Professional Documents
Culture Documents
LAB SHEET
POWER STATIONS
EET4116
TRIMESTER I (2012/2013)
*Note: On-the-spot evaluation may be carried out during or at the end of the
experiment. Students are advised to read through this lab sheet before doing
experiment. Your performance, teamwork effort, and learning attitude will count
towards the marks.
Experiment # 1
Overcurrent Protection of a Substation Power Transformer
Instructions:
1. Read this lab sheet carefully and understand the procedure of performing the
experiment before coming to the laboratory.
2. Do not switch on the power supply unless permitted by the teacher.
3. Do not make or break any connection with the power supply on.
4. Handle the equipment with care.
5. Complete the experiment and submit the report before leaving the laboratory.
Objective
To design an overcurrent protection including earth fault protection of a threephase substation power transformer with overcurrent relays and current
transformers.
To test the protection scheme designed using the Workstation and Protective
Relay Control Station available in the Lab.
Introduction
For economic considerations, small-three-phase power transformers (less than 100
kVA) are usually protected with fuses. The main disadvantage of using fuses to
protect power transformers is their long operating time under low overcurrent
conditions. This delays transformer disconnection, and in certain cases, provides little
protection to the transformer and rather protects the system disconnecting the faulty
transformer after the fault has reached an advanced stage.
The protection schemes for large power transformers usually include differential
protection and/or restricted earth fault protection. In this case, transformer
disconnection is achieved through circuit breakers, and overcurrent relays can be
added to the protection schemes to provide overcurrent protection. This additional
protection serves as a general backup protection in case of a failure of the main
protection system.
Figure 1 shows overcurrent and earth fault protection system of a three-phase power
transformer implemented with protective relays. In this system, the power transformer
primary currents are measured through three CTs (current transformers) and the
secondary currents of the CTs are connected to the overcurrent relays. The earth fault
relay is connected in the neutral circuit of the CT secondaries. This arrangement
allows the measurement of each of the line currents by the overcurrent relays and the
vector sum of the line current by the earth fault relay. Note that the earth fault relay
must be of low impedance type to allow measurement of the line currents by the
overcurrent relays.
Fig. 3 Connection diagram of the equipment in the Protective Relay Control Station
On the AC/DC Current Sensitive Relay
INPUT switch - - - - - - - - - - - - - - - - - - - - - - - - - AC
MODE switch - - - - - - - - - - - - - - - OVER CURRENT
On the Universal Fault Module
INITIATE FAULT button - - - - - - - - released position
FAULT DURATION switch- - - - - - - - - - - 0.3 30 s
On the Current Transformer Module
Current transformers CT1, CT2 and CT3 - - - O (open)
7. Set the current set point of the Three-Phase Overcurrent Relay to approximately
200% of the nominal full-load current of the power transformers, taking into
account the transformation ratio of the current transformers.
8. Set the time delay of the Three-Phase Overcurrent Relay to approximately 5 s.
Adjust the set point and hysteresis of the AC/DC Current Sensitive Relay to
100mA and 5%, respectively.
9. Turn on the DC Power Supply of the Protective Relay Control Station.
10. On Transmission Grid A, set switch S2 to O (open) position to open the
contactor CR2. This will prevent operation of the protection system and allow the
operation of the protective relays to be observed.
5
11. Turn on the Power Supply and set the voltage control knob to the 100% position.
Set the primary line current (indicated by ammeter I1) should be approximately
equal to the full-load current of the power transformers by adjusting the resistive
loads.
12. On the Universal Fault Module, depress the INITIATE FAULT button to shortcircuit one phase of the three-phase load. While doing this, observe the circuit
currents and voltages as well as tripping indicator (red LED) on the Three-Phase
Overcurrent Relay and AC/DC Current Sensitive Relay. Record the current and
voltages in the blank spaces.
(Note: You may have to initiate this fault a few times to record the circuit
currents and voltages)
I1 = . A
I2 = A
I3 = A
E1 = V
E2 = V
Is the earth fault protection stable when the current through one phase of the
three-phase power transformer is high?
Yes
No
On the Universal Fault Module, place the INITIATE FAULT button in the release
position.
13. On the Faultable Transformers, set the fault switch FS1 on the transformer T1 to
the position I to insert an earth fault near the middle of the primary winding of
transformer T1. While doing this, observe the circuit currents and voltages as
well as the tripping indicator on the Three-Phase Over Current Relay and AC/DC
Current Sensitive Relay.
Record the currents and voltages in the following blank spaces.
I1 = . A
I2 = A
E1 = V
E2 = V
I3 = A
On the Faultable Transformers, set the fault switch FS1 on the transformer T1 to
the position O to remove the earth fault
6
14. On the Transmission Grid A, set switch S2 to the I (close) position to close
contactor CR2. This will allow operation of the protection system.
15. On the Universal Fault Module, depress the INITIATE FAULT button to shortcircuit one phase of the three-phase load. While doing this observe the circuit
currents and the tripping indicator on the Three-Phase Overcurrent Relay.
Describe what has happened.
Has the large fault current been cleared by the overcurrent protection system?
Yes
No
On the Universal Fault Module, place the INITIATE FAULT button in the
released position.
16. On Control Relays 1 of the Protective Relaying Control Station, press the RESET
button of control relay CR1 to reset the protection system.
On the Faultable Transformer, set fault switch FS1 of transformer T1 to I position
to insert an earth fault near the middle of the primary winding of transformer T1.
While doing this, observe the circuit currents and the tripping indicator on the
AC/DC Current Sensitive Relay.
Describe what has happened.
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------Has the earth fault at the primary winding of the power transformer been cleared
by the earth fault protection in the overcurrent protection system?
Yes
No
Exercise
1. Discuss what do you have learned from this experiment
7
Details
The hands-on capability of the students and their efforts
during the lab sessions will be assessed.
The students will be evaluated on the spot based on the
theory concerned with the lab experiments and the
observations.
Each student will have to submit his/her lab discussion
sheet and recorded experimental data on the same day of
performing the lab experiments.
Experiment #2
8
Assessment Components
Development of Program and flow chart (3)
MATLAB coding and testing (4)
Report (3)