TITSEC(EOA)
ARAR-ED001
SHEET OF
i i
OF 4
ENGINEERING CONSULTANT
TCE CONSULTING ENGINEERS LIMITED
73/1, ST. MARKS ROAD
BANGALORE 560 001
INDIA
CONTRACTOR:
AL-TOUKHI COMPANY FOR INDUSTRY & TRADING
P.O. BOX 497, RIYADH 11411, KINGDOM OF SAUDI ARABIA
TEL. 00966-1-4633660 : FAX. 009661-4631150
A 28-06-2004
GL
SJH
SR
SJH
REV NO . DATE
PREPARED BY
CHECKED BY
CLEARED BY
APPROVED BY
FILENAME : 278172300.doc
CONTENTS
SHEET OF
i i
OF 4
CONTENTS
CLAUSE No.
DESCRIPTION
PAGE No.
1.0
INTRODUCTION
2.0
OBJECT
3.0
SIZING
4.0
CONCLUSIONS
ANNEXURE 1
ANNEXURE 2
ANNEXURE-3
ANNEXURE-4
ISSUE
A
FILE NAME: F120R1
WRITEUP
SHEET OF
2 7
OF 4
1.0
INTRODUCTION
1.1
1.2
2.0
OBJECT
2.1
2.2
Reference Documents:
SEC-EOAs
specification
requirements
for
Generator
Transformer defined under Cl.No.3.03 (1), page 37 of 336 of
PTS-1022.
ISSUE
A
WRITEUP
SHEET OF
3 7
OF 4
( Al-Toukhi may please enter the Amendment No. and date above
as the same is not available with TCE )
3.0
SIZING
INPUT DATA
3.1
Generator Parameters:
Guaranteed Average Unit Gross
Power Output at 50 Deg C site
ambient temperature
(Refer Annexure-1)
Generator Maximum Continuous
Output at 15 Deg C site ambient
temperature
(Refer Annexure-4)
Generator Maximum Continuous
Output at 50 Deg C site ambient
temperature corresponding to a
Generator liquid temperature of
54 Deg C
81920 kW
(Al-Toukhi to get this confirmed
from GE before submitting the
calculations to SEC-EOA)
64500kW
13.8kV
Rated Frequency
60 Hz
Power Factor
0.8
ISSUE
A
FORM NO. 120 R1
3.2
3.3
WRITEUP
SHEET OF
4 7
OF 4
See Annexure3
40/50MVA
Type of Cooling
ONAN/ONAF
Rated Voltage
13.8/132kV
Rated Frequency
60 Hz
Power Factor
0.8
Impedance
132 kV
145kV
Rated Frequency
60 Hz
3.4
50C
-5C
Relative Humidity
100%
ISSUE
A
Altitude
WRITEUP
SHEET OF
5 7
OF 4
iii)
3.5.2 SEC-EOA clarified vide A.114 (page 5 of 11), Clarification No.05 dated
28th December 2003 that the inlet cooling system requirement is limited
to the provision in the inlet air ducting and it has no impact on the
sizing of the Generator Transformer, 132kV Cables etc.
3.5.3 Further, SEC-EOA clarified vide A.119 (page 8 of 11), Clarification
No.05 dated 28th December 2003 that, in future, the Gas Turbine
Power output enhancement by intake air cooling will be limited to
match with the maximum Generator rating at 50 Deg C. Therefore,
there is no need to consider any reserve capacity to be in built into the
sizing of Generator and downstream electrical equipment.
3.6
WRITEUP
SHEET OF
6 7
OF 4
60.16MW
3.6.2 The Generator Transformer shall match with the Maximum Continuous
Rating of Generator at 50 Deg C maximum site ambient conditions.
As mentioned in Cl.3.1 above,
The Maximum Continuous Rating of
=
Generator at 50 Deg C site ambient conditions.
=
64.50MW
80.625MVA
at 0.8 P.F
3.6.3 The ONAF rating of the Generator Transformer is matched with the
Maximum Continuous Rating of Generator at ambient temperature of
50C since as per IEC 76-2, part-2, Clause 3, page 9 of IEC76-2, the
Power figure for the alternative with the highest cooling capacity is the
rated power of the transformer.
Rating of Generator Transformer
=
at 50 Deg C site maximum ambient conditions
and at ONAF cooling.
81MVA
80% of 81MVA
64.8MVA
12.5%.
ISSUE
A
FORM NO. 120 R1
WRITEUP
SHEET OF
7 7
OF 4
CONCLUSION
Summarising the above, the sizing of the Generator Transformer results in
the data listed below.
Rated Power (ONAN/ONAF)
65/81 MVA.
Ref. Temperature
Rated Frequency
60 Hz
Cooling
ONAN / ONAF
YNd11
12.5%
ii)
ISSUE
A
v)
WRITEUP
SHEET OF
8 7
OF 4
The temperature rises shall be in accordance with IEC60076 duly considering the Site conditions specified
under Cl.No.4.01.1 (page 70 of 336) of PTS-1022.
ISSUE
A
FILE NAME: F120R1