You are on page 1of 6

TASK ORDER # TBD PWS LCT SIMULATOR POWER REQUIREMENT

SAR

DOLLARS

SAR 0.00

$0.00

Purchase and install Disconnect Switch, 3P, 200A, 600 V on outside the North-West Wall of
2 Simulation Building B029 for use by the TBOS at the Hangar.

SAR 0.00

$0.00

Purchase, install and terminate power cable, 4/C (conductor 3 phase + neutral) + ground, 160
Amperes minimum, XLPE (Cross-linked polyethylene) 600/1000V insulation, with outer overall
3 jacket (EPR or thermoplastic), stranded copper conductor and including pulling inside the new
EMT conduit (sized per NEC) which terminates to the new 160A MCCB at MDP-029 and the
new Disconnect Switch (see item 2).

SAR 0.00

$0.00

Purchase and install EMT conduit from MDP-029 to the New Disconnect Switch (see item 3)
4 including all brackets and accessories as required to tie up with the existing cable tray and cutting
of the North-West wall.

SAR 0.00

$0.00

SAR 0.00

$0.00

Bldg B-029
Purchase and install one (1) MCCB (Molded Case Circuit Breaker), 3P, 160A, 36KA, Code
1SDA067418R1, type XT1N 160 TMD 160-11600 3 P F F 160A 36KA, ABB-SACE make
(see MDP-029 drawings attached), including cutting of MDP-029 Front Panel allocated space
1
and installation to MDP-029 Space Bus Bars and frames for branch circuit of the TBOS at the
Hangar of B029

Fill in the five holes with concrete and repaint with at least one primer and two (2) finished coat
matching the type of paint and color and architectural finishes to existing wall. This wall will be
5 used to install the New 200 A Disconnect Switch (see item 2) and for use by the TBOS installer
for their installation of two other disconnect switches (comes with TBOS).

Weld two (2) C channel steel at the Vertical Beam Steel Structure so that the LCT installer can
mount their Disconnect Switch and provide a 4 inch hole on the North Wall for installation of
6 EMT conduit by LCT installer, coordinate with LCT installer the required place and length of the
C channel (proper size to have a vertical mounting of Disconnect Switch) and location of the
hole.
Class Room C-00
Purchase and install Disconnect Switch, 3P, 80A minimum, 600V rated for the 45KVA Step7 down transformer of the MT-STT Trainer at the class room designated by MNG Aviation.
Purchase and installation of EMT Conduit (sized per power cable size per item 3 below)
including all brackets and mounting accessories to the concrete ceiling and concealed above false
8 ceiling from the main Panelboard at electrical room and the class room (tentatively class room 2,
the correct room need to be confirmed with MNG Aviation).
Purchase power cable, 4/C (conductor 3 phase + neutral) + ground, 80 Amperes minimum,
XLPE (Cross-linked polyethylene) 600/1000V insulation, with outer overall jacket (EPR or
thermoplastic), stranded copper conductor and including pulling inside the new EMT conduit
9
(item 2 above) and termination to the spare 80A MCCB at Panelboard in electrical room and the
new Disconnect Switch (see item 1) for the 45KVA step-down transformer of MT-STT Trainer.

SAR 0.00

$0.00

SAR 0.00

$0.00

SAR 0.00

$0.00

SAR 0.00

$0.00

TASK ORDER # TBD PWS LCT SIMULATOR POWER REQUIREMENT

Bldg B-029
Purchase and install one (1) MCCB (Molded Case Circuit Breaker), 3P, 160A, 36KA, Code
1SDA067418R1, type XT1N 160 TMD 160-11600 3 P F F 160A 36KA, ABB-SACE make
(see MDP-029 drawings attached), including cutting of MDP-029 Front Panel allocated space
1
and installation to MDP-029 Space Bus Bars and frames for branch circuit of the TBOS at the
Hangar of B029

Purchase and install Disconnect Switch, 3P, 200A, 600 V on outside the North-West Wall of
2 Simulation Building B029 for use by the TBOS at the Hangar.
Purchase, install and terminate power cable, 4/C (conductor 3 phase + neutral) + ground, 160
Amperes minimum, XLPE (Cross-linked polyethylene) 600/1000V insulation, with outer overall
3 jacket (EPR or thermoplastic), stranded copper conductor and including pulling inside the new
EMT conduit (sized per NEC) which terminates to the new 160A MCCB at MDP-029 and the
new Disconnect Switch (see item 2).
Purchase and install EMT conduit from MDP-029 to the New Disconnect Switch (see item 3)
4 including all brackets and accessories as required to tie up with the existing cable tray and cutting
of the North-West wall.
Fill in the five holes with concrete and repaint with at least one primer and two (2) finished coat
matching the type of paint and color and architectural finishes to existing wall. This wall will be
5 used to install the New 200 A Disconnect Switch (see item 2) and for use by the TBOS installer
for their installation of two other disconnect switches (comes with TBOS).

Weld two (2) C channel steel at the Vertical Beam Steel Structure so that the LCT installer can
mount their Disconnect Switch and provide a 4 inch hole on the North Wall for installation of
6 EMT conduit by LCT installer, coordinate with LCT installer the required place and length of the
C channel (proper size to have a vertical mounting of Disconnect Switch) and location of the
hole.
Class Room C-00
Purchase and install Disconnect Switch, 3P, 80A minimum, 600V rated for the 45KVA Step7 down transformer of the MT-STT Trainer at the class room designated by MNG Aviation.

Purchase and installation of EMT Conduit (sized per power cable size per item 3 below)
including all brackets and mounting accessories to the concrete ceiling and concealed above false
8 ceiling from the main Panelboard at electrical room and the class room (tentatively class room 2,
the correct room need to be confirmed with MNG Aviation).
Purchase power cable, 4/C (conductor 3 phase + neutral) + ground, 80 Amperes minimum,
XLPE (Cross-linked polyethylene) 600/1000V insulation, with outer overall jacket (EPR or
thermoplastic), stranded copper conductor and including pulling inside the new EMT conduit
9
(item 2 above) and termination to the spare 80A MCCB at Panelboard in electrical room and the
new Disconnect Switch (see item 1) for the 45KVA step-down transformer of MT-STT Trainer.

PERFORMANCE PERIOD : 6-8 DAYS

QUIREMENT
SAR

DOLLARS

SAR 5,500.00

$1,466.67

SAR 11,500.00 $3,066.67

NEMA 3R
~15 METERS

SAR 6,000.00

$1,600.00

SAR 7,000.00

$1,866.67

SAR 4,600.00

$1,226.67

SAR 2,500.00

$666.67

SAR 5,500.00

$1,466.67

SAR 8,200.00

$2,186.67
36LM

SAR 5,600.00

$1,493.33
36LM

SAR 56,400.00 $15,040.00

You might also like