ENGINEERING SPECIFICATION
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
PDVSA N253
REVISION
FECHA
NOV.00
Pgina 1
.Men Principal
Indice manual
Indice volumen
Indice norma
Index
SECTION 1 (GENERAL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1
Exceptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1
5.2.
5.3
5.4
7
7
7
5.5
5.6
6.6
3
6
6
1. CONTROL REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1
1.2
1.3
1.4
Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Status Indicators and Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communications Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery Management System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
9
11
11
2 PROTECTION REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13
3 EQUIPMENT SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13
14
17
19
ENGINEERING SPECIFICATION
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
PDVSA N253
REVISION
FECHA
NOV.00
Pgina 2
.Men Principal
Indice manual
Indice volumen
Indice norma
SECTION 1 (GENERAL)
1
OVERVIEW
This specification covers the Particular Requirements for the design,
manufacture, testing and shipment of Uninterruptible Power Systems UPS for
use in oil refineries, gas plants, chemical plants, exploration and production
facilities, and supply/marketing installations owned by PDVSA.
This specification consists of three sections:
1.
2.
3.
This specification along with the Owners UPS Data Sheet (Appendix A) and the
requirements of international standards mentioned shall be considered
complementary. Any conflict among them shall be referred to the Owner for
clarification before proceeding with design and manufacture.
Clauses that are not mentioned herein shall remain applicable as written. When
the word should appears in IEC620403 it must be substituted by shall and,
therefore, considered mandatory.
The additional requirements or clarifications specified herein are required in order
to:
a.
b.
1.1
Exceptions
Bidder shall state in his offer that the UPS complies with the requirements of this
Specification without exception, or shall declare the exceptions and/or deviations
giving a clear explanation and proposed options (see Appendix C).
ENGINEERING SPECIFICATION
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
PDVSA N253
REVISION
FECHA
NOV.00
Pgina 3
.Men Principal
Indice manual
Indice volumen
Indice norma
5.1
ENGINEERING SPECIFICATION
PDVSA N253
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
REVISION
FECHA
NOV.00
Pgina 4
.Men Principal
5.1.1.1
Indice manual
Indice volumen
Indice norma
BATTERY
CABINET(S)
OR BATTERY ROOM
NORMAL
INCOMING
AC SUPPLY
UPS
CABINET(S)
MAINTENANCE
BYPASS CABINET(S)
BYPASS
AC SOURCE
COMMUNICATIONS
PANEL
CB1
CB4
BYPASS
BREAKER
IMPUT
BREAKER
ISOLATION
TRANSFORMER
BATTERY
SWITCH
(SEE NOTE 1)
CB2
DC
BREAKER
RECTIFIER/
BATTERY CHARGER
INVERTER
REGULATOR
(SEE NOTE 1)
SYNC
TO FIELD LOAD
BANK TEST
CONNECTION
(SEE NOTE 1)
ALARM
CB5
TRANSF.
SECONDARY
BREAKER
CLF
STATIC SWITCH
NC NO
BATTERY
(SEE NOTE 2)
FIELD LOAD
BANK TEST
CONNECTION
CB6
NC
SW1
MAINTENANCE
BYPASS SWITCH
CLF
SW2
CB3
OUTPUT
BREAKER
PANELBOARD
(SEE NOTE 1)
AC OUTPUT
NOTE 1 Only if is specified in Appendix A
NOTE 2 Required to UPS larger than 10 KVA
ENGINEERING SPECIFICATION
PDVSA N253
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
REVISION
FECHA
NOV.00
Pgina 5
.Men Principal
Indice manual
Indice volumen
Indice norma
X + Y KVA
X + Y KVA
UPS 1
(SEE NOTE 1)
STS 1
UPS 2
(SEE NOTE 1)
X + Y KVA
STS 2
X + Y KVA
X KVA
Y KVA
ENGINEERING SPECIFICATION
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
PDVSA N253
REVISION
FECHA
NOV.00
Pgina 6
.Men Principal
5.1.2.
Indice manual
Indice volumen
Indice norma
5.1.2.1
5.1.2.2
5.1.3.5
5.2.
5.3
5.3.1
ENGINEERING SPECIFICATION
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
PDVSA N253
REVISION
FECHA
NOV.00
Pgina 7
.Men Principal
5.4
Indice manual
Indice volumen
Indice norma
5.5
5.6
6.6
6.6.30
6.6.31
6.6.32
6.6.33
ENGINEERING SPECIFICATION
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
PDVSA N253
REVISION
FECHA
NOV.00
Pgina 8
.Men Principal
Indice manual
Indice volumen
Indice norma
1.1
Alarms
Metering
Status indicators
Control functions for UPS startup, shutdown, transfer and maintenance
bypass operations.
Metering
As minimum, the following parameters shall be displayed in accuracy of 1
percent:
1.
Input AC voltage / per phase / per AC supply. (normal incoming and by pass)
2.
Input AC current / per phase / per AC supply. (normal incoming and by pass)
3.
DC battery voltage.
4.
DC battery current.
5.
6.
7.
8.
9.
10. Efficiency.
11.
Power factor.
ENGINEERING SPECIFICATION
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
PDVSA N253
REVISION
FECHA
NOV.00
Pgina 9
.Men Principal
1.2
Indice manual
1.
2.
Indice volumen
Indice norma
System normal
2.
UPS on battery
3.
UPS on bypass
4.
5.
Battery discharging
6.
7.
8.
DC overvoltage
9.
Ac output overload
12. Imminent Shutdown due to transfer to bypass not available and output
overload period expired, over temperature period expired, or lowlow
battery discharge voltage.
13. AC critical load on bypass AC source
14. Battery system fault
15. Inverter failure
16. Fan failure
17. Battery disconnect or DC breaker in openposition
Pushbuttons shall be provided to test and reset visual and audible alarms.
Audible alarms shall automatically reactivate after silencing upon reocurrence of
a subsequent alarm condition.
Alarm relays for remote status shall be provided when specified in Appendix A.
ENGINEERING SPECIFICATION
PDVSA N253
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
REVISION
FECHA
NOV.00
Pgina 10
.Men Principal
Indice manual
Indice volumen
Indice norma
Form C dry contacts, voltage free, and circuitry shall be provided for remote
indication and alarming of the following conditions:
UPS Condition
Display
Normal
Yes
No
Trouble
Yes
Yes
On battery
Yes
Yes
On Bypass
Yes
Yes
The remote UPS Trouble alarm shall be activated, as a minimum, on any of the
following conditions:
a.
b.
c.
AC output overload
d.
Equipment overtemperature
e.
Synchronization loss
f.
Shutdown imminent
g.
h.
Inverter failure
i.
j.
The remote alarm feature shall be time delayed to avoid nuisance alarms caused
by transient conditions.
Maintenance of meters, switches, indicator/display lamps, and related electrical
elements shall not require shutdown of the UPSpowered AC load.
1.2.1
Mimic Panel
The mimic panel shall depict the singleline diagram of the UPS system and
indicate whether the AC load is being supplied from the incoming AC supply, the
Bypass AC source, or the battery. The parameters to be displayed should include,
but not be limited to, the following:
a.
b.
c.
Normal operation
d.
Bypass operation
ENGINEERING SPECIFICATION
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
PDVSA N253
REVISION
FECHA
NOV.00
Pgina 11
.Men Principal
1.2.2
Indice manual
Indice volumen
Indice norma
Alarm Queue
The alarm queue shall display the 200 most recent alarms and events in
chronological order (most recent first). The alarms shall be displayed in the
following format: sequence number, date, time, and description of the alarm.
1.3
Communications Interface
An RS232C, RC485 or modbus interface port shall be provided for remote
display of UPS status information at a computer terminal. The appropiate
communication protocol software shall be provided.
If required in Appendix A, the UPS shall provide an alternate user interface to the
UPS running data through an ANSIx3.64 compatible terminal. The displayed data
shall be user selectable by a menu screen. When a data screen is selected, it shall
be continuously updated to reflect the state of the UPS.
When specified, a 56 Kbps modem shall be provided for remote access via
telephone line or IP address for network access.
1.4
ENGINEERING SPECIFICATION
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
PDVSA N253
REVISION
FECHA
NOV.00
Pgina 12
.Men Principal
Indice manual
Indice volumen
Indice norma
BATTERY
MANAGEMENT
SYSTEM
BATTERIES
+
ENGINEERING SPECIFICATION
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
PDVSA N253
REVISION
FECHA
NOV.00
Pgina 13
.Men Principal
Indice manual
Indice volumen
Indice norma
PROTECTION REQUIREMENTS
The UPS shall have builtin protection against undervoltage, overcurrent and
overvoltage conditions including lowenergy lightning surges introduced on the
incoming AC power supply. UPS operation and the critical AC load bus shall not
be affected by impressed transient voltage and current levels when tested in
accordance with the guidelines provided by the Owner.
The type and location of protection and switching devices shall be as indicated and
sized according to UPS rating.
A circuit breaker shall be provided on the AC input. This breaker shall not trip with
the rectifier/charger operating in the currentlimit mode at maximum rated
ambient temperature.
The inverter shall have electronic currentlimiting protection to prevent damage
to components for currents above the overload capability. The inverter shall be
selfprotecting against any magnitude of connected output overload. The control
logic shall sense and rapidly remove the inverter from the critical AC load without
the requirement to clear protective fuses.
The inverter shall be provided with the following DC protection:
S DC overvoltage disconnection
S DC undervoltage alarm (low battery voltage)
S DC undervoltage disconnection (lowlow battery voltage / end of discharge)
EQUIPMENT SAFETY
Manufacturer shall prepare labeling on hazards, warnings and/or caution to
indicate the precautions to be followed. These labels shall be such that it can be
read and understood by those who may encounter the equipment before they are
exposed to the hazards identified.
ENGINEERING SPECIFICATION
PDVSA N253
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
REVISION
FECHA
NOV.00
Pgina 14
.Men Principal
Indice manual
Indice volumen
Indice norma
APPENDIX A
TECHNICAL DATA SHEET
UNINTERRUPTIBLE POWER SYSTEM
(UPS)
APPLICABLE TO:
PURCHASE
PROPOSAL
AS BUILT
1
FACILITY NAME
PAGE
TAG EQUIPMENT:
OF
REQUISITION No.
PROJECT No.
CONTRACTOR PROJECT No.
UNUSUAL SERVICE CONDITIONS (4.2)
DAMAGING FUMES
MOISTURE
STEAM
DUST
ABRASIVE DUST
SALT AIR
RATIOACTIVE LEVELS
SYSTEM TYPE:
BATTERY:
DELTA
TO BE PROVIDED BY OWNER
10%
OTHER:
2%
OTHER:
%
%
OTHER:
5%
SPECIAL CONDITIONS:
TRANSIENT VOLTAGE:
HARMONICS
< 0.08
UPS EFFICIENCY:
%
OTHER:
OTHER:
>90%
OTHER:
FROM BACK
FROM BELOW
FROM ABOVE
FROM SIDE
FROM BACK
FROM BELOW
FROM ABOVE
FROM SIDE
FROM BACK
FROM BELOW
FROM ABOVE
FROM SIDE
THD:
#PHASE:
#WIRE:
UPS OUTPUT SPECIFICATIONS (5.3)
VFISS111
INPUT P.F:
INPUT FREQUENCY:
0.8
OTHER:
TOLERANCE:
ENGINEERING SPECIFICATION
PDVSA N253
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
REVISION
FECHA
NOV.00
Pgina 15
.Men Principal
Indice manual
Indice volumen
Indice norma
APPENDIX A
TECHNICAL DATA SHEET
UNINTERRUPTIBLE POWER SYSTEM
(UPS)
APPLICABLE TO:
PURCHASE
PROPOSAL
AS BUILT
2
FACILITY NAME
PAGE
TAG EQUIPMENT:
OF
REQUISITION No.
PROJECT No.
CONTRACTOR PROJECT No.
RATED OUTPUT VALUES AND CHARACTERISTICS (5.3.2)
RATED OUTPUT VOLTAGE:
OUTPUT FREQUENCY (Hz):
%
%
KVA:
P.F.:
# PHASES:
PF:
PF:
TOTAL LOAD:
KVA
PF:
BALANCED LOAD:
KVA
UNBALANCED LOAD:
STATICS LOAD:
PF:
KVA
1
% OF TOTAL LOAD
KVA / PHASE
NUMBER OF CIRCUITS:
ENVIROMENTAL CONDITIONS
TEMPERATURE (C):
EXPECTED LIFE:
SEISMIC AREA:
OTHER:
ALARMS AND INDICATORS
INDICATORS
REMOTE INDICATION
ALARMS
INDICATORS
ALARMS
REMOTE INDICATION
AC OUTPUT OVERLOAD
SYSTEM NORMAL
UPS ON BATTERY
EQUIPMENT OVERTEMPERATURE
UPS ON BYPASS
SYNCHRONISM LOSS
IMMINENT SHUTDOWN
BATTERY DISCONNECTED OR
DC BREAKER OPENED
TO BE PROVIDED BY OWNER
INDOOR
OUTDOOR
CORROSIVE AGENTS:
COASTAL OR OFFSHORE
VENTILATED BUILDING
HVAC BUILDING
OTHER:
BATTERY ROOMS:
WIDTH:
HEIGTH:
LENGHT:
RC485
NO
ENGINEERING SPECIFICATION
PDVSA N253
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
REVISION
FECHA
NOV.00
Pgina 16
.Men Principal
Indice manual
Indice volumen
Indice norma
APPENDIX A
TECHNICAL DATA SHEET
UNINTERRUPTIBLE POWER SYSTEM
(UPS)
APPLICABLE TO:
PROPOSAL
PURCHASE
AS BUILT
3
FACILITY NAME
PAGE
TAG EQUIPMENT:
OF
REQUISITION No.
PROJECT No.
CONTRACTOR PROJECT No.
TEMPERATURE (C)
MIN:
MAX:
MIN:
MAX:
INTERNATIONAL STANDARDS:
UL LISTED
FM
NEMA
CSA CERTIFIED
OTHER:
EXPECTED LIFE:
LOW
YEARS
RIPPLE CURRENT:
CELL TYPE:
HIGH
DISCHARGE RATE:
OTHER:
30 mV
LEAD CALCIUM
SEALED CELL
NICKEL CADMIUM
VENTED CELL
OTHER:
MANUFACTURER*:
MODEL NUMBER*:
FLOAT VOLTAGE/CELL*
MAXIMUM:
MINIMUM:
HEGHT:
WIDTH:
DEPTH:
FILLED
EMPTY
ADDITIONAL ELECTROLYTE REQUIRED (%):
FILLED
EMPTY
MODEL:
RACK MODEL:
FLOAT VOLTAGE (V/CELL):
BATTERY RACK
MATERIAL:
NUMBER OF STEPS:
HEIGHT:
NUMBER OF TIERS:
WIDTH:
DEPTH:
MINIMUM:
ENGINEERING SPECIFICATION
PDVSA N253
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
REVISION
FECHA
NOV.00
Pgina 17
.Men Principal
Indice manual
Indice volumen
Indice norma
APPENDIX B
TECHNICAL DATA SHEET
MANUFACTURERS DECLARATION
APPLICABLE TO:
PROPOSAL
PURCHASE
AS BUILT
1
FACILITY NAME
PAGE
TAG EQUIPMENT:
OF
REQUISITION No.
PROJECT No.
CONTRACTOR PROJECT No.
CONSTRUCTION
MODEL CATALOGUE REFERENCE:
MODEL RATING (W/VA):
WEIGHT (KG)
ENVIROMENTAL
AMBIENT STORAGE TEPERATURE RANGE (4.1.4) (C):
RATED INPUT VOLTAGE AND VOLTAGE TOLERANCE (5.2.2 AND 6.3.2.1) (V):
RATED INPUT CURRENT (5.2.2 AND 6.3.2.10) (Ar.m.s):
RANGE OF LOAD POWER FACTOR PERMITTED LINEAR LOAD (5.3.2 AND 6.3.5.1):
OUTPUT VOLTAGE UNBALANCED AT REFERENCE UNBALACED LOAD (MULTIPHASE ONLY) (5.3.2 AND 6.3.4.5) (%):
MAXIMUM PHASE ANGLE VARIATION (MULTIPHASE ONLY) (5.3.2 AND 6.3.4.5) (DEGREES):
NONVISUAL VOLTAGE RISE TIME 0,1 TO 0,9 PEAK (IF WAVEFORM EXCEEDS 0,5 V/s) (6.3.4.4) (V/s):
ENGINEERING SPECIFICATION
PDVSA N253
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
REVISION
FECHA
NOV.00
Pgina 18
.Men Principal
Indice manual
Indice volumen
Indice norma
APPENDIX B
TECHNICAL DATA SHEET
MANUFACTURERS DECLARATION
APPLICABLE TO:
PROPOSAL
PURCHASE
AS BUILT
2
FACILITY NAME
PAGE
TAG EQUIPMENT:
OF
REQUISITION No.
PROJECT No.
CONTRACTOR PROJECT No.
EFFICIENCY
EFFICIENCY INPUT / OUTPUT (6.6.11) (%):
RATED INPUT VOLTAGE AND VOLTAGE TOLERANCE (5.2.2 AND 6.3.2.1) (V):
MAXIMUM PHASE ERROR (6.3.6.4) (DEGREES):
ENGINEERING SPECIFICATION
TECHNICAL SPECIFICATION
PDVSA FOR UNINTERRUPTIBLE
POWER SYSTEMS (UPS)
PDVSA N253
REVISION
FECHA
NOV.00
Pgina 19
.Men Principal
Indice manual
Indice volumen
Indice norma
APPENDIX C
DEVIATIONS AND EXCEPTIONS TAKEN BY BIDDER
CLAUSE
EXCEPTIONS/DEVIATIONS
BIDDER:
EXPLANATION AND
PROPOSED OPTION
DATE: