(OHFWULFDO1RWHV

$UWLFOHV
SharingAbstracts,NotesonvariousElectricalEngineeringTopics.

$EVWUDFWRI&3:'3DUW
$EVWUDFWRI&3:',QWHUQDO(OHFWULILFDWLRQ3DUW
/LJKWLQJ&LUFXLW
PerCircuitNotmorethan10PointsofLightingorTotal800Wattwhichisless

3RZHU&LUFXLW
ForResidentialPerCircuitLessthan2Noof5A/15APlugSocket
ForNonResidentialPerCircuitLessthan1Noof5A/15APlugSocket

3OXJ6RFNHW
InResidentialwiring,wiringofSocketoutletshallbedonebycopperCableonly

0LQ6L]HRI:LUH
ForLightingCircuitSmallestsizeofconductorshallbe1.5Sq.mm
ForPowerCircuitSmallestsizeofconductorshallbe4Sq.mm

3OXJ6RFNHW

5A/6Aor15A/16ASocketshallbeinstalledatfollowingheights:
ForNonResidentialbuilding23cmaboveFloor,
ForKitchen23cmabove
Platform,
ForBathroomnotSocketisprovidedinbathroomMCB/ICwillbe2.1meterfromfixed
applianceandatleast1meterawayfromShower.

2SHUDWLQJ5RG
OperatingRod/HandleofDistributionBoardattheheightofmin2meter

'%&OHDUDQFH
ClearDistanceinfrontofSwitchBoard/D.Bshallbemin1meter.
IftheremaybebareconnectionatbackofSwitchBoardthanspacebehindS/Wshallbe
eitherlessthan20cmormorethan75cm.
NofuseBodyshallbemountedwithin2.5comedgeofD.BorPanel
Clearancebetween2.5cmismaintainedbetweenoppositepolarity.

6ZLWFK%R[
SwitchBoxorRegularBoxshallbemountednormally1.25meterfromfloorlevel.

)DQ+RRN
ForFanHookinconcreteroof12mmdiameterMSRodinUShape,horizontallyLegat
Topatleast19cmoneitherside.
ConnectionbetweenadjustmentBuilding(OutHouse,Garages)(SafetyClearance)
Ifthedistancewithadjustmentbuildingislessthan3meterandthereisnoanyRoad
intervalthanGIpipeofsuitablesizeshallbeinstalled.Thispipeshallbeexposedonwallat
heightofnotlessthan2.5meter.
Ifthedistancewithadjustmentbuildingismorethan3meterandthereisanyRoadinterval
thanGIpipeofsuitablesizeshallbeinstalled.Thispipeshallbeexposedonwallatheight
ofnotlessthan4meter.

0HWDOOLF&RQGXLW
ShallbeusedforIndustrialwiring,HeavymechanicalStress,shallbeISImarked,The
Thicknessshallnotbelessthan1.6mm(16SWG)forconduitsupto32mmDiameterandnot
lessthan2mm(14SWG)forconduitabove32mmDia.
Nosteelconduitlessthan20mmDiametershallbeused.
ForrigidConduitIS:2509/IS:3419andForFlexibleConduitIS:6946.
AllMetallicconduitaccessoriesshallbethreadedtype(Notpingrip,clampgrip)
Saddleforsurfaceconduitworkonwallshallnotlessthan0.55mm(24gauge)forconduit
upto25mmDiameternotlessthan0.9mm(20gauge)forlargerDiameter

0HWDOOLF2XWOHWV
ForeCastBoxes:Wallthicknessshallbeatleast3mm.
ForWeldedmildSteelBox:Wallthicknessshallnotbelessthan1.2mm(18gauge)forBoxes
uptosize20cmX30cm.AboveThissize1.6mm(16guage)thickMSBoxesshallbeused.
CleardepthofOutlessBoxshallnotbelessthan60mm.Thiswillbeincreasedasper
mountingofFanregulator

%HQGVLQ&RQGXLWV
Bendingradiusnotlessthan7.5cm

)L[DWLQJ&RQGXLWVRQ6XUIDFH
Conduitsshallbefixedbysaddlesnotlessthan1meterintervalbutincaseofcoupler/Bends
ineithersideofsaddles,Thesaddleshallbefitted30cmfromfitting.

-XQFWLRQ%R[
DepthofJunctionBoxshallbemin65mmasperIS:2667.

)LVK:LUH
GIfishwireof1.6mm/1.2mm(16SWG)shallbeused

1RQ0HWDOOLF&RQGXLW$FFHVVRULHV
NormallygripType.
PVCBoxIS:5133(PartII)thicknessnotlessthan2mm,CleardepthofPVCBoxesnotless
than60mm.

1RQ0HWDOOLF6XUIDFH&RQGXLW
Conduitsshallbefixedbysaddlesnotlessthan60cmintervalbutincaseofcoupler/Bends
ineithersideofsaddles,Thesaddleshallbefitted15cmfromfitting.

%XVEDU
Bulbarshallbe100A,200A,300A,400A,500A,600A,800A
TheCrosssectionareaofBusbarshallbesameasPhaseBusbar(Upto200A)forhigher
CapacityNeutralBusbarmustbenotlessthanhalfcrosssectionareasofPhaseBusbar.
BusbarshallbesuitablyinstalledwithPVCsleeve/Tap.
BusbarChambershallbefabricatedwithMSangleforFrameworkandsheetsteelof
thicknessnotlessthan1.5mm.
Minimumclearancebetweenphasestoearthshallbe26mmandphasetophaseshallbe
32mm.

%XVEDU7UXFNLQJ
BusbarTruckingaregenerallyusedforinterconnectionbetweenT/Cover500KVA/D.Gset
over500KVAandtheirswitchBoardPanel.
BusbarTruckingenclosuresheetsteelofmin2mmthickness

(DUWKLQJ
TypeofearthlingarePipeearthling/Plateearthling/Stripearthling
LengthofBuriedstripshallnotbelessthan15meter.
Twocopperstrip,eachsize50mmX5mmshallbeprovidedaseachbusbarin11KVS/Sor
D.Ggenerally.
Eachstripshouldbeconnectedseparatelytoearth.
TwonoofBodyearthlingofT/C,Panel,D.GareconnectedtoearthBus.
NeutralLeadsofT/C,D.GshallnotbeconnectedtoearthBus.
TheminimumCrosssectionareofprotectiveconductor(Notcontainedwithincableor
wire)2mmDia(14SWG)forCopper,2.5mmDia(12SWG)forG.I,2.24mmDia(13SWG).

(DUWKLQJ3LWVKDOOQRWEHFORVHUWKDQPHWHUIURP
%XLOGLQJ
TopofPipeearthlingelectrodeshallnotbelessthan20cmbelowthegroundlevel.
PlateelectrodeshallbeburiedingroundwithfaceverticalanditsTopnotlessthan3meter
belowgroundlevel.
Thestripofearthlingelectrodeshallbeburiedintrenchnotlessthan0.5mdeep.
Ifstripelectrodecannotbelaidinstraightlength.ItmaybeZigzagwithdeviationupto45
Degreefromaxisofstrip.
InPlateEarthingDiagramofwaterpipeshallnotbelessthan20mmandinPipeearthling
reducerof40mmX20mmshallbeused.
EarthingPitSizeshallbenotlessthan30cmX30cmX30cm.
ThicknessofMScoverofearthlingpitshallbenotlessthan6mmandhavinglocking
arrangements.
Earthingresistanceofeachelectrodeshallbelessthan5andforRockySoilnotlessthan
8
EarthingconduitforearthlingwireshallbeMediumclass15mmDiagramGIpipeandfor
EarthingStripshallbemediumclass40mmDiagramGIPipe.

&RQGXFWRU&OHDUDQFH PLQ  'LIIHUHQW9ROWDJH


WhentwoconductorofdifferentVoltageareerectedonsamesupportminclearance
betweenLV/MVand11KVshallbemin1meter.

&RQGXFWRU&OHDUDQFH PLQ  'LIIHUHQW6XSSRUW

AClearancenotlessthanheightoftallestsupportmaybemaintainedbetweenparallel
overheadlineonDifferentsupport.
WhentwooverheadlinecrosseachotherverticalclearancebetweenLV/MVand11KVshall
notbelessthan1.25meterandforLV/MVand33KVlineshallbenotlessthan2meter.

&RQGXFWRU&OHDUDQFH PLQ  $FURVV5RDG


MinConductorClearanceacrossRoad:ForLV/MVLineis5.8meterandforHVLine
6.1meter

&RQGXFWRU&OHDUDQFH PLQ  $ORQJ5RDG


MinConductorClearancealongRoad:ForLV/MVLineis5.5meterandforHVLine
5.8meter

&RQGXFWRU&OHDUDQFH PLQ  $ORQJ$FURVV


MinConductorClearancealong/acrossRoad:ForLV/MV/HVupto11Kv(BareConductor)
Lineis4.6meter.
MinConductorClearancealong/acrossRoad:ForLV/MV/HVupto11Kv(Insulated
Conductor)Lineis4.0meter.
MinConductorClearancealong/acrossRoad:ForHV(11Kvto33Kv)Lineis
5.2meter.
MinConductorClearancealong/acrossRoad:ForEHV(above33Kv)is5.2meter+0.3meter
forevery33KV(Notlessthan6.1).

&RQGXFWRU&OHDUDQFH PLQ  )URP%XLOGLQJ


MinConductorVerticalClearanceaboveBuilding:ForLV/MVLineis2.5meterfrom
highestPoint.
MinConductorHorizontalClearancenearBuilding:ForLV/MVLineis1.5meterfrom
nearestPoint.
MinConductorVerticalClearanceaboveBuilding:ForMV/EHV(upto33KV)Lineis
3.7meterfromhighestPoint.
MinConductorVerticalClearanceaboveBuilding:ForMV/EHV(above33KV)Lineis
3.7meter+0.3meterforevery33KV

MinConductorHorizontalClearanceaboveBuilding:ForMV/EHV(Upto11KV)Lineis
1.2meter.
MinConductorHorizontalClearanceaboveBuilding:ForEHV(Upto33KV)Lineis
02meter.
MinConductorHorizontalClearanceaboveBuilding:ForEHV(above33KV)Lineis
2meter+0.3meterforevery33KV

&RQGXFWRU&OHDUDQFH PLQ  &DEOHFURVVLQJ 


ThehorizontalandverticaldistancebetweenPowerandCommunicationcableshallnotbe
lessthan60cm.

&RQGXFWRU&OHDUDQFH PLQ  5DLOZD\FURVVLQJ 


Aftertakingapprovalofrailwayauthority,Cableunderrailwaytrackshallbemin1meter
frombottomofsleeperunderRCCorcastIronPipe.
CableinparalleltoRailwaytrackshallbemin3meterfarawayfromcenterofnearest
Track.

&DEOHWUHQFK
Forsinglecable:Forbelow11Kv.MinlengthofTrenchshallbe35cmanddepthshallbemin
75cm(withsandcushioningof8cmatbottom+Cable+protectivecovering/Sand
cushioningof17cmaboveCable)andwithoutCushioningDepthshallbe75cm+25cm.
Forsinglecable:Forabove11Kv.MinlengthofTrenchshallbe35cmanddepthshallbemin
1.2meter(withsandcushioningandprotectivecovering).
Formulticableinhorizontallevel:Mindistancebetweentwocableshallbe20cmandmin
distancebetweencableandedgeoftrenchonbothsideshallbe15cm
FormulticableinVerticallevel:Mindistancebetweentwocableshallbe30cm.(minSand
cushioningatbottomoftrenchshallbe8cm+Cable+minSandcushioningof
30cm+Cable+protectivecovering/Sandcushioningof17cmaboveCable)
ForLV/MVcablecushioningisnotrequiredwherethereisnopossibilityofmechanical
damages.
Extraloopofcableatendshallbe3meterforcabletermination/Joints.

&DEOH5RXWH0DUNHU

CableRouteMarkershallbemin0.5meterawayfromcabletrenchattheintervalnot
exceeding100meterparallel.
PlateTypeCableRouteMarkershallbemadeof100mmX5mmGI/AluminumPlate
welded/Boltedon35mmX35mmX6mmIronangleof60cmLong.
CementConcrete(C.C)typemarkershallbemadeinformationof1:2:4.

&DEOH%HQGLQJ5DGLXV

Voltage

1Core

Unarmored(Multi
core)

Armored(Multi
core)

11KV

20D

15D

12D

22KV

20D

20D

15D

33KV

20D

25D

20D

&DEOH/\LQJLQ3LSH
ForSingleConductorShallbemin10cmDiameterandmorethanTwoCableshallbemin
15cmDia.

&DEOHLQ5RDG&URVVLQJ
InRoadCrossingCableshallbelaidmin1meterbelowRoadinPipe.

&DEOH7UD\ 3HUIRUDWHG
CableTraymaybefabricatedbytwoangleironsof50mmX50mmX6mmastwo
longitudinalmemberswithcrossbracingbetweenthem50mmX5mmwelded/Boltedat
angleand1meterspacingof2mmthickMSsheet.

6WHHO7XEXODU3ROH
1/6lengthofSteelTubularPole+30cmfrombaseshallbecoatedwithBlackBituminous
paintonbothinternallyandexternally.Theremainingportionofthepoleshallbepainted

withRedoxide.

&URVVDUP
LV/MVLine:MSangleironofsizenotlessthan50mmX50mmX6mm
(4.5kg/meter)
11KVLine:MSangleironofsizenotlessthan65mmX65mmX6mm(5kg/meter)
LV/MVLine:MSChanelironofsizenotlessthan
75mmX40mmX4.8mm(7.14kg/meter)
11KVLine:MSChanelironofsizenotlessthan75mmX40mmX4.8mm(7.14kg/meter)
ForLV/MVLine:Mindistanceshallbe5cmbetweencenterofinsulationpinandendof
crossarm.
For11KVLine:Mindistanceshallbe10cmbetweencenterofinsulationpinandendof
crossarm.

&URVVDUP/HQJWK
Voltage

Nomof
HorizontalCon

LengthofCross
Arm

LV/MV

2Conductors

55cm

LV/MV

4Conductors

115cm

LV/MV

4Conductors

175cm

11KV

3Conductors

225cm

,QVXODWRUV
ForLV/MVOverheadLine:Pin/ShackleInsulatorandFor11KVLinePin/DiscInsulator
ForPinInsulatorforLV/MVline:StalkLength135mmShankLength125mm,minLoad
2KN.
ForPinInsulatorfor11KVline:StalkLength165mmShankLength150mm,minLoad
2KN.

'&ODPS

DclampshallbemadeofMSFlatsizeof50mmX6mm,heightof75mmGalvanizedandonly
usedforverticalconfigurationforLV/MVLineonly.

3ROH7RS&ODPS
PoleTopclampmadefromFlatiron50mmX8mm.

6WD\ZLUH5RG
StaywireRodshallnotbelessthan1.8mLongand19mmDia.AnchorPlateshallnotbe
lessthan45mmX45mmX7.5mm.

2YHUKHDG&RQGXFWRU PLQ
ForLV/MVLine:AAC(AllAlu.Conductor)7/1/2.21mm,ACSR6/1/1/2.11mm,AAAC(All
Alu.AlloyConductor)7/2.09mm(20Sqmm)
For11KV/33KVLine:AAC(AllAlu.Conductor)N/A,ACSR6/1/1/2.11mm,AAAC(All
Alu.AlloyConductor)7/2.56mm(30Sqmm)

%LQGLQJ:LUH
BindingWirewithinsulatorshallbedonewith2.6mm(12SWG)softaluminumwire.

(DUWKLQJLQ2YHUKHDG/LQH
Earthingwireshallnotbelessthan4mm(8SWG)andmin3earthlingPitperKMshallbe
required.
IfthereisnoContinuouswireforearthlinginoverheadlinethaneachpoleshouldbe
earthed.

6DPH6XSSRUW

ForLV/MVLineonSameSupportVerticaldistance:BetweenPhasetoEarthshallbemin
30cmandBetweenPhasetoPhasemin20cm
ForLV/MVLineonSameSupportHorizontaldistance:BetweenLivewireoneithersideof
supportshallbe45cm.
ForLV/MVLineonSameSupportHorizontaldistance:BetweenLivewireonsamesideof
supportshallbe30cm.
ForLV/MVLineonSameSupportHorizontaldistance:Betweencentralofpininsulatorto
endofcrossArmshallbe05cm.
ForHVLineinTriangularConfigurationfor11KV/33KVLineshallbemin1.5meter.

2YHUKHDG/LQH6WUXWV
ThePitforStrutsshallbelocatednotlessthan1.8meterfrompoleside.ThedepthofPit
shallbeatleast1.2meter

'DQJHUERDUG
AllSupportcarryingHVLineshallbefittedwithDangerBoard(IS:25511982)atheightof
3meter.

$QWL&OLPELQJ'HYLFH
ForHVLine(IS:2781978)having4PointBarbs75mm+12mmapartweight128/125
gm/metershallbewrappedhelicallywithpitchof75mmaroundLimbofPoleheightof
3.5meterto5to6meter.

/RRSLQJ%R[
LoopingBusshallbefabricatedfromMSSheetof1.6mm(16SWG)thickness,MinSize
250mmX200mmX100mmforsinglecableentryandfor250mmX300mmX100mmformore
thantwocableentry

)HHGHU3LOODU

FeederPillarshallbefabricatedmin2mmthickMSsheetandhingedtypedoubledoorat
frontside.IfwidthofPillarshallbelessthan60cmthansinglehingedtypedoorshallbe
permitted.
MinheightofPedestalofFeederPillarshallbenotlessthan45cmand1to2meterheight
fromRoadLevel.
EachFeederPillarshallbeearthedwith2noofEarthingelectrode

6XEVWDWLRQ
ClearHeightofS/SBuildingshallbemin3.6meter.

$UHDRI6XEVWDWLRQ
Sub
Station

TotalTransformerRoom
Area

TotalS/SArea
(Transformer,HT/LT
PanelwithoutD.G)

2X500KVA

36Sq
meter

130Sq
meter

3X500KVA

54Sq
meter

172Sq
meter

2X800KVA

39Sq
meter

135Sq
meter

3X800KVA

58Sqmeter

181Sq
meter

2X1000KVA

39Sq
meter

149Sq
meter

2X1000KVA

58Sq
meter

197Sq
meter

5HVSRQVHVWR$EVWUDFWRI&3:'3DUW
Gabrielsays:
September6,2011at3:10pm
Isomuchenjoyyournotesonclearance.Plscanyousendmoreimportantnoteson

Isomuchenjoyyournotesonclearance.Plscanyousendmoreimportantnoteson
electricalthatcanhelpmeinthisprofection.
Reply
CHANDRASHEKHARMsays:
July11,2012at8:58am
VERYUSEFULINFORMATION,GOODEFFORTS
Reply
jaspalsinghsays:
December2,2011at2:47pm
howmanylight/fan/caallbelletc.fortype4residentlalflats&whatwillbesantionedload
Reply
NiharRajsays:
December25,2011at5:28pm
DearJignesh
Keepupthegoodwork.Bestwishes
Reply
ArunSahoosays:
May26,2012at6:18pm
ExcellantWorkMrJignesh.IamaSrDesignEngratABBandmywifeisinCSEB.Weboth
likedurblog.Itisveryhelpful
Reply
merajsays:
July6,2012at4:17pm
excellentnotes,canuprovidesomemoreinformationaboutluxlevelcalcandelectrical
designing
Reply
VishwaMurthy.Vaggasays:
July14,2012at6:32am
Sir,IamworkingforapvtorganisationinT&Ddivision,willyoupleaseexplainus
regardinghowtocalculatethecurrentcarryingcapacityofAAACandACSRconductors.
Reply
Jignesh.Parmarsays:
July14,2012at2:18pm
RuTalkingaboutSelectionofOverheadconductorforDistributionLine???Forthat
YouhavetoCalculateVoltageRegulationofLine.ExcelSheetforthatisalreadygiven
inThisBlog.
IfyoutalkaboutCurrentCapacityofOverheadlinethanItisnormallygivenonCatalog
ofItsManufacture.
Reply
JitendraMahidasays:
August10,2012at6:29am
veryverygoodinformationforelectricalengineer,Iamsalutetoyoureffortforknowledge

veryverygoodinformationforelectricalengineer,Iamsalutetoyoureffortforknowledge
share&readymaterial
Reply
THIRUGNANAM.Psays:
August28,2012at6:05pm
DearMr.JIGNESH.PARMAR,
Iamveryusefulforyourguidelineinelectricalclerenceandallotherguidelinebooks,to
much
thaks.thisisusefulforournewgenarations.
warmregards,
P.Thirugnanam,
sitemanager,
siemensnairobikena,
mb.no.706099746
Reply
Syedmansoorsays:
October17,2012at6:16am
DearSir
PleaseuploadGeneralspecificationofelectricalworks(External)part2,imnotabletofind
thatbookanywhere,sopleaseuploadit,iwillbeverythankfultoyou.
Reply
ChandrashekharMandwekarsays:
October29,2012at11:27am
veryimportantinformation
Reply
Abilsays:
February9,2013at11:39am
Siramworkingasanelectricalconsultantsocanyourefermesomebooksthatcanincrease
mydesignknowledge..Thankyouforthisblogasthisisreallyinformative
Reply
MSureshsays:
March7,2013at11:47am
howtoimprovethevoltage(overcomevoltagedrop)overthelongdistamcelaid(>1KM)
LTpowerXLPEcable??Canwedoitbyprovidingcapacitorbankoranyotheralternative
method??
Reply
Jignesh.Parmarsays:
March7,2013at2:11pm
YoucanimproveVDbyinstallingCapacitorattrailenduptocertainlimitonly.
FordecreasingVDyouhavetoupgradeyourCablesizeordecreasedistanceonly.
Reply

Er.SKPalsays:
October4,2013at5:42am
Pleasecheckthesizeofcable.For2.85KMcablesizerequired240Sqmmevenfor10
Amploadgiving8voltdrop
.
Reply
ANILDESHAPANDEsays:
March26,2013at11:12am
Theinformationisveryuseful.Congratsfortheefforts.
Reply
Bhavinkumarchovatiyasays:
June4,2013at4:54am
superb.
Reply
Bhavinkumarchovatiyasays:
June4,2013at4:58am
sir,iwantingtoknowaboutsubstiondesingsoineeddistancebetweenequipmentto
equipmentdistanceofs/slikeisolatortoctplzgivwmeans
Reply
Murugananthamsays:
September19,2013at12:33pm
Dearsirthisisveryusefulforme.PleasetellmetheabovedetailsfromWhichstandard
pleasereplymesir.
Reply
Jignesh.Parmarsays:
September19,2013at5:30pm
ItisalreadystandardCentralpublicworksdepartmentCPWD,India
Reply
soumyaksays:
September28,2013at3:51pm
dearsir,iwanttoknowaboutconcretingdetailsforerectionofpccpole9mlong,STP11
MT,staypurpose.
Reply
S.Kundusays:
November14,2013at10:19am
DearMrJigneshParmer,
Ihaveseenthissitewhichisveryhelpfultometogettingmoreknowledgeandinformation
regardingequipments,calculationandsomestandard.Youarerequestedtopleaseshare
sometestingknowledgeaboutrelaytesting,transformertestingprocedure,andelectronics
relatedissuelikedrive,softstarterandtherecommissioningprocedure.
Regards,
SumanKundu,

Reply
B.VenkatReddysays:
March4,2014at8:26am
DearSir,
ManyThanksforyourEffortsforshearingEngineeringKnowledge,Itsreallyvery
ImportantforeveryElectricalEngineer.
BeWell,
B.VenkatReddy.
Reply
Gunjanbaghelsays:
March14,2014at8:00am
Veryusefulinformationgoodeffortsallthebest.
Reply
Anandsays:
June26,2014at12:01pm
canyoupl.tellmeifthereisanyruletoconsiderELCBforindustrialsocketsinkitchen.
Reply
ASRREDDYsays:
September18,2014at9:56am
ElectricalArticles&Notes
ByJIGNESH.N.PARMAR,thisisavailableinbookforminIndia.
Weneedabouttransmissionlinesurveyandcalculations
Reply
fawadsays:
January26,2015at10:53am
respectedsir,itisveryusefulinformationforelectricalengrs,sir,iappreciateyourwork.
thanks.
Reply
AshutoshVermasays:
February17,2015at10:00am
DearJignesh,
doyouoranyonehavetheswithgearsizingcalculationI.e.includingselectionofMCCB,
fusesetc.
illbeverythankful
Reply