Professional Documents
Culture Documents
LV SWITCHGEAR
Page 1 of 14
A.
1.1
Make
: BHEL-EPD
1.2
Type
1.3
Reference Standard
1.4
Volt
1.5
Phase, Frequency
No., Hz : 3, 50
1.6
1.7
1.9
1.10
a)
Interrupting Symmetrical
KA
b)
KA rms : 50
: 50
Insulation Level
1-min., 50 Hz Voltage withstand KV rms
1.8
R1
: 2.5
Construction
a)
Yes/No : Yes
b)
Yes/No : Yes
Enclosure
a)
Degree of Protection
b)
Yes/No : Yes
R1
R1
DOCUMENT TITLE:
LV SWITCHGEAR
2.0
CONSTRUCTION
2.1
Design
2.2
a)
Completely compartmentalised
b)
2.3
Yes/No : Yes
b)
Voltage Transformers
Yes/No
: Yes
c)
Protective Relays
Yes/No
: Yes
d)
Yes/No
: Yes
Breaker Cubicle
a)
b)
2.4
2.5
Page 2 of 14
Yes/No : Yes
: Yes
: Yes
b)
: Yes
2.6
2.7
: Yes
R1
R1
DOCUMENT TITLE:
LV SWITCHGEAR
Page 3 of 14
3.0
3.1
Make
: HINDALCO/JINDAL
3.2
Material
: Aluminium,grade-63401
3.3
Reference, Standard
: IS 5082 (E91E)
3.4
3.5
: 105
3.6
mm
: 25
b) Phase to ground
mm
: 25
3.7
Yes/No
: Yes
3.8
Make
: DDE
: Non-hygroscopic,
Flame retardant,
High tensile strength Track
resistance type.
Type
c)
Voltage class
KV
: 415
: Min 28 mm
4.0
CIRCUIT BREAKER
4.1
Make
4.2
Type
: Air break
4.3
Reference Standard
: IEC: 60947-2
:C&SElectric/L&T/GE/Siemens/Schnieder
DOCUMENT TITLE:
LV SWITCHGEAR
Page 4 of 14
4.4
Rated Voltage
: 415
4.5
Rated Frequency
Hz
: 50
4.6
No. of Poles
4.7
Rated Currents
a)
b)
4.8
: 3
Amp.
KA rms.
: 50
Deg.C.
: 40
4.9
: Continuous
4.10
Operating duty
: 0-3'-CO-3'-CO
4.11
4.12
Insulation Level
1-minute 50 Hz voltage withstand
4.13
4.14
KA.peak
: 105
KV rms.
: 2.5
Between poles
mm
: 25
b)
mm
: 25
Operating Mechanism
a)
Type
b)
c)
: Yes
DOCUMENT TITLE:
4.15
4.16
4.17
4.18
LV SWITCHGEAR
Page 5 of 14
Rating
b)
Voltage
: 220V D.C.
Closing Coil
a)
Voltage
: 220V D.C.
b)
: (85 - 110%)
Tripping Coil
a)
Voltage
: 220V D.C.
b)
: (70 - 110%)
a)
: Yes
b)
: Yes
5.0
FUSE
5.1
Make
: S&S/L&T/GE/Siemens/Alstom /CGL
5.2
Type
: HRC
5.3
Reference standard
5.4
6.0
CONTACTORS
6.1
Make
:C&SElectric/L&T/GE/Siemens/Schnieder/ABB
6.2
Type
DOCUMENT TITLE:
LV SWITCHGEAR
Page 6 of 14
6.3
Reference standard
6.4
Duty class
: AC - Class III-category
AC3 for unidirectional drives and
AC4 for bi- directional /inching duty drives
DC - Class I - category DC2.
6.5
Utilization category
Non - Reversible Motor AC3
6.6
: 4 min
b)
: 4 min
7.0
7.1
Push Buttons
a)
Make
Cands/C&S Electric/GE/Vaishno/ABB/GEC
:BCH/L&T/Schneider/Siemens/Tecknic Control
b)
Alstom/RAAS Control/TM/Honeywell/
Tele mechanic
:Spring Return Push To Actuate
c)
Contact rating
: DDE
i)
7.2
Amp
240 V AC
Amp
220 V DC
Amp
: DDE & 2A
b)
DOCUMENT TITLE:
LV SWITCHGEAR
c)
Voltage
Page 7 of 14
: DDE
8.0
CURRENT TRANSFORMER
8.1
Make
8.2
Type
: Cast Resin
8.3
Reference Standard
: IS: 2705
8.4
: Yes
8.5
Rated frequency
: 50 Hz
8.6
a)
Differential C.T.
: PS
b)
Relaying C.T.
: 5P10
c)
Metering C.T.
8.7
Short-Circuit Withstand
a)
KA rms. : 50
b)
Dynamic current
KA peak : 105
8.8
Class of Insulation
: E or Better
8.9
: 30
8.10
9.0
VOLTAGE TRANSFORMER
9.1
Make
KV rms : 2.5
DOCUMENT TITLE:
LV SWITCHGEAR
Page 8 of 14
9.2
Type
: Cast Resin
9.3
Reference Standard
: IS: 3156
9.4
Voltage ratio
: 415/110
9.5
Rated frequency
: 50 Hz
9.6
Accuracy class
: 3P
9.7
VA burden
: DDE
9.8
Continuous
: 1.9
b)
30 seconds
: 3
9.9
Class of Insulation
: E or Better
9.10
: 40
9.11
9.12
Winding Connection
9.13
Kvp
: 2.5
a)
Primary
: star
b)
Secondary
: star
Fuses
a)
Continuous rating
Amp.
: DDE
b)
KA rms. : 50
10.0
RELAYS
10.1
: Yes
10.2
Type of mounting
: Fixed
10.3
Reference Standard
: IS-3231
DOCUMENT TITLE:
10.4
LV SWITCHGEAR
Page 9 of 14
3. Outgoing Feeder
Apart from protection relays, each electrically operated breaker shall be provided withanti-pumping
(94)(inbuilt of breaker), lockout (86) Lockout relay shall be hand reset type.
11.0
METERS
11.1
Make
: DDE
11.2
Type
: switchboard
11.3
Reference Standard
: IS-722
11.4
Size
11.5
Scale
: Full
11.6
Accuracy class
: 2%
11.7
Meter Switch
a)
Make
: DDE
b)
Type
c)
Cat. No.
: DDE
Rotary
12.0
SECONDARY WIRING
12.1
Type of Insulation
: PVC
12.2
Voltage grade
: 1100 V
DOCUMENT TITLE:
LV SWITCHGEAR
12.3
Conductor material
12.4
b)
Current Circuit
12.5
Wires identified at both
ends with markers ?
: Copper
: 1.5 Sq.mm
: 2.5 Sq.mm
: YES
13.0
TERMINAL BLOCK
13.1
Make
: Phoenix/Connect well/Elemex/Wago/
Essen Deinki/Technoplast/Tosha/
Controls&Switchgear/Jainson
13.2
Type
: box-clamp
13.3
Voltage grade
: 1100 V
14.0
CABLE TERMINATION
14.1
Cable termination/connection
furnished as specified
14.2
Make
: NA
b)
Type
: NA
c)
: NA
14.3
14.4
Cable Lugs
14.5
: Yes
Yes/No : Yes
a)
Type
: crimp
b)
Material
: tinned copper
Cable Gland
DOCUMENT TITLE:
14.6
LV SWITCHGEAR
Page 11 of 14
a)
Type
: Double compression
b)
Material
c)
: YES
d)
: YES
: CRCA
b)
: CRCA
c)
: 3
15.0
BUSDUCT CONNECTION
15.1
15.2
a)
Top entry
Yes/No : YES
b)
Side entry
Yes/No : NO
Yes/No : Yes
16.0
GROUND BUS
16.1
: YES
16.2
Material
: Galvanized steel
16.3
Size
: 75 x 10 mm
17.0
NAME PLATE
17.1
Material
: anodized aluminium
17.2
Thickness
: 3 mm
DOCUMENT TITLE:
LV SWITCHGEAR
18.0
18.1
Cubicle Heater
a)
18.2
Thermostat controlled
Page 12 of 14
: Yes
Plug Socket
a)
Type
: 3 pin , Industrial
b)
Rating
: 5A
19.0
A.C./D.C. SUPPLY
19.1
19.2
a)
b)
c)
a)
b)
20.0
PAINTING
20.1
Finisha)
Inside
: as per specification
b)
Outside
DOCUMENT TITLE:
LV BUSDUCT
Page 13 of 14
B.
1.1
Type
: Non-segregated
1.2
Service
: Indoor/Outdoor
1.3
Rated Voltage
: 415
1.4
Phase
Nos.
: 3
1.5
Frequency
Hz
: 50
1.6
: 10%(absolute sum)
1.7
Service voltage
(for space heater)
2.0
: 2.5 KV(rms)
3.0
4.0
Amp
a) Bus conductor
i) With Silver Plated bolted joints
: 55 C
: 40 C
5.0
6.0
Symmetrical Momentary
KA for 1 Sec. KA peak
Main Run
50 KA
105 KA
Material
a)
Conductor
:Aluminium
DOCUMENT TITLE:
LV BUSDUCT
b)
Enclosure
7.0
Shipping Section(Maximum)
8.0
Bus Insulator
9.0
10.0
Page 14 of 14
: 3M
a)
Voltage class
KV
: 1.1
b)
Creepage distance
c)
Material
d)
Conductor mounting
e)
Earth Clearance
: 25 mm
mm
: 28mm/KV
Material of enclosure
:Aluminium
b)
Thickness of enclosure mm
:3mm
c)
: 2mm
Phase to phase
:25mm
b)
Phase to earth
:25mm