You are on page 1of 80

Damper Actuators

Technical Databook

Belimo Asia Pacific

Version 5.1

Damper Actuator standard type naming

Product naming
e.g.

24

-SR

Torque
General Damper Actuator
40Nm
20Nm
10Nm
5Nm
2Nm

G
S
N
L
C

Mechanical Fail-Safe Damper Actuator


30Nm
20Nm
10Nm
4Nm
2.5Nm

E
S
N
L
T

Electronic Fail-Safe Damper Actuator


40Nm

General Damper Actuator


Mechanical Fail-Safe Damper Actuator
Electronic Fail-Safe Damper Actuator

M
F
K

New Generation General Damper Actuator for Asia Pacific


Power supply
AC/DC 24V
AC 100...240V (AC 230V for Mechanical Fail-Safe Damper Actuator)

24
230

Function
General Damper Actuator
Open/Close, 3-point
Modulating DC (0)2...10V
Auxiliary switch
Form fit
Terminal connection

Blank
-SR
-S
-F
-T

Mechanical Fail-Safe Damper Actuator


Open/Close
Modulating DC (0)2...10V
3-point
Auxiliary switch

Blank
-SR
-3
-S,-S2

Electronic Fail-Safe Damper Actuator


3-point

-MF

V5.1. 05.2013 Subject to modification

For customising types of damper actuators, please contact your nearest Belimo sales representative.

Contents
Product overview

General Damper Actuator, 2Nm


CMU24(-F8/-F10)(-T)

CMU24-SR-R

CMU230(-F8/-F10)

General Damper Actuator, 5Nm


LMU24(-S/-F/-T)

10

LMU24-SR

11

LMU230(-S/-F)

12

LMU230SR

13

General Damper Actuator, 10Nm


NMU24(-S/-T)

14

NMU24-SR

15

NMU230(-S)

16

NMU230SR

17

General Damper Actuator, 20Nm


SMU24(-S)

18

SMU24-SR

19

SMU230(-S/-F)

20

SMU230SR

21

General Damper Actuator, 40Nm


GMU24

22

GMU24-SR

23

GMU230

24

Fast Running Damper Actuator, 4Nm


LMQU24

25

LMQU24-SR

26

Fast Running Damper Actuator, 8Nm


NMQU24

27

NMQU24-SR

28

Fast Running Damper Actuator, 16Nm


SMQU24

29

SMQU24-SR

30

SMDU230

31

Mechanical Fail-Safe Damper Actuator, 2.5Nm


TF24(-S)

32

TF24-3

33

TF24-SR

34

TF230(-S)

35

Mechanical Fail-Safe Damper Actuator, 4Nm


LF24(-S)

36

LF24-3

37

LF24-SR

38

LF230(-S)

39

V5.1. 05.2013 Subject to modification

Mechanical Fail-Safe Damper Actuator, 10Nm


NFU

40

NFU-S2

41

Note:

NFU24-SR

42

Using Belimo Damper Actuators:

SFU

43

g The actuators listed in this catalogue are intended for the


operation of air dampers in HVAC systems.

SFU-S2

44

SFU24-SR

45

g The damper actuator is not allowed to be used outside the


specified field of application, especially in aircraft.

Mechanical Fail-Safe Damper Actuator, 30Nm


EFU24-S2

46

The enclosure of the actuator equipment may only be


opened by the manufacturer. It contains no components
which the user can replace or repair.

EFU24-SR

47

EFU230-S2

48

The device contains electrical and electronic components


and is not allowed to be disposed of as household refuse.
All locally valid regulations and requirements must be
observed.

Mechanical Fail-Safe Damper Actuator, 20Nm

Electronic Fail-Safe Damper Actuator, 40Nm


GKU24

49

GKU24-MF

50

Mounting instructions

51

Wiring diagrams

65

Torque requirements:

Auxiliary switch adjustment

71

g When calculating the torque required to operate dampers,


it is essential to take into account all the data supplied by
the damper manufacturer concerning cross sectional area,
design, mounting and air flow condition.

Electrical accessories

72

Mechanical accessories

73

Replacement table (for Mechanical Fail-Safe Damper Actuators)

75

Damper Actuator product overview

General Damper Actuator

2Nm

5Nm

10Nm

20Nm

40Nm

CMU..

LMU..

NMU..

SMU..

GMU..
GMU24*

Open/Close, 3-point
AC/DC 24V 50/60Hz

CMU24(-F8/-F10)(-T)

Auxiliary switch built-in 1 SPDT


AC 100...240V 50/60Hz

CMU230(-F8/-F10)

Auxiliary switch built-in 1 SPDT

LMU24(-F/-T)

NMU24(-T)

SMU24

LMU24-S

NMU24-S

SMU24-S

LMU230

NMU230

SMU230

LMU230-S

NMU230-S

SMU230-S

LMU24-SR

NMU24-SR

SMU24-SR

LMU230SR

NMU230SR

SMU230SR

6...20mm

8...26.7mm

GMU230*

Modulating
Control signal DC (0)2...10V, feedback DC 2...10V
AC/DC 24V 50/60Hz

CMU24-SR-R**

AC 100...240V 50/60Hz
Running time

75s

Shaft diameter

6...12.7mm

150s

Sound power level


Manual override

GMU24-SR

Max. 35dB(A)

10...20mm

12...25.2mm

Max. 45dB(A)

Gear disengaging by magnet

Gear disengaging by push button

Electrical connection

Cable 1m (-T: Terminal)

Direction of rotation

Selected by switch

Angle of rotation

Max. 95, can be limited at both ends with mechanical adjustable end stops

Position indicator

Mechanical, plug-on

Degree of protection

IP54 (-T: IP20)

EMC

CE according to 89/336/EEC

LVD***

CE according to 73/23/EEC

Ambient temperature

-30...+50C

Non-operation temperature

-40...+80C

Humidity

5...95% RH, non-condensing

* Only Open/Close, no 3-point.


** CMU24-SR-R: Control signal (0)2V at the right side, and the left side is available on request.
*** For 230V models.

General Damper Actuator

4Nm

8Nm

16Nm

LMQU..

NMQU..

SMQU..

LMQU24

NMQU24

SMQU24

SMDU..

Open/Close
AC 24V 50/60Hz, DC 24V
AC 100...240V 50/60Hz

SMDU230

Modulating
Control signal DC (0)2...10V, feedback DC 2...10V
AC 24V 50/60Hz, DC 24V

LMQU24-SR

Running time

2.5s

Sound power level


Manual override
Electrical connection
Direction of rotation

SMQU24-SR

4s
826.7mm

7s

20s

1225.2mm

10...20mm

Max. 52dB(A)

Max. 55dB(A)

Disengaging the gearing latch by means of a push button, self-resetting


Cable 1m
Selected by switch

Angle of rotation

Max. 95, can be limited at both ends with mechanical adjustable end stops

Position indicator

Mechanical, plug-on

Degree of protection

IP54

EMC

CE according to 2004/108/EC

LVD*

CE according to 2006/95/EC

Ambient temperature
Non-operation temperature
Humidity
* For 230V models.

-30+40C (without restrictions); +40+50C (with restrictions)


-40+80C
5...95% RH, non-condensing

V5.1. 05.2013 Subject to modification

Shaft diameter

NMQU24-SR

Damper Actuator product overview

2.5Nm

4Nm

TF..

LF..

AC/DC 24V 50/60Hz

TF24

LF24

Auxiliary switch built-in 1 SPDT

TF24-S

LF24-S

AC 230V 50/60Hz

TF230**

LF230

Auxiliary switch built-in 1 SPDT

TF230-S

LF230-S

TF24-3**

LF24-3

AC/DC 24V 50/60Hz

TF24-SR

LF24-SR

Running time

<75s*
<25s

40-75s*
<20s

6...12mm

8...16mm

Mechanical Fail-Safe Damper Actuator


Open/Close

3-point
AC/DC 24V 50/60Hz
Modulating
Control signal DC (0)2...10V, feedback DC 2...10V
-Motor
-Spring return

Shaft diameter
Sound power level

-Motor

Open/Close max. 50dB(A)


Modulating and 3-point max. 35dB(A)

-Spring

Open/Close max. 50dB(A)


Modulating and 3-point max. 30dB(A)

62dB(A)

Electrical connection

Cable 1m

Direction of rotation

Selected by mounting L/R

Angle of rotation

Max. 95

Mechanical end stops

Yes

Position indicator

Yes

Degree of protection

IP42

IP54

EMC

CE according to 89/336/EEC

LVD***

CE according to 73/23/EEC

Ambient temperature

-30...+50C

Non-operation temperature

-40...+80C

Humidity

5...95% RH, non-condensing

V5.1. 05.2013 Subject to modification

* LF24-3 and all -SR types are 150s.


** TF24-3 nominal voltage is AC 24V, TF230 nominal voltage is AC 100...240V.
*** For 230V models.

Damper Actuator product overview

Mechanical Fail-Safe Damper Actuator

10Nm

20Nm

30Nm

NFU..

SFU..

EFU..

Open/Close
AC 24...240V / DC 24...125V

NFU

SFU

Auxiliary switch built-in 2 SPDT

NFU-S2

SFU-S2

EFU24-S2

EFU230-S2

AC/DC 24V 50/60Hz

NFU24-SR

SFU24-SR

EFU24-SR

Running time

Open/Close 75s; modulating 150s


20s @ 20 ...+50C / max. 60s @ 30C

AC/DC 24V 50/60Hz


Auxiliary switch built-in 2 SPDT
AC 230V 50/60Hz
Auxiliary switch built-in 2 SPDT
Modulating
Control signal DC (0)2...10V, feedback DC 2...10V
-Motor
-Spring return

Shaft diameter
Sound power level

Open/Close 60s; modulating 150s


20s @ 20 ...+50C / max. 60s @ 30C

10...25.4mm / 14...25.4mm

12...26.7mm / 12...25.2mm

-Motor

Open/Close max. 45dB(A)


Modulating max. 40dB(A)
max. 62dB(A)

Open/Close max. 55dB(A)


Modulating max. 45dB(A)
max. 71dB(A)

-Spring return
Electrical connection

Cable 1m

Direction of rotation

Selected by mounting L/R

Angle of rotation

Max. 95

Mechanical end stops

Yes

Position indicator

Yes

Degree of protection

IP54

EMC

CE according to 89/336/EEC

LVD*

CE according to 2006/95/EC

Ambient temperature

-30...+50C

Non-operation temperature

-40...+80C

Humidity

5...95% RH, non-condensing

* For 230V only.

40Nm

Electronic Fail-Safe Damper Actuator

GKU..

Open/Close
AC/DC 24V 50/60Hz

GKU24

AC/DC 24V 50/60Hz

GKU24-MF

Running time

150s
35s

90...150s
35s

Modulating / 3-point
Control signal DC (0)2...10V, feedback DC 2...10V

Shaft diameter
Sound power level

-Standard
-Power off position

12...26.7mm / 12...25.2mm
Max. 53dB(A)
Max. 61dB(A)

Electrical connection

Cable 1m

Direction of rotation

Selected by mounting L/R

Angle of rotation

Max. 95

Mechanical end stops

Yes

Position indicator

Yes

Degree of protection
EMC

IP54
CE according to 2004/108/EC

Ambient temperature

-30...+50C

Non-operation temperature

-40...+80C

Humidity

5...95% RH, non-condensing

V5.1. 05.2013 Subject to modification

-Standard
-Power off position

CMU24(-F8/-F10)(-T)

For operation of air control dampers in HVAC system


Torque:

2Nm

Nominal voltage:

AC/DC 24V

Control:

Open/Close or 3-point

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC/DC 19.2...28.8V

Power consumption

0.5W @ nominal torque / 0.2W @ holding

For transformer sizing

1VA

Connection

Terminals for 3x1.5mm2 CU wire or 3x1.0mm2 CU litz wires


1m, 3x0.75mm2

(-T)
cable

Torque

2Nm @ nominal voltage

Direction of rotation

Depends on electrical installation

Manual override

Gear disengagement by magnet

Angle of rotation no limiters


with limiters

Endless
Fixed 315 or 0... 287.5 with mechanical end stops,
can be adjusted in 2.5 increments

Running time

75s

Sound power level

Max. 35dB(A)

Position indicator

Mechanical, pluggable
with integrated magnet for gear disengagement

Protection class

III (safety extra-low voltage)

Degree of protection (-T)


cable

IP20
IP54

EMC

CE according to 89/336/EEC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft
Form fit (-F8)
(-F10)

6...12.7mm
8x8mm
10x10mm

Weight

0.13...0.22kg

Dimensions [mm]

16
149

12 1

28

121

56

28

130

56

56

V5.1. 05.2013 Subject to modification

20

16

16

14 9

158
28

CMU24-F8-T

28

CMU24-T

28

CMU24

CMU24-SR-R

For operation of air control dampers in HVAC system


Torque:

2Nm

Nominal voltage:

AC/DC 24V

Control signal:

DC (0)2...10V

Position feedback:

DC 2...10V

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC/DC 19.2...28.8V

Power consumption

1W @ nominal torque / 0.5W @ holding

For transformer sizing

2VA

Connecting cable

Cable 1m, 4x0.75mm2

Torque

2Nm @ nominal voltage

Control signal Y

DC(0)210V @ input impedance 100k

Position feedback signal U

DC 210V @ max. 1mA

Position accuracy

5%

Direction of rotation

Y=0V at right end stop position

Manual override

Gear disengagement by magnet

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

75s

Sound power level

Max. 35dB(A)

Position indicator

Mechanical, pluggable
with integrated magnet for gear disengagement

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 89/336/EEC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft

6...12.7mm

Weight

0.22kg

* -R: Control signal (0)2V at right side

16

28

Dimensions [mm]

158

130

V5.1. 05.2013 Subject to modification

56

28

CMU230(-F8/-F10)

For operation of air control dampers in HVAC system


Torque:

2Nm

Nominal voltage:

AC 100...240V

Control:

Open/Close or 3-point

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 100...240V 50/60Hz

Nominal voltage range

AC 85...265V

Power consumption

1.5W @ nominal torque / 1W @ holding

For transformer sizing

3VA

Connecting cable

Cable 1m, 3x0.75mm2

Torque

2Nm @ nominal voltage

Direction of rotation

Depends on electrical installation

Manual override

Gear disengagement by magnet

Angle of rotation no limiters


with limiters

Endless
Fixed 315 or 0... 287.5 with mechanical end stops,
can be adjusted in 2.5 increments

Running time

75s

Sound power level

Max. 35dB(A)

Position indicator

Mechanical, pluggable
with integrated magnet for gear disengagement

Protection class

II (Totally insulated)

Degree of protection

IP54

EMC
Low voltage directive

CE according to 2004/108/EC
CE according to 2006/95/EC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft
Form fit (-F8)
(-F10)

6...12.7mm
8x8mm
10x10mm

Weight

0.22kg

Dimensions [mm]

16

16

20

CMU230-F8

28

CMU230

158

158
28

130

130

56

56

V5.1. 05.2013 Subject to modification

28

LMU24(-S/-F/-T)

For operation of air control dampers in HVAC system


Torque:

5Nm

Nominal voltage:

AC/DC 24V

Control:

Open/Close or 3-point

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC/DC 19.2...28.8V

Power consumption

1W @ nominal torque / 0.2W @ holding

For transformer sizing

1.5VA

Auxiliary switch (-S)

1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable

Connection

Cable 1m, 3x0.75mm2


Cable 1m, 3x0.75mm2
Max. 3x1.5mm2

-motor
-auxiliary switch (-S)
-terminals (-T)

Torque

5Nm @ nominal voltage

Direction of rotation

Selectable by switch

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

150s

Sound power level

Max. 35dB(A)

Position indicator

Mechanical, remote visible

Protection class

III (safety extra-low voltage)

Degree of protection LMU24(-S/-F)


LMU24-T

IP54
IP20

EMC

CE according to 89/336/EEC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 37mm

Shaft

LMU24(-S/-T)
LMU24-F

6...20mm
8x8mm

Weight

0.5kg

10

V5.1. 05.2013 Subject to modification

5.2

33

33

33

5.2

Dimensions [mm]

LMU24-SR

For operation of air control dampers in HVAC system


Torque:

5Nm

Nominal voltage:

AC/DC 24V

Control signal:

DC (0)2...10V

Position feedback:

DC 2...10V

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC/DC 19.2...28.8V

Power consumption

1W @ nominal torque / 0.4W @ holding

For transformer sizing

2VA

Connecting cable

Cable 1m, 4x0.75mm2

Torque

5Nm @ nominal voltage

Control signal Y

DC (0)2...10V @ input impedance 100k

Position feedback signal U

DC 210V @ max. 1mA

Position accuracy

5%

Direction of rotation

Selectable by switch

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

150s

Sound power level

Max. 35dB(A)

Position indicator

Mechanical, remote visible

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 89/336/EEC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft
Weight

6...20mm
0.5kg

33

5.2

Dimensions [mm]

V5.1. 05.2013 Subject to modification

11

LMU230(-S/-F)

For operation of air control dampers in HVAC system


Torque:

5Nm

Nominal voltage:

AC 100...240V

Control:

Open/Close or 3-point

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 100...240V 50/60Hz

Nominal voltage range

AC 85...265V

Power consumption

1.5W @ nominal torque / 0.5W @ holding

For transformer sizing

3.5VA

Auxiliary switch (-S)

1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable

Connection

Cable 1m, 3x0.75mm2


Cable 1m, 3x0.75mm2

-motor
-auxiliary switch (-S)

Torque

5Nm @ nominal voltage

Direction of rotation

Selectable by switch

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

150s

Sound power level

Max. 35dB(A)

Position indicator

Mechanical, remote visible

Protection class

II (Totally insulated)

Degree of protection

IP54

EMC
Low voltage directive

CE according to 89/336/EEC
CE according to 73/23/EEC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length
Shaft

Min. 37mm
LMU230(-S)
LMU230-F

Weight

6...20mm
8x8mm
0.55kg

Dimensions [mm]
LMU230(-S)

61

47

47

61

LMU230-F

116

16

20

116
28.5

41

22

94

41

V5.1. 05.2013 Subject to modification

94

66
30
5.2

66

22

12

33

33

5.2

100.5

LMU230SR

For operation of air control dampers in HVAC system


Torque:

5Nm

Nominal voltage:

AC 100...240V

Control signal:

DC (0)2...10V

Position feedback:

DC 2...10V

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 100...240V 50/60Hz

Nominal voltage range

AC 85...265V

Power consumption

2W @ nominal torque / 1W @ holding

For transformer sizing

4VA

Connecting cable -power supply


-signal

Cable 1m, 2x0.75mm2


Cable 1m, 4x0.75mm2

Torque

5Nm @ nominal voltage

Control signal Y

DC (0)2...10V @ input impedance 100k

Position feedback signal U

DC 210V @ max. 1mA

Position accuracy

5%

Direction of rotation

Selectable by switch

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

150s

Sound power level

Max. 35dB(A)

Position indicator

Mechanical, remote visible

Protection class

II (Totally insulated)

Degree of protection

IP54

EMC
Low voltage directive

CE according to 89/336/EEC
CE according to 73/23/EEC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft

6...20mm

Weight

0.7kg

47

61

Dimensions [mm]

33

66

V5.1. 05.2013 Subject to modification

5.2

116

22

116

41

13

NMU24(-S/-T)

For operation of air control dampers in HVAC system


Torque:

10Nm

Nominal voltage:

AC/DC 24V

Control:

Open/Close or 3-point

Technical data
Electrical data

Functional data

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC/DC 19.2...28.8V

Power consumption

1.5W @ nominal torque / 0.2W @ holding

For transformer sizing

3.5VA

Auxiliary switch (-S)

1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable

Connection

Cable 1m, 3x0.75mm2


Cable 1m, 3x0.75mm2
Max. 3x1.5mm2

-motor
-auxiliary switch (-S)
-terminals (-T)

Torque

10Nm @ nominal voltage

Direction of rotation

Selectable by switch

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

150s

Sound power level

Max. 35dB(A)

Position indicator

Mechanical, remote visible

Protection class

Working conditions

Degree of protection

Dimensions / weight

III (safety extra-low voltage)


NMU24(-S)
NMU24-T

IP54
IP20

EMC

CE according to 89/336/EEC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 40mm (20mm with K-NA for reverse mounting-optional)

Shaft

8..26.7mm (8...20mm with K-NA)

Weight

0.75kg

Dimensions [mm]

65.6

NMU24-T

60

60

62

NMU24(-S)

124

25

14

99

41

25

99

V5.1. 05.2013 Subject to modification

5.2

80

80

40

40

5.2

124

NMU24-SR

For operation of air control dampers in HVAC system


Torque:

10Nm

Nominal voltage:

AC/DC 24V

Control signal:

DC (0)2...10V

Position feedback:

DC 2...10V

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC/DC 19.2...28.8V

Power consumption

2W @ nominal torque / 0.4W @ holding

For transformer sizing

4VA

Connecting cable

Cable 1m, 4x0.75mm2

Torque

10Nm @ nominal voltage

Control signal Y

DC (0)2...10V @ input impedance 100k

Position feedback signal U

DC 210V @ max. 1mA

Position accuracy

5%

Direction of rotation

Selectable by switch

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

150s

Sound power level

Max. 35dB(A)

Position indicator

Mechanical, remote visible

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 89/336/EEC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft

8...26.7mm (8...20mm with K-NA)

Weight

0.8kg

60

62

Dimensions [mm]

V5.1. 05.2013 Subject to modification

80

40

5.2

124

25

99

41

15

NMU230(-S)

For operation of air control dampers in HVAC system


Torque:

10Nm

Nominal voltage:

AC 100...240V

Control:

Open/Close or 3-point

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 100...240V 50/60Hz

Nominal voltage range

AC 85...265V

Power consumption

2.5W @ nominal torque / 0.6W @ holding

For transformer sizing

5.5VA

Auxiliary switch (-S)

1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable

Connection -motor
-auxiliary switch (-S)

Cable 1m, 3x0.75mm2


Cable 1m, 3x0.75mm2

Torque

10Nm @ nominal voltage

Direction of rotation

Selectable by switch

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

150s

Sound power level

Max. 35dB(A)

Position indicator

Mechanical, remote visible

Protection class

II (Totally insulated)

Degree of protection

IP54

EMC
Low voltage directive

CE according to 89/336/EEC
CE according to 73/23/EEC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 40mm (20mm with K-NA for reverse mounting-optional)

Shaft

8..26.7mm (8...20mm with K-NA)

Weight

0.8kg

60

62

Dimensions [mm]

80

25

16

99

41

V5.1. 05.2013 Subject to modification

40

5.2

124

NMU230SR

For operation of air control dampers in HVAC system


Torque:

10Nm

Nominal voltage:

AC 100...240V

Control signal:

DC (0)2...10V

Position feedback:

DC 2...10V

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 100...240V 50/60Hz

Nominal voltage range

AC 85...265V

Power consumption

3.5W @ nominal torque / 1W @ holding

For transformer sizing

6.5VA

Connection

Cable 1m, 2x0.75mm2


Cable 1m, 4x0.75mm2

-power supply
-signal

Torque

10Nm @ nominal voltage

Control signal Y

DC (0)2...10V @ input impedance 100k

Position feedback signal U

DC 210V @ max. 1mA

Position accuracy

5%

Direction of rotation

Selectable by switch

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

150s

Sound power level

Max. 35dB(A)

Position indicator

Mechanical, remote visible

Protection class

II (Totally insulated)

Degree of protection

IP54

EMC
Low voltage directive

CE according to 89/336/EEC
CE according to 73/23/EEC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 40mm (20mm with K-NA for reverse mounting-optional)

Shaft

8...26.7mm (8...20mm with K-NA)

Weight

0.95kg

60

62

Dimensions [mm]

5.2

40

80

V5.1. 05.2013 Subject to modification

124

25

121

41

17

SMU24(-S)

For operation of air control dampers in HVAC system


Torque:

20Nm

Nominal voltage:

AC/DC 24V

Control:

Open/Close or 3-point

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC/DC 19.2...28.8V

Power consumption

2W @ nominal torque / 0.2W @ holding

For transformer sizing

4VA

Auxiliary switch (-S)

1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable

Connection -motor
-auxiliary switch (-S)

Cable 1m, 3x0.75mm2


Cable 1m, 3x0.75mm2

Torque

20Nm @ nominal voltage

Direction of rotation

Selectable by switch

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

150s

Sound power level

Max. 45dB(A)

Position indicator

Mechanical, remote visible

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 89/336/EEC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 42mm (20mm for reverse mounting)

Shaft

10..20mm (10...26.7mm with K-ENSA - optional)

Weight

1.05kg

56

64

Dimensions [mm]

88

30

18

109

41

V5.1. 05.2013 Subject to modification

44

5.2

139

SMU24-SR

For operation of air control dampers in HVAC system


Torque:

20Nm

Nominal voltage:

AC/DC 24V

Control signal:

DC (0)2...10V

Position feedback:

DC 2...10V

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC/DC 19.2...28.8V

Power consumption

2W @ nominal torque / 0.4W @ holding

For transformer sizing

4VA

Connecting cable

Cable 1m, 4x0.75mm2

Torque

20Nm @ nominal voltage

Control signal Y

DC (0)2...10V @ input impedance 100k

Position feedback signal U

DC 210V @ max. 1mA

Position accuracy

5%

Direction of rotation

Selectable by switch

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

150s

Sound power level

Max. 45dB(A)

Position indicator

Mechanical, remote visible

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 89/336/EEC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 42mm (20mm for reverse mounting)

Shaft

10..20mm (10...26.7mm with K-ENSA - optional)

Weight

1.05kg

56

64

Dimensions [mm]

88

V5.1. 05.2013 Subject to modification

44

5.2

139

30

109

41

19

SMU230(-S/-F)

For operation of air control dampers in HVAC system


Torque:

20Nm

Nominal voltage:

AC 100...240V

Control:

Open/Close or 3-point

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 100...240V 50/60Hz

Nominal voltage range

AC 85...265V

Power consumption

2.5W @ nominal torque / 0.6W @ holding

For transformer sizing

6VA

Auxiliary switch (-S)

1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable

Connection -motor
-auxiliary switch (-S)

Cable 1m, 3x0.75mm2


Cable 1m, 3x0.75mm2

Torque

20Nm @ nominal voltage

Direction of rotation

Selectable by switch

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

150s

Sound power level

Max. 45dB(A)

Position indicator

Mechanical, remote visible

Protection class

II (Totally insulated)

Degree of protection

IP54

EMC
Low voltage directive

CE according to 89/336/EEC
CE according to 73/23/EEC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 42mm (20mm for reverse mounting)

Shaft

SMU230(-S)
SMU230-F

Weight

10..20mm (10...26.7mm with K-ENSA-optional)


12x12mm
1.05kg

Dimensions [mm]

64

SMU230(-S)

56

SMU230-F

30

109
139
5.2
44

44

4.2
8.8

20

88

75

30

109

41

V5.1. 05.2013 Subject to modification

97
5.2

23

SMU230SR

For operation of air control dampers in HVAC system


Torque:

20Nm

Nominal voltage:

AC 100...240V

Control signal:

DC (0)2...10V

Position feedback:

DC 2...10V

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 100...240V 50/60Hz

Nominal voltage range

AC 85...265V

Power consumption

3.5W @ nominal torque / 1W @ holding

For transformer sizing

6.5VA

Connection

Cable 1m, 2x0.75mm2


Cable 1m, 4x0.75mm2

-power supply
-signal

Torque

20Nm @ nominal voltage

Control signal Y

DC (0)2...10V @ input impedance 100k

Position feedback signal U

DC 210V @ max. 1mA

Position accuracy

5%

Direction of rotation

Selectable by switch

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

150s

Sound power level

Max. 45dB(A)

Position indicator

Mechanical, remote visible

Protection class

II (Totally insulated)

Degree of protection

IP54

EMC
Low voltage directive

CE according to 89/336/EEC
CE according to 73/23/EEC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 42mm (20mm for reverse mounting)

Shaft

10..20mm (10...26.7mm with K-ENSA-optional)

Weight

1.2kg

56

64

Dimensions [mm]

5.2
44

88

V5.1. 05.2013 Subject to modification

139

30

131

41

21

GMU24

For operation of air control dampers in HVAC system


Torque:

40Nm

Nominal voltage:

AC/DC 24V

Control:

Open/Close

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC/DC 19.2...28.8V

Power consumption

4W @ nominal torque / 2W @ holding

For transformer sizing

6VA

Connecting cable

Cable 1m, 3x0.75mm2

Torque

40Nm @ nominal voltage

Direction of rotation

Selectable by switch

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

150s

Sound power level

Max. 45dB(A)

Position indicator

Mechanical, remote visible

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 89/336/EEC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 52mm (20mm for reverse mounting)

Shaft

12...26.7mm / 12...25.2mm

Weight

1.7kg

Dimensions [mm]
Standard :

>52

12...26.7

>12 <25.2

>20

12...26.7

>12 <25.2

70

Length

60

Damper spindle

12...18mm

116
22...26.7mm

12...18mm

36

22

143

41

V5.1. 05.2013 Subject to modification

12...22mm

58

5.2

179

GMU24-SR

For operation of air control dampers in HVAC system


Torque:

40Nm

Nominal voltage:

AC/DC 24V

Control signal:

DC (0)2...10V

Position feedback:

DC 2...10V

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC/DC 19.2...28.8V

Power consumption

4.5W @ nominal torque / 2W @ holding

For transformer sizing

6.5VA

Connecting cable

Cable 1m, 4x0.75mm2

Torque

40Nm @ nominal voltage

Control signal Y

DC (0)2...10V @ input impedance 100k

Position feedback signal U

DC 210V @ max. 1mA

Position accuracy

5%

Direction of rotation

Selectable by switch

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

150s

Sound power level

Max. 45dB(A)

Position indicator

Mechanical, remote visible

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 89/336/EEC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 52mm (20mm for reverse mounting)

Shaft

12...26.7mm / 12...25.2mm

Weight

1.7kg

Dimensions [mm]
Standard :

>52

12...26.7

>12 <25.2

>20

12...26.7

>12 <25.2

70

Length

60

Damper spindle

12...22mm

12...18mm

22...26.7mm

12...18mm

9
116

V5.1. 05.2013 Subject to modification

58

5.2

179

36

143

41

23

GMU230

For operation of air control dampers in HVAC system


Torque:

40Nm

Nominal voltage:

AC 100...240V

Control:

Open/Close

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 100...240V 50/60Hz

Nominal voltage range

AC 85...265V

Power consumption

5W @ nominal torque / 2W @ holding

For transformer sizing

9VA

Connecting cable

Cable 1m, 3x0.75mm2

Torque

40Nm @ nominal voltage

Direction of rotation

Selectable by switch

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

150s

Sound power level

Max. 45dB(A)

Position indicator

Mechanical, remote visible

Protection class

II (Totally insulated)

Degree of protection

IP54

EMC
Low voltage directive

CE according to 89/336/EEC
CE according to 73/23/EEC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 52mm (20mm for reverse mounting)

Shaft

12..26.7mm / 12...25.2mm

Weight

1.7kg

Dimensions [mm]
Standard :

>52

12...26.7

>12

<25.2

>20

12...26.7

>12

<25.2

70

Length

60

Damper spindle

12...18mm

22...26.7mm

12...18mm

36

24

143

41

V5.1. 05.2013 Subject to modification

116

12...22mm

58

5.2

179

LMQU24

For operation of air control dampers in HVAC system


Torque:

4Nm

Nominal voltage:

AC/DC 24V

Control:

Open/Close (not made for


3-point applications)

Technical data
Electrical data

Functional data

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC 19.2...28.8V / DC 21.6...28.8V

Power consumption

13W @ nominal torque / 1.5W @ holding

For transformer sizing

23VA (Imax. 20A @ 5ms)

Connecting cable

Cable 1m, 3x0.75mm2

Torque

4Nm @ nominal voltage

Direction of rotation

Reversible with switch 0

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

2.5s

Automatic adjustment of operating


range to match the mechanical
angle of rotation

Manual triggering of the adaption by pressing the


Adaption button

Sound power level

Max. 52dB(A)

Position indicator

Mechanical, remote visible

Negative torque

Working conditions

50% from nominal torque (with restrictions)

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 2004/108/EC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
!

Dimensions / weight

or 1

-30...+40C (without restrictions)


+40...+50C (with restrictions)

Non-operation temp.

-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Weight

0.85kg

52

75

Dimensions [mm]

40

5.2

124

Length
40

8...26.7

20

8...20

80

V5.1. 05.2013 Subject to modification

Damper spindle

* Option (accessory K-NA)

25

121

41

25

LMQU24-SR

For operation of air control dampers in HVAC system


Torque:

4Nm

Nominal voltage:

AC/DC 24V

Control signal:

DC (0)2...10V

Position feedback:

DC 2...10V

Technical data
Electrical data

Functional data

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC 19.2...28.8V / DC 21.6...28.8V

Power consumption

13W @ nominal torque / 1.5W @ holding

For transformer sizing

23VA (Imax. 20A @ 5ms)

Connecting cable

Cable 1m, 4x0.75mm2

Torque

4Nm @ nominal voltage

Control signal Y

DC (0)2...10V @ input impedance 100k

Position feedback signal U

DC 2...10V @ max. 0.5mA

Position accuracy

5%

Direction of rotation

Reversible with switch 0 or 1

Direction of motion at Y=0V

At switch position 0

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

2.5s

Automatic adjustment of operating


range and measuring signal U to
match the mechanical angle of
rotation

Manual triggering of the adaption by pressing the


Adaption button

Sound power level

Max. 52dB(A)

Position indicator

Mechanical, remote visible

Negative torque

Working conditions

50% from nominal torque (with restrictions)

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 2004/108/EC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
!

Dimensions / weight

resp. 1

-30...+40C (without restrictions)


+40...+50C (with restrictions)

Non-operation temp.

-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Weight

0.85kg

40

5.2

124

Length
40

8...26.7

20

8...20

80

Damper spindle

* Option (accessory K-NA)

26

25

121

41

V5.1. 05.2013 Subject to modification

52

75

Dimensions [mm]

NMQU24

For operation of air control dampers in HVAC system


Torque:

8Nm

Nominal voltage:

AC/DC 24V

Control:

Open/Close (not made for


3-point applications)

Technical data
Electrical data

Functional data

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC 19.2...28.8V / DC 21.6...28.8V

Power consumption

13W @ nominal torque / 1.5W @ holding

For transformer sizing

23VA (Imax. 20A @ 5ms)

Connecting cable

Cable 1m, 3x0.75mm2

Torque

8Nm @ nominal voltage

Direction of rotation

Reversible with switch 0

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

4s

Automatic adjustment of operating


range to match the mechanical
angle of rotation

Manual triggering of the adaption by pressing the


Adaption button

Sound power level

Max. 52dB(A)

Position indicator

Mechanical, remote visible

Negative torque

Working conditions

50% from nominal torque (with restrictions)

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 2004/108/EC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
!

Dimensions / weight

or 1

-30...+40C (without restrictions)


+40...+50C (with restrictions)

Non-operation temp.

-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Weight

0.97kg

52

77

Dimensions [mm]

44

Damper spindle

Length

8
88

V5.1. 05.2013 Subject to modification

5.2

139

* Option (accessory K-SA)

30

131

41

27

NMQU24-SR

For operation of air control dampers in HVAC system


Torque:

8Nm

Nominal voltage:

AC/DC 24V

Control signal:

DC (0)2...10V

Position feedback:

DC 2...10V

Technical data
Electrical data

Functional data

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC 19.2...28.8V / DC 21.6...28.8V

Power consumption

13W @ nominal torque / 1.5W @ holding

For transformer sizing

23VA (Imax. 20A @ 5ms)

Connecting cable

Cable 1m, 4x0.75mm2

Torque

8Nm @ nominal voltage

Control signal Y

DC (0)2...10V @ input impedance 100k

Position feedback signal U

DC 2...10V @ max. 0.5mA

Position accuracy

5%

Direction of rotation

Reversible with switch 0 or 1

Direction of motion at Y=0V

At switch position 0

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

4s

Automatic adjustment of operating


range and measuring signal U to
match the mechanical angle of
rotation

Manual triggering of the adaption by pressing the


Adaption button

Sound power level

Max. 52dB(A)

Position indicator

Mechanical, remote visible


!

Negative torque

Working conditions

50% from nominal torque (with restrictions)

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 2004/108/EC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
!

Dimensions / weight

resp. 1

-30...+40C (without restrictions)


+40...+50C (with restrictions)

Non-operation temp.

-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Weight

0.95kg

Length

8
88

Damper spindle

44

5.2

139

*
* Option (accessory K-SA)

28

30

131

41

V5.1. 05.2013 Subject to modification

52

77

Dimensions [mm]

SMQU24

For operation of air control dampers in HVAC system


Torque:

16Nm

Nominal voltage:

AC/DC 24V

Control:

Open/Close (not made for


3-point applications)

Technical data
Electrical data

Functional data

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC/DC 21.6...26.4V

Power consumption

15W @ nominal torque / 1.5W @ holding

For transformer sizing

26VA (Imax. 20A @ 5ms)

Connecting cable

Cable 1m, 3x0.75mm2

Torque

16Nm @ nominal voltage

Direction of rotation

Reversible with switch 0

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

7s

Automatic adjustment of operating


range to match the mechanical
angle of rotation

Manual triggering of the adaption by pressing the


Adaption button

Sound power level

Max. 52dB(A)

Position indicator

Mechanical, remote visible

Negative torque

Working conditions

50% from nominal torque (with restrictions)

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 2004/108/EC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
!

Dimensions / weight

or 1

-30...+40C (without restrictions)


+40...+50C (with restrictions)

Non-operation temp.

-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Weight

1.7kg

83

Dimensions [mm]

Length

62

Damper spindle

12...22mm

12...18mm

22...26.7mm

12...18mm

116

V5.1. 05.2013 Subject to modification

58

5.2

179

36

143

41

29

SMQU24-SR

For operation of air control dampers in HVAC system


Torque:

16Nm

Nominal voltage:

AC/DC 24V

Control signal:

DC (0)2...10V

Position feedback:

DC 2...10V

Technical data
Electrical data

Functional data

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC/DC 21.6...26.4V

Power consumption

15W @ nominal torque / 1.5W @ holding

For transformer sizing

26VA (Imax. 20A @ 5ms)

Connecting cable

Cable 1m, 4x0.75mm2

Torque

16Nm @ nominal voltage

Control signal Y

DC (0)2...10V @ input impedance 100k

Position feedback signal U

DC 2...10V @ max. 0.5mA

Position accuracy

5%

Direction of rotation

Reversible with switch 0 or 1

Direction of motion at Y=0V

At switch position 0

Manual override

Gearing latch disengaged by push button, self-resetting

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

7s

Automatic adjustment of operating


range and measuring signal U to
match the mechanical angle of
rotation

Manual triggering of the adaption by pressing the


Adaption button

Sound power level

Max. 52dB(A)

Position indicator

Mechanical, remote visible

Negative torque

Working conditions

50% from nominal torque (with restrictions)

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 2004/108/EC

Mode of operation

Type 1 (EN 60730-1)

Ambient temp.
!

Dimensions / weight

resp. 1

-30...+40C (without restrictions)


+40...+50C (with restrictions)

Non-operation temp.

-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Weight

1.7kg

Length

58

5.2

179

9
12...18mm

22...26.7mm

12...18mm

116

12...22mm

30

36

143

41

V5.1. 05.2013 Subject to modification

62

Damper spindle

83

Dimensions [mm]

SMDU230
For operation of air control dampers in HVAC system
Torque:

16Nm

Running time

20s

Nominal voltage:

AC 100...240V

Control:

Open/Close or 3-point

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 100...240V 50/60Hz

Nominal voltage range

AC 85...265V

Power consumption

4.5W @ nominal torque / 1W @ holding

For transformer sizing

8VA

Connecting cable

Cable 1m, 3x0.75mm2

Torque

16Nm @ nominal voltage

Direction of rotation

Reversible with switch 0

Manual override

Gearing disengaged by pressing the push button, can be locked

Angle of rotation

Max. 95, can be limited with adjustable mechanical end stops

Running time

20s

Sound power level

Max. 55dB(A)

Position indicator

Mechanical, remote visible

resp. 1

Protection class

II (Totally insulated)

Degree of protection

IP54

EMC
Low voltage directive

CE according to 2004/108/EC
CE according to 2006/95/EC

Mode of operation

Type 1 (EN60730-1)

Rated impulse voltage

4kV

Control pollution degree

Ambient temp.

-30...+50C

Non-operation temp.

-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Weight

1kg

56

Damper spindle

64

Dimensions [mm]

Length
10 ... 20 1)
10 ... 20 1)

10
10

1) CrNi (INOX) 12 ... 20

44

5.2

139

88

V5.1. 05.2013 Subject to modification

30

131

41

31

Mechanical Fail-Safe Damper Actuator TF24(-S)

For operation of air control dampers that perform safety function


Torque:

2.5Nm

Nominal voltage:

AC/DC 24V

Control:

Open/Close

Integrated auxiliary switch (TF24-S)

Technical data
Electrical data

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC 19.2...28.8V / DC 21.6...28.8V

Power consumption

2.5W @ nominal torque / 1.5W @ holding

For transformer sizing

5VA

Auxiliary switch (-S)

1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable

Connecting cable -motor


Cable 1m, 2x0.75mm2
-auxiliary switch (-S) Cable 1m, 3x0.75mm2

Functional data

Torque

2.5Nm @ nominal voltage

Direction of rotation

Selectable by mounting L/R

Angle of rotation

Max. 95, 37...100% adjustable by mechanical stops

Running time

Working conditions

Dimensions / weight

-motor
-spring return

75s
25s @ -20...+50C / max. 60s @ -30C

Sound power level -motor


-spring return

Max. 50dB(A)
Max. 62dB(A)

Position indicator

Mechanical

Protection class

III (safety extra-low voltage)

Degree of protection

IP42

EMC

CE according to 89/336/EEC

Mode of operation

Type 1.AA (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 84mm
Min. 20mm

Clamp up
Clamp down

Shaft

6...12mm

Weight

0.6kg

61
6

6...12

84

17

Dimensions [mm]

10
20

32

84

36

V5.1. 05.2013 Subject to modification

77

5.3

38.5

104

Mechanical Fail-Safe Damper Actuator TF24-3

For operation of air control dampers that perform safety function


Torque:

2.5Nm

Nominal voltage:

AC 24V

Control:

3-point

Technical data
Electrical data

Functional data

Nominal voltage

AC 24V 50/60Hz

Nominal voltage range

AC 19.2...28.8V

Power consumption

2.5W @ nominal torque / 1W @ holding

For transformer sizing

4VA

Connecting cable

Cable 1m, 4x0.75mm2

Torque

2.5Nm @ nominal voltage

Direction of rotation

Selectable by mounting L/R

Angle of rotation

Max. 95, 37...100% adjustable by mechanical stops

Running time

Working conditions

Dimensions / weight

-motor
-spring return

150s
25s @ -20...+50C / max. 60s @ -30C

Sound power level -motor


-spring return

Max. 35dB(A)
Max. 62dB(A)

Position indicator

Mechanical

Protection class

III (safety extra-low voltage)

Degree of protection

IP42

EMC

CE according to 89/336/EEC

Mode of operation

Type 1.AA (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 84mm
Min. 20mm

Clamp up
Clamp down

Shaft

6...12mm

Weight

0.6kg

17

Dimensions [mm]

84

61

6...12

77

38.5

V5.1. 05.2013 Subject to modification

5.3

104

20

84

10

36

33

Mechanical Fail-Safe Damper Actuator TF24-SR

For operation of air control dampers that perform safety function


Torque:

2.5Nm

Nominal voltage:

AC/DC 24V

Control signal:

DC (0)2...10V

Position feedback:

DC 2...10V

Technical data
Electrical data

Functional data

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC 19.2...28.8V / DC 21.6...28.8V

Power consumption

2.5W @ nominal torque / 1W @ holding

For transformer sizing

4VA

Connecting cable

Cable 1m, 4x0.75mm2

Torque

2.5Nm @ nominal voltage

Control signal Y

DC (0)2...10V @ input impedance 100k

Position feedback signal U

DC 210V @ max. 0.5mA

Direction of rotation

Selectable by mounting L/R

Angle of rotation

Max. 95, 37...100% adjustable by mechanical stops

Running time

Working conditions

Dimensions / weight

-motor
-spring return

150s
25s @ -20...+50C / max. 60s @ -30C

Sound power level -motor


-spring return

Max. 35dB(A)
Max. 62dB(A)

Position indicator

Mechanical

Protection class

III (safety extra-low voltage)

Degree of protection

IP42

EMC

CE according to 89/336/EEC

Mode of operation

Type 1.AA (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 84mm
Min. 20mm

Clamp up
Clamp down

Shaft

6...12mm

Weight

0.6kg

17

Dimensions [mm]

84

61

6...12

20

34

84

36

10

V5.1. 05.2013 Subject to modification

38.5

77

5.3

104

Mechanical Fail-Safe Damper Actuator TF230(-S)

For operation of air control dampers that perform safety function


Torque:

2.5Nm

Nominal voltage:

AC 100...240V

Control:

Open/Close

Integrated auxiliary switch (TF230-S)

Technical data
Electrical data

Nominal voltage

AC 100...240V 50/60Hz

Nominal voltage range

AC 85...265V

Power consumption

2.5W @ nominal torque / 1.5W @ holding

For transformer sizing

5VA

Auxiliary switch (-S)

1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable

Connecting cable -motor


Cable 1m, 2x0.75mm2
-auxiliary switch (-S) Cable 1m, 3x0.75mm2

Functional data

Torque

2.5Nm @ nominal voltage

Direction of rotation

Selectable by mounting L/R

Angle of rotation

Max. 95, 37...100% adjustable by mechanical stops

Running time

Working conditions

Dimensions / weight

-motor
-spring return

75s
25s @ -20...+50C / max. 60s @ -30C

Sound power level -motor


-spring return

Max. 50dB(A)
Max. 62dB(A)

Position indicator

Mechanical

Protection class

II (Totally insulated)

Degree of protection

IP42

EMC
Low voltage directive

CE according to 89/336/EEC
CE according to 73/23/EEC

Mode of operation

Type 1.AA (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 84mm
Min. 20mm

Clamp up
Clamp down

Shaft

6...12mm

Weight

0.6kg

17

Dimensions [mm]

84

104

5.3

77

38.5

V5.1. 05.2013 Subject to modification

61

6...12

10
20

84

36

35

Mechanical Fail-Safe Damper Actuator LF24(-S)

For operation of air control dampers that perform safety function


Torque:

4Nm

Nominal voltage:

AC/DC 24V

Control:

Open/Close

Integrated auxiliary switch (LF24-S)

Technical data
Electrical data

Functional data

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC 19.2...28.8V / DC 21.6...28.8V

Power consumption

5W @ nominal torque / 2.5W @ holding

For transformer sizing

7VA

Auxiliary switch (-S)

1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable

Connecting cable -motor


-auxiliary switch (-S)

Cable 1m, 2x0.75mm2


Cable 1m, 3x0.75mm2

Torque

4Nm @ nominal voltage

Direction of rotation

Selectable by mounting L/R

Angle of rotation

Max. 95, 37...100% adjustable by mechanical stops

Running time

Working conditions

Dimensions / weight

-motor
-spring return

40...75s
20s @ -20...+50C / max. 60s @ -30C

Sound power level -motor


-spring return

Max. 50dB(A)
Max. 62dB(A)

Position indicator

Mechanical

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 2004/108/EC

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 84mm
Min. 20mm

Clamp up
Clamp down

Shaft

8...16mm

Weight

1.4kg

82

6.5

8...16

57

18.5

Dimensions [mm]

181
155

49

10

49

1
.8
.6
.4
.2

80

16.8
18

93
125

36

V5.1. 05.2013 Subject to modification

12.6

6.5

98

25

Mechanical Fail-Safe Damper Actuator LF24-3

For operation of air control dampers that perform safety function


Torque:

4Nm

Nominal voltage:

AC/DC 24V

Control:

3-point

Technical data
Electrical data

Functional data

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC 19.2...28.8V / DC 21.6...28.8V

Power consumption

2.5W @ nominal torque / 1W @ holding

For transformer sizing

5VA

Connecting cable

Cable 1m, 4x0.75mm2

Torque

4Nm @ nominal voltage

Direction of rotation

Selectable by mounting L/R

Angle of rotation

Max. 95, 37...100% adjustable by mechanical stops

Running time

Working conditions

Dimensions / weight

-motor
-spring return

150s
20s @ -20...+50C / max. 60s @ -30C

Sound power level -motor


-spring return

Max. 30dB(A)
Max. 62dB(A)

Position indicator

Mechanical

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 2004/108/EC

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 84mm
Min. 20mm

Clamp up
Clamp down

Shaft
Weight

8...16mm
1.4kg

10

V5.1. 05.2013 Subject to modification

49

Dimensions [mm]

16.8

37

Mechanical Fail-Safe Damper Actuator LF24-SR

For operation of air control dampers that perform safety function


Torque:

4Nm

Nominal voltage:

AC/DC 24V

Control signal:

DC (0)2...10V

Position feedback:

DC 2...10V

Technical data
Electrical data

Functional data

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC 19.2...28.8V / DC 21.6...28.8V

Power consumption

2.5W @ nominal torque / 1W @ holding

For transformer sizing

5VA

Connecting cable

Cable 1m, 4x0.75mm2

Torque

4Nm @ nominal voltage

Control signal Y

DC (0)2...10V @ input impedance 100k

Position feedback signal U

DC 210V @ max. 0.7mA

Direction of rotation

Selectable by L/R switch


Selectable by L/R mounting

Angle of rotation

Max. 95, 37...100% adjustable by mechanical stops

Running time

Working conditions

Dimensions / weight

-motor
-spring return

150s
20s @ -20...+50C / max. 60s @ -30C

Sound power level -motor


-spring return

Max. 30dB(A)
Max. 62dB(A)

Position indicator

Mechanical

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 2004/108/EC

Mode of operation

Type 1.AA (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 84mm
Min. 20mm

Clamp up
Clamp down

Shaft
Weight

8...16mm
1.4kg

16.8

38

V5.1. 05.2013 Subject to modification

10

49

Dimensions [mm]

Mechanical Fail-Safe Damper Actuator LF230(-S)

For operation of air control dampers that perform safety function


Torque:

4Nm

Nominal voltage:

AC 230V

Control:

Open/Close

Integrated auxiliary switch (LF230-S)

Technical data
Electrical data

Functional data

Nominal voltage

AC 230V 50/60Hz

Nominal voltage range

AC 198...264V

Power consumption

5W @ nominal torque / 3W @ holding

For transformer sizing

7VA

Auxiliary switch (-S)

1 SPDT, 1mA...3(0.5)A, AC 250V, adjustable

Connecting cable -motor


-auxiliary switch (-S)

Cable 1m, 2x0.75mm2


Cable 1m, 3x0.75mm2

Torque

4Nm @ nominal voltage

Direction of rotation

Selectable by mounting L/R

Angle of rotation

Max. 95, 37...100% adjustable by mechanical stops

Running time

Working conditions

Dimensions / weight

-motor
-spring return

40...75s
20s @ -20...+50C / max. 60s @ -30C

Sound power level -motor


-spring return

Max. 50dB(A)
Max. 62dB(A)

Position indicator

Mechanical

Protection class

II (Totally insulated)

Degree of protection

IP54

EMC
Low voltage directive

CE according to 2004/108/EC
CE according to 2006/95/EC

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Shaft length

Min. 84mm
Min. 20mm

Clamp up
Clamp down

Shaft

8...16mm

Weight

1.55kg

82

6.5

8...16

57

18.5

Dimensions [mm]

181

12.6

49

10

49

.2
0

.8
.6
.4

6.5

98

25

80

V5.1. 05.2013 Subject to modification

155

16.8
18

93
125

39

Mechanical Fail-Safe Damper Actuator NFU

Damper actuator for operating air control dampers in ventilation


and air-conditioning systems for building services installations
Torque:

10Nm

Nominal voltage:

AC 24...240V / DC 24...125V

Control:

Open/Close

Technical data
Electrical data

Functional data

Nominal voltage

AC 24...240V 50/60Hz, DC 24...125V

Nominal voltage range

AC 19.2...264V / DC 21.6...137.5V

Power consumption

6W @ nominal torque / 2.5W @ holding

For transformer sizing

6VA @ AC 24V; 6.5VA @ AC 120V; 9.5VA @ AC 240V

Connecting cable

Cable 1m, 2x0.75mm2

Torque

10Nm @ nominal voltage

Direction of rotation

Selectable by mounting L/R

Manual override

By manual override key

Angle of rotation
Running time

Working conditions

Dimensions / weight

Max. 95, adjustable by mechanical stops


-motor
-spring return

75s
20s @ -20...+50C / max. 60s @ -30C

Sound power level -motor


-spring return

Max. 45dB(A)
Max. 62dB(A)

Position indicator

Mechanical

Protection class

II (Totally insulated)

Degree of protection

IP54

EMC
Low voltage directive

CE according to 2004/108/EC
CE according to 2006/95/EC

Mode of operation

Type 1.AA (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Weight

2kg

Damper shaft

85

Standard :
- clamp (with insert)

59

20

Dimensions [mm]

Length
10
14...25.4

Length

49

80

19...25.4 12...18

19...25.4 12...18
Optional 2:
- clamp (optional via configuration)
Damper shaft

40

32

27
162

Length

172

10...19

14...20

182

10...19

14...20

236

V5.1. 05.2013 Subject to modification

Damper shaft

98

Optional 1:
1- clamp (without insert)

10

RONT
2-F

10...22

Mechanical Fail-Safe Damper Actuator NFU-S2

Damper actuator for operating air control dampers in ventilation


and air-conditioning systems for building services installations
Torque:

10Nm

Nominal voltage:

AC 24...240V / DC 24...125V

Control:

Open/Close

2xSPDT auxiliary switches

Technical data
Electrical data

Functional data

Nominal voltage

AC 24...240V 50/60Hz, DC 24...125V

Nominal voltage range

AC 19.2...264V / DC 21.6...137.5V

Power consumption

6W @ nominal torque / 2.5W @ holding

For transformer sizing

6VA @ AC 24V; 6.5VA @ AC 120V; 9.5VA @ AC 240V

Auxiliary switch (-S2)

2 SPDT, 1mA...3(0.5)A, AC 250V


one fixed at 10%, one adjustable 10...90%

Connecting cable -motor


-auxiliary switch (-S2)

Cable 1m, 2x0.75mm2


Cable 1m, 6x0.75mm2

Torque

10Nm @ nominal voltage

Direction of rotation

Selectable by mounting L/R

Manual override

By manual override key

Angle of rotation
Running time

Working conditions

Dimensions / weight

Max. 95, adjustable by mechanical stops


-motor
-spring return

75s
20s @ -20...+50C / max. 60s @ -30C

Sound power level -motor


-spring return

Max. 45dB(A)
Max. 62dB(A)

Position indicator

Mechanical

Protection class

II (Totally insulated)

Degree of protection

IP54

EMC
Low voltage directive

CE according to 2004/108/EC
CE according to 2006/95/EC

Mode of operation

Type 1.AA.B (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Weight

2.2kg

Damper shaft

85

Standard :
- clamp (with insert)

59

20

Dimensions [mm]

Length
10
14...25.4

Length

49

80

Damper shaft

98

Optional 1:
1- clamp (without insert)

V5.1. 05.2013 Subject to modification

19...25.4 12...18

19...25.4 12...18
Optional 2:
- clamp (optional via configuration)
Damper shaft

10

RONT
2-F

10...22

32

27
162

Length

172

10...19

14...20

182

10...19

14...20

236

41

Mechanical Fail-Safe Damper Actuator NFU24-SR


Damper actuator for operating air control dampers in ventilation
and air-conditioning systems for building services installations
Torque:

10Nm

Nominal voltage:

AC/DC 24V

Control signal:

DC (0)2...10V

Position feedback:

DC 2...10V

Technical data
Electrical data

Functional data

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC 19.2...28.8V / DC 21.6...28.8V

Power consumption

3.5W @ nominal torque / 2.5W @ holding

For transformer sizing

6VA

Connecting cable

Cable 1m, 4x0.75mm2

Torque

10Nm @ nominal voltage

Control signal Y

DC (0)2...10V @ input impedance 100k

Position feedback signal U

DC 210V @ max. 0.5mA

Position accuracy

5%

Direction of rotation

Reversible with switch


/
Selectable by mounting L/R

Manual override

By manual override key

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

Working conditions

Dimensions / weight

-motor
-spring return

150s
20s @ -20...+50C / max. 60s @ -30C

Sound power level -motor


-spring return

Max. 40dB(A)
Max. 62dB(A)

Position indicator

Mechanical

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 2004/108/EC

Mode of operation

Type 1.AA (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Weight

2kg

Damper shaft

85

Standard :
- clamp (with insert)

59

20

Dimensions [mm]

Length
10
14...25.4
49

19...25.4 12...18

19...25.4 12...18
Optional 2:
- clamp (optional via configuration)
Damper shaft

42

32

27
162

Length

172

10...19

14...20

182

10...19

14...20

236

V5.1. 05.2013 Subject to modification

Length

80

Damper shaft

98

Optional 1:
1- clamp (without insert)

10

RONT
2-F

10...22

Mechanical Fail-Safe Damper Actuator SFU

Damper actuator for operating air control dampers in ventilation


and air-conditioning systems for building services installations
Torque:

20Nm

Nominal voltage:

AC 24...240V / DC 24...125V

Control:

Open/Close

Technical data
Electrical data

Functional data

Nominal voltage

AC 24...240V 50/60Hz, DC 24...125V

Nominal voltage range

AC 19.2...264V / DC 21.6...137.5V

Power consumption

7W @ nominal torque / 3.5W @ holding

For transformer sizing

7VA @ AC 24V; 8.5VA @ AC 120V; 18VA @ AC 240V

Connecting cable

Cable 1m, 2x0.75mm2

Torque

20Nm @ nominal voltage

Direction of rotation

Selectable by mounting L/R

Manual override

By manual override key

Angle of rotation
Running time

Working conditions

Dimensions / weight

Max. 95, adjustable by mechanical stops


-motor
-spring return

75s
20s @ -20...+50C / max. 60s @ -30C

Sound power level -motor


-spring return

Max. 45dB(A)
Max. 62dB(A)

Position indicator

Mechanical

Protection class

II (Totally insulated)

Degree of protection

IP54

EMC
Low voltage directive

CE according to 2004/108/EC
CE according to 2006/95/EC

Mode of operation

Type 1.AA (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Weight

2.2kg

Damper shaft

85

Standard :
- clamp (with insert)

59

20

Dimensions [mm]

Length
10
14...25.4

Length

49

80

Damper shaft

98

Optional 1:
1- clamp (without insert)
19...25.4 12...18

19...25.4 12...18

V5.1. 05.2013 Subject to modification

Optional 2:
- clamp (optional via configuration)
Damper shaft

10

RONT
2-F

10...22

32

27
162

Length

172

10...19

14...20

182

10...19

14...20

236

43

Mechanical Fail-Safe Damper Actuator SFU-S2

Damper actuator for operating air control dampers in ventilation


and air-conditioning systems for building services installations
Torque:

20Nm

Nominal voltage:

AC 24...240V / DC 24...125V

Control:

Open/Close

2xSPDT auxiliary switches

Technical data
Electrical data

Functional data

Nominal voltage

AC 24...240V 50/60Hz, DC 24...125V

Nominal voltage range

AC 19.2...264V / DC 21.6...137.5V

Power consumption

7W @ nominal torque / 3.5W @ holding

For transformer sizing

7VA @ AC 24V; 8.5VA @ AC 120V; 18VA @ AC 240V

Auxiliary switch (-S2)

2 SPDT, 1mA...3(0.5)A, AC 250V


one fixed at 10%, one adjustable 10...90%

Connecting cable-motor
-auxiliary switch (-S2)

Cable 1m, 2x0.75mm2


Cable 1m, 6x0.75mm2

Torque

20Nm @ nominal voltage

Direction of rotation

Selectable by mounting L/R

Manual override

By manual override key

Angle of rotation
Running time

Working conditions

Dimensions / weight

Max. 95, adjustable by mechanical stops


-motor
-spring return

75s
20s @ -20...+50C / max. 60s @ -30C

Sound power level -motor


-spring return

Max. 45dB(A)
Max. 62dB(A)

Position indicator

Mechanical

Protection class

II (Totally insulated)

Degree of protection

IP54

EMC
Low voltage directive

CE according to 2004/108/EC
CE according to 2006/95/EC

Mode of operation

Type 1.AA.B (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Weight

2.4kg

Damper shaft

85

Standard :
- clamp (with insert)

59

20

Dimensions [mm]

Length
10
14...25.4
49

19...25.4 12...18

19...25.4 12...18
Optional 2:
- clamp (optional via configuration)
Damper shaft

44

32

27
162

Length

172

10...19

14...20

182

10...19

14...20

236

V5.1. 05.2013 Subject to modification

Length

80

Damper shaft

98

Optional 1:
1- clamp (without insert)

10

RONT
2-F

10...22

Mechanical Fail-Safe Damper Actuator SFU24-SR

Damper actuator for operating air control dampers in ventilation


and air-conditioning systems for building services installations
Torque:

20Nm

Nominal voltage:

AC/DC 24V

Control signal:

DC (0)2...10V

Position feedback

DC 2...10V

Technical data
Electrical data

Functional data

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC 19.2...28.8V / DC 21.6...28.8V

Power consumption

5W @ nominal torque / 3.5W @ holding

For transformer sizing

7VA

Connecting cable

Cable 1m, 4x0.75mm2

Torque

20Nm @ nominal voltage

Control signal Y

DC (0)2...10V @ input impedance 100k

Position feedback signal U

DC 2...10V @ max. 0.5mA

Position accuracy

5%

Direction of rotation

Reversible with switch


/
Selectable by mounting L/R

Manual override

By manual override key

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

Working conditions

Dimensions / weight

-motor
-spring return

75s
20s @ -20...+50C / max. 60s @ -30C

Sound power level -motor


-spring return

Max. 40dB(A)
Max. 62dB(A)

Position indicator

Mechanical

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 2004/108/EC

Mode of operation

Type 1.AA (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Weight

2.2kg

Damper shaft

85

Standard :
- clamp (with insert)

59

20

Dimensions [mm]

Length
10
14...25.4

V5.1. 05.2013 Subject to modification

Length

49

80

Damper shaft

98

Optional 1:
1- clamp (without insert)
19...25.4 12...18

19...25.4 12...18
Optional 2:
- clamp (optional via configuration)
Damper shaft

10

RONT
2-F

10...22

32

27
162

Length

172

10...19

14...20

182

10...19

14...20

236

45

Mechanical Fail-Safe Damper Actuator EFU24-S2


Mechanical Fail-Safe Actuator with emergency function for
adjusting air dampers in ventilation and air conditioning
systems in buildings.
Torque:

30Nm

Nominal voltage:

AC/DC 24V

Control:

Open/Close

2xSPDT auxiliary switches

Technical data
Electrical data

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC 19.2...28.8V / DC 21.6...28.8V

Power consumption

9.5W @ nominal torque / 4.5W @ holding

For transformer sizing

16VA

Auxiliary switch (-S2)

2xSPDT, 1mA...3(0.5)A, AC 250V


one fixed at 10%, one adjustable 10...90%

Connecting cable-motor
-auxiliary switch

Functional data

Dimensions / weight

Cable 1m, 6x0.75mm2

Torque

30Nm @ nominal voltage

Position accuracy

5%

Direction of rotation

Selectable by mounting L/R

Manual override

With hand crank and interlocking switch

Angle of rotation

Max. 95, can be limited with adjustable mechanical end stops

Running time

Working conditions

Cable 1m, 2x0.75mm2

-motor
-spring return

60s
20s @ 20 ...+50C / max. 60s @ 30C

Sound power level -motor


-spring return

Max. 55dB(A)
Max. 71dB(A)

Position indicator

Mechanical

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 2004/108/EC

Mode of operation

Type 1.AA.B (EN60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Weight

4.5kg

Length

22 ... 26.7 mm

12 ... 18 mm

35
50

35

143
188
238
272
322

46

V5.1. 05.2013 Subject to modification

12 ... 18 mm
112

12 ... 22 mm

138

13.5

12 ... 26.7 >12 < 25.2


12 ... 26.7 >12 < 25.2

120.5

Damper spindle

80

27

Dimensions [mm]

Mechanical Fail-Safe Damper Actuator EFU24-SR


Mechanical Fail-Safe Actuator with emergency function for
adjusting air dampers in ventilation and air conditioning
systems in buildings.
Torque:

30Nm

Nominal voltage:

AC/DC 24V

Control signal:

DC (0)2...10V

Position feedback signal:

DC 2...10V

Technical data
Electrical data

Functional data

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC 19.2...28.8V / DC 21.6...28.8V

Power consumption

7W @ nominal torque / 4.5W @ holding

For transformer sizing

12VA

Connecting cable

Cable 1m, 4x0.75mm2

Torque

30Nm @ nominal voltage

Control signal Y

DC (0)2...10V @ input impedance 100k

Position feedback signal U

DC 2...10V @ max. 0.5mA

Position accuracy

5%

Direction of rotation

Reversible with switch


/
selectable by mounting L / R

Manual override

With hand crank and interlocking switch

Angle of rotation

Max. 95, can be limited with adjustable mechanical end stops

Running time

Working conditions

Dimensions / weight

-motor
-spring return

150s
20s @ 20 ...+50C / max. 60s @ 30C

Sound power level -motor


-spring return

Max. 45dB(A) @ 150s running time


Max. 71dB(A)

Position indicator

Mechanical

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 2004/108/EC

Mode of operation

Type 1.AA (EN60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Weight

4.3kg

Length

12 ... 18 mm

22 ... 26.7 mm

12 ... 18 mm

138

12 ... 22 mm

112

V5.1. 05.2013 Subject to modification

13.5

12 ... 26.7 >12 < 25.2


12 ... 26.7 >12 < 25.2

120.5

Damper spindle

80

27

Dimensions [mm]

35
50

35

143
188
238
272
322

47

Mechanical Fail-Safe Damper Actuator EFU230-S2


Mechanical Fail-Safe Actuator with emergency function for
adjusting air dampers in ventilation and air conditioning
systems in buildings.
Torque:

30Nm

Nominal voltage:

AC 230V

Control:

Open/Close

2xSPDT auxiliary switches

Technical data
Electrical data

Nominal voltage

AC 230V 50/60Hz

Nominal voltage range

AC 198...264V

Power consumption

9.5W @ nominal torque / 4.5W @ holding

For transformer sizing

22VA

Auxiliary switch (-S2)

2xSPDT, 1mA...3(0.5)A, AC 250V


one fixed at 10%, one adjustable 10...90%

Connecting cable -motor


-auxiliary switch

Functional data

Dimensions / weight

Cable 1m, 6x0.75mm2

Torque

30Nm @ nominal voltage

Position accuracy

5%

Direction of rotation

Selectable by mounting L/R

Manual override

With hand crank and interlocking switch

Angle of rotation

Max. 95, can be limited with adjustable mechanical end stops

Running time

Working conditions

Cable 1m, 2x0.75mm2

-motor
-spring return

60s
20s @ 20 ...+50C / max. 60s @ 30C

Sound power level -motor


-spring return

Max. 55dB(A)
Max. 71dB(A)

Position indicator

Mechanical

Protection class

II (Totally insulated)

Degree of protection

IP54

EMC
Low voltage directive

CE according to 2004/108/EC
CE according to 2006/95/EC

Mode of operation

Type 1.AA.B (EN60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Weight

4.5kg

Dimensions [mm]

22 ... 26.7 mm

12 ... 18 mm

35
50

35

143
188
238
272
322

48

V5.1. 05.2013 Subject to modification

12 ... 18 mm

112

12 ... 22 mm

138

13.5

12 ... 26.7 >12 < 25.2


12 ... 26.7 >12 < 25.2

120.5

27

Length

80

Damper spindle

Electronic Fail-Safe Damper Actuator GKU24

Parameterisable damper actuator with capacitor technology


for adjusting air dampers with emergency control function and
extended functionalities in ventilation and air-conditioning systems
for building services installations and in laboratories.
Torque:

40Nm

Nominal voltage:

AC/DC 24V

Control:

Open/Close

Technical data
Electrical data

Functional data

Working conditions

Dimensions / weight

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC 19.2...28.8V / DC 21.6...28.8V

Power consumption

12W @ nominal torque / 3W @ holding

For transformer sizing

21VA

Connecting cable

Cable 1m, 2x0.75mm2

Torque

40Nm @ nominal voltage

Emergency setting position (POP)

0...100% adjustable

Bridging time (PF)

2s

Position accuarcy

5%

Direction of rotation -motor


-POP

As an option with
/
Reversible with switch 0 ... 100%

Manual override

Gearing latch disengaged by push button

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

-standard
-POP

150s
35s @ 0...+50C

Sound power level

-standard
-POP

Max. 52dB(A) @ 150s running time


Max. 61dB(A)

Position indicator

Mechanical

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 2004/108/EC

Certification

Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14

Mode of operation

Type 1.AA (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

See Dimensions

Weight

1.8kg

Dimensions [mm]
Damper spindle

12 ... 26.7 >12 < 25.5


12 ... 26.7 >12 < 25.5

179

12 ... 22 mm

12 ... 18 mm

22 ... 26.7 mm

12 ... 18 mm

99

116

V5.1. 05.2013 Subject to modification

60

87

210

Length

36

174

49

Electronic Fail-Safe Damper Actuator GKU24-MF


Parameterisable damper actuator with capacitor technology
for adjusting air dampers with emergency control function and
extended functionalities in ventilation and air-conditioning systems
for building services installations and in laboratories.
Torque:

40Nm

Nominal voltage:

AC/DC 24V

Control:

DC (0)2...10V

Position feedback signal U:

DC (0)2...10V

Technical data

Functional data

Nominal voltage

AC 24V 50/60Hz, DC 24V

Nominal voltage range

AC 19.2...28.8V / DC 21.6...28.8V

Power consumption

12W @ nominal torque / 3W @ holding

For transformer sizing

21VA (Imax 20A @ 5ms)

Connecting cable

Cable 1m, 5x0.75mm2

Torque

40Nm @ nominal voltage

Control signal Y

DC (0)2...10V @ input impedance 100k

Position feedback signal U

DC 2...10V @ max. 0.5mA

Emergency setting position (POP)

0...100% adjustable

Bridging time (PF)

1...10s adjustable (factory setting 2s)

Position accuarcy

5%

Direction of rotation -motor


-POP
-Y=0V

As an option with
/
Reversible with switch 0 ... 100%
At switch position 1
or 0
, respectively

Manual override

Gearing latch disengaged by push button

Angle of rotation

Max. 95, adjustable by mechanical stops

Running time

-standard
-POP

Automatic adjustment of
running time, operating range
and measuring signal U to
match the mechanical angle of
rotation

Manual triggering of the adaption by pressing the


Adaption button

Override control

MAX (maximum position)


= 100%
MIN (minimum position)
= 0%
ZS (intermediate position, only AC) = 50%

Sound power level

-standard
-POP

Working conditions

Dimensions / weight

50

90...150s adjustable (factory setting 150s/90)


35s @ 0...+50C

MAX = (MIN + 32%)...100%


MIN = 0%...(MAX 32%)
ZS = MIN...MAX

Max. 53dB(A) @ 90s running time


Max. 52dB(A) @ 150s running time
Max. 61dB(A)

Position indicator

Mechanical

Protection class

III (safety extra-low voltage)

Degree of protection

IP54

EMC

CE according to 2004/108/EC

Certification

Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14

Mode of operation

Type 1.AA (EN 60730-1)

Ambient temp.
Non-operation temp.

-30...+50C
-40...+80C

Humidity

5...95% RH, non-condensing

Maintenance

Maintenance-free

Dimensions (LxWxH)

210x116x87mm (same dimensions as GKU24)

Weight

1.8kg

V5.1. 05.2013 Subject to modification

Electrical data

CMU.. Mounting instructions

1
>32
m

3
2.5

5
10

60

90
45

30

12

15

6 ... 12.7 mm

75
90

15

0
12

2.5
30

45

60

75 9
0

10
5

70 20 mm

75

60 45 30

12
0

10
5

90

60 45 30

10
5

75

12
0

12

90 1
05

90

75

3.1 ... 3.2 mm

60 45 30

12
0

10
5

90

90 1
05

2
90 1
05

12
0

12
0

4
8
75

60 45 30

90
10
5

60 45 30

12
0

75

6 Nm

90 10
5

12

10
5

90

12
0

90 10
5

12
0

120 60

15

0
12

30

45

60

75 90

10
5

90

75 60

45

30
15

12
0

5
10

12
0

15

0
12

75

90

5
10

75

90

30

45

60

75 9
0

10
5

5
10

60

45

30
15

90

75 60

45

30
15

12
0

5
10

10
5
0
12

60

75 9
0

10
5

12

45

10
5

60 45 30

90

30

60 45 30

15

0
12

75
75
90

12
0
0

ma
90

75 60

45

30

15

12
0

5
10

5
.9

CMU24-SR..

90 10
5

30 mm

30

45

60

75 9
0

10
5

m
m

V5.1. 05.2013 Subject to modification

15

0
12

33

A
24V

230 V

1
51

LMU../LMS.. Mounting instructions

2
> 37

6 ... 20

>6

< 20

10

6 Nm

1m m

1
2

52

Z-PI
V5.1. 05.2013 Subject to modification

65

NMU../NMS.. Mounting Instructions

40

8 ... 26.7

>8

< 26.7

10

10

1
9 Nm

1mm

2
V5.1. 05.2013 Subject to modification

Z-PI

65

53

SMU../SMDU../SMS.. Mounting instructions

48

CrNi (INOX)

10 ... 20

10

20

12 ... 20

10

20

10

10

1
9 Nm
CrNi(INOX)15 Nm

1 mm

1
2

5
1

1
2

65
1
2
3

54

4
5

V5.1. 05.2013 Subject to modification

Z-PI

GMU../GMS.. Mounting instructions

2
1

>52

12 ... 22 mm

12 ... 18 mm

4
2
12 ... 18 mm

13

22 ... 26.7 mm

15 Nm
CrNi (INOX) 25 Nm

1m m
1

2
1

V5.1. 05.2013 Subject to modification

2
Z-PI

>20

1
2

65

55

LMQU../NMQU.. Mounting instructions

"

"
"
-.26









/.26
















 /N


NN






56

V5.1. 05.2013 Subject to modification

;1*

SMQU.. Mounting instructions



NN

NN


NN




NN


15 Nm
CrNi (INOX) 25 Nm


NN







V5.1. 05.2013 Subject to modification

;1*






57

TF.. Mounting instructions

min
. 84

6...12.7mm

37...100%
R

!
max. 1 Nm

58

V5.1. 05.2013 Subject to modification

ZG-TF1

TF../LF.. Mounting instructions

ZDB-TF

L
min
. 20

6...12.7mm

37...100%
R

ZDB-TF

8...16

.6

.6

. 84

.8

1
.8

.8

min

.2

Mad

Made

e in

erlan
Switz

.4

0
L

.6

00%
7...1

.4

.4
.2

.2

d
erlan
in Switz

L
Made

V5.1. 05.2013 Subject to modification

8...16

min

in Sw

and
itzerl

1
.8

. 20

1
.8

.8

.6

.6

.4

.4
.2

.2

Made

Mad

e in

0
L

d
erlan
in Switz

d
erlan
Switz

00%
7...1

.6
.4
.2

ZDB-LF

0
L

ZDB-LF

in
Made

d
erlan
Switz

ZDB-LF

59

NFU../SFU.. Mounting instructions

10...22

19...25.4

min

. 85

10...22

min

. 15

19...25.4

10
10 Nm

33 ... 100%
.2

.8

.4

.3

.2 .1

V5.1. 05.2013 Subject to modification

.5

60

.4
.6

.9
.8
.7
.6

EFU.. Mounting instructions

12 ... 22 mm

117 m
m

12 ... 18 mm

20 m

22 ... 26.7 mm

12 ... 18 mm

12 ... 22 mm

12 ... 18 mm

22 ... 26.7 mm

12 ... 18 mm

< 26.7 mm
< 20 mm
< 16 mm

0
.1
.2

.3
.4

.9
.5

.6

.7

.8

0
.1
.2

.3
.4

0=Y

0=Y

.6

.7

.8

< 26.7 mm
< 20 mm
< 16 mm

V5.1. 05.2013 Subject to modification

.9
.5

0=Y

0=Y

61

EFU.. Mounting instructions

40 ... 100%

.9

.8

.7

.6

13
15 Nm
Y=0

Y=0

12 m
m

25 Nm

Y=0

62

Y=0

V5.1. 05.2013 Subject to modification

IN

GKU.. Mounting instructions




NN

NN

NN

NN

NN









 /N

$S/J */09
/N


 NN


V5.1. 05.2013 Subject to modification



;1M


63

GKU.. Mounting instructions





NN


64

V5.1. 05.2013 Subject to modification

Wiring diagrams-General Damper Actuator

Wiring diagrams: CMU.. series actuators


Notes:
Parallel connection of several actuators is possible.
Power consumption must be observed.

Open/Close control
~

Connection via safety


isolated transformer

AC 24V
+ DC 24V

3-point control
AC 24V
+ DC 24V

Connection via safety


isolated transformer

CMU24(-T)
CMU24-F8(-F10)

CMU24(-T)
CMU24-F8(-F10)

Modulating control
~

AC 24V
+ DC 24V

Connection via safety


isolated transformer

!
Y

DC (0)2...10V

DC 2...10V

CMU24-SR-R

3-point control

Open/Close control
N

L AC 100...240V

L AC 100...240V

V5.1. 05.2013 Subject to modification

CMU230
CMU230-F8(-F10)

CMU230
CMU230-F8(-F10)

65

Wiring diagrams-General Damper Actuator

Wiring diagrams: Open/Close actuatorsparallel connection possible, please note the performance data.

AC 24V
DC 24V

2-wire control
Connection via safety
isolated transformer

1-wire control

AC 24V
DC 24V

Connection via safety


isolated transformer

Direction of rotation
0

(while

direction of rotation reverses)


1

S1 S2 S3

S1 S2 S3

Direction of rotation
1

(while

direction of rotation reverses)


1

S1 S2 S3

LMU24-S, NMU24-S
SMU24-S

0...100%

S1 S2 S3

S1 S2 S3

S1 S2 S3

LMU24-S, NMU24-S
SMU24-S

0...100%

LMU24(-T/-F), NMU24(-T), SMU24


GMU24, LMQU24, NMQU24, SMQU24

LMU24(-T/-F), NMU24(-T)
SMU24, GMU24*
L AC 100...240V

AC 100...240V

0
1

S1 S2 S3

S1 S2 S3

1
S1 S2 S3

S1 S2 S3

LMU230-S, NMU230-S
SMU230-S

0...100%

0...100%

S1 S2 S3

S1 S2 S3

LMU230-S, NMU230-S
SMU230-S

LMU230(-F), NMU230(-F)
SMU230(-F), SMDU230, GMU230*

LMU230(-F), NMU230
SMU230(-F), SMDU230, GMU230

*GMU.. only for Open/Close application.

Wiring diagram: Modulating actuatorsparallel connection possible, please note the performance data.
Position - signal voltage
+

AC 24V
DC 24V

T
1

Connection via safety


isolated transformer

% of 95

DC (0)2...10V

DC 2...10V

100

Open

50

LM(Q)U24-SR, NM(Q)U24-SR
SM(Q)U24-SR, GMU24-SR

Closed

0
0

Y
10 [ V ]

Closed

clockwiseclosing
damper

66

Open

Direction of rotation
1

Y
U
2

anti-clockwise
-closing
damper

Reversing
switch 1
Y=0

AC 100...240V
AC 24V power output

Reversing
switch 0
Y=0

DC (0)2...10V
DC 2...10V

LMU230SR, NMU230SR
SMU230SR

V5.1. 05.2013 Subject to modification

Wiring diagrams-Mechanical Fail-Safe Damper Actuator

Wiring diagrams: Open/Close actuators


Notes:
Parallel connection of several actuators is possible.
Power consumption must be observed.
N

AC 100...240V (for TF230..)

AC/DC 24V

S1 S2 S3

<x

>x

x = 0...100%

AC 230V (for LF230..)


AC/DC 24V

<x
>x

x = 0...100%

AC 24...240V

DC 24...125V

LF230-S, LF24-S

10%...90% adjustable

10%

NFU-S2, SFU-S2

NFU, SFU

AC 230V (for EFU230-S2)

AC/DC 24V

Connection via safety


isolated transformer

S1 S2 S3 S4 S5 S6

Connection via safety


isolated transformer

LF230, LF24

V5.1. 05.2013 Subject to modification

S1 S2 S3

TF230-S, TF24-S

TF230, TF24

Connection via safety


isolated transformer

Connection via safety


isolated transformer

S1 S2 S3 S4 S5 S6

10%

10%...90% adjustable EFU24-S2, EFU230-S2

67

Wiring diagrams-Mechanical Fail-Safe Damper Actuator

Wiring diagram: 3-point actuators


Notes:
Connection via safety isolating transformer.
Parallel connection of several actuators is possible.
Power consumption must be observed.
Mounting side
1

AC 24V

.8

.8

Connection via safety


isolated transformer

.6

.6
.4

.4
.2

.2
0

Reversing switch

a
(Y 1 )

Y1

Y2

b
(Y 2 )

stop

stop

stop

stop

TF24-3

Mounting side
1

AC 24V
+ DC 24V

Connection via safety


isolated transformer

.8

.8

.6

.6
.4

.4
.2

.2
0

Reversing switch

Y1

Y2

68

b
(Y 2 )

stop

stop

stop

stop

LF24-3

V5.1. 05.2013 Subject to modification

a
(Y 1 )

Wiring diagrams-Mechanical Fail-Safe Damper Actuator

Wiring diagram: modulating actuators


Notes:
Connection via safety isolating transformer.
Parallel connection of several actuators is possible.
Power consumption must be observed.

Mounting side

AC 24V
+ DC 24V

Connection via safety


isolated transformer

.8

.8

.6

.6

.4

.4

DC (0)2...10V

U
1

.2

.2

DC 2...10V

Reversing switch

5
with
Y=0

with
Y=0

with
Y=0

with
Y=0

TF24-SR

Mounting side

AC 24V
+ DC 24V

Connection via safety


isolated transformer

.8

.8

.6

.6

.4

.4

DC (0)2...10V

U
1

.2

.2

DC 2...10V

AC 24V
+ DC 24V

Reversing switch

with
Y=0

with
Y=0

with
Y=0

with
Y=0

LF24-SR

Connection via safety


isolated transformer

Mounting side
1

.8

.8

DC (0)2...10V

.6

.6
.4

.4

DC 2...10V

.2

.2

Reversing switch

V5.1. 05.2013 Subject to modification

NFU24-SR, SFU24-SR
EFU24-SR

with
Y=0

with
Y=0

with
Y=0

with
Y=0

69

Wiring diagrams-Electronic Fail-Safe Damper Actuator

Wiring diagram: Open/Close actuators


~

AC 24V
+ DC 24V

Connection via safety


isolated transformer

GKU24

Wiring diagram: -MF

Y1

Connection via safety


isolated transformer

DC (0)2...10V

DC 2...10V

GKU24-MF

O p e n / C l o s e c o nt r o l
~

AC 24V
+ DC 24V

3 - p oi n t c o nt r ol

Connection via safety


isolated transformer

AC 24V
+ DC 24V

Y1

70

DC 2...10V

GKU24-MF

U
1

Reversing switch

Connection via safety


isolated transformer

Y1

Y2

DC 2...10V

a
(Y 1 )

b
(Y 2 )

stop

stop

GKU24-MF

V5.1. 05.2013 Subject to modification

T
1

AC 24V
+ DC 24V

Auxiliary switch adjustment

Auxiliary switch adjustment for General Damper Actuators


1. Press the pushbutton, manually operate the universal clamp to
desired switch position.

S2 S3

S2 S3

2. Turn switch pointer to the middle line.

S1

3. When actuator moves clockwise (counter clockwise) to switch


position, switch indicator passes the middle line counter clockwise
(clockwise), the contact between S1 and S3 is disconnected
(connected) and the contact between S1 and S2 is connected
(disconnected).

S1

2
1

Note: The switching point should be about 5 from the mechanical


end stops (1 short step on the scale).

Auxiliary switch adjustment for Mechanical Fail-Safe Damper Actuators


LF..-S (Mounting side R); NFU-S2, SFU-S2, EFU..-S2 (Mounting side L)
Starting point: Actuator in safe position
Procedure
Turn the knob of the auxiliary switch until the
tip of the arrow is pointing to the required
switching position (see right). Example:
Switching point setting = 4 corresponds to
40% angle of rotation.
When the actuator runs to the operating
position (ccw
), the switch knob will also
rotate counter-clockwise (ccw
) and the
auxiliary switch will operate as the tip of the
arrow passes the scale zero (S1S3 linked).

1
1

.8

.8
.6
.4

.6

.2

.4

0
S2

S2
S1

.2
0

S3

S1

S3

V5.1. 05.2013 Subject to modification

Fast Running Q.. Actuators operating controls and indicators

71

Electrical accessories

Actuators
CMU

LMU

NMU

SMU

GMU

TF

LF

NFU

SFU

EFU

GKU

S..A..

Auxiliary switch, add on


S1A
1xSPDT 3A(0.5A), AC 250V
S2A
2xSPDT 3A(0.5A), AC 250V
S2A -F 2xSPDT 3A(0.5A), AC 250V

P..A..

Feedback potentiometer, add on


P140A..
140
P500A..
500
P1000A..
1000
P2800A..
2800
P5000A..
5000
P10000A..
10000
P200A-F
200

SGA24

Positioner for surface mounting


0...100%
Reversible operating range DC 0...10V
or DC 2...10V

1)

1)

1)

1)

1)

1)

1)

1)

1)

1)

2)

SGE24

Positioner for rack mounting


0...100%
Reversible operating range DC 0...10V
or DC 2...10V

1)

1)

1)

1)

1)

1)

1)

1)

1)

1)

2)

SGF24

Positioner for front-panel mounting


0...100%
Reversible operating range DC 0...10V
or DC 2...10V

1)

1)

1)

1)

1)

1)

1)

1)

1)

1)

2)

ZDA24

Digital position indicator for front-panel mounting


0...99%
Front size 72x72mm
Operating range DC 2...10V

1)

1)

1)

1)

1)

1)

1)

1)

1)

1)

2)

1) For ..-SR

72

V5.1. 05.2013 Subject to modification

2) For ..-MF

Mechanical accessories

Actuators
LMU
AN-20

Actuator arm

AH-25

Actuator arm

AH-GMA

Actuator arm

AV6-20

Shaft extension
Length approximately 170mm
For damper spindles 6...20mm
Extension 10mm

AV8-25

Shaft extension
Length approximately 250mm
For damper spindles 8...25mm
Extension 20mm

IND-AFB

NFU/SFU.. position indicator

K6-1

Spindle clamp for LF..


For damper spindles 16...20mm

K7-2

NFU/SFU.. standard clamp


1/2, 3/4, 1.05

K-ENSA

Spindle clamp
For damper spindles 8...20mm

K-NA

Reversible spindle clamp


For damper spindles 8...20mm

NMU
LMQU
NMQU

SMU
SMDU

GMU
SMQU

TF

LF

NFU

SFU

(except
NMQU)
K-SA

Reversible spindle clamp


For damper spindles 10...20mm

V5.1. 05.2013 Subject to modification

(NMQU)
KG8

Ball joint
Suitable for damper crank arm KH8
For round steel rod with 8mm
Zinc-plated steel

KG10A

Ball joint
Suitable for damper crank arm KH8
For round steel rod with 10mm
Zinc-plated steel

73

Mechanical accessories

Actuators

ZG-118

NFU/SFU.. mounting bracket

ZG-AFB

NFU/SFU.. crank arm adapter kit

ZG-AFB118

NFU/SFU.. crank arm adapter kit

ZG-GMA

Mounting kit
For flat and side mounting

ZG-LF1

Damper linkage kit


For side mounting (with 2 ball joint KG8)

ZG-LF3

Damper linkage kit


For side mounting (with 2 ball joint KG8)

ZG-NMA

Mounting kit
For flat and side mounting

ZG-SMA

Mounting kit
For flat and side mounting

ZG-TF1

Damper linkage
For flat mounting

Z-AF

Retrofit adapter for NG NFU/SFU.. while


replacing old NF/AF/AFR

ZF10-NSA-F

10x10 formfit adapter


multpack 20 pieces

ZF12-NSA-F

12x12 formfit adapter


mutipack 20 pieces

ZF16-NSA-F

16x16 formfit adapter


mutipack 20 pieces

74

NMU
LMQU
NMQU

SMU
SMDU

GMU
SMQU

TF

LF

NFU

SFU

V5.1. 05.2013 Subject to modification

LMU

Replacement table for Mechanical Fail-Safe Damper Actuators

Series

Old models

New Generation

Description

NFU..

NF24

NFU

Open/Close 10Nm

NF230
NF24-S

Open/Close 10Nm
NFU-S2

Open/Close 10Nm, 2xSPDT auxiliary switch

NF24-SR

NFU24-SR

Modulating 10Nm

AF24

SFU

Open/Close 20Nm

NF230-S

SFU..

Open/Close 10Nm, 2xSPDT auxiliary switch

AFR24

Open/Close 20Nm

AF230

Open/Close 20Nm

AFR230
AF24-S

Open/Close 20Nm
SFU-S2

AFR24-S

Open/Close 20Nm, 2xSPDT auxiliary switch

AF230-S

Open/Close 20Nm, 2xSPDT auxiliary switch

AFR230-S
AF24-SR
AFR24-SR

V5.1. 05.2013 Subject to modification

Open/Close 20Nm, 2xSPDT auxiliary switch

Open/Close 20Nm, 2xSPDT auxiliary switch


SFU24-SR

Modulating 20Nm
Modulating 20Nm

75

76

77

78

Markets Asia Pacific


ASIA PACIFIC HEADQUARTERS
Belimo Actuators Ltd.
Room 207, 2/F, New Commerce Center
19 On Sum Street, Shatin, N.T.
Hong Kong
Tel:
+852 2687 1716
Fax: +852 2687 1795
E-mail: info.asiapacific@belimo.ch

Belimo AUSTRALIA
Melbourne Office:
Belimo Actuators Pty. Ltd.
12 Enterprise Court
Mulgrave Business Park
Mulgrave, VIC 3170, Australia
Tel:
+61 (0)3 9545 0844
Fax: +61 (0)3 9545 0855
E-mail: info.australia@belimo.ch
Sydney Office:
Belimo Actuators Pty. Ltd.
Suite 2.20, 32 Delhi Road
North Ryde, NSW 2113, Australia
Tel:
+61 (0)2 9805 1777
Fax: +61 (0)2 9805 1722
E-mail: info.australia@belimo.ch

Belimo CHINA
Shanghai Office:
Belimo Actuators (Shanghai) Trading Ltd.
479 Chun Dong Road, Building C-2
Xin Zhuang Industry Park
Shanghai 201108
P.R. China
Tel:
+86 21 5483 2929
Fax: +86 21 5483 2930
E-mail: info.shanghai@belimo.ch
Beijing Office:
Belimo Actuators Ltd.
Room 605, Hai Chang Edifice
44 Liang Ma Qiao Road
Beijing 100016
P.R. China
Tel:
+86 10 6462 1382
Fax: +86 10 6462 1383
E-mail: info.beijing@belimo.ch
Chongqing Office:
Belimo Actuators Ltd.
Room 4, 9th floor, Unit 7, Luoma Jiari Gardan
No. 36, Qing Ling Road, Nan'an District
Chongqing 400060
P.R. China
Tel:
+86 23 6275 3155
Fax: +86 23 6280 3380 *519
E-mail: info.chongqing@belimo.ch
Guangzhou Office:
Belimo Actuators Ltd.
Room 1202, Skyline Plaza
644 Tong Fu East Road, Haizhu Area
Guangzhou 510240
P.R. China
Tel:
+86 20 3435 1860
Fax: +86 20 3435 1870
E-mail: info.guangzhou@belimo.ch

Belimo HONG KONG


Hong Kong Office:
Belimo Actuators Ltd.
Room 207, 2/F, New Commerce Center
19 On Sum Street, Shatin, N.T.
Hong Kong
Tel:
+852 2687 1716
Fax: +852 2687 1795
E-mail: info.hongkong@belimo.ch

Japan Office:
Belimo Actuators Ltd.
7th Floor, Honjo-Azumabashi DJ Building
4-19-3, Honjo, Sumida-ku
Tokyo 130-0004 Japan
Tel:
+81-3-6823-6961
Fax: +81-3-3626-3911
E-mail: info.japan@belimo.ch
Malaysia Office:
Belimo Actuators Ltd.
12-1, Jalan PJS 10/2, Subang Indah
46000 Petaling Jaya Selangor, Malaysia
Tel:
+603 5631 2188
Fax: +603 5638 2189
E-mail: info.malaysia@belimo.ch
Singapore Office
Belimo Actuators Ltd.
1 Tannery Road #08-04, One Tannery
Singapore 347719
Tel:
+65 6842 1626
Fax: +65 6842 1630
E-mail: info.singapore@belimo.ch
Taiwan Office:
Belimo Actuators Ltd.
7F-2, No.343, Jhonghe Road, Yonghe City
Taipei County 234, Taiwan
Tel:
+886 2 2922 8805
Fax: +886 2 2922 8806
E-mail: info.taiwan@belimo.ch
Thailand Office:
Belimo Actuators Ltd.
90/2 Pensiri Place
Soi Phaholyothin 32, Phaholyothin Road
Chandrakasem, Jatujak
Bangkok 10900, Thailand
Tel:
+662 9415582-3
Fax: +662 9415584
E-mail: info.thailand@belimo.ch

Belimo INDIA
Mumbai Office:
Belimo Actuators India Pvt. Ltd.
23/ ABCD, Govt. Industrial Estate,
Charkop, Kandivali West,
Mumbai 400067, India
Tel:
+91 22 4025 4800
Fax: +91 22 4025 4899
E-mail: info.india@belimo.ch
Bangalore office:
Belimo Actuators India Pvt. Ltd.
Sreerama Complex,
No. 13, 2nd Floor, 5th Cross Road,
6th Block, Koramangala,
Bangalore 560097, India
Tel:
+91-80-40906311
Fax: +91-80-40906288
E-mail: info.india@belimo.ch
New Dehli Office:
Belimo Actuators India Pvt. Ltd.
Flat No. 516, DLF Tower B,
Jasola Distt. Centre, Jasola,
New Delhi 110025, India
Tel:
+91 11 41078501 to 41078507
Fax: +91 11 41078508
E-mail: info.india@belimo.ch
Chennai Office:
Belimo Actuators India Pvt. Ltd.
#25, Bagavadam Street, T-Nagar
Chennai - 600017, India
Tel:
91 44 42999450
Fax: 91 44 42999451
E-mail: info.india@belimo.ch

79

Innovation, Quality
and Consultancy:

93010-00160

A partnership for
motorising HVAC
actuators

Belimo regional head offices


EU BELIMO Automation AG
Brunnenbachstrasse 1
8340 Hinwil, Switzerland
Tel: +41 43 843 61 11
Fax: +41 43 843 62 68
E-mail: info@belimo.ch

AP Belimo Actuators Ltd.


Room 207, 2/F, New Commerce Center
19 On Sum Street, Shatin, N.T., Hong Kong
Tel: +852 2687 1716
Fax: +852 2687 1795
E-mail: info.asiapacific@belimo.ch

US BELIMO Aircontrol (USA), Inc.


43 Old Ridgebury Road
Danbury, CT 06813-2928
USA
Tel: +800 543-9038 / 203 791-9915
Fax: +800 228-8283 / 203 791-9919

Or contact your nearest Sales Representative

www.belimo.com

You might also like