GCU-20

Generator/Engine
Control Unit
Features
Microprocessor Based Design
Universal LED Graphic Interface, Displays
Generator Status and Failures
Modular Design, Quick Installation

With Annunciator Output


Selectable MPU Signal for Speed Sensing
Suitable for Pump Engine control
With Lamp Test Function for All Front Panel
LEDs and Annunciator Lamps
Provide IDLE control For Elec. Governors
Five Adjustable Time Delay Potentiometers
Six DIP Switches For Specification Setting

* Together with RA-20 Annunciator Module


Specifications

Adjustable Timers
Engine Pre-Heat

2 ~ 30 Seconds

Starter Cranking time

1 ~ 15 Seconds

Energize to STOP

1 ~ 15 Seconds

Engine Idle (Governor)

0 ~ 300 Seconds

Engine Cool-down

0 ~ 300 Seconds

Protection & Alarm Status Indicators


Start Failure

Underspeed

High Water Temperature

No Speed Signal

Low Oil Pressure

Extra Prog. Input

Overspeed

DC Supply
Alternator Input Range

9.0 to 36 VDC
5 ~ 300VAC
50/60 Hz
MPU Signal Input Range
2V to 70V Peak
Rated MPU Frequency
100 Hz ~ 10,000 Hz
Fuel Solenoid Signal Output 10 Amp @ 12/24VDC
Start Signal Output
10 Amp @ 12/24VDC
Annunciator Output
300mA @ 12/24VDC
Power Consumption
Under 3VA on Auto
Operating Temperature
-20 ~ 70 C
Relative Humidity
< 90 %
Weight

Mechanical Specifications (mm/Inch)

????????????????
???????????????????????

??????????
?????????????
???????????
???????????????????????
??????????????
???????????????????

????????

?????????????

Installing Panel

200 gram

?
Remote Annunciator Module
Together with GCU-20 Module or other ECU with Annunciator output

Features
Works Up to 1500 Meters from The Host Module Using 18 AWG
Cable (@12/24VDC)
Universal LED Graphic Interface, Displays Generator Status and
Failures
Modular Design, Quick Installation
Circuits are Finger Safe with UL94-V0 Epoxy Protection
Simplify All Wiring with Pluggable Terminal Block
Easy Assembly & Maintenance with No Chance of Wiring Mistakes

Icon Reference Table


Icon

Description

Icon?

Description

Low Oil Pressure Alarm

Wrong speed Alarm

Auxiliary Alarm (Flashing)

No Speed Signal Alarm (Flashing)


Engine Running Indicator

High Water Temperature Alarm


Engine IDLE Indicator (Flashing)
Over Crank Alarm

Common Alarm Indicator

Specifications?
Rated Input Voltage

9.0 to 36 VDC

Operating Temperature

-20~+70 ?

Working Distance from Host ECU

1500 Meters

Relative Humidity

Maximum 95%

Standard Cable

18 AWG

Dimensions

88.0 (L) x 88.0 (W) x 37.5 (H) mm

Terminal Block Capacity

300 VAC / 15A

Weight

150 gram

Power Consumption

Under 1.0 VA

Mechanical Specifications

(Unit : mm[inch] )

Installing Panel

Universal 16 Amp 1/2 Wave Self Excited


Automatic Voltage Regulator Can Be
Used In Parallel Operation
Compatible with Marelli Motori M40FA640A-MARK I and
Caterpillar AVR(*1)

Features
< 0.5% Regulation
Suitable for brushless type generator Sensing Input
170~510 VAC
Can be used in Parallel Operation
16 ADC Current Output
Suitable Frequency 50/60 Hz
Soft Start Voltage Ramping
Load CT Current Compensation, Analogue Voltage Input

Specifications
Sensing Input

Power Input

Output

Voltage Regulation

Voltage 170~510 VAC Single Phase 2 wire

Voltage Build-up

Residual volts at AVR terminal > 5 VAC

Frequency 50/60 Hz

External Volts Adjustment

Voltage 60~300 VAC Single Phase 2 wire

CT Current Compensation Input

Max. 90 VDC @ 240 VAC input

Analogue Input

5 VDC 10% AC @ 3 VDC

Current Continuous 16A,

Unit Power Dissipation

Max. 10 Watt

Intermittent 20A for 10 Sec.

Thermal Drift

Resistance Min. 6 @ 35 VDC

Under Frequency Protection

5% with 2 K 1 watt trimmer


1A or 5A (Selectable)

0.03% per change in AVR ambient

< 0.5% (with 4% engine governing)

55 Hz @ 60 Hz , 45 Hz @ 55 Hz
(Adjustable)

Environment
Vibration

3.3G @ 100~2 KHz

Relative Humidity

Maximum 95%

Operation Temperature

-40~70

Storage Temperature

-40~85

Mechanical Specifications

Unit : mm
41

106

VOLT

Voltage Adjustment

STAB

Stability Adjustment

U/F

To Set the U/F(*2) Knee Point

DROOP

To Adjust Droop

TRIM

Analogue Input Adjustment

Physical Specification

138

156

88

AVR Control Function

X
5

Dimension

156.0 (L) x 106.0 (W) x 41.0 (H) mm

Weight

450 g 2%

Notes (*) :
1. Use for reference purpose only and not a genuine, Marelli Motori and Caterpillar
product.
2. U/F : Under Frequency protection

Built as a Mid Level voltage regulator for


use on a Marathon* generator with PMG
Self Excited Automatic Voltage Regulator
using IGBT Insulated Gate Bipolar
Transistors

Features
< 1% Regulation
110 / 220 / 400 VAC Input
PMG input Frequency 40 to 500Hz
PMG Voltage input from 25~300VAC

PMG can be single and 3 phase


Under Frequency Protection
Two-stage For STAB Adjusting Range

Specifications
Sensing Input

Terminal 0-110V 95 ~ 140V


Terminal 0-240V 185 ~ 250V

Full Load PMG

Terminal 0-400V 310 ~ 540V

+Auxiliary Winding

Frequency
Output

50/60Hz Singl Phase

<180VAC

Voltage Build-up

Single Phase 150/180Hz

Harmonic Residual Volt. >5 VAC

Voltage 90VDC @ 220VAC

Under Frequency Protection

U/F Range 42 ~ 62Hz

Current Continuous 8A

External Voltage Adjustment

10% with1K Ohm

Intermittent 12A for 10sec


Resistence 10 to 100 Ohms

EMI Suppression

Internal Electromagnetic Interference Filtering

Voltage Regulation

< 1% (with 4% engine governing)

Environment
Vibration

1.5G @ 5 ~ 30 Hz

Operating Temperature

5.0G @ 30 ~ 500 Hz

Relative Humidity

-40 to 60 Degree C.

Storage Temperature

< 95%
-40 ~?85

Mechanical Specifications
AVR Controls

Functions

VOLT

Voltage Adjustment

STAB

Stability Adjustment

U/F

UFRO Knee point set

DROOP

Droop Adjustment

TRIM

Analogue Input Adjustment

U/F DIP

U/V Rate Set

Physical Specifications

* This is not a Marathon Products


The Marathon Name is use for
Reference purpose only

UNIT : mm

Dimension

150.0 (L) x 135.0 (W) x 55.3 (H) mm

Weight

480 g 2%

8 Amp With Full Harmonic (Compounding Winding)


AVR or Harmonic + Auxiliary Winding or PMG
Automatic Voltage Regulator PWM Output
Compatible with Leroy Somer R438 * regulators
*All manufacturer names, numbers, symbols and descriptions are used for reference purpose
only and do not imply that any part is the product of these manufacturer.

Features
< 1% Regulation
110 / 220 / 380 VAC Programmable Input
Harmonic Frequency 40~500 Hz
Harmonic Voltage 25~300 VAC
Under Frequency Protection
Two-stage For STAB Adjusting Range
PWM Output

Specifications
Sensing Input

Terminal 0-110V = 95~135V

Volts Regulation

< 1% (with 4% engine governing)

Terminal 0-220V = 180~250V

Voltage Build-up

Harmonic residual volt. > 5 VAC

Terminal 0-380V = 360~515V

External Volts Adjustment

10% @ 1K

Frequency

EMI Suppression

Internal electromagnetic Interference

50/60 Hz single phase

Filtering
Voltage

Output

150 VDC @ 220 VAC

Current Continuous 8A
Intermittent 12A for 10 sec.

Under Frequency Protection

U/F range 42~62 Hz

Droop Current Transformer

N:5A or N:1A

Unload Harmonic + Auxiliary

> 40 VAC

Winding
Resistance 10~100

Full Load Harmonic + Auxiliary

< 250 VAC Single Phase 40~500 Hz

Winding

Environment
Operation Temperature
Storage Temperature

-40~+60

Relative Humidity

-40~+85

Mechanical Specifications

Vibration

Maximum 95%

1.5G @ 5~30 Hz / 5.0G @ 30~500 Hz

(Unit : mm)

AVR Control Function

A1 A2 VR VR S1 S2 S3

X1 Z1 X2 Z2 F+ F- 0V 110 220 380

UFRO
UF

STAB

LAM DROOP VOLT

TRIM

VOLT

Voltage Adjustment

STAB

Stability Adjustment

U/F

UFRO Knee point set

DROOP

Droop Adjustment

TRIM

Analogue Input Adjustment

U/F DIP

U/V Rate Set

Physical Specification

ON

Dimensions

150.0 (L) x 135.0 (W) x 55.3 (H) mm

Weight

480 g 2%

AMF Controller Interface Module


With Pluggable Terminal Block to AMF Controller*1 & BTS*1

Features
For use in Electrical Operation and Mechanical Maintenance Transfer
Switch connecting to Assorted Brand AMF Controller Available on the
Market
Simplify All Wiring with Pluggable Terminal Block
Easy Assembly & Maintenance with No Chance of Wiring Mistakes
Circuits are Finger Safe with UL94-V0 Epoxy Protection
Built-In 3 Phase Fuses to Protect Mains & Generator Circuits
Build-In Adjustable Transfer Delay Time for Mains and Generator
(10~15 Seconds)

Specifications
Item

Function

Current

Fuse Capacity

F1

Protect Normal Power Circuit

6.3A

50 KA @ 500 VAC

F2

Protect Normal Power Circuit

6.3A

50 KA @ 500 VAC

F3

Protect Normal Power Circuit

6.3A

50 KA @ 500 VAC

F4

Protect Emergency Power Circuit

6.3A

50 KA @ 500 VAC

F5

Protect Emergency Power Circuit

6.3A

50 KA @ 500 VAC

F6

Protect Emergency Power Circuit

6.3A

50 KA @ 500 VAC

Item

Function

Capacity

TB1

Connect to Transfer Switch

300VAC / 15A

TB2

C o n ne c t to A M F C o n t r o l l e r

300VAC / 15A

Mains "ON"

Transfer from Generator to Mains

250VAC / 7A

Generator "ON"

Transfer from Mains to Generator

250VAC / 7A

Mechanical Specifications

(Unit : mm)

Physical Specification
Dimensions

150.0 (L) x 135.0 (W) x 45.5 (H) mm

Weight

260 g 2%

*1 BTS : Basic Transfer Switch


*2 AMF : Automatic Mains Failure Controller

U N IT: m m

Description : Harness for use with CM0900


Usage : Connect CM0900 Control to Transfer Switch--Two Extra wires for Remote Start Connection terminal
Part NO

Length

Rated Volt

Housing

HU-087

870 mm

600VAC

AMP 770022-1

HU-150A

1500 mm

600VAC

AMP 770022-1

? ?

DoubleThrow Heavyduty ATS


with Center Off
125Amps 0.7 PF 90 to 600VACrated 3 pole
Features
Compact design -- easy installation & programming

?
?

Electrically operated, mechanically held with manual


overr ide
(Open Tr ansition) with adjustable time in neutr al
Comprehensive LE D digital display
Normal & Emergency OV and UV M onitor ing
M anufactures with high quali ty UL 94V-0 Plastic

Patent Number: U.S. Pat. No. 7,557,683

One time Exercise in 1 to 4 weeks interval with and without L oad


Recommended for use, by the Cell -Phone Industr y, Home and I ndustrial applications

TS3P125 Specifications

TC-V2 Specifications

Rated Voltage

600VAC

Over Volt Setting

110 to 530 VAC (adjustable)

Rated Cur rent

125A

Over Volt Reset

Below 10 VAC of the OV setting

Rated Frequency

50/60 HZ

Under Volt Setting

80 to 470 VAC (adjustable)

Tr ansfer

Double Throw Type

Under Volt Reset

Exceed 10 VAC of the UV setting

Operating Cur rent

2.0A @ 220V

Adjustable Time Delay

Poles

TDEN

0~90 Sec.

3P

TDNE

0~90 Sec.

Rated Short-Time Cur rent

3.0 KA/1 Sec@ 250VAC

TDEC

0~90 Sec.

Shor t Circuit Peak Value

7.5 KA

TDES

0~30 Sec.

Utili zation Categor y

AC-33A*

TDOFF

1~20 Sec.

L ife

> 6000Times/ With Load

Nor mal ON Capacity

7A @ 250VAC Max

Rated Coil Operating

TCS3P125-11 / 90~140 VAC

Standby ON Capacity

7A @ 250VAC Max

Voltage

TCS3P125-22 /180~270 VAC

Remote Start Capacity

6A @ 277 VAC / 6A @ 28 VDC Max

Class

PC

Power Consumption

< 1W

Connection

Front

Panel Cut-Out

47.0 0.5 mm x 1620.5 mm

Mechanical Specifications

Unit : mm

General Specifications
Temperature

-10~70?

Humidity

< 95%

Dimensions

167.0(H) x 172.0(W) x 85.0(D) mm

Weight

1.8 Kg 2%

* I EC60947-6 Util ization Categor y AC-33A :


1. Frequent operations.
2. Motor loads or mixed loads including motors, resistive loads
and up to 30% incandescent lamp.

Double Throw ATS With Neutral OFF

Rated Current 125 Amps Voltage 220/120 VAC

Features
Built-in control with choice of installation either on the side
of the switch or separately on the enclosure door
Electrically operated mechanically held type ATS
Manual Emergency Override handle
Delay on OFF position (Adjustable from 0 to 18 sec.)
Switch and connection indicator lights
Checks for normal source over and under voltages
Built-in 7-Days exerciser -- with or without load
Adjustable TDEN, TDNE, TDES, TDEC timers
Designed for the cell-phone industry, industrial & home use
Compact size

TS125

Specifications

Rated Voltage
Rated Current
Rated Frequency
Transfer
Operating Current
Poles
Rated Short-Time Current
Short Circuit Peak Value
Utilization Category
Life
Model Number
Class

Connection
Plastic

120/240 VAC
125 A
50/60 Hz
Double Throw Type
2.6A @ 220V
2P
10 KA/one sec. @ 250 VAC
25 KA
AC-33A*
>6000 Times With Load
TSC2P125-22
PC
Front
UL94V-0

Overvoltage Trip
Overvoltage Reset
Undervoltage Trip
Undervoltage Reset
Adjustable Time Delay

Remote Start Dry Contact Capacity


Power Consumption
Door Mount Cut-Out

270VAC (Factory Set)


260VAC
170VAC (Factory Set)
180VAC
TDEN
0 ~ 30 Sec. 10%
TDNE
0 ~ 30 Sec. 10%
TDEC 0 ~ 120 Sec. 10%
TDES 0 ~ 90 Sec. 10%
TD OFF 0 ~ 18 Sec. 10%
6A @ 277 VAC / 6A @ 28 VDC Max
< 1W
47.0 0.5 mm Wide x 162 0.5 mm
1.8 Inches wide x 6.4 Inches High

Mechanical Specifications

General Specifications
Temperature
Humidity
Weight
Dimensions

-10 ~ 70 Degree C
< 97%
1.6 KG / 3.5 lbs
H*W*D=168.0*151.5*85.0mm
H*W*D= 6.6 x 6 x 3.35

Note: IEC60947-6
Utilization Category AC-33A
1. Frequent operations
2. Motor loads or mixed loads including motors, resistive
loads and up to 30% incandescent lamp

UNIT: mm

Assembles using the ATS-01


TSP-15 Logic boards and
Plated Cooper Buss Bars

Universal Electronic Engine Governor


Controller with Smoke Limiting, & Idle Speed. Works
with Built-in & Non-Built-in PTs Pumps, also can be used
with Low Current, Electric over Hydraulic Oil Pumps Type
Governor Actuators

Features
Works on a wide ranges of MPU/flywheel frequencies
15Amp Max Output
Suitable for all types of diesel and Gas engines
High Sensitivity and stable at Low Frequency Variations
Moisture, vibration, and rust protected, Epoxy encapsulated
electronics
For Use With Isochronous Generators & Automatic Paralleling
PLC controls
Idle Speed Adjustment and connections for a Remote Speed
POT

Specifications
Operating Voltage

12/24 VDC Auto Select

Ramp Time

3 to 20 Sec. Adjustable

Output Current

From 20ma to 15Amp

Operation Environment

Vibration

Frequency Range

600Hz~9500Hz (PMG Signal)

Relative Humidity Maximum 95%

Idle Speed Frequency

Adjustable From 30~85% of normal

Operation Temp.

Speed Band

0.25% at Steady State

Storage Temp.

Temp. Stability

Between -40~85 Better than 0.5%

Dimension

147.0 (L) x 114.0 (W) x 40.0 (H) mm

between

Weight

700g 2%

Remote Speed Adjustment Range

Adjustable Range 5% with 5

(2 mode)

K potentiometer

Mechanical Specifications

DROOP

INT.

GAIN

Unit : mm

RAMP-TIME

3G @ 100~2KHz

-40~85
-40~85

DIP Switch Description


SW1

ON 600~1200Hz

SW2

ON 1200~2500Hz

SW3

ON 2500~5000Hz

SW4

ON 5000~9500Hz

SW

Governor Controls
POWER : DC12/24V
SW1-ON 600~1200HZ
SW2-ON 1200~2500HZ
SW3-ON 2500~5000HZ
SW4-ON 5000~9500HZ
IDLE SPEED

REMOTE
SPEED POT

+
1

IDLE

ACT

RUN SPEED

ILS

DROOP
GAIN
Int.

Droop rate Adjustment


MPU Output Gain Adjustment
Engine Stability Adjustment

10 MPU 11

RAMP TIME
SPEED
IDLE

Soft Start Adjustment


Speed Adjustment
Idle Speed Adjustment

Magnetic Pickups (MPU)


Is a measuring device for monitoring the speed of the driving force.
When a ferromagnetic object (Usually the generators flywheel gear)
passes by the tip of the MPU, it produces a magnetic field, the MPU
induced a voltage signal internally, and the frequency of the voltage as
the input to the speed control signal and accurately measure the prime
mover speed.

Specifications

Environment

DC Resistance

95 3%

Operating Temperature

-40~+100

Output Signal

12 VAC (P-P) @ 5 KHz

Vibration

3G @ 100~2 KHz

Clearance

0.5 mm

Mechanical Specifications

(Unit : mm[inch] )

TYPE : EM81

TYPE : EM121

Installation Reference

(Unit : mm[inch] )

27.6VDC 3A
International Model

Automatic Battery Charger for Generators


GENERAL INFORMATION
Model SS3524 Intelligent Switch Mode Battery Charger
Is an easy to install compact charger specially intended for
use in gensets. It's wide input voltage range allows the
charger to be used in many different countries.

The SS3524
battery chargers
use computer
technology to
sense the battery
condition and
maintain the
correct charge and
maintenance levels

The charger is designed for permanent connection to


automotive batteries. It maintains the battery fully charged,
without overcharging or gassing. The charger is protected
from reverse polarity, short circuit and overloads.
Emergency Charge Fail Alarm is conveniently built in.
Multiple units may be connected in parallel in order to
obtain higher current ratings.

SPECIFICATIONS

DANGER

Power supply : 100 ~ 240V, 45 ~ 65 Hz


DC Output : 27.6VDC 3ADC (continuously)
Charge Mode : Float
DC Voltage Regulation :
<1%
Efficiency : >80% @full load
Operating Temperature : 0 C ~ 40 C
Humidity :
0 ~ 90% Relative Humidity
Vibration & Shock : 5 ~ 50Hz 2mm pk - pk
50 ~ 100 Hz 1mm pk - pk
100 mm drop onto chassis face
Contact Capacity : 0.5A @240VAC
Protection : current limiting protection
short circuit protection
reverse polarity protection
Weight : 0.72 Kgs (1.6 lbs) Powder Coated Aluminum

INSTALLATION INSTRUCTIONS

1. Danger: Potentially lethal voltages are present


inside the charger. Do not open case and attempt
to adjust or repair this unit.
2. Ventilate battery enclosure, batteries generate
explosive hydrogen gas.
3. Avoid flames and sparks near batteries
4. Avoid high humidity and corrosive gases near charger
5. Minimum battery voltage must higher than 10 VDC or
the charger will automatically disconnect.
6. This is not a power supply. Use only as a battery
charging.

OUTLINE DRAWING

2.9"

1. Use on a 2 x 12V Lead Acid Battery only


2. With Line power disconnected, connect Battery terminals
"+/-" to battery leads "+/-"
3. Connect Line voltage to battery charger on lines L1 & L2,
form 100 to 240 Vac 50/60 Hz
4. Charging voltage should be 27.6+/-0.2VDC and the
indicate LED marked "ON" should illuminated when
power is ON

TM

McPherson
Controls

2.61

6. With Power ON check charge current LED bar. The


current decreases as the battery charges.
7. "0 A" indicates the battery is fully charged.
9. Charger can remains connected during engine cranking
and running.
10. Voltage sensing circuit automatically disconnect power
when the battery is fully charged.
11. Emergency Charge Fail Alarm Relay Available for use
as part of a charge fail engine protection alarm.

4.43"

Caution! Crimp and property secure terminal lugs on to


power wires to avoid shorts

ON
Attention
Battery Low

TM

0.7 1.5 2.2 3.0


Charging Current (A)

24V AUTOMATIC BATTERY CHARGER


Power In : 100 to 240
Output : 27.6 Vdc 3 Adc

Model
SS3524

Power
100 to

L1

Charge Fail Relay

L2

Output

4.72"

McPherson@mtspowerproducts.com
www.mtspowerproducts.com
1.800-541-7677

Page 41

13.8VDC 5A
International Model
Automatic Battery Charger for Generators
GENERAL INFORMATION
Model SS3512 Intelligent Switch Mode Battery Charger
Is an easy to install compact charger specially intended for
use in gensets. It's wide input voltage range allows the
charger to be used in many different countries.

The SS3512
battery chargers
use computer
technology to
sense the battery
condition and
maintain the
correct charge and
maintenance levels

The charger is designed for permanent connection to


automotive batteries. It maintains the battery fully charged,
without overcharging or gassing. The charger is protected
from reverse polarity, short circuit and overloads.
Emergency Charge Fail Alarm is conveniently built in.
Multiple units may be connected in parallel in order to
obtain higher current ratings.

DANGER

SPECIFICATIONS
Power supply : 100 ~ 240V, 45 ~ 65 Hz
DC Output :
13.8VDC 5ADC (continuously)
Charge Mode: Float
DC Voltage Regulation:
<1%
Efficiency :
>80% @full load
Operating Temperature :
0 C ~ 40 C
Humidity :
0 ~ 90% Relative Humidity
Vibration & Shock: 5 ~ 50Hz 2mm pk - pk
50 ~ 100 Hz 1mm pk - pk
100 mm drop onto chassis face
Contact Capacity: 0.5 @240VAC
Protection :
current limiting protection
short circuit protection
reverse polarity protection
Weight : 0.72 Kgs (1.6 lbs) Powder Coated Aluminum

1. Danger: Potentially lethal voltages are present


inside the charger. Do not open case or attempt
to adjust or repair this unit.
2. Ventilate battery enclosure, batteries generate
explosive hydrogen gas.
3. Avoid flames and sparks near batteries
4. Avoid high humidity and corrosive gases near charger
5. Minimum battery voltage must higher than 5 VDC or
the battery charger will automatically disconnect.
6. This is not a power supply. Use only as a battery
charging.

INSTALLATION INSTRUCTIONS

OUTLINE DRAWING

2.9"

1. Use on a 12V Lead Acid Battery only


2. With Line power disconnected, connect Battery terminals
"+/-" to battery leads "+/-"
3. Connect Line voltage to battery charger on lines L1 & L2,
form 100 to 240 Vac 50/60 Hz
4. Charging voltage should be 13.8+/-0.2VDC and the
indicate LED marked "ON" should illuminated when
power is ON

Page 42
TM

McPherson
Controls

2.61

6. With Power ON check charge current LED bar. The


current decreases as the battery charges.
7. "0 A" indicates the battery is fully charged.
9. Charger can remains connected during engine cranking
and running.
10. Voltage sensing circuit automatically disconnect power
when the battery is fully charged.
11. Emergency Charge Fail Alarm Relay Available for use
as part of a charge fail engine protection alarm.

4.43"

Caution! Crimp and property secure terminal lugs on to


power wires to avoid shorts

ON
Attention
Battery Low

TM

1.2 2.5 3.7 5.0


Charging Current (A)

12V AUTOMATIC BATTERY CHARGER


Power In : 100 to 240
Output : 13.8 Vdc 5 Adc

Model
SS3512

Power
100 to

L1

Charge Fail Relay

L2

4.72"

McPherson@mtspowerproducts.com
www.mtspowerproducts.com
1.800-541-7677

Output

Automatic Float Battery Charger


12 and 24 volt 10 Amps Low Ripple
Features
Adjustable for Lead Acid and NiCad Batteries
Float Charge Factory Det For Lead Acid
Battery, Charger Will Supply Current Until
Battery voltage is Equal to Set Voltage
Over-Voltage Protection
Current Limiting Protection
For Use in 120 and 240 Volt Inputs

Specifications
AC Power Input

1 Phase 120Vac +/- 10%


1 Phase 240Vac +/- 10%

Final Charge

13.8 Vdc for CH1912


27.6 Vdc for CH1924

Output Current

10Adc Mx for CH1912


10Adc Vdc for CH1924

Power Input Fuse 5 Amp / 250 Vac


Dimencion

12 Inches Wide
7 Inches High
5.5 Inches Deep

Unit Power Dissipation


Protection

Weight

230 W Max

Reverse Polarity
Over Voltage
Short Circuit
Current Limiting
5.4 Kg --- 12 lbs

CH1712
CH1724
Automatic Battery Charger
Wall Mountable 20Amp
Features







Low Ripple Voltage ( Below +/- 3% )


Float / Equalize Charge Mode
Adjustable Equalize Charging Time
Voltage Detector and Over Voltage Protection
No Current Drain When Input Power Is Off
Set Any Charge Current Up To 20 Amp with
Over Current Protection
 Selectable 110 / 220 VAC Input

Specifications
AC Power Input

Voltage

1 Phase 100 / 220 VAC 10%

Charge Mode

Float Charge and Equalize Charge

Frequency

50 / 60 Hz

Cooling

Forced Fan Cooling

Efficiency

80% @ Full Load

CH1724 Charge 24 VDC Battery at 28.8 VDC

Ripple

3%

CH1712 Charge 12 VDC Battery at 13.8 VDC

Protection

Short circuit, over current,

5%

Equalize Charge Output Voltage CH1712 Charge 12 VDC Battery at 14.5 VDC

Float Charge Output Voltage

CH1724 Charge 24 VDC Battery at 27.6 VDC

charge fail alarm, over voltage

Equalize Charge Voltage Range

12 VDC 13.5VDC ~ 16.0VDC Adjustment

no current drain when input power is off

24 VDC 27.0VDC ~ 31.0VDC Adjustment

Dimension

400 (L) x 300 (W) x 295 (H) mm

Float Charge Voltage Range

12 VDC 13.0VDC ~ 14.5VDC Adjustment

Weight

CH1712

24.6 Kg 2

CH1724

30.0 Kg 2

24 VDC 25.8VDC ~ 28.0VDC Adjustment


Output Current Range

0.5 ADC ~ 20.0 ADC

Operation Temp.

-10 ~ 40

Output Voltage Regulation

< 1%

Storage Temp.

-20 ~ 40

Equalize Charging Time

61224 Hours setting

Relative Humidity

< 90 %

Mechanical Specifications
FRONT VIEW AND ILLUSTRATIONS
DC Voltage Meter
DC Current Meter
Power LED
Float Charge LED
Equalize Charge LED
Equalize Charge Setting Button
Input Power MCCB
Output Power MCCB
Adjustable Equalize Voltage
Adjustable Charge Voltage
Adjustable Float Charge Current

UNIT: mm

Compact muffler systems designed to supply high-quality


intake and exhaust sound
attenuation to the industrial
engine and compressor
market.
We also designed, engineered
and manufacture to meet
OEM customer specifications.

www.mcphersoncontrols.com

2
2.5

71/8

2ID

83/4

3ID

151/2

4
5

147/8

4ID

151/2 231/8 167/8 151/2

16

5ID

193/8 253/8 241/4 193/8

22

6ID

193/8 313/8 251/4 193/8

2.5ID 133/8

131/2 109/16

149/16 147/8 133/8

16

167/8 151/2

MCPHERSON HEAVY DUTY FILTER & WATER SEPARATORS


McPherson Controls preassembles filter kits are
intended for easy installation on the vacuum side of the
engine fuel pump. These assemblies protect the engine
injection system from water, tank rust, dirt, algae, and
varnishes. Contaminated diesel fuels can no longer harm
your engine.
Similar to the RACOR* Model 1000FH this assemblies
can be fitted with a large number of aftermarket filter
cartridges including; RACOR*, Baldwin*, Donaldson*,
Fleet-Guard*, Luber-Finer*, etc. they can in 2, 10, and 20
micron.

Model WS1000-1A Similar to RACOR* 1000FH


Max Flow Rate: 180 gph
Size 11.5 High, 5.8 Wide, 4.8 Depth
Port Size 3/4-16UNF
Wt 10 lbs

Model WS1000-2A Similar to RACOR* 75/1000FHX


Max Flow Rate: 360 gph
Size 22 High,18.75 Wide, 11 Depth
Port Size 7/8-14UNF
WT 31 lbs
* For reference purpose only, not a genuice RACOR, Baldwin*,
Donaldson*, Fleet-Guard*, Luber-Finer* product

4501 NW 27 ave
Miami FL 33142
Ph 305-634-1511
Fax 305-634-1461

Model WS1000-2A Similar to RACOR* 79/1000FHV


Max Flow Rate: 540 gph