Professional Documents
Culture Documents
CONTROL CIRCUITS
a.
INTRODUCTION
During power system faults, devices are used for fast isolation of
affected equipment to save them from damage. Special circuits called
control circuits are used to realize the above objective. Control circuits
are used for other functions besides switching on or off of circuit
breakers and isolators as enumerated below:
1. Voltage
raise or
lower
in
tap
changer
device of
power
transformers.
2. Frequency regulation and load control.
3. Power system monitoring such as power factor control.
4. Alarm and indication control.
5. Circuit supervision.
6. Audio/visual annunciation.
B.
28
D.C. supply
A.C. supply
D. C. SUPPLY
The major source of D. C. supply is from a storage battery. The storage
battery types commonly used are:
(a)
(b)
Auxiliary D.C. supply has standard voltage ratings of 24V, 30V, 36V,
48V, 50V, 60V, 72V, 110V, 220V and 250V. Generally 110V is used for
Trip/Close control. In some cases a combination of 50V and 110V D.C.
are used. In this case the relay coil energizes an auxiliary interposing
relay whose contacts make to energize an 110V D.C. breaker trip/close
coil which in turn opens/closes the contacts of a breaker.
Standard ampere-hour ratings of auxiliary D.C. supply are 45, 60, 100,
250, 500 and 1000AH.
The voltage rating and the Ampere-Hour rating are decided by:
(i)
(ii)
29
(iii)
which will indicate the actual pole that is faulty. In some installations,
a switch is used to monitor the amount of voltage leaking to ground.
Under normal conditions P-E and N-E voltages are equal. But a pole
loses the voltages to ground if faulty.
30
A.C. SUPPLY
The A.C. supply for the control circuits is obtained from a station
auxiliary transformer.
In this case, if
supply from one source fails then, supply from the other source is
readily available.
31
TRIP CIRCUIT
The control circuit for the opening of switchgear during normal
operation or on fault is usually known as Trip Circuit.
To ensure that this circuit does not fail whenever a signal is sent to
operate
the
breaker/disconnect
switch,
it
is
being
monitored
The
relay is wired in such a way that the relay coil is energized as long as
the trip circuit is healthy. If for any reason there is a fault within the
trip circuit causing a loss of D.C. supply, this relay de-energises causing
the mechanical target to flag, which will indicate, Trip circuit faulty.
This relay is usually a self-reset relay, which resets itself as soon as the
D.C. supply is restored.
charger is faulty or the D.C. fuse gets ruptured as a result of a shortcircuit fault within the D.C. circuit. A control scheme showing the trip
circuit supervision wiring is as shown in Figs. 1 and 2.
32
33
34
35
36
37
MS
- Heater
PBC, PBT
52 CS
LS
- Limit switch
LSS
LCS
RSS
L/R
- Local/remote position
CC / TC
- Closing/Trip coil
ITR
HTPB
HTL
BOL
BCL
ATL
52a, b
51
64N