Efficiency

5
6

13 Inverter efficiency
14 No.
of
Inverters
Configuration

15 Inverter Type

power
94% to 98% at full load
with To be provided by Vendor
(8*25KW, to meet nominal
output power 4*50KW, at 3 nos.
bldgs with each having N+1
configuration or better)
To be mentioned by Vendor

Page 2 of 4

Each 50KW solar system


will consist of 3 no. inverter
modules of min. 25 KW
each. (* all the inverters
provided shall be of similar
rating)

16 Spare Inverter Module

2 no.

17 Idle Current

< 4% of rated capacity

18 Regulation

2% for DC I/p variation & o/p


load variation
150% for 1 minute

19 Overload Features

21 Operating Temperature

Forced Air cooling, with


temperature controlled
cooling fan
0 to 50 C

22 Relative Humidity

95% Maximum

20 Cooling

Display shall indicate system


functional parameters and
protection functional indicator
24 Data monitor and display controls RS485, Ethernet OR RS232
connectivity

23 LED/LCD Display :
Indications

25 Protections
26 a. Input over voltage
b. Low/high frequency
c. Short circuit
d. Under/over output voltage
e. Over Temperature
f. Grid Input under voltage / over
voltage with auto recovery
g. DC disconnect device
h. DC reverse polarity
i. Anti Islanding Protection as per
the standard
IP 21(for indoor) as per IEC 529
27 Enclosure Protection
1. IEC 62103
28 Safety
2. IEC 62109 Part 1 & 2
3. Galvanic Isolation at input &
output through
transformer
< 45dB at 1 Meter
29 Audible Noise
MPPT suitable for hybrid
30 Power Control
operation.
31 Communication peripherals for LAPTOP (preferably Apple
make)
DATA analysis

G. Catalogue

To be submitted along with the


bid

SPV Modules drawings, Solar


(To be submitted compulsorily along with the array layout,
Tender)
Site & plant layout,

H. Drawings

Page 3 of 4

Note: No cell to be kept blank.Vendor to give comments(compliance or non compliance) against each point

Page 4 of 4