DWG 40xx Troubleshooting

Troubleshooting for synchronous generator type 40xx


NOTE: At first, before checking the machine it is required to disconnect all electronic parts from
the terminal box of the generator (also the EMC filter)!
Ensure that the voltage regulator (mounted in the top of the terminal box) is disconnected.
Check of the exciter winding:
In a cold state of the machine (approx 25C), the exciter resistance is measurable between the red and
the grey wire going to the 6pin connector to the voltage regulator. These values should be measured
between 24 up to 27 Ohms. The insulation resistance between the case potential (measured with
500VDC) should be more than 100 kOhms.
Check of the winding resistance of the main stator:
The following resistance values can be read out at the datasheet table listed at page 2.
The listed values should be checked:

between the phases L1-L2-L3 (U-V-W) the resistance UV.


between the phases and the neutral wire L1-N, L2-N, L3-N the resistance U-N
between the voltage regulator supply wires (violet) the resistance ZU-ZV
between the voltage regulator supply (violet) and the neutral wire (blue) the resistance ZU-N
recommended to the VDE 0105-100 should the insulation resistance in a potential free system
more than 150 Ohm/Volt. The insulation resistance can be measured between every phase and
the case of the generator (green/yellow wire).

The measured values of the main stator winding could be differing from the rated values. It depends also
on the accuracy of the measuring equipment. The important fact is, that the measured values, witch are
belonging together should be always the same value.
If the values are differing highly from the rated values of the data sheet table, the machine should be
checked at GTS service.
terminal box
L1 - brown

L1

PE

L2 - white

L2

L3 - black

L3

N - blue
PE green/yellow
DWG
3~

AVR electronic
exciter red
exciter grey
ZU violet
ZV violet
ZW violet

picture 1

GTS Generator-Technik GmbH & Co.KG


editor: Christian Bradler

Telefon: +49 (0) 7174 / 898 00-0

version date: 09.06.2010

eMail: info@gts-generator.com
page - 1 -

DWG 40xx Troubleshooting

ID: 40xx
application
type

synchronous AC generator for power grid substitution

10 / 6 KVA

15 / 10 KVA

20 / 12 KVA

construction

DWG synchronous brushless internal pole generator

voltage regulation

Electronic AVR LCAR4HS

operating mode

S1 (continuous duty)

number of poles

number of phases

3 ~ Y-wired (neutral wire present)

nominal output power at


n = 1500 rpm

3~: 10 KVA
only 1~: 6 KVA

3~: 15 KVA
only 1~: 10 KVA

nominal voltage
nominal current

3~: 20 KVA
only 1~: 12 KVA

400 / 230 V
3~ 400 V: 14,4 A
only 1~ 230 V: 26 A

3~ 400 V: 21,5 A
only 1~ 230 V: 43,4 A

3~ 400 V: 28,8 A
only 1~ 230 V: 52,1 A

terminal

Terminal box with junction plate M8. Attached load and/or control cable wiith
external regulator on demand

Miscellaneous

voltage regulator mounted in the cover of the terminal box

nominal rotation speed

1500 min-1
Variation of nominal rotation speed on demand

Protection class / Safety


measure

IP 54 (IP69K on demand) / Potential separation

main stator winding


resistance

U-V: 0,65 Ohm


U-N: 0,32 Ohm
ZU-ZV: 0,82 Ohm
ZU-N: 0,41 Ohm

resistance of exciter
winding

U-V: 0,44 Ohm


U-N: 0,22 Ohm
ZU-ZV: 0,65 Ohm
ZU-N: 0,32 Ohm

U-V: 0,3 Ohm


U-N: 0,15 Ohm
ZU-ZV: 0,83 Ohm
ZU-N: 0,41 Ohm

26,7 Ohm (cold state at 25C)


picture 2