Professional Documents
Culture Documents
Wind Energy Research Center, Korea Institute of Energy Research, Yuseong-gu Jang-Dong 71-2, Daejeon 305-343, Republic of Korea
Power Distribution Laboratory, Korean Electric Power Research Institute, Republic of Korea
c
Hanbat National University , Building Services Engineering, Republic of Korea
b
a r t i c l e
i n f o
Article history:
Received 13 April 2007
Received in revised form 22 February 2008
Accepted 27 February 2008
Available online 16 July 2008
Keywords:
Doubly fed induction-generator
Variable-speed wind-turbine
Voltage control
Voltage-source converter
a b s t r a c t
This paper presents a modeling and a control of doubly fed induction-generator (DFIG)-based variablespeed wind-turbine. A detail dynamic model of a DFIG-based wind-turbine grid-connected system is
presented in the dq-synchronous reference frame. Along with conventional control schemes for wind
turbine, an innovative voltage control scheme is proposed that manipulates dynamically the reactive
power from the voltage-source converter (VSC) with taking into account its operating state and limits.
2008 Elsevier B.V. All rights reserved.
1. Introduction
Increased wind power generation has inuenced the overall
power system operation and planning in terms of power quality, security, stability, and voltage control [16]. The local power
ow pattern and the systems dynamic characteristics change when
large wind turbines (WTs) are connected to the utility grid [7].
Both xed-speed and variable-speed WTs are presently used in
Europe and North America. To achieve the required voltage regulation, xed-speed WTs are often complemented by additional
equipment and/or compensating devices that may be installed in
close proximity or at a remote location [811]. Doubly fed induction
generators (DFIGs) are also becoming popular for variable-speed
WTs, particularly in North America, with the modern units often
exceeding the 3 MW level [12]. Variable-speed WTs utilize power
electronic converter technology that in addition to accommodating variable-speed operation also enables rapid control of real and
reactive power [13].
In many WT applications, variable-speed operation is achieved
by appropriately controlling the back-to-back voltage-source converters (VSC). There have been a great number of publications
proposing various control solutions to achieve desirable dynamic
performance and decoupled control of active and reactive power.
Although different in implementation, most commonly used converters enable the WTs to maintain the required power factor
Corresponding author.
E-mail address: hee-sang@kier.re.kr (H.-S. Ko).
0378-7796/$ see front matter 2008 Elsevier B.V. All rights reserved.
doi:10.1016/j.epsr.2008.02.018
1842
1
b
1
b
1
b
1
b
ds
dt
d
qs
dt
d
dr
= Rs ids + e
qs
+ vds
= vqs + Rs iqs e
ds
= vdr + Rr idr + s
qr
dt
d qr
= vqr + Rr iqr s
dt
(1)
dr
with
ds
dr
qs
qr
(2)
(3)
(4)
1843
Fig. 4. Block diagram of the VSC controller showing the input/output variables.
didl
= vd2 vd1 Rtr idl + e Ltr iql
dt
diql
= vq2 vq1 Rtr iql e Ltr idl
dt
Co dvq1
dvd1
= iql e Co vd1
= idl + e Co vq1 ,
b dt
dt
(5)
(7)
Qjset
= min
Qjmax ,
Qjmax
Qrmax + Qgmax
Qpcc
where subscript lt stands for lter (see Fig. 2), and 1 and 2 indicate voltage output from the grid-side converter controller and the
voltage of bus 1, respectively.
RL load
Lload didL
= vd1 Rload idL + e Lload iqL
b dt
Lload diqL
= vq1 Rload iqL e Lload idL
b dt
Co dvd1
Co dvq1
= idL + e Co vq1 ,
= iqL e Co vd1
b dt
b dt
(8)
(9)
1844
Table 1
Operating conditions in the operation of Mode 1
BUS
Load
3
(PCC)
WT
TR
1
2
a
b
V (pu)
0.9879
Grid
Cable
Total
Load
0.9927
0.9926
P (pu)
Q (pu)
0.5391
0.3408
0.8799
1.1a
0.03873
0.11870
0.07998
0.1b
0.3415
0.3415
0
0.001206
Resistance.
Reactance.
Fig. 8. Comparison between the full-order (42nd) and the reduced-order (6th)
transfer function from the injected reactive power to the voltage at PCC.
(Scmax )2 Pj2
(10)
Fig. 11. Voltage observed at the PCC due to the wind speed variation.
1845
Fig. 12. Voltage observed at the PCC due to the 40% (left) and 50% (right) impedance decrease.
available in Simulink [23]. The resulting transfer function magnitude and phase for a considered operating point of interest are
shown in Fig. 8.
Since the order of the linearized model is very high, a modelorder reduction technique [24] is used to nd a lower order approximate transfer function that is more suitable for the purpose of tuning the controller gains. In this paper, a balanced realization modelorder reduction technique was considered as it preserves the dominant states of the system in terms of the input/output behaviour.
The reduced-order model is then obtained by neglecting modes
with the smallest Hankel singular values. The model reduction is
carried out using the Control System Toolbox [25]. Fig. 8 shows the
reduced 6th-order transfer function for the same operating point.
Fig. 13. Active and reactive power observed at the PCC due to 40% (left) and 50% (right) impedance decrease.
1846
Fig. 14. Voltage observed at the PCC due to voltage drop at innite-bus (left) and fault at the bus 3 (right).
speed variations, the local-load variations, and large-signal disturbances such as the three-phase symmetrical fault and voltage sag
were conducted to compare the dynamic responses of the system
with different controls. In comparison, Mode 1 indicates the conventional PFC-mode operation of WT, which Qrset and Qgset are set to
zero. As another conventional operation, Mode 2 implies that the
conventional local voltage control at the terminal of WT where Qrset
is actively utilized while Qgset is set to zero. Mode 3 is the proposed
scheme when both converters are used for voltage control at the
PCC; thus, both Qrset and Qgset can be instantly utilized.
6. Case studies
Fig. 15. Active and reactive power observed at the stator (Ps , Qs ), the rotor (Pr , Qr ), and the grid-side converter (Pg , Qg ) in Mode 1 (left), Mode 2 (middle), and Mode 3 (right).
1847
Fig. 16. DC-voltage observed at the DC-link and the AC-current observed at the grid-side converter in Mode 1 (left), Mode 2 (middle), and Mode 3 (right).
voltage has been recovered to its predened value. In the case of 50%
decrease of the local-load impedance, when in the Mode 1, the load
impedance changes resulted in noticeable drop of the bus voltage
(by 8%). When the WT operated in Mode 2 and 3, the voltage drop
was signicantly reduced (to 2%). However, the proposed control
scheme, Mode 3, performed faster in the bus-voltage recovery at the
PCC. Since the maximally available instantaneous reactive-power
from both converters was fully utilized, the steady-state errors from
Fig. 17. AC-voltage observed at the stator and the rotor windings in Mode 1 (left), Mode 2 (middle), and Mode 3 (right).
1848
Fig. 18. AC-current observed at the stator and the rotor windings in Mode 1 (left), Mode 2 (middle), and Mode 3 (right).
Mode 2 and Mode 3 were noticed. Fig. 13 showed the active and
reactive power observed at the PCC in the case of the 40% and 50%
impedance decrease, respectively.
6.3. Fault ride-through study
To consider a large-signal disturbance, voltage sag was assumed
at the innite-bus whose voltage was assumed by 20% decrease
from its initial value. As shown in the left-hand side in Fig. 14, the
voltage deviation by 20% has been noticed in Mode 1 while Mode
2 and 3 resulted in the voltage deviation by 12%. However, Mode 3
showed faster voltage recovery than others.
To implement another large-signal disturbance, a three-phase
symmetrical fault was assumed in the middle of TL. To emulate
this fault scenario, the fault was assumed at t = 0.2 s and was subsequently cleared at t = 0.7 s by restoring the initial TL impedance.
As can be noted in the right-hand side in Fig. 14, the fault resulted
in signicant voltage swings that can undesirably interfere with
the protection circuitry and possibly trip the WT. From this point of
view, it is desirable to minimize and/or suppress the voltage swings.
During the fault, the voltage drop has been slightly improved in
Mode 2 and 3. After the fault was cleared, faster voltage recovery to
reach to its predened voltage at the PCC was noticed in Mode 3.
In the case of the fault at the bus 3, Figs. 1518 showed more
system responses according to different mode operations such that
the active and the reactive power observed at the stator (Ps , Qs ), the
rotor (Pr , Qr ), and the grid-side converter (Pg , Qg ), the DC-voltage
observed at the DC-link and the AC-current observed at the gridside converter, the AC-voltage observed at the stator and the rotor
windings, and AC-current observed at the stator and the rotor windings.
7. Conclusion
This paper presented the modeling of DFIG-based variablespeed wind-turbine and demonstrated an advanced voltage control
scheme. The goal of investigation was to make use of available
0.15 ]
1849
SMES, in: IEEE 35th Annual Power Electronics Specialists Conference, vol. 6,
2004, pp. 42784284.
[17] Y. Kubota, T. Genji, K. Miyazato, N. Hayashi, H. Tokuda, Y. Fukuyama, Verication
of cooperative control methods for voltage control equipment on distribution
network simulator considering interconnection of wind power generators, in:
IEEE Transmission and Distribution Conference and Exhibition, vol. 2, 2002, pp.
11511156.
[18] J.G. Slootweg, S.W.H. de Haan, H. Polinder, W.L. Kling, General model for representing variable speed-wind turbines in power system dynamics simulations,
IEEE Trans. Power Syst. 18 (1) (2003) 144151.
[19] T. Ackermann, Wind Power in Power Systems, John Wiley & Sons, Ltd., UK, 2005.
[20] P.C. Krause, O. Wasynczuk, S.D. Sudhoff, Analysis of Electric Machinery and
Drive Systems, John Wiley & Sons Inc., New Jersey, 2002.
[21] H.S. Ko, Supervisory voltage control scheme for grid-connected wind farms,
Ph.D. Dissertation, Dept. Elect. and Comp. Eng., Univ. of British Columbia, Vancouver, BC, Canada, 2006.
[22] K. strm, T. Hgglung, PID Controllers, Lund Institute of Technology, 2004.
[23] Matlab and Simulink, Math Works, 2000.
[24] K. Zhou, J.C. Doyle, Essentials of Robust Control, Prentice Hall, New Jersey, 1998.
[25] Control System Toolbox for use with Matlab , MathWorks, 2000.
Hee-Sang Ko received his B.S. degree in electrical engineering from Cheju National
University, Jeju, Korea, in 1996, his M.Sc. degree in electrical engineering from Pennsylvania State University, University Park, USA, in 2000, and his Ph.D. in electrical and
computer engineering from the University of British Columbia, Vancouver, Canada,
in 2006. He is a researcher in Wind Energy Research Center, Korea Institute of Energy
Research. His research interests include wind power generation, power systems
voltage and transient stability, data processing for power systems security analysis,
electricity market analysis, and system identication.
Gi-Gab Yoon received his B.S., M.Sc., and Ph.D. degree in electrical engineering from
Hanyang University, Seoul, Korea, in 1983, 1988, and 1999. He has over 20 years of
research experience in the eld of power systems. He has published a number of
papers and provided the technical advices and consultations for industrial organizations and consulting rms. He is presently a senior researcher in power system
laboratory and advanced distribution system group at Korea Electric Power Research
Institute (Kepri). He manages and executes a number of key projects including wind
power generation system, distribution power system, intelligent power network
architecture, and modeling and control of power system.
Nam-Ho Kyung received his B.S. degree in electrical engineering from Seoul National
University, Seoul, Korea, in 1978, his M.Sc. and Ph.D. degree in electrical engineering
from Korea Advanced Institute of Science and Technology, Korea, in 1980 and 1987,
respectively. From 2006, he is the header of Wind Energy Research Group.
Won-Pyo Hong received his B.S degree in Electrical Engineering from Sungsil University, Seoul, Korea, in 1978, his M.Sc. and Ph.D. degree in Electrical Engineering
from Seoul National University, Seoul, Korea, in 1980 and 1989 respectively. He
is a professor of the Department of Building Services Engineering at the Hanbat National University. His research activities are in the areas of the building
and industrial application of eld-bus, energy management, building automation
and control, intelligent networked control, and control and planning of distributed
energy resource.