Professional Documents
Culture Documents
Windell Peters
Manager-Codes
AGL Resources, Inc.
Atlanta, GA
C. John Beck
Senior Advising Engineer
Pacific Gas and Electric Company
San Francisco, CA
Jack Rea
Manager-Customer Services
Oklahoma Natural Gas Co.
Oklahoma City, OK
Paul Cabot
Administrator, National Fuel Gas Code
American Gas Association
Washington, DC
James A. Ranfone
AGA Ex-Officio Member (Non-voting)
Terrance Carolan
Mechanical Inspector
Emmet County
Harbor Springs, MI
Charles Gerber
Mechanical/Plumbing Supervisor
County of Henrico Building Inspections
Richard, VA
Timothy Ray Hillman
Plumbing Field Investigator
Oklahoma Construction Industries Board
Oklahoma City, OK
Martin Petchul
Manager, Codes and Technical Training
Piedmont Natural Gas
Charlotte, NC
ICC PUBLIC HEARING ::: February 2005
Mark Riley
Inspector Supervisor
City of Troy
Troy, MI
Bruce Swiecicki
Senior Technical Advisor
National Propane Gas Association
Frankfort, IL
John Wasson, Jr. CBO
Chief of Inspections
City of Greenville
Greenville, SC
Staff Secretary:
Gregg Gress
Senior Technical Staff
International Code Council
FG1
FG2
FG1-04/05
202 (New definition)
Proponent: Guy McMann, Jefferson County, CO,
representing Colorado Association of Plumbing &
Mechanical Officials
Add new definition as follows:
NUISANCE. Public nuisance as known in common law or
in equity jurisprudence; whatever is dangerous to human life
or detrimental to health; whatever structure or premises is
not sufficiently ventilated, , with respect to its intended
occupancy; and whatever renders the air unwholesome.
Reason: The word nuisance is used twice in this document, in section
108.7 and 503.8. This definition will aid in understanding of what a
nuisance really is in the context that it is used. The language was
extracted from the IPC and tailored for this document solely for the
convenience of the user.
Analysis: It is not evident why the proposed definition is specific to
ventilation air. The definition uses subjective terms (e.g., sufficiently and
unwholesome).
Cost Impact: None
AS
ASF
AM
AMF
D
DF
For example, fans may have been listed as in-line fans or power
ventilators, but are being used as in-line commercial kitchen ventilators.
Some duct wraps have met certain standards and test criteria for the
product itself, but have not been tested for protection of other products
in a fire scenario. Furnaces that are listed for residential indoor use are
being installed in outdoor locations serving commercial establishments.
Unlisted appliances are being produced more and more each day. Some
appliance manufacturers actually promote two categories of
appliances; one that is listed and labeled and one thats not. The ones
that are not listed and labeled are always less expensive and usually
look just like the listed and labeled ones. Where are the cost cutting
measures taken? They might remove some safety provisions that a
listing would require. From an installer, shop owner, or code
enforcement visual inspection these units look like any other unit. You
cannot base an appliance approval on engineering evaluation unless it
comes from a 3rd party, Nationally Recognized Testing Laboratory
(NRTL), (i.e. a Listing). It can certainly be a one-time field evaluation
from a NRTL, but, it must be from qualified entities possessing the tools,
equipment and experience to evaluate issues such as fuel input rates
and power output rates, carbon monoxide production levels, and other
life safety issues associated with appliances. It should not be
acceptable to have an appliance manufacturers staff engineer report
to you with generic statements such as this product works within safe
guidelines. This is not adequate. This added text will cause this
potentially hazardous life safety compromise to cease.
Cost Impact: None
AS
ASF
AM
AMF
D
DF
FG3-04/05
FG2-04/05
301.3
FG3
AS
ASF
AM
AMF
D
DF
Revise as follows:
303.4 Protection from physical vehicle impact damage.
Appliances shall not be installed in a location where subject
to physical vehicle impact damage unless except where
protected by an approved means barriers meeting the
requirements of the International Fire Code. Protection is
not required for appliances that are located out of the
vehicles normal travel path.
Reason: The main intent of Section 303.4 is the protection of
appliances located and installed in garages and carports from vehicle
damage. The reference to the IFC for these barrier provisions is
inappropriate because the main intent in the IFC is to provide protection
for large volumes of stored flammable and hazardous materials.
The term physical used in the IFGC is too broad and subject to
open interpretation. Substituting the term means for barriers is
intended to recognize that there are other ways (other than a physical
barrier) to provide equal protection. For example, locating the appliance
in a corner or bay of a garage where it is impossible for the vehicle to
pose a concern.
Cost Impact: None
FG4-04/05
301.16 (New)
FG6-04/05
AS
ASF
AM
AMF
D
DF
FG5-04/05
303.4
Proponent: James Ranfone, American Gas Association,
representing AGA Building Energy Codes and Standards
Committee
FG4
AS
ASF
AM
AMF
D
DF
303.8 (New)
Proponent: Guy McMann, Jefferson County, CO,
representing Colorado Association of Plumbing &
Mechanical Officials
Add new text as follows:
303.8 Negative pressure atmospheres. Appliances
equipped with draft hoods and not vented in accordance with
the provisions of Section 503.2.1 or 503.3.4 shall not be
located in a negative pressure atmosphere where such
negative pressure will adversely affect the flow of
combustion products to the outdoors.
Reason: Water heaters located in commercial kitchen environments
with negative pressure are subject to improper venting as a result of
reverse flow in the vent system, which could prove hazardous to the
kitchen occupants over time. Contaminants produced by the combustion
of natural gas include nitric oxide, carbon monoxide, carbon dioxide,
nitrogen dioxide and water vapor. These by-products may play havoc
in people with respiratory complications. It doesnt take much negative
pressure to overcome a typical water heater venting system thus
preventing the vent from priming, resulting in the contaminants migrating
through the kitchen. Although the contaminants may become somewhat
diluted, depending on the equipment location, dilution cannot be
depended upon to bring products of combustion down to a safe level.
The end result is an appliance that is not venting correctly. Most
restaurants are initially balanced with a slight positive pressure to
control insects, but the kitchens can be kept negative to control odors.
Any tweaking of the system usually makes the whole building go
negative. Isolating the appliance is the only way to insure proper venting
due to the fact that many kitchens operate at negative pressures
ICC PUBLIC HEARING ::: February 2005
AS
ASF
AM
AMF
D
DF
FG7-04/05
305.3
Proponent: James Ranfone, American Gas Association,
representing AGA Building Energy Codes and Standards
Committee
Revise as follows:
305.3 Elevation of ignition source. Equipment and
appliances having an ignition source shall be elevated such
that the source of ignition is not less than 18 inches (457
mm) above the floor in hazardous locations and public
garages, private garages, repair garages, motor fueldispensing facilities and parking garages. For the purpose
of this section, rooms or spaces that are not part of the
living space of a dwelling unit and that communicate directly
with a private garage through openings shall be considered
to be part of the private garage.
Exception: Elevation of the ignition source is not
required for appliances that are listed as flammable
vapor ignition resistant and for installation without
elevation.
Reason: The phrase and for installation without elevation has caused
enforcement confusion. Listed flammable vapor ignition resistant
appliances do not require elevation. The term ignition is added to use
the correct terminology.
AS
ASF
AM
AMF
D
DF
FG9-04/05
305 (New) and various other sections in
Chapters 4 and 6 (New)
Proponent: James Ranfone, American Gas Association,
representing AGA Building Energy Codes and Standards
Committee
Add new text as follows:
305.3.1 (IFGS) Installation in residential garages. In
residential garages where appliances are installed in a
separate, enclosed space having access only from outside
of the garage, such appliances shall be permitted to be
installed at floor level, provided that the required combustion
air is taken from the exterior of the garage.
AS
ASF
AM
AMF
D
DF
FG8-04/05
305.3.1
Proponent: Charles Gerber, Henrico County VA,
representing Virginia Plumbing & Mechanical Inspectors
Association and Virginia Building & Code Officials
Association
Revise as follows:
305.3.1 (Supp) Parking garages. Connection of a parking
garage with any room in which there is a fuel-fired appliance
shall be by means of a vestibule providing a two-doorway
clearance above the cooking top of not less than 30 in. (760
mm) to combustible material and metal cabinets. A
minimum clearance of 24 in. (610 mm) is permitted where
one of the following is installed:
1. The underside of the combustible material or metal
cabinet above the cooking top is protected with not
less than 1/4 in. (6 mm) insulating millboard covered
with sheet metal not less than 0.0122 in. (0.3 mm)
thick.
2. A metal ventilating hood constructed of sheet metal
not less than 0.0122 in. (0.3 mm) thick is installed
above the cooking top with a clearance of not less
than 1/4 in. (6 mm) between the hood and the
underside of the combustible material or metal
cabinet. The hood width shall be not less than the
width of the appliance and shall be centered over the
appliance.
3. A listed cooking appliance or microwave oven is
installed over a listed cooking appliance and in
compliance with the terms of the upper appliances
listing and the manufacturers instructions.
630.3 (IFGS) Combustion and ventilation air. Where
unvented infrared heaters are installed, natural or
mechanical means shall provide outdoor ventilation air at a
rate of not less than 4 cfm per 1,000 Btu/h (0.38
m3/min/kW) of the aggregate input rating of all such heaters
installed in the space. Exhaust openings for removing flue
products shall be above the level of the heaters.
630.4 (IFGS) Installation in commercial garages and
aircraft hangars. Overhead infrared heaters installed in
garages for more than three motor vehicles and in aircraft
hangars shall be installed in accordance with Sections
305.9, 305.10 and 305.11.
Reason: The IFGC lacks various provisions that help ensure that
appliances are safely installed. These provisions are in the National
Fuel Gas Code. The American Gas Association is asking the ICC
membership whether these provisions are necessary in the IFGC and
to consider extracting them.
Analysis: The text in this proposal is extracted from the National Fuel
Gas Code (ANSI Z223.1) and has been editorially revised as necessary
to make it conform to ICC style and format conventions. It is the intent of
this proposal that the text be either accepted as is, without modification,
or rejected. The proposed text was either added to the NFGC (ANSI
Z223.1) after the creation of the International Fuel Gas Code or was
not included by the drafting committee when the IFGC was initially
drafted. If this text is accepted by the ICC membership, it will be placed
in the IFGC and designated as IFGS text, meaning that such text is
maintained by the ANSI Z223 (NFGC) Committee process, not the ICC
code development process.
NFPA 409 and NFPA 30A are currently referenced standards in ICC
Codes. It is the opinion of staff that NFPA 88A complies with Section 3.6
of the ICC Code Development Procedures.
Cost Impact: None
AS
ASF
AM
AMF
D
DF
FG10-04/05
305.4
Proponent: John R. Wiggins, Underwriters Laboratories,
Inc.
Revise as follows:
305.4 Public garages. Appliances located in public
garages, motor fuel-dispensing facilities, repair garages or
other areas frequented by motor vehicles shall be installed
a minimum of 8 feet (2438 mm) above the floor. Where
motor vehicles exceed 6 feet (1829 mm) in height and are
capable of passing under an appliance, appliances shall be
installed a minimum of 2 feet (610 mm) higher above the
floor than the height of the tallest vehicle.
Exception: The requirements of this section shall not
apply where the appliances are protected from motor
vehicle impact and installed in accordance with Section
305.3 and NFPA 88B 30A.
Reason: After the adoption of the 1996 edition of NFPA 30A, the
Technical Committee on Automotive and Marine Service Stations was
given responsibility for NFPA 88B, Standard for Repair Garages, and
was also charged with responsibility for developing fire safety
requirements for alternative fuels, such as compressed natural gas
(CNG), when these fuels are dispensed along with liquid fuels. With
respect to repair garages, the technical committee decided to integrate
the technical requirements of NFPA 88B into NFPA 30A. In Chapter 8,
replace NFPA 88B with NFPA 30A.
AS
ASF
AM
AMF
D
DF
FG11-04/05
311 (New), Appendix E (New)
Proponent: James Ranfone, American Gas Association,
representing AGA Building Energy Codes and Standards
Committee
1. Add new text as follows:
SECTION 311 (IFGS)
PROCEDURES TO BE FOLLOWED TO
PLACE EQUIPMENT IN OPERATION
FG7
TABLE 311.1
GAS INPUT TO BURNER IN
CUBIC FEET PER HOUR
SECONDS
FOR ONE
REVOLUTION
10
180
360
720
1,800
11
164
327
655
1,636
12
150
300
600
1,500
13
138
277
555
1,385
14
129
257
514
1,286
16
112
225
450
1,125
17
106
212
424
1,059
18
100
200
400
1,000
19
95
189
379
947
20
90
180
360
900
21
86
171
343
857
22
82
164
327
818
23
78
157
313
783
24
75
150
300
750
1 ft
2 ft
5 ft
46
92
185
462
40
45
90
180
450
41
44
88
176
440
42
43
86
172
430
43
42
84
167
420
44
41
82
164
410
45
40
80
160
400
46
39
78
157
391
47
38
77
153
383
49
37
73
147
367
50
36
72
144
360
51
35
71
141
353
52
35
69
138
346
53
34
68
136
340
54
33
67
133
333
55
33
65
131
327
56
32
64
129
321
57
32
63
126
316
58
31
62
124
310
ft3
1 ft3
2 ft3
5 ft
26
69
138
277
692
27
67
133
267
28
64
129
29
62
30
FG8
39
SECONDS
FOR ONE
REVOLUTION
1 ft3
2 ft3
5 ft3
667
60
30
60
120
300
257
643
62
29
58
116
290
124
248
621
64
29
56
112
281
60
120
240
600
66
29
54
109
273
31
58
116
232
581
68
28
53
106
265
32
56
113
225
563
70
26
51
103
257
33
55
109
218
545
72
25
50
100
250
34
53
106
212
529
74
24
48
97
243
35
51
103
206
514
76
24
47
95
237
36
50
100
200
500
78
23
46
92
231
37
49
97
195
486
80
22
45
90
225
38
47
95
189
474
ICC PUBLIC HEARING ::: February 2005
82
22
44
88
220
84
21
43
86
214
86
21
42
84
209
88
20
41
82
205
90
20
40
80
200
94
19
38
76
192
98
18
37
74
184
100
18
36
72
180
104
17
35
69
173
108
17
33
67
167
116
15
31
62
155
120
15
30
60
150
130
14
28
55
138
140
13
26
51
129
150
12
24
48
120
160
11
22
45
112
170
11
21
42
106
180
10
20
40
100
FG9
Table E.1 Utility Gases (cubic feet per hour at sea level)
Pressure at Orifice
(in. w.c.)
Orifice or
Drill Size
3.5
10
80
.48
.52
.55
.63
.69
.73
.79
.83
.88
79
.55
.59
.64
.72
.80
.84
.90
.97
1.01
78
.70
.76
.78
.88
.97
1.04
1.10
1.17
1.24
77
.88
.95
.99
1.11
1.23
1.31
1.38
1.47
1.55
76
1.05
1.13
1.21
1.37
1.52
1.61
1.72
1.83
1.92
75
1.16
1.25
1.34
1.52
1.64
1.79
1.91
2.04
2.14
74
1.33
1.44
1.55
1.74
1.91
2.05
2.18
2.32
2.44
73
1.51
1.63
1.76
1.99
2.17
2.32
2.48
2.64
2.78
72
1.64
1.77
1.90
2.15
2.40
2.52
2.69
2.86
3.00
71
1.82
1.97
2.06
2.33
2.54
2.73
2.91
3.11
3.26
70
2.06
2.22
2.39
2.70
2.97
3.16
3.38
3.59
3.78
69
2.25
2.43
2.61
2.96
3.23
3.47
3.68
3.94
4.14
68
2.52
2.72
2.93
3.26
3.58
3.88
4.14
4.41
4.64
67
2.69
2.91
3.12
3.52
3.87
4.13
4.41
4.69
4.94
66
2.86
3.09
3.32
3.75
4.11
4.39
4.68
4.98
5.24
65
3.14
3.39
3.72
4.28
4.62
4.84
5.16
5.50
5.78
64
3.41
3.68
4.14
4.48
4.91
5.23
5.59
5.95
6.26
63
3.63
3.92
4.19
4.75
5.19
5.55
5.92
6.30
6.63
62
3.78
4.08
4.39
4.96
5.42
5.81
6.20
6.59
6.94
61
4.02
4.34
4.66
5.27
5.77
6.15
6.57
7.00
7.37
60
4.21
4.55
4.89
5.52
5.95
6.47
6.91
7.35
7.74
59
4.41
4.76
5.11
5.78
6.35
6.78
7.25
7.71
8.11
58
4.66
5.03
5.39
6.10
6.68
7.13
7.62
8.11
8.53
57
4.84
5.23
5.63
6.36
6.96
7.44
7.94
8.46
8.90
56
5.68
6.13
6.58
7.35
8.03
8.73
9.32
9.92
10.44
55
7.11
7.68
8.22
9.30
10.18
10.85
11.59
12.34
12.98
54
7.95
8.59
9.23
10.45
11.39
12.25
13.08
13.93
14.65
53
9.30
10.04
10.80
12.20
13.32
14.29
15.27
16.25
17.09
52
10.61
11.46
12.31
13.86
15.26
16.34
17.44
18.57
19.53
51
11.82
12.77
13.69
15.47
16.97
18.16
19.40
20.64
21.71
50
12.89
13.92
14.94
16.86
18.48
19.77
21.12
22.48
23.65
49
14.07
15.20
16.28
18.37
20.20
21.60
23.06
24.56
25.83
48
15.15
16.36
17.62
19.88
21.81
23.31
24.90
26.51
27.89
47
16.22
17.52
18.80
21.27
23.21
24.93
26.62
28.34
29.81
46
17.19
18.57
19.98
22.57
24.72
26.43
28.23
30.05
31.61
45
17.73
19.15
20.52
23.10
25.36
27.18
29.03
30.90
32.51
44
19.45
21.01
22.57
25.57
27.93
29.87
31.89
33.96
35.72
FG10
43
20.73
22.39
24.18
27.29
29.87
32.02
34.19
36.41
38.30
42
23.10
24.95
26.50
29.50
32.50
35.24
37.63
40.07
42.14
41
24.06
25.98
28.15
31.69
34.81
37.17
39.70
42.27
44.46
40
25.03
27.03
29.23
33.09
36.20
38.79
41.42
44.10
46.38
39
26.11
28.20
30.20
34.05
37.38
39.97
42.68
45.44
47.80
Table E.1 Utility Gases (Cubic feet per hour at sea level) (Continued)
Pressure at Orifice (in. w.c.)
Orifice
or Drill
Size
3.5
10
38
27.08
29.25
31.38
35.46
38.89
41.58
44.40
47.27
49.73
37
28.36
30.63
32.99
37.07
40.83
43.62
46.59
49.60
52.17
36
29.76
32.14
34.59
39.11
42.76
45.77
48.88
52.04
54.74
35
32.36
34.95
36.86
41.68
45.66
48.78
52.10
55.46
58.34
34
32.45
35.05
37.50
42.44
46.52
49.75
53.12
56.55
59.49
33
33.41
36.08
38.79
43.83
48.03
51.46
54.96
58.62
61.55
32
35.46
38.30
40.94
46.52
50.82
54.26
57.95
61.70
64.89
31
37.82
40.85
43.83
49.64
54.36
58.01
61.96
65.97
69.39
30
43.40
46.87
50.39
57.05
62.09
66.72
71.22
75.86
79.80
29
48.45
52.33
56.19
63.61
69.62
74.45
79.52
84.66
89.04
28
51.78
55.92
59.50
67.00
73.50
79.50
84.92
90.39
95.09
27
54.47
58.83
63.17
71.55
78.32
83.59
89.27
95.04
99.97
26
56.73
61.27
65.86
74.57
81.65
87.24
93.17
99.19
104.57
25
58.87
63.58
68.22
77.14
84.67
90.36
96.50
102.74
108.07
24
60.81
65.67
70.58
79.83
87.56
93.47
99.83
106.28
111.79
23
62.10
67.07
72.20
81.65
89.39
94.55
100.98
107.49
113.07
22
64.89
70.08
75.21
85.10
93.25
99.60
106.39
113.24
119.12
21
66.51
71.83
77.14
87.35
95.63
102.29
109.24
116.29
122.33
20
68.22
73.68
79.08
89.49
97.99
104.75
111.87
119.10
125.28
19
72.20
77.98
83.69
94.76
103.89
110.67
118.55
125.82
132.36
18
75.53
81.57
87.56
97.50
108.52
116.03
123.92
131.93
138.78
17
78.54
84.82
91.10
103.14
112.81
120.33
128.52
136.82
143.91
16
82.19
88.77
95.40
107.98
118.18
126.78
135.39
144.15
151.63
15
85.20
92.02
98.84
111.74
122.48
131.07
139.98
149.03
156.77
14
87.10
94.40
100.78
114.21
124.44
133.22
142.28
151.47
159.33
13
89.92
97.11
104.32
118.18
128.93
138.60
148.02
157.58
165.76
12
93.90
101.41
108.52
123.56
135.37
143.97
153.75
163.69
172.13
11
95.94
103.62
111.31
126.02
137.52
147.20
157.20
167.36
176.03
10
98.30
106.16
114.21
129.25
141.82
151.50
161.81
172.26
181.13
100.99
109.07
117.11
132.58
145.05
154.71
165.23
175.91
185.03
103.89
112.20
120.65
136.44
149.33
160.08
170.96
182.00
191.44
105.93
114.40
123.01
139.23
152.56
163.31
174.38
185.68
195.30
FG11
109.15
117.88
126.78
142.88
156.83
167.51
178.88
190.46
200.36
111.08
119.97
128.93
145.79
160.08
170.82
182.48
194.22
204.30
114.75
123.93
133.22
150.41
164.36
176.18
188.16
200.25
210.71
119.25
128.79
137.52
156.26
170.78
182.64
195.08
207.66
218.44
128.48
138.76
148.61
168.64
184.79
197.66
211.05
224.74
235.58
1
136.35
147.26
158.25
179.33
194.63
209.48
223.65
238.16
250.54
For SI units: 1 Btu/hr = 0.293 W, 1 ft 3 = 0.028 m3,
1 ft = 0.305 m, 1 in. w.c. = 249 Pa.
Notes:
1. Specific gravity = 0.60, Orifice Coefficient = 0.90
2. For utility gases of another specific gravity, select multiplier from Table E.3. For altitudes above 2,000 ft (610 m), first
select the equivalent orifice size at sea level from Table E.4
Table E.2 LP-Gases (Btu per hour at sea level)
Orifice or Drill
Size
Propane
Butane
.008
519
589
.009
656
744
.010
812
921
.011
981
1,112
.012
1,169
80
1,480
1,326
1,678
79
1,708
1,936
78
2,080
2,358
77
2,629
2,980
76
3,249
3,684
75
3,581
4,059
74
4,119
4,669
73
4,678
5,303
72
5,081
5,760
71
5,495
6,230
70
6,375
7,227
69
6,934
7,860
68
7,813
8,858
67
8,320
9,433
66
8,848
10,031
65
9,955
11,286
64
10,535
11,943
63
11,125
12,612
62
11,735
13,304
61
12,367
14,020
60
13,008
14,747
59
13,660
15,486
58
14,333
16,249
57
15,026
17,035
FG12
56
17,572
19,921
55
21,939
24,872
54
24,630
27,922
53
28,769
32,615
52
32,805
37,190
51
36,531
41,414 1
50
39,842
45,168
49
43,361
49,157
48
46,983
53,263
Orifice or
Drill Size
Propane
Butane
47
50,088
56,783
46
53,296
60,420
45
54,641
61,944
44
60,229
68,280
43
64,369
72,973
42
71,095
80,599
41
74,924
84,940
40
78,029
88,459
39
80,513
91,215
38
83,721
94,912
37
87,860
99,605
36
92,207
104,532
35
98,312
111,454
34
100,175
113,566
33
103,797
117,672
32
109,385
124,007
31
117,043
132,689
30
134,119
152,046
29
150,366
170,466
28
160,301
181,728
27
168,580
191,114
26
175,617
199,092
25
181,619
205,896
24
187,828
212,935
23
192,796
218,567
22
200,350
227,131
21
205,525
232,997
20
210,699
238,863
19
223,945
253,880
18
233,466
264,673
Propane
Butane
Notes:
1. Btu per cubic foot
2,516
3,280
2. Specific gravity
1.50
2.01
3. Pressure at orifice,
11
11
Inches w.c.
0.9
0.9
4. Orifice Coefficient
5. For altitudes above 2,000 ft (610 mm), first select the
equivalent orifice size at sea level from Table E.4.
FG13
Multiplier
Specific
Gravity
Multiplier
0.45
0.50
1.155
1.095
0.95
1.00
0.795
0.775
0.55
1.045
1.05
0.756
0.60
0.65
1.000
0.961
1.10
1.15
0.739
0.722
0.70
0.75
0.926
0.894
1.20
1.25
0.707
0.693
0.80
0.866
1.30
0.679
0.85
0.90
0.840
0.817
1.35
1.40
0.667
0.655
FG14
Table E.4 Equivalent Orifice Sizes at High Altitudes (includes 4% input reduction for each 1000 ft)
Orifice
Size at
2000
3000
4000
5000
6000
7000
8000
9000
10,000
10
10
12
10
12
13
15
Sea
Level
11
12
13
14
16
10
12
13
14
15
17
10
11
12
13
14
16
17
10
11
12
13
14
15
16
18
10
11
12
13
13
15
16
17
18
11
12
12
13
14
16
17
18
19
10
12
13
13
14
15
16
17
18
19
11
13
13
14
15
16
17
18
19
20
12
13
14
15
16
17
17
18
19
20
13
15
15
16
17
18
18
19
20
22
14
16
16
17
18
18
19
20
21
23
15
16
17
17
18
19
20
20
22
24
16
17
18
18
19
19
20
22
23
25
17
18
19
19
20
21
22
23
24
26
18
19
19
20
21
22
23
24
26
27
19
20
20
21
22
23
25
26
27
28
20
22
22
23
24
25
26
27
28
29
21
23
23
24
25
26
27
28
28
29
22
23
24
25
26
27
27
28
29
29
23
25
25
26
27
27
28
29
29
30
24
25
26
27
27
28
28
29
29
30
25
26
27
27
28
28
29
29
30
30
26
27
28
28
28
29
29
30
30
30
27
28
28
29
29
29
30
30
30
31
28
29
29
29
30
30
30
30
31
31
29
29
30
30
30
30
31
31
31
32
30
30
31
31
31
31
32
32
33
35
31
32
32
32
33
34
35
36
37
38
32
33
34
35
35
36
36
37
38
40
33
35
35
36
36
37
38
38
40
41
34
35
36
36
37
37
38
39
40
42
35
36
36
37
37
38
39
40
41
42
36
37
38
38
39
40
41
41
42
43
37
38
39
39
40
41
42
42
43
43
FG15
38
39
40
41
41
42
42
43
43
44
39
40
41
41
42
42
43
43
44
44
40
41
42
42
42
43
43
44
44
45
Size at
2000
3000
4000
5000
6000
7000
8000
9000
10,000
41
42
42
42
43
43
44
44
45
46
42
42
43
43
43
44
44
45
46
47
43
44
44
44
45
45
46
47
47
48
44
45
45
45
46
47
47
48
48
49
45
46
47
47
47
48
48
49
49
50
46
47
47
47
48
48
49
49
50
50
47
48
48
49
49
49
50
50
51
51
48
49
49
49
50
50
50
51
51
52
49
50
50
50
51
51
51
52
52
52
50
51
51
51
51
52
52
52
53
53
51
51
52
52
52
52
53
53
53
54
52
52
53
53
53
53
53
54
54
54
53
54
54
54
54
54
54
55
55
55
54
54
55
55
55
55
55
56
56
56
55
55
55
55
56
56
56
56
56
57
56
56
56
57
57
57
58
59
59
60
57
58
59
59
60
60
61
62
63
63
58
59
60
60
61
62
62
63
63
64
59
60
60
61
61
61
61
62
62
63
62
63
63
64
64
64
64
65
65
65
61
62
62
63
63
64
65
65
66
66
62
63
63
64
64
65
65
66
66
67
63
64
64
65
65
65
66
66
67
68
64
65
65
65
66
66
66
67
67
68
65
65
66
66
66
67
67
68
68
69
66
67
67
68
68
68
69
69
69
70
67
68
68
68
69
69
69
70
70
70
68
68
69
69
69
70
70
70
71
71
69
70
70
70
70
71
71
71
72
72
70
70
71
71
71
71
72
72
73
73
71
72
72
72
73
73
73
74
74
74
72
73
73
73
73
74
74
74
74
75
73
73
74
74
74
74
75
75
75
76
Sea
Level
FG16
74
74
75
75
75
75
76
76
76
76
75
75
76
76
76
76
77
77
77
77
76
76
76
77
77
77
77
77
77
77
77
77
77
77
78
78
78
78
78
78
78
78
78
78
79
79
79
79
80
80
79
79
80
80
80
80
.013
.012
.012
.012
80
80
.013
.013
.013
.012
.012
.012
.012
.011
AS
ASF
AM
AMF
D
DF
FG12-04/05
401.1.2 (New)
Proponent: Gregory G. Victor, Glendale Fire Department,
Glendale, AZ, representing himself
Add new text as follows:
401.1.2 Location of gas meters. The location of gas
meters shall be approved by the code official.
Reason: There is currently no provision in the codes that provides for
the approval of the location of the gas meter. A local utility in our area
has located the gas meter within inches of the only exit from
townhouses. Should a fire include the metering equipment it could
easily render the only exit from the structure inaccessible. This
situation should not be acceptable to building officials. This proposal
places a requirement for the approval of the location of gas meters.
This provision was located in the Uniform Mechanical Code but was not
carried forward during the drafting process. We think this is an
important requirement and we urge your approval of this proposal.
AS
ASF
AM
AMF
D
DF
FG13-04/05
404.1
Proponent: Guy McMann, Jefferson County, CO,
representing Colorado Association of Plumbing &
Mechanical Officials
Revise as follows:
404.1 Prohibited locations. Piping shall not be installed in
or through a circulating air duct, clothes chute, chimney or
gas vent, ventilating duct, dumbwaiter or elevator shaft.
Piping that is downstream of the point of delivery and serves
a townhouse unit shall not pass through other townhouse
units.
Reason: The code lacks guidance concerning piping located in areas
not controlled by the owners of the property. No portion of a system
should be subject to conditions that may exist as a result of the piping
being located in an area not accessible or controlled by the parties
whom the pipe serves. Townhouses are a prime example. Several lines
leave the meter location passing through the crawl spaces of the other
units leaving those portions of the system subject to damage or
tampering by those in control of the other units. Imagine if a particular
line had a left-right coupling in it or a union because its not considered
a concealed space, and the piping is manipulated for any reason. Its
quite possible that the coupling or union could be tweaked enough to
cause a leak or be unthreaded to a point of failure possibly causing an
explosion when the furnace or water heater located down there fires
off. This is not a desirable situation. This language would require each
line to enter the building independently. The cost impact would be minor
if any at all and is much more tolerable than an accident. As to address
the committees concerns, some of the language has been deleted to
clarify that its not so much the property boundry but the actual building
area itself that other people have access to. Condominiums are
irrelevant in that the owners do not have control of the units walls and
floors, only the air space within the unit. This code change targets
townhouses with accessible crawl spaces but may be applicable in
other situations.
Cost Impact: None
FG17
AS
ASF
AM
AMF
D
DF
FG14-04/05
404.5, 704.1.2.3.5
Proponents: Charles Gerber, Henrico County VA,
representing Virginia Plumbing & Mechanical Inspectors
Association and Virginia Building & Code Officials
Association
Rene Beliveau, City of Golden CO, representing Colorado
Association of Plumbing and Mechanical Officials
depending on whether 1/2 inch or 3/8 inch gypsum were use, the nail
would penetrate from 1-11/16 inch to 1-9/16 inch, plus counter sink, for
8 penny nails; and 1-3/16 inch to 1-1/16 inch, plus counter sink, for 6
penny nails. If 1/4 inch paneling is utilized, the potential problem
increases. While it may not be required to use 8 penny nails for the
proper attachment of trim, the decision of which nail to use is frequently
determined by what nail is on hand and available, not what is required
or prudent. Additionally, with the use of pneumatic nailers, the depth of
counter sinking is not as easily regulated.
It is clear that the 1 inch dimension does not provide adequate
protection. The 1-1/2 inch dimension is taken form the International
Plumbing Code Section 305.8, the International Mechanical Code Section
305.5, and the International Residential Code Sections M1308.2 and
P2603.2.1 and is recommended here for consistency and ease of
enforcement. These sections are frequently enforced by the same
inspectors and it makes no sense to require less protection for
hydrogen gas piping than for water, waste and vent, or mechanical
piping.
Revise as follows:
Cost Impact: None
FG18
AS
ASF
AM
AMF
D
DF
FG15-04/05
408.4
Proponent: Guy Tomberlin, Fairfax County, VA,
representing Virginia Plumbing & Mechanical Inspectors
Association and Virginia Building & Code Officials
Association
Revise as follows:
408.4 Sediment trap. Where a sediment trap is not
incorporated as part of the gas utilization equipment, a
sediment trap shall be installed downstream of the
equipment shutoff valve as close to the inlet of the
equipment as practical and within 6 feet of the appliance
inlet connection, measured along the centerline of the piping
or connector. The sediment trap shall be either a tee fitting
with a capped nipple of any length connected to in the
bottom opening of the run of the tee or other device
approved as an effective sediment trap. Illuminating
appliances, ranges, clothes dryers and outdoor grills need
not be so equipped.
Reason: This clearly states the intent of this section. It is common
practice for sediment traps to be placed ahead of the shutoff valve. A
common arrangement is a 3/4" or 1" pipe drop with a sediment trap on
the bottom of the drop and a " gas shutoff on the branch of the tee.
Current text would require a 3/4" or 1" gas shutoff valve because it
requires the valve to be upstream of the sediment trap. The intent is to
make sure that the sediment trap is within 6 feet of the appliance inlet.
There is no minimum length of the nipple required to serve as a sediment
trap, this includes the use of an all thread nipple. The sediment trap is
simply installed to catch any potential debris in the gas system.
Typically, all that is found in a sediment trap is maybe some small pipe
ICC PUBLIC HEARING ::: February 2005
AS
ASF
AM
AMF
D
DF
FG16-04/05
FG17-04/05
409.6 (New), 401.1.1, 101.2.2; IFC 510.2 (New)
Proponent: James Anjam, Arlington County, VA,
representing Virginia Plumbing & Mechanical Inspectors
Association & Virginia Building Code Official Association
THIS PROPOSAL IS ON THE AGENDA OF THE FUEL
GAS AND THE FIRE CODE DEVELOPMENT
COMMITTEES. SEE THE TENTATIVE HEARING ORDERS
FOR THESE COMMITTEES.
PART I IFGC
409.5
Proponent: Guy Tomberlin, Fairfax County VA,
representing Virginia Plumbing & Mechanical Inspectors
Association and Virginia Building & Code Officials
Association
Revise as follows:
409.5 Equipment shutoff valve. Each appliance shall be
provided with a shutoff valve separate from the appliance.
The shutoff valve shall be located in the same room as the
appliance, not further than 6 feet (1829 mm) from the
appliance measured along the centerline of the connector
or piping, and shall be installed upstream from the union,
connector or quick disconnect device it serves. Such
shutoff valves shall be provided with access.
Exception: Shutoff valves for vented decorative
appliances and decorative appliances for installation in
vented fireplaces shall not be prohibited from being
installed in an area remote from the appliance where
such valves are provided with ready access. Such valves
shall be permanently identified and shall serve no other
equipment. Piping from the shutoff valve to within 3 feet
(914 mm) of the appliance connection shall be sized in
accordance with Section 402.
Reason: Current text does not state how to measure the 6 foot
limitation. Section 411.1.2.1 of the 2004 Supplement states that
connectors are measured along their centerline to determine length.
Locating the shutoff valve should be measured no differently. For
example, a shutoff valve might be located 6 feet from the upper corner
of a furnace, measured in a direct line, but, there could be 8 to 10 feet
or more of developed pipe length between the valve and the appliance
inlet. This scenerio complies with current code.
AS
ASF
AM
AMF
D
DF
FG19
AS
ASF
AM
AMF
D
DF
AS
ASF
AM
AMF
D
DF
PART II IFC
Public Hearing: Committee:
Assembly:
AS
ASF
AM
AMF
D
DF
FG19-04/05
410.4 (New), 202 (New)
Proponent: Sidney Cavanaugh, Cavanaugh Consulting,
Burbank, CA, representing Plus! Safety Products
1. Add new text as follows:
410.4 Excess flow valves. Excess flow valves shall be
listed for the application, shall be listed as complying with
ASTM F2138, ASTM F1802 and CSA 3 and shall be
installed in accordance with the manufacturers installation
instructions.
2. Add new definition as follows:
PART I IFGC
Public Hearing: Committee:
Assembly:
FG18-04/05
ASTM F1802-97
410.1
Proponent: James Ranfone, American Gas Association,
Washington, D.C., representing AGA Building Energy
Codes and Standards Committee
Revise as follows:
410.1 Pressure regulators. A line pressure regulator shall
be installed where the appliance is designed to operate at
a lower pressure than the supply pressure. Line gas
pressure regulators shall be listed as complying with ANSI
Z21.80. Access shall be provided to pressure regulators.
Pressure regulators shall be protected from physical
damage. Regulators installed on the exterior of the building
shall be approved for outdoor installation.
Reason: The IFGC requires equipment to be listed but does not state
the appropriate standard for line pressure regulators. The proposed
revision will add the appropriate standard, ANSI Z21.80 Line Pressure
Regulators, 2003 Edition.
FG20
CSA 3-2000
Analysis: It is the opinion of staff that ASTM F1802. ASTM F2138 and
CSA 3 comply with Section 3.6 of the ICC Code Development
Procedures.
Cost Impact: None
AS
ASF
AM
AMF
D
DF
FG20-04/05
411.1, 411.1.1 (New)
Proponent: Richard Sekerchak, Dormont Manufacturing
Company, Export, PA
1. Revise as follows:
FG21-04/05
AS
ASF
AM
AMF
D
DF
416 (New)
1. Rigid metallic pipe and fittings.
2. Corrugated stainless steel tubing (CSST) where
installed in accordance with the manufacturers
instructions.
3. Semirigid metallic tubing and metallic fittings.
Lengths shall not exceed 6 feet (1829 mm) and shall
be located entirely in the same room as the
appliance. Semirigid metallic tubing shall not enter
a motor-operated appliance through an unprotected
knockout opening.
4. Listed and labeled appliance connectors in
compliance with ANSI Z21.24 and installed in
accordance with the manufacturers installation
instructions and located entirely in the same room
as the appliance.
5. Listed and labeled quick-disconnect devices used in
conjunction with listed and labeled appliance
connectors.
6. Listed and labeled convenience outlets used in
conjunction with listed and labeled appliance
connectors.
7. Listed and labeled appliance connectors complying
with ANSI Z21.69 and listed for use with food service
equipment having casters, or that is otherwise
subject to movement for cleaning, and other large
movable equipment.
8. Listed and labeled outdoor appliance connectors in
compliance with ANSI Z21.75/CSA 6.27 and
installed in accordance with the manufacturers
installation instructions.
FG21
FG22
AS
ASF
AM
AMF
D
DF
FG22-04/05
502.7 (New)
Proponent: Rene M. Beliveau, City of Golden CO,
representing Colorado Association of Plumbing and
Mechanical Officials
Add new text as follows:
AS
ASF
AM
AMF
D
DF
FG23-04/05
505.1.1
Proponent: James Ranfone, American Gas Association,
Washington, D.C., representing AGA Building Energy
Codes and Standards Committee
Delete and substitute as follows:
FG23
with this option. Until the appliance industry develops a safe method to
light appliance pilot lights, this is a proven, safe alternative that needs
to remain as an option.
Reason: The new text directs the code official and installer to the IMC
since it contains extensive installation provisions for exhaust systems
used in commercial cooking applications. The IFGC is not the
appropriate code for such coverage.
Analysis: Currently, the IMC does not have any coverage specific to
the use of kitchen exhaust hood systems to vent the combustion gases
from gas-fired cooking appliances. The current text of Section 505.1.1
was placed in the IFGC as an appliance specific extension of current
Section 503.3.4, which also addresses the use of exhaust hoods for
appliance venting.
FG25-04/05
AS
ASF
AM
AMF
D
DF
FG24-04/05
505.1.1
Proponent: Cordell Tobin, Arlington County VA,
representing Virginia Plumbing & Mechanical Inspectors
Association and Virginia Building & Code Officials
Association
Revise as follows:
505.1.1 (Supp) Commercial cooking appliances vented
by exhaust hoods. Where commercial cooking appliances
are vented by means of the Type I or Type II kitchen
exhaust hood system that serves such appliances, the
exhaust system shall be fan powered and the appliances
shall be interlocked with the exhaust hood system to
prevent appliance operation when the exhaust hood system
is not operating. Where a solenoid valve is installed in the
gas piping as part of an interlock system, gas piping shall
not be installed to bypass such valve. Dampers shall not be
installed in the exhaust system.
Exception: An interlock between the cooking
appliance(s) and the exhaust hood system shall not be
required where heat sensors or other approved methods
automatically activate the exhaust hood system when
cooking operations occur.
Reason: This has been the preferred method of many designers to
achieve positive venting of flue gases associated with commercial
cooking operations. It provides a luxury to the business owners so that
they do not have to re-light appliances each morning. Industry has
clearly stated that this equipment is not safe to re-light everyday
Current text takes away this cost saving allowance for restaurant
owners that has been a proven safe and effective part of exhaust
interlock. This method has been used for years in many jurisdictions
and there have been absolutely zero reported incidents associated
FG24
AS
ASF
AM
AMF
D
DF
505.1.1
Proponent: James Ranfone, American Gas Association,
representing AGA Building Energy Codes and Standards
Committee
Revise as follows:
505.1.1 (Supp) Commercial cooking appliances vented
by exhaust hoods. Where commercial cooking appliances
are vented by means of the Type I or Type II kitchen
exhaust hood system that serves such appliances, the
exhaust system shall be fan powered and the appliances
shall be interlocked with the exhaust hood system to
prevent appliance operation when the exhaust hood system
is not operating. Where a solenoid valve is installed in the
gas piping as part of an interlock system, gas piping shall
not be installed to bypass such valve. Dampers shall not be
installed in the exhaust system.
Exception: An interlock between the cooking
appliance(s) and the exhaust hood system shall not be
required where heat sensors or other approved methods
automatically activate the exhaust hood system when
cooking operations occur. An interlock between the
cooking appliance(s) and the exhaust hood system shall
not be required for appliances that are of the manually
operated type and are factory equipped with standing
pilot burner ignition systems.
Rea s o n : The exception will prevent the potentially hazardous field
retrofitting of listed commercial equipment and the unnecessary
relighting of standing pilots designed for continuous operation. The
change would reinstate an exception for manual-type appliances with
factory installed standing pilots. This exception was deleted from the
code during the 2002 revision process without technical or safetyrelated justification.
The Z83/CSA Joint Gas Food Service Equipment Technical Advisory
Group (TAG) supports the inclusion of the exception. The TAG is made
up of representatives of most major food service equipment
manufacturers in North America, responsible for updating ANSI
Z83.11/CSA 1.8, Gas Good Service Equipment. The TAG states, We
believe that the exception is needed to help ensure that there are no
field alterations to food service equipment that would void the design
certification of the equipment or create an unsafe condition.
Manually operated cooking appliances in a commercial setting are
in operation only when kitchen staff is present. Any concerns that the
exhausting system is not operating when these appliances are in use
would be readily apparent by the staff and corrective action
undertaken. No evidence was provided that kitchen personnel have
AS
ASF
AM
AMF
D
DF
AS
ASF
AM
AMF
D
DF
FG27-04/05
621.7, 621.7.1 (New)
621.4
1. Revise as follows:
Revise as follows:
FG26-04/05
AS
ASF
AM
AMF
D
DF
FG28 -04/05
630.2
Proponent: Dennis Martinelli, Fairfax County VA,
representing Virginia Plumbing & Mechanical Inspectors
Association and Virginia Building & Code Officials
Association
Revise as follows:
630.2 Support. Infrared radiant heaters shall be safely and
adequately fixed in an approved position independent of gas
FG25
Reason: These terms are not necessary for the application of the
code. They are vague and ambiguous words and these types of terms
do not result in uniform application and enforcement of the codes.
PART I IFGC
AS
ASF
AM
AMF
D
DF
FG29-04/05
631.2
Revise as follows:
631.2 Installation. In addition to the requirements of this
code, the installation of boilers shall be in accordance with
the manufacturers instructions and the International
Mechanical Code. Operating instructions of a permanent
type shall be attached to the boiler. Boilers shall have all
controls set, adjusted and tested by the installer. A
complete control diagram together with complete boiler
operating instructions shall be furnished by the installer.
The manufacturers rating data and the nameplate shall be
attached to the boiler.
Reason: The IFGC provides all necessary provisions for the installation
of listed gas boilers.
Analysis: The IMC contains many requirements for boilers that were
intended to apply to all boilers, regardless of fuel-type. Without the
reference to the IMC, it could be interpreted that Chapter 10 of the IMC
does not apply to gas-fired boilers. The IMC requirements include:
installation, piping, safety valves, pressure relief valves, electrical,
expansion tanks, low-water cutoffs, gauges and testing.
Cost Impact: None
AS
ASF
AM
AMF
D
DF
PART I IFGC
FG30-04/05
635 (New); IMC 926 (New); IRC 1904 (New)
Proponent: Guy Tomberlin, Fairfax County VA,
representing Virginia Plumbing & Mechanical Inspectors
Association and Virginia Building & Code Officials
Association
AS
ASF
AM
AMF
D
DF
AS
ASF
AM
AMF
D
DF
PART II IMC
Public Hearing: Committee:
Assembly:
AS
ASF
AM
AMF
D
DF
FG31-04/05
701.1
Proponent: Larry Fluer, Fluer, Inc., Paso Robles, CA,
representing Compressed Gas Association
Revise as follows:
701.1 Scope. The installation of gaseous hydrogen
systems shall comply with this chapter and Chapters 30
and 35 of the International Fire Code. Compressed gases
shall also comply with Chapter 27 of the International Fire
Code for general requirements. Containers provided with
pyrophoric material shall also comply with Chapter 41 of
the International Fire Code. Containers having residual
gaseous hydrogen shall be considered as full for the
purposes of the controls required.
Reason: As currently written, Section 701.1 is in conflict with Section
3503.1.6 of the IFC. Metal hydride storage systems can contain
pyrophoric solids; however, the IFC directs that when metal hydride
storage systems are used, the hazard classification of the system is
to be based on the hydrogen stored without regard to the metal hydride
content. Deletion of the reference to Chapter 41 will remove the
conflict between the IFGC and the IFC.
Chapter 30 of the IFC prescribes requirements for all compressed
gases. Section 3001.1 requires partially full containers to be regulated
in the same manner as full containers. IFGC 701.1 and 707.1 require
gaseous hydrogen systems to be in compliance with the IFC. Whether
or not the containers are full or contain residual is of no consequence
as specific requirements for containers are within the purview of the
IFC. Compliance with the IFC as required by the charging language will
ensure that containers having residual pressure are regulated as full
containers.
Cost Impact: None
AS
ASF
AM
AMF
D
DF
FG32-04/05
Revise as follows:
Reason: Without revision, the current wording has the effect of limiting
the number of hydrogen-fueled vehicles stored in such occupancies to
three. Rather than restricting the number of vehicles stored, it is the
FG27
intent that the refueling area be limited both in size (i.e., 850 square
feet) and number of vehicles (i.e., three) being refueled. Additionally
it was felt that improvements to the sentence structure of the Sections
(IFGC 703.1.1.1, IMC 304.4.1.1, IRC M1307.4.1.1) which describe the
location and size of the openings will improve interpretation and
enforcement. No other technical revisions have been made.
Analysis: Contrary to the reason statement, the revised text does not
limit the number of vehicles being refueled to three.
AS
ASF
AM
AMF
AS
ASF
AM
AMF
D
DF
D
DF
FG34-04/05
FG33-04/05
704.1.2.2
Proponent: Larry Fluer, Fluer, Inc., Paso Robles, CA,
representing Compressed Gas Association
1. Revise as follows:
704.1.2.2 Identification of piping systems. Piping
systems used to convey gaseous hydrogen shall be
identified and marked HYDROGEN, at intervals not
exceeding 10 feet (3048 mm). Letters of such marking shall
be in a color other than the color of the piping. Piping shall
be identified a minimum of one time in each room or space
through which it extends shall be marked in accordance
with ANSI A13.1. Markings used for piping systems shall
consist of the name of the contents and shall include a
direction-of-flow arrow. Markings shall be provided at all of
the following locations:
1.
2.
3.
4.
At each valve
At wall, floor and ceiling penetrations
At each change of direction
At intervals not exceeding 20 feet (6096 mm).
FG28
704.1.2.3
Proponent: Larry Fluer, Fluer, Inc., Paso Robles, CA,
representing Compressed Gas Association
Revise as follows:
704.1.2.3 (Supp) Piping design and construction. Piping
and tubing materials shall be Type 304, Type 304L, Type
316 or Type 316L 300 series stainless steel or materials
listed or approved for hydrogen service and the use intended
through the full range of operating conditions to which they
will be subjected. Piping systems shall be designed and
constructed to provide allowance for expansion, contraction,
vibration, settlement and fire exposure.
Reason: Compressed gas industry standards allow the use of
austenitic (300 series) stainless steels meeting the temperature limits of
ASME B31.3. It allows the use of Types 302, 316L and any of the other
alloys in the 300 series range. For example, type 302 stainless steel
and Type 316L stainless steels are commonly found as are other of the
300 series steels found in valves and fittings commonly used in the
fabrication of stainless steel piping systems. The restriction imposed by
the IFGC to only Types 304, 304L, 316 and 316L is impractical and fails
to recognize the common use of series 300 stainless steel for systems
of the type employed.
The term piping system is a defined term that includes the piping,
valves and fittings from the point of delivery to the point of use.
Cost Impact: None
AS
ASF
AM
AMF
D
DF
FG35-04/05
704.1.2.3.1, 704.1.2.3.2 (New), 704.1.2.3.3
(New), 704.1.2.3.2, 704.1.2.3.3, 704.1.2.3.6
Proponent: Guy Tomberlin, Fairfax County VA,
representing Virginia Plumbing & Mechanical Inspectors
systems with operating pressures less than 5 psig. With the constant
development of gaseous hydrogen systems utilizing pressures far
greater than 5 psig, these new provisions will greatly enhance safety
issues associated with interior hydrogen piping.
Cost Impact: None
AS
ASF
AM
AMF
D
DF
FG36-04/05
704.1.2.3.3
AS
ASF
AM
AMF
D
DF
FG37-04/05
704.1.2.3.8
Proponent: Larry Fluer, Fluer, Inc., Paso Robles, CA,
representing Compressed Gas Association
Revise as follows:
704.1.2.3.8 Settlement. Piping passing through interior
concrete or masonry walls shall be protected against
differential settlement.
FG29
AS
ASF
AM
AMF
D
DF
FG38-04/05
AS
ASF
AM
AMF
D
DF
1. Revise as follows:
704.1.2.4 Joints. Joints on in piping and tubing in hydrogen
service shall be listed for hydrogen service, inclusive as
complying with ASME B31.3 to include the use of welded,
brazed, flared, socket, slip or and compression fittings.
Gaskets and sealants used in hydrogen service shall be
listed for hydrogen service as complying with ASME B31.3.
Threaded or and flanged connections shall not be used in
areas other than hydrogen cutoff rooms or and outdoors.
2. Add new text as follows:
704.1.2.4.1 Brazed joints. Brazing alloys shall have a
melting point greater than 1000EF (538EC).
704.1.2.4.2 Electrical continuity. Mechanical joints shall
maintain electrical continuity through the joint or a bonding
jumper shall be installed around the joint.
Reason:
1. Section 704.1.2.4. Listed joints are being required. It is not clear
how this will be done. ASME B31.3 considers the use of the term
listed to be a material or component which conforms to a
specification listed in the appendix or to standards integral to the
materials specification tables of B31.3. On the other hand, the term
listed as used in the IFGC is defined to require that listed materials
be included in a list published by a Nationally Recognized Testing
Laboratory (NRTL), inspection agency or other organization
concerned with product evaluation. ASME is not an NRTL, nor is
it an inspection agency or an organization concerned with product
evaluation.
It is difficult to imagine that UL, FM or others will have listing
standards for the myriad of joints envisioned or available. For systems
required to conform to ASME B31.3 as specified in Section 704.1.2, the
requirements for listing should be in harmony with B31.3. Approval of
this code change will ensure that the intent of ASME B31.3 is met.
2. Section 704.1.2.4.1. ASME B31.3 does not specify a minimum
temperature for brazing alloys. Unless specified low temperature
materials could be used leading to early failure in the event of fire
exposure. A temperature of 1000 degrees F has been used for
consistency with standards of the Compressed Gas Association
and NFPA. The minimum temperature was established in NFPA 50B
FG30
FG39-04/05
Chapter 8
Proponent: Standards writing organizations as listed
below.
Revise as follows:
American National Standards Institute
25 West 43rd Street
Fourth Floor
New York, NY 10036
ANSI
Standard
reference
number
Z21.1-2003
Title
2000
Z21.5.1-2002 1999
Z21.5.2-2001
Z21.10.1-2004 2001
Z21.10.3-2001
Z21.11.2-2002
Z21.47-2003 2001
Z21.50-2003 2000
Z21.56-2001
Z21.60-2003
Z21.69-2002
Z21.84-2002
UL
Standard
reference
number
1777-2004 98
Z21.86-2004 2000
Z21.88-2002
Z83.4-2003 1999
Z83.8-2002
Z83.11-2002
Z83.18-2000
ASTM
Standard
reference
number
Title
Standard for Chimney Liners with Revisions
through July 1998
AS
ASF
AM
D
AMF DF
ASTM International
100 Barr Harbor Drive
West Conshohocken, PA 19428-2959
Title
A 106-04 02a
B 88-03 02
B 280-03 02
D 2513-04a 03
NFPA
Standard
reference
number
Title
58-01
04
82-99 04
85-04 01
211-00 03
853-00 03
FG31
FG32