Reviewed for general conformance with Contract
drawings and specifications.
ACTION :

1 Approved

Disapproved.

For information/reference
only.

Information category with


comments. Resubmission
required.

Approved except as

2 noted. Forward final


drawing.

Approved except as
noted. Resubmission
required.

Approval of Contract documents by the Consultant shall


not relieve the Seller of his responsibility for any errors
and fulfilment of Contract requirements.

Digitally signed by Santanu


Chakraborty
DN: cn=Santanu Chakraborty,
o=DCPL, ou=Power Cell-B,
email=santanuc@in.dclgroup.com,
c=IN
Date: 2015.05.07 16:43:13 +05'30'

IB THERMAL POWER STATION


2 X 660 MW UNITS 3 & 4

CONSULTING ENGINEERS
KOLKATA - INDIA

Orissa Power Generation


Corporation Ltd.

IB TPS - 2X660 MW
Units 3 & 4
Jharsuguda, Orissa

BGR Energy Systems


Ltd.

Booster Pump motor is not appeared in LT


Auxiliary Transformer Sizing Calculation of
Water System. BGR to check & confirm
TECHNICAL DATASHEET FOR Fire
AC MOTOR
to consider the same in next/final revision of
transformer sizing calculation.

1.0

GENERAL

1.1

Application

: BOOSTER PUMP

1.2

Quantity

:1

1.3

Make

: CROMPTON GREAVES LTD

1.4

Frame Size

: ND200L

1.5

Applicable Standard

2.0

TYPE AND RATING

2.1

Type of Motor

2.2

Service

: 3Ph AC, Squirrel Cage Induction


Motor (IE2 Energy Efficient Class)
: INDOOR

2.3

Duty Cycle/Designation

: Continuous/S1

2.4

Rated Continuous Output

2.5

: IS:1231;IS:12075;IS:12065;IS:325,
IS:12615:2011

a) At 40 Deg.C ambient

KW

: 32.61

b) At 50 Deg.C ambient

KW

: 30

Speed
a) Rated Speed

r.p.m. : 1480

b) Synchronous Speed

r.p.m. : 1500

2.6

Rated Voltage & % variation

: 415V; +/-10%

2.7

Rated Frequency & % variation

: 50 Hz; +/-5%

2.8

Combined voltage and frequency


Variation % (absolute sum)

: 10%

2.9

Full load current

Amps : 54 AMP

2.10

No load current

Amps : 19 AMP (APPROX)

2.11

Rated Power Factor

Development Consultants Pvt. Ltd.

: 0.84
Page 1 of 6

Orissa Power Generation


Corporation Ltd.

2.12

IB TPS - 2X660 MW
Units 3 & 4
Jharsuguda, Orissa

BGR Energy Systems


Ltd.

Efficiency at rated voltage and frequency


a) Full load

: 92.3

b) 3/4 load

: 92.3

c) 1/2 load

: 92

3.0

PERFORMANCE

3.1

Method of Starting

3.2

Starting Current

: DOL

a) Starting Current at rated voltage % FLC : 550%FLC SUB TO IS TOL


b) Starting current at 110% voltage % FLC : 605%FLC SUB TO IS TOL
3.3

Torque
a) Full load torque

kg.m : 19.74 KG.M

b) Starting Torque at rated voltage kg.m : 150%FLT


c) Pull out torque
3.4

3.5

3.6

kg.m : 225%FLT

Starting time at (% of Voltage)


(considering motor GD=motor GD)

80%

100%

0.5

a)

With load

sec.

0.8

b)

Without load (driven equipment


Coupled)
sec

0.32

Safe stall time at (% of Voltage)

80%

0.2

100%

110%

0.42

0.17

110%

a) Hot condition

sec.

: 19SEC

12SEC

10SEC

b) Cold condition

sec.

: 38SEC

24SEC

20SEC

a) Heating time constant

min

: 45 MIN

b) Cooling time constant

min

: 90 MIN

Time Constant

Development Consultants Pvt. Ltd.

Page 2 of 6

Orissa Power Generation


Corporation Ltd.

3.7

IB TPS - 2X660 MW
Units 3 & 4
Jharsuguda, Orissa

BGR Energy Systems


Ltd.

Starts
a) Permissible No. of equally spaced
starts per hour

: Three (3)

b) Permissible No. of starts in quick


succession

: Two (2)

3.8

Voltage required at motor terminals to start


with connected load and accelerate to full
speed without exceeding acceptable
wingding temperature
: 80% Rated Voltage

3.9

Noise Level at 1 m distance

: 85 dB

3.10

Vibration Level

: 2.2mm/s

3.11

3.12

Suitable for sudden application of 150%


rated voltage during bus transfer

: Yes

Capable of operating satisfactorily at


full load for 5 minutes without injurious
heating with 75% rated voltage at motor terminals

: Yes

3.13 Capable of withstanding the stresses


imposed if started at 110% of rated voltage

: Yes

4.0

CONSTRUCTION

4.1

Degree of Protection of Enclosure

: IP55

4.2

Method of Cooling

: TEFC

4.3

Insulation Class

: Class F /VPI

4.4

Temperature Rise Over 50 Deg.C ambient


(By resistance)

: 70 deg.C

4.5

Tropicalized (Yes/No )

: YES

4.6

Winding Connection

: Delta

4.7

Bearings

Please also provide


bearing make &
type for NDE

D.E.

N.D.E.

a)

Make

SKF/FAG/EQUIVALENT

b)

Type

BALL BEARING

Development Consultants Pvt. Ltd.

Page 3 of 6

Orissa Power Generation


Corporation Ltd.

IB TPS - 2X660 MW
Units 3 & 4
Jharsuguda, Orissa

c) Recommended lubricant
d) Is lubricant IOC equivalent

4.8

Terminal box
shall be suitable
for turning 360
degree in steps
of 90 degree.
Please mention.

Motor Terminal Box

BGR Energy Systems


Ltd.

:
GREASED FOR LIFE
: N.A. since greased for life

a)

Type

b)

Fault withstand Current KA

c)

Fault Current Withstand Time Sec.

Please note that lubricant shall be limited to


normally available types with IOC equivalent.
: CI BGR
Non-phase
also to segregated
note that Grease lubricated
bearings shall be pre-lubricated and shall
: 50KA
have provisions for in-service positive
lubrication with drains to guard against over
lubrication.
: 0.25sec

d)

Suitable Cable Size

: 1RX3CX35mm2

e)

Position

: RHS FROM DE

4.9

Painting

4.10

Direction of Rotation from DE w.r.t terminal : Clockwise

5.0

ACCESSORIES

5.1

Space Heaters

5.2

5.3

5.4

: 631 AS PER IS: 5


As per LT Power cable sizing
calculation for Fire Water PMCC,
motor terminal box for booster
pump shall be suitable for
3CX95 sq.mm.

a)

No. x Watt

: 60WX1 NOS.

b)

Volt, phase, frequency

: 240V, 1 Ph, 50 hz

Winding temperature detector


a)

Type

: N.A.

b)

Nos. furnished

: N.A.

Bearing temperature detector


a)

Type

: N.A.

b)

Nos. furnished

: N.A.

Temperature Indicators
a)

Type

: N.A.

b)

Nos. provided

: N.A.

c)

Locations

: N.A.

Development Consultants Pvt. Ltd.

Page 4 of 6

Orissa Power Generation


Corporation Ltd.

5.5

5.6

5.7

5.8

5.9

IB TPS - 2X660 MW
Units 3 & 4
Jharsuguda, Orissa

BGR Energy Systems


Ltd.

Temperature Alarm Contact


a)

Nos. provided

: N.A.

b)

Locations

: N.A.

c)

Contact rating

: N.A.

Flow Switch
a)

Type

: N.A.

b)

Nos. provided

: N.A.

c)

Locations

: N.A.

d)

Contact Rating

: N.A.

Current Transformer for differential protection


a)

Nos. provided

: N.A.

b)

Current Ratio

: N.A.

c)

Class

: N.A.

d)

Knee point voltage

: N.A.

e)

Excitation current at VK/2

: N.A.

Accessory Terminal Box


a)

No. provided

: 1 NO.

b)

Suitable cable size

: 1RX2CX2.5mm

Speed Switch
a)

Type

: N.A.

b)

Nos. provided

: N.A.

c)

Locations

: N.A.

d)

Contact Rating

: N.A.

6.0

GROUNDING

6.1

No. of grounding pads provided

Development Consultants Pvt. Ltd.

Page 5 of 6

Orissa Power Generation


Corporation Ltd.

IB TPS - 2X660 MW
Units 3 & 4
Jharsuguda, Orissa

BGR Energy Systems


Ltd.

a)

On motor body

: 2 NOS.

b)

On terminal box

: 1 NOS INSIDE MAIN TB

7.0

MISCELLANEOUS

7.1

Type of mounting

: B3 - HORIZONTAL

7.2

Overall dimension (L x B x H) in mm

: AS PER GA DRAWING

7.3

Moment of Inertia (GD.SQ / 4)

7.4

a)

Stator

Kg.Sq.m

: N.A.

b)

Rotor

Kg.Sq.m

: 0.3325

c)

Total

Kg.Sq.m

: 0.3325

Weight
a)

Stator

Kg

: 151

b)

Rotor

Kg

: 101

c)

Total

Kg

: 252

Total weight of Motor is not


matching with GA drawing of
Pump. Please check.

All performance figures are subject to IS tolerance.

Development Consultants Pvt. Ltd.

Page 6 of 6