You are on page 1of 4

NOUWERK

G L O B A L

A LT E R N AT I V E

P O W E R

S O L U T I O N S

NOUWERK

G LO B A L A LT E R N AT I V E P OW E R S O LU T I O N S

300-495 kVA DIESEL GENERATOR SETS


Features:
l
l
l

l
l
l

High quality, reliable and complete power units.


Long life with compact design.
Quality components including Cummins engines and Stamford
alternators.
Excellent fuel efficiency.
Easy start and maintenance possibilities.
Every generating set is subject to a comprehensive test
programme including full load testing and control and safety
shut down function settings.
Fully engineered with a wide range of options and accessories
including canopy, sound proof canopy and on-road trailer.

Contents:

NOUWERK

Design Features

Page 2

Technical Data

Page 3-4

65 4th FLOOR, NARATHIWAT ROAD

SILOM

T: +66 2 2375978 - 9

BANGRAK

F: +66 2 237 5974

BANGKOK

10500 THAILAND

NOUWERK

G L O B A L

A LT E R N AT I V E

P O W E R

S O L U T I O N S

NOUWERK

G LO B A L A LT E R N AT I V E P OW E R S O LU T I O N S

PREMIUM range

PAGE 2

300-495 kVA DIESEL GENERATOR SETS Design Features


ENGINE
l
l
l
l
l
l
l
l
l
l
l
l
l

CONTROL SYSTEM

Heavy duty diesel engine.


Four stroke, water cooled, turbocharged
Direct injection fuel system.
12/24 V D.C. starter and charge alternator.
Replaceable fuel filter, oil filter and dry element air filter.
Cooling radiator and fan.
Starter battery (with lead acid) including Rack and Cables
Flexible fuel connection hoses and manual oil sump drain valve.
Indutrial capacity exhaust silencer and steel bellows.
Fuel stop solenoid
Fuel pump
Jacket water heater (at automatic models).
Operation manuals and circuit diagram documents.

l Control, supervision and protection panel is mounted on the genset base frame.
The control panel is equipped as follows:
1. Auto, Mains Failure Control Panel:
Panel euipment:
Control with AMF module
Static battery charger
Emergency stop push button
a) Generating set control module features:
The module is used to monitor a mains supply and automatically start a
standby generating set.
Micro-processor based design
Automatic control of mains and generator contactors
Monitors engine performance and AC power output
LED alarm indication
Front panel configuration of timers and alarm trip points
Easy push button control
STOP/RESET - MANUAL - AUTO - TEST - START

ALTERNATOR
l
l
l
l
l
l
l

Brushless, single bearing system, flexile disc, 4 poles.


Insulation class H
Temperature class H
Standard degree of protection IP21
Self-exciting and self-regulating.
Impregnation with tropiclised epoxy varnish.
Solid stade Automatic Voltage Regulator.

CHASSIS
l The complete generator set is mounted as whole on a heavy-duty fabricated,
steel base frame.
l Antivibration pads are fixed between the engine/alternator feet and the base frame.
l Base frame design incorporates an integral fuel tank.
l The generating set can be liefted or carefully pushed/pulled by the base frame.
l Dial type fuel gauge and drain plug on the fuel tank.
l Forklift pockets within base frame (up to 500kVA).

CANOPY
l
l
l
l
l
l
l
l
l

All canopy parts are designed with modular principles.


Without welding assembly.
Doors on each side.
All metal canopy parts are painted by electrostatic polyester powder paint.
Exhaust selincer is protected against environment influences.
Thermally insulated engine exhaust system.
Emergency stop push button is installed outside of canopy.
Easy lifting and moving.
Easy maintenance and operation.

DIESEL ENGINE
Oil heater
ALTERNATOR
3 pole output circuit breaker
Anti-Condesation heater
PANEL
Charge ammeter
Transfer switch 3 pole
Transfer switch 4 pole
Earth fault, single set

NOUWERK

c) Alarms:
Over and Under Speed Start and Stop Failure Over Current Under / Over Generator Voltage
Low and High Battery Volt
Charge fall
Low Oil Pressure
Emergency stop
High engine temperature
c) LED Indications:
Mains available
Generator available
Mains on load
Generator on load

ACCESSORIES
Bulk fuel tank
Automatic filling system
Low fuel level alarm
Residential silencer
Enclosure of soundproof canopy
Trailer
Manual oil drain pump
Tool kit for maintenance

65 4th FLOOR, NARATHIWAT ROAD

b) Metering via LED display:


Generator Volts (L-L / L-N)
Generator Ampere (L1,L2,L3)
Generator Frequency (Hz)
Engine hours run
Engine oil pressure (PSI-Bar)
Engine temperature ( C)
Plant battery volts
Mains Volts (Ph-Ph/Ph-N)

2. Power Outlet Terminal Board Mounted on the Genset Baseframe.

SILOM

T: +66 2 2375978 - 9

BANGRAK

F: +66 2 237 5974

BANGKOK

10500 THAILAND

NOUWERK

G L O B A L

A LT E R N AT I V E

P O W E R

S O L U T I O N S

NOUWERK

G LO B A L A LT E R N AT I V E P OW E R S O LU T I O N S

PREMIUM range

PAGE 3

300-495 kVA DIESEL GENERATOR SETS Technical Data ... continued next page
MODEL

NAA300

NAD330

NAC330

NAC350

NLS350

NAC385

Power Pf.0.8 standby

300kVA 240kW

330kVA 264kW

330kVA 265kW

350kVA 280kW

350kVA 280kW

385kVA 308kW

Power Pf.0.8 prime

273kVA 218kW

300kVA 240kW

300kVA 240kW

316kVA 252kW

320kVA 256kW

350kVA 280kW

Make

Aksa

Doosan

Cummins

Cummins

Caterpillar

Cummins

Model

WD618-42D

P126TI-II

NTA855-G1A

NTA855-G1B

12V135JZD

NTA855-G2A

Alternator

Aksa

Aksa

Stamford

Stamford

Omega

Stamford

Engine Power Output at rated rpm

259 kWm 347 HP

265 kWm 355 HP

291 kWm 390 HP

321 kWm 430.46 HP

300 kWm 400 HP

343 kWm 460 HP

Aspiration and Cooling

Turbocharged & IC*

Turbocharged & IC*

Turbocharged & AC*

Turbocharged & AC*

Turbocharged

Turbocharged & AC*

Total Displacement (Litre)

11.6

11.05

14

14

25.75

14

No. of Cylinders and Build

6 - inline

6 - inline

6 - inline

6 - inline

12-V

6 - inline

Engine Speed (rpm)

1500

1500

1500

1500

1500

1500

Bore and Stroke (mm)

126 x 155

123 x 155

140 x 152

140 x 152

135 x 150

140 x 152

Compression Ratio

16.5: 1

17: 1

14.5: 1

14: 1

16.5: 1

14: 1

Governor

Electronic

Electronic

Electronic

Electronic

Electronic

Electronic

Fuel Consumption at full load (L/Hr)

55

63.1

61

68

75

72

Fuel Tank Capacity (Litre)

525

525

525

525

320

525

Oil Capacity (Litre)

24

23

38.6

38.6

75

38.6

Coolant Capacity (Litre)

86

19

60.6

60.6

79

60.6

Radiator Cooling Air (m./min)

460

481

456

456

13

456

Air Intake - Engine (m./min)

25

20.1

21.18

22.5

20

22.5

Exhaust Gas Flow (m./min)

61

47.4

49.56

58.8

57.8

59.16

Noise Level db(A)@m

86

86

85

79

<70

86

DIESEL ENGINE

Standby: Continuous running at variable load for duration of an emergency. No overload is permitted on these ratings. In accordance with ISO3046.
Prime: Continuous running at variable load for unlimited periods with 10% overload available for 1 hour in any 12 hour period. In accordance with ISO 8528, ISO 3046.
*AC: After Cooled * IC : Inter Cooled

SOUND ATTENUATED TYPE

NAA300

NAD330

NAC330

NAC350

NLS350

NAC385

Dimensions mm (L x W x H)

3900 x 1463 x 2166

4520 x 1460 x 2190

4500 x 1463 x 2150

4500 x 1463 x 2150

3800 x 1450 x 1760

4600 x 1463 x 2150

Dry Weight (kg)

3390

3250

3860

3860

2750

3980

NOUWERK

65 4th FLOOR, NARATHIWAT ROAD

SILOM

T: +66 2 2375978 - 9

BANGRAK

F: +66 2 237 5974

BANGKOK

10500 THAILAND

NOUWERK

G L O B A L

A LT E R N AT I V E

P O W E R

S O L U T I O N S

NOUWERK

G LO B A L A LT E R N AT I V E P OW E R S O LU T I O N S

PREMIUM range

PAGE 4

300-495 kVA DIESEL GENERATOR SETS Technical Data ... continued


MODEL

NAD410

NAC412

NLS418

NAD475

NLS495

Power Pf.0.8 standby

410kVA 328kW

412kVA 329.6kW

418kVA 335kW

475kVA 380kW

495kVA 395kW

Power Pf.0.8 prime

370kVA 296kW

375kVA 300kW

380kVA 300kW

425kVA 340kW

450kVA 360kW

Make

Doosan

Cummins

Caterpillar

Doosan

Caterpillar

Model

P158LE-I

NTAA855-G7

12V135AZLD

P158LE

12V135BZLD

Alternator

Aksa

Stamford

Omega

Aksa

Omega

Engine Power Output at rated rpm

327 kWm 438 HP

377 kWm 505 HP

370 kWm 500 HP

363 kWm 487 HP

370 kWm 500 HP

Aspiration and Cooling

Turbocharged & IC*

Turbocharged & IC*

Turbocharged

Turbocharged & IC*

Turbocharged

Total Displacement (Litre)

14.6

14

25.75

14.6

26.5

No. of Cylinders and Build

8-V

6 - inline

6 - inline

8-V

12-V

Engine Speed (rpm)

1500

1500

1500

1500

1500

Bore and Stroke (mm)

128 x 142

140 x 152

135 x 152

128 x 142

135 x 155

Compression Ratio

15: 1

14: 1

16.5: 1

15: 1

16.4: 1

Governor

Electronic

Electronic

Electronic

Electronic

Electronic

Fuel Consumption at full load (L/Hr)

78.7

86

85

89.3

90

Fuel Tank Capacity (Litre)

750

525

350

750

450

Oil Capacity (Litre)

28

38.6

75

28

75

Coolant Capacity (Litre)

20

60.6

83

20

83

Radiator Cooling Air (m./min)

623

456

13

623

14

Air Intake - Engine (m./min)

23.5

30.6

24.2

25.3

28.8

Exhaust Gas Flow (m./min)

59.5

69

69.9

78.3

83

Noise Level db(A)@m

83

88

<70

83

<70

DIESEL ENGINE

Standby: Continuous running at variable load for duration of an emergency. No overload is permitted on these ratings. In accordance with ISO3046.
Prime: Continuous running at variable load for unlimited periods with 10% overload available for 1 hour in any 12 hour period. In accordance with ISO 8528, ISO 3046.
*AC: After Cooled * IC : Inter Cooled

SOUND ATTENUATED TYPE

NAD410

NAC412

NLS418

NAD475

NLS495

Dimensions mm (L x W x H)

4600 x 1600 x 2150

4500 x 1463 x 2150

3800 x 1450 x 1760

4600 x 1600 x 2150

3800 x 1450 x 1760

Dry Weight (kg)

3460

4060

3050

3530

3050

NOUWERK

65 4th FLOOR, NARATHIWAT ROAD

SILOM

T: +66 2 2375978 - 9

BANGRAK

F: +66 2 237 5974

BANGKOK

10500 THAILAND

You might also like