You are on page 1of 4

Module 1 Input Module

cable # Input Input description


1 106 generator circuit breaker close relay
2 A3 generator circuit breaker trip
3 503 Emergency stop PB
4 504 Watch dog Relay
5 505 breaker control Switch in auto
6 506 Multifunction relay healthy
7 507 Lockout relay
8 508 initiate immediate shutdown

Module 2 Input Module


cable # Input Input description
1 G56 engine Running relay
2 G86 engine failure relay
3 G85 engine common alarm relay
4 G211 engine prelubed
5 G257 engine in remote mode (auto)
6 516 power unit UG04 failure alarm
7 B2 tie circuit breaker closed relay
8 C2 generator-tie circuit breaker closed relay

Module 3 Input Module


cable # Input Input description
1 A4 earth switch of 52G
2 552b group 1 breaker close status
3 523b group 2 breaker close status
4 524b group 3 breaker close status
5 A38 AVR common alarm
6 526b close relay
7 527b shedding request group 2
8 528b shedding pulse request group 2

Module 4 Input Module


cable # Input Input description
1 513b shedding request group 3
2 532b shedding pulse request group 3
3 533b low level switch
4 534b high level switch
5 535b neutral groung control switch
6 536b engine compressor trip
7 537 ground fault
8 400T common motor fault

Module 5 Input Module


cable # Input Input description
1 D2 gas turbine A breaker close status
2 E2 gas turbine B breaker close status
3 S2 steam turbine breaker close stat
4 543b normal shedding enable
5 544b DCS edg start request
6 545b DCS edg stop request
7 546b DCS tie breaker close request
8 547b NGS close feedback

Module 6 output Module


cable # Input Input description
1 112 initiate breaker manual close
2 104 initiate breaker close(auto)
3 100 initiate trip delay
4 121 reset gov/regulator baising signal
5 123 command GCM to do unloading
6 122 alarm aknowledge to GCM
7 557 initiate synchronization to GCM
8 558 alarm horn

Module 7 output Module


cable # Input Input description
1 261 processor running
2 262 initiate remote start to generator
3 263 initiate remote stop to generato
4 264 warning light
5 265 initiate remote prelube to generator
6 266 initiate trip to group 1 breaker
7 267 initiate trip to group 2 breaker
8 268 initiate trip to group 3 breaker
Module 8 output Module
cable # Input Input description
1 271 initiate trip during emergency case
2 272 synchronizing contactor number 1
3 273 neutral groung switch closing rel
4 274 neutral groung switch opening relay
5 275 diesel compressor starting signal
6 276 diesel compressor stopping signal
7 277 synchronizing relay number 2
8 278 spare
Module 2 Input Module
cable # Input Input description
1 G56 Running relay
2 G86 engine failure relay
3 G85 engine common alarm relay
4 G211 engine pre lubed
5 G257 engine in remote mode
6 516 main failure alarm
7 B2 K 39 closed
8 C2 k 42 closed

You might also like