EN294-1240-G
Forwards
Thank you very much for your purchasing Minebeas Digital Peak Holder CSD819C.
This manual explains installation procedures and connecting method and also operating
method for the Digital Peak Holder CSD819C. Make use of it properly after reading
through the manual carefully.
Be sure to deliver the manual to the end user. Moreover, the end user should keep the
manual at hand after reading it over.
This manual is intended for the technical experts to read.
The contents of the manual may subject to change for improvement without notice.
I
Warning
Warning may cause injury or accident that may harm to the operator.
Dont do these things described here.
II
Use the instrument where the temperature/humidity specifies with the range as
follows
Environmental temperature
Environmental humidity
10 to 50
Less than 85 %R.H. (Non condensing)
Warning
III
(2) Installation
When installing the instrument, install as referring to the following figures and
secure the space around the instrument.
Each dimensions of the instrument and required dimensions for the environmental
spaces are as follows:
Outline dimensions
Side
Front
Rear
Upper
Unitmm
IV
2. Power supply
Warning
Be sure to check that the power supply is off in connecting each cable. If the work is
done while the power is on, there may have the case that electric shock to the
operator or even may have damage to the instrument.
Before supplying the power, check that the indication of power supply voltage
/specifications for the instrument and the power going to supply should be the
same. If they are not equal, contact with Minebea.
If you use the instrument without checking them, it may cause a damage in the
instrument or electric shock to the operator.
3. Application note
Warning
Warning
Warning
Warning
Warning
Before using a new instrument or exchanging the strain gage applied transducer
for a new one, be sure to make calibration. If calibration will not be made, the
correct measuring results may not be obtained nor which may cause malfunction in
the instrument and there may exist damage in peripheral equipments.
Besides, even though calibration has been made, there may occur the similar case
when the results are not correct, so make calibration, again.
In case of using the instrument, check that the connections are executed properly.
If not connected properly, the correct measuring result will not be obtained, nor it
may cause malfunctions of the instrument, damage to the peripheral equipments or
even more serious accidents.
Do not push the panel sheet on the instrument with the excessive strong force nor
push it with sharp edge object such as a driver.
If neglected, it may cause a damage to the panel switch and even have the
possibility of damage to resist to environments or operational performances.
Warning
Dont remove the cover of the case of the instrument, nor peel off the panel sheet
nor take the instrument into pieces.
If neglected, it may cause a damage to the case and the panel sheet and even have
the possibility of damage to resist to environments or operational performances.
At the time of shipment from the factory, the instrument has been plated with a
clear sheet on the panel sheet for protective purpose.
In case of application, use the instrument after removing the clearsheet first.
4. CE conformity standard
This instrument has suited the following standard.
EN6132612006
Electrical equipment for measurement, control, and laboratory use EMC requirements
Immunity test requirements for equipment intended for use in
industrial locations
EN610101 2001
Safety requirements for electrical equipment for measurement, control and laboratory use
Part 1 : General requirement
Warning
Please observe the following conditions strictly when this instrument suits the
abovementioned standard.
If neglected, there is a possibility of not suiting the abovementioned standard.
(1). Wiring
1 Shield processing
Cables other than power cable must use all shielded cables.
Please connect all shielded cables with F.G. terminal on No.2 terminal block.
2 Grounding
The ground of this instrument shall apply the individual ground by using the protective ground
terminal
VI
History of revision
Date
July. 2005
DRW.NO.EN2941240
DRW.NO.EN2941240A
June 2009
DRW.NO.EN2941240B
Due to ECN.FN0902035
Changed CE conformity standard EN613261:2006
Addition
Immunity test requirements for equipment intended for
use in industrial locations
Feb. 2010
DRW.NO.EN2941240C
Due to ECN.FN1002026
Change
Front covers logo is changed.
April 2007
May, 2010
DRW.NO.EN2941240D
Due to ECN.FN1001019A
Addition
34. [Applicable environment]is added.
1110.Accessories Panel monting gasket is added.
DRW.NO.EN2941240E
Due to ECN.FN1002140
Change
Minebea logo is changed
Jan. 2011
DRW.NO.EN2941240F
May 2012
DRW.NO.EN2941240G
Due to ECN.FN1002140D
Change
Minebea logo is changed
Oct. 2010
VII
Index
Forwards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11. Features
..........................................................
2
3
3. Installation procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
31.
32.
33.
34.
Installation place . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Location where installation is not allowed. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Applicable environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
4
5
6
4. Connecting method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
8
9
9
14
15
16
17
5. Calibration procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
19
51. Preparations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
19
19
37
39
39
42
42
43
6. Operation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
44
20
25
31
33
35
61.
key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
611. Operated in the Measurement mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
62.
key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
621. Operated in the Measurement mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
622. Operation is made in another mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
63.
631. Operated in the Measurement mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
632. Operation is made in another mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
64.
key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
641. When operated in the Measurement mode. . . . . . . . . . . . . . . . . . . . . . . . .
642. When operated in another modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
65.
key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
651. When operated in the Measurement mode. . . . . . . . . . . . . . . . . . . . . . . . .
66.
key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
661. When operated in the Measurement mode . . . . . . . . . . . . . . . . . . . . . . . .
662. When the A/Z function is selected. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
67.
671. When operated in the Measurement mode. . . . . . . . . . . . . . . . . . . . . . . . .
68.
key
44
44
44
44
44
44
44
45
45
45
45
45
45
46
46
46
46
46
............................................................
46
47
71. External control input signal and open collector output signal . . . . . . . . . . . .
711. Input signal for external control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
712. Open collector output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
713. Equivalent circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
72. Comparator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
721. ON/OFF for the Comparator S0, S1, S2, S3 and S4. . . . . . . . . . . . . . . . .
722. Changeover of comparator code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
723. Change of set value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
724. Operation on comparator S1, S2, S3 and S4 . . . . . . . . . . . . . . . . . . . . . . .
725. Comparative target for comparator S1, S2, S3 and S4 . . . . . . . . . . . . . .
726. Operation of comparator SO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
727. Hysteresis on comparator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
728. Light on/off setting of comparator value display section . . . . . . . . . . . .
73. How to use the filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
731. Analog filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
732. Digital filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
47
47
48
48
49
49
49
50
51
52
53
56
57
58
58
58
58
59
59
60
69
78
85
91
92
93
93
93
93
93
93
94
94
94
95
95
97
99
102
103
103
104
104
110
8. Function mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
112
112
114
9. Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
122
122
122
122
123
123
123
124
124
125
126
126
127
127
127
128
129
130
135
136
136
137
137
138
140
144
145
146
155
161
11. Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
162
111.
112.
113.
114.
162
162
163
163
115.
116.
117.
118.
119.
1110.
Comparator function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Open collector output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Various kinds of functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standard specifications at the shipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
164
164
164
165
165
165
1111. Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11111. Current output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11112. BCD output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11113. RS232C interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11114. RS422/485 interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1112. Outline dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
165
165
166
166
167
168
12. Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
169
121. Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
122. Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
169
169
13. Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
170
170
172
173
1. General
The instrument is a digital peak holder for the application of strain gage applied transducer.
11. Features
Main features for CSD819C are as follows :
(1) Compact size and light weight
96 mm96 mm130 mm Approx.500 g
0.025 %F.S.
key.
Lights on when CHECK is ON by pressing
Lights on when any peak mode is selected.
Lights on when any peak mode measurement is proceeded.
Lights on when any peak mode measurement is completed.
key
Used when shifting to the Function mode.
key
Executes zero set. (Onetouched zero point adjustment)
key
Used when the changing mode of S0, S1, S2, S3 and S4 for comparison value selecting number
is called, and used for the numeric carryingover at the time of various kind of setting.
2
key
Used for the changeover of comparison value selecting display, and the numeric increment at
the time of various kind of setting.
10
key
Used for the changeover of peak and track.
11
key
Used for reset of hold value.
12
key
Used for registering set values at the time of various kinds of settings.
13
key
Used when ON/OFF of CHECK value is required.
14
Terminal block 1
Connects with external control input, open collector output, various kinds of strain gage
applied transducer such as load cell and analog output.
Terminal block 2
Connects with AC power supply, shielded wire and a grounding wire. (When it is out of CE
conformity standard.)
3. Installation procedures
31. Installation place
Use the instrument where the temperature/humidity specifies within the range as
follows:
Environmental temperature
Environmental humidity
10 to 50
85 %RH or less(Non condensing.)
Warning
D Do not expose the instrument in direct sunlight and/or high temperature area.
D Do not use the instrument in a high humid area.
D Do not install the instrument where there is high mechanical vibrations and shock.
D Do not use the instrument where there are excess of dusts and fine particles.
D Do not install the instrument where there include any corrosive gas or any salty
atmosphere.
D Do not install the instrument where there is rapid change of temperature and humidity.
D Do not install the instrument near the devices that are magnetized or generate an
electromagnetic field.
D Do not install the instrument where there may suffer radioactivity or radioactive rays.
D Avoid the location where chemical reaction may take place such as in a laboratory, or like
that.
33. Installation
When installing the instrument, install as the following figures and secure the
space around the instrument.
Each dimensions of the instrument and required dimensions for the environmental spaces are as
follows:
Outline dimensions
Side
Front
Rear
Upper
Unitmm
By inserting the panel mount gasket, the front panel section becomes IP65 (International Protection Code) or equivalent in dustproof and waterproof construction.
4. Connecting method
41. Layout of the terminal block
There are 2 pieces of terminal block and M4 thread, one has 21 points of terminals and the other
has 3 points of terminals.
Layout of terminal blocks and thread are shown in the following figure.
1
Descriptions
AOUT
AOUT
ZERO
HOLD
10
PEAK/
TRACK
Strain gage
applied
t
transducer
d
Analog output
External control
i
input
Terminal
Nos.
Descriptions
11
RESET
12
SEL.1
13
SEL.2
14
COM.1
15
END
16
S0
17
S1
18
S2
19
S3
20
S4
21
COM.2
Applications
External control
input
Open
p collector
output
Applications
Application
Power supply
Frame ground
(Functional ground)
Application
Protective ground
Warning
D Please go after turning off the power supply without fail when you connect the wires.
D Since the terminal blocks at rear side of the instrument is made of resin, take care not to
drop it down or not to apply strong impact.
D Recommended torque to tighten the terminal screws for terminal block is as follows
Terminal block
Terminal block 1
0.6 Nm
Terminal block 2
1.4 Nm
1.4 Nm
D The suitable crimp type terminal lugs for the terminal block are as follows:
Terminal block
Width of crimp
type terminal lugs
Terminal block 1
6.2 mm or less
Terminal block 2
9.0 mm or less
43. Connection
431. Connection with strain gage applied transducers
The instrument can connect with strain gage applied transducers, such as load cell, pressure
transducer and so on. Here, we will describe the example of connections with load cell, so the
connection with another type of strain gage applied transducers is proceeded in the same way.
1
WHT
BLU
RED
Shield
GRN
3m
When this instrument suits with the CE conformity standard, please connect the
shielded wire with F.G. terminal (Terminal block 2 Terminal No.3).
Connection with 1 piece of load cell and Junction box for extension use(B304) and
CSD819C
GRN
1
WHT
BLU
B304
RED
3m
Shield
Junction box
CAB502
to CSD819C
When this instrument suits with the CE conformity standard, please connect the
shielded wire with F.G. terminal (Terminal block 2 Terminal No.3).
10
Connection with 2 to 4 pieces of load cells, Summing type junction box(B307) and CSD819C
CAB502
11
GRN
WHT
B307
BLU
RED
Shield
Junction box
1W
1R
1G
1B
1Y
RD
OR
BK
WH
GN
BL
YE
2W
2R
2G
2B
2Y
3W
3R
3G
3B
3Y
BLU
4W
4R
4G
4B
YEL(Shield)
4Y
RED
WHT
GRN
BLU
to CSD819C
YEL(Shield)
When this instrument suits with the CE conformity standard, please connect the
shielded wire with F.G. terminal (Terminal block 2 Terminal No.3).
12
Connection with 2 to 4 pieces of load cells, Summing type junction box(SB310) and
GRN
1
WHT
BLU
RED
Shield
CSD819C
SB310
CAB502
Output port
Input port No.1
to CSD819C
RD
RD
WH GR BL YE
RD
WH
WH GR BL YE
GR
Input port
No.4
BL
YE
RD
WHGR BL YE
or
Y type
WH GR BL YE
B
A
B
A
RD
A3.2 mm or less
B7 mm or less
Round type
When this instrument suits with the CE conformity standard, please connect the
shielded wire with F.G. terminal (Terminal block 2 Terminal No.3).
13
or
Shield
Warning
Connect the external control input surely as shown in the above figure.
If neglected, it may cause an unexpected failure and/or malfunction to the
instrument.
For the connections with external control inputs, be sure to apply shielded cable,
and the shielded cable is connected with E terminal of the instrument. (Terminals
No.5) If not connected, it may cause malfunction due to the effects from external
noises and so on.
When this instrument suits with the CE conformity standard, please connect the
shielded wire with F.G. terminal (Terminal block 2 Terminal No.3).
14
Shield
Load
(Please prepare an external power
supply for the load separately. )
Surge preventive element
Warning
Connections with open collector outputs is made securely according to the figures
and also within the specified open collector output. If neglected, it may cause an
unexpected failure and/or malfunction to the instrument.
For the protection of the open collector output of the instrument, connect the surge
preventive element that satisfies the characteristics of external load to connect. If
neglected, it may cause unexpected failure and/or malfunction on the open collector
output of this instrument.
For the connections with open collector outputs, be sure to apply shielded cable,
and the shielded cable is connected with E terminal of the instrument. (Terminal
No.5) If not connected, it may cause malfunction due to the effects from external
noises and so on.
When this instrument suits with the CE conformity standard, please connect the
shielded wire with F.G. terminal (Terminal block 2 Terminal No.3).
15
AC100 V to AC240 V
(Permissible variation rangeAC85 V to AC264 V)
50/60 Hz
Approx.15 VA at maximum. (at AC100 V)
Warning
AC100 V to AC240 V
(Permissible variation range
AC85 V to AC264 V)
Connections with the power supply and the earth is made securely according to the
figures and also within the rated capacity of the instrument. If neglected, it may
cause an unexpected cause of failure.
16
V
Shield
Warning
Please make the connection of voltage output surely as showing above, and use its
connection in the specified load resistance.
If neglected, it may cause an unexpected failure and/or malfunction to the
instrument.
For the connections with voltage outputs, be sure to apply shielded cable, and the
shielded cable is connected with the E terminal of the instrument (Terminal No.5).
If not connected, it may cause malfunction due to the effects from external noises
and so on.
When this instrument suits with the CE conformity standard, please connect the
shielded wire with F.G. terminal (Terminal block 2 Terminal No.3).
17
Warning
Please make the connection of current output surely as showing above, and also use
its connection in the specified load resistance.
If neglected, it may cause an unexpected failure and/or malfunction to the
instrument.
For the connections with current outputs, be sure to apply shielded cable, and the
shielded cable is connected with the E terminal of the instrument (Terminal No.5).
If not connected, it may cause malfunction due to the effects from external noises
and so on.
When this instrument suits with the CE conformity standard, please connect the
shielded wire with F.G. terminal (Terminal block 2 Terminal No.3).
18
5. Calibration procedures
Warning
Before using the new instrument or after exchanging the strain gage applied
transducer with a new one, be sure to make calibration.
If calibration is not made, correct measured results may not be obtained, or it may
cause malfunction to the instrument and it may damage the peripheral equipment.
Moreover, even if calibration has made, there may occur the similar case as above
when the result is not correct. So make precise calibration again.
The calibration for the instrument and Display value at the time of minimum
analog output(F21) and Display value at the time of maximum analog output
(F22) are not interlocked. In due course, make check on the setting for F21 and
F22 securely. If neglected, correct outputs may not be obtained, or it may cause
malfunction to the instrument and it may damage the peripheral equipment.
51. Preparations
According to the Chapter 4. Connecting method, connect the instrument and the strain gage
applied transducer properly, then supply the power.
Calibration method to register the output (conversion with mV/V) of strain gage applied
transducer at the time of maximum display (weighing capacity) after setting the load to zero
(Initial load condition with tare weight).
Calibration method (Actual load calibration) to register by the reading output of strain gage
applied transducer, when setting in the condition of zero load applied (Initial load application
with tare) and in the condition of actual load applied individually.
Calibration procedures to apply registration again for zero point only(Tare weight
cancellation).
The accuracy of calibration obtained from is 1/1 000 or so. If the accuracy more
than 1/1 000 is required, make calibration of type.
In the following paragraphs, we will describe each calibration procedure by showing the
examples with load cell applied.
19
521. Calibration method to register the output of strain gage applied transducer at the time
of maximum display after setting the load to zero.
Warning
Before using a new instrument or exchanging the strain gage applied transducer
for a new one, be sure to make calibration.
If calibration will not be made, correct measured results may not be obtained nor it
may cause malfunction in the instrument and there may exist damage to the
peripheral equipment.
Besides, even though the calibration has been made, there may occur the similar
case when the result is not correct, so make calibration again.
During the calibration is executing, be sure to make cancellation (Execution of
F98) for compensated data on zero set
When the changeover target of the calibration data is set to the changeover by
external control input (Setting of F80 00001 or 00011), execute the
calibration after the changeover of the calibration data changed by the external
control output(SEL.1 and SEL.2).
is pressed, the display will change as the reverse direction of the following arrow
marks.
FUNCCCALLCALZEROSPANTARECHEK
MONTVCALVADJSYMMFUNCCCAL
(Hereinafter, it will repeat.)
Procedures
Press the
key for approx. one second.
The setting display section shows FUNC.
The load display value continuously shows the
present load value.
Press the
key once.
The setting display section shows CCAL.
20
Procedures
Press the
key.
CCAL mode can be entered, then the load
display section shows SCAL.
Press the
key.
The load display section shows D01.
When the calibration has completed already, the
set value of minimum scale registered at that
time will be displayed.
Set the minimum scale with the right keys.
Setting value for the minimum scale are 4 (four)
kind as follows:
1, 2, 5, 10
Press the
key.
The load display section shows DISP.
21
Procedures
Press the
key.
The load display section shows 2000, and the
minimum display digit flashes on and off.
When the calibration has completed already, the
maximum display value registered at that time is
displayed.
20020 000
50050 000
1 00099 990
10
Press the
key.
The load display section shows S MV.
22
Procedures
Press the
key.
The load display section shows 0.5000, and the
digit of 100 flashes on and off.
In case that calibration has completed already,
the registered output value of load cell at that
time will be displayed. After the ACAL mode is
over, the load display section shows the present
load.
Set the given value with the right keys, which is
subtracted the output value of load cell at the
time of initial load application from the output
value of load cell corresponding to the maximum
display value set in the step 6.
Press the
key.
The load display section shows ZERO.
Here, set the instrument with initial load
application.
23
Procedures
Press the
key.
The load display section shows ZERO with
lighting display on and off, then zero adjustment
can be started.
Error code
Error code
OVER
OVER
Press the
key.
After CCAL mode is over, the load display
section shows the present load.
11
24
522. Calibration procedures to register the output of strain gage applied transducer at the
time of zero and the maximum display
(1) Procedure by key operation
Warning
Before using a new instrument or exchanging the strain gage applied transducer
for a new one, be sure to make calibration.
If calibration will not be made, correct measured results may not be obtained nor it
may cause malfunction in the instrument and there may exist damage to the
peripheral equipment.
Besides, even though the calibration has been made, there may occur the similar
case when the result is not correct, so make calibration again.
During the calibration is executing, be sure to make cancellation (Execution of
F98) for compensated data on zero set
When the changeover target of the calibration data is set to the changeover by
external control input(Setting of F80 00001 or 00011), execute the
calibration after the changeover of the calibration data changed by the external
control output(SEL.1 and SEL.2).
is pressed, the display will change as the reverse direction of the following arrow
marks.
FUNCCCALLCALZEROSPANTARECHEK
MONTVCALVADJSYMMFUNCCCAL
(Hereinafter, it will repeat.)
Procedures
Press the
key for about one second
The setting display section shows FUNC.
The load display value continuously shows the
present load value.
25
Procedures
Press the
key twice.
It makes the setting display section proceed as
FUNCCCALLCAL.
Press the
key.
LCAL mode can be entered, then the load
display section shows SCAL.
Press the
key.
The load display section shows D01.
When the calibration has completed already, the
set value of minimum scale which has registered
at that time is displayed.
Set the minimum scale with the right keys.
Setting values for the minimum scale are (four)
kinds as follows
1, 2, 5, 10
Press the
key.
The load display section shows DISP.
26
Procedures
Press the
key.
The load display section shows 2000 and the
minimum display digit flashes on and off.
When the calibration has completed already, the
maximum display value which has registered at
that time is displayed.
20020 000
50050 000
1 00099 990
10
Press the
key.
The load display section shows LOAD.
27
Procedures
Press the
key.
The load display section shows 2000 and the
minimum display digit flashes on and off.
When the calibration has completed already, the
maximum display value which has registered at
that time is displayed.
By the
h setting off minimum scale,
l the
h
8
Press the
key.
The load display section shows ZERO.
Here, set the initial load application.
28
Procedures
Press the
key.
The ZERO on load display section flashes on
and off, and zero adjustment can be started.
11
29
Procedures
Press the
key.
The SPAN on the load display section flashes
on and off, and span adjustment can be started.
Press the
key.
After LCAL mode is over, the load display
section shows the present load.
13
30
During zero set is executed and also during effective for Peak ON, Zero fine
adjustment mode cant be entered into. (Displays ER5.)
The Zero fine adjustment can be entered after the cancellation of the Compensated
data at Zero set (Execution of F98) and set the peak OFF.
When the changeover target of the calibration data is set to the changeover by
external control input(Setting of F80 00001 or 00011), execute the
calibration after the changeover of the calibration data changed by the external
control output(SEL.1 and SEL.2).
When the
key is pressed with the setting display section of FUNC, the
display will change as the following arrow marks indicate at every time the key is
Procedures
Press the
key for about one second.
The setting display section shows FUNC.
The load display value continuously shows the
present load value.
Press the
key three times.
It makes display in the load display section
proceeded as FUNCCCALLCAL
ZERO.
Here, set the initial load condition.
31
Procedures
Press the
key.
Zero fine adjustment mode can be entered, then
the display on load display section shows the
present load value and lights on and off. At the
same time, set the present load value to 0 with
the right keys.
Press the
key.
The indication of load display section shows
END.
Press the
key.
After quitting from zero fine adjustment mode,
the load display section shows the present load
value.
32
During zero set is executed and also during effective for Peak ON, Span fine
adjustment mode cant be entered into. (Displays ER5.)
The Zero fine adjustment can be entered after the cancellation of the Compensated
data at Zero set (Execution of F98) and set the peak OFF.
When the changeover target of the calibration data is set to the changeover by
external control input(Setting of F80 00001 or 00011), execute the
calibration after the changeover of the calibration data changed by the external
control output(SEL.1 and SEL.2).
When the
key is pressed with the setting display section of FUNC, the
display will change as the following arrow marks indicate at every time the key is
Procedures
Press the
key for about one second
The setting display section shows FUNC.
The load display value continuously shows the
present load value.
Press the
key four times.
It makes the setting display section proceeded as
FUNCCCALLCALZERO
SPAN.
Here, set the maximum load that can be applied
within the maximum value on the load cell.
33
Procedures
Press the
key.
Span fine adjustment mode can be entered, then
the display on load display section shows the
present load value and lights on and off. At the
same time, adjust the present load value to be the
same load applied on the load cell with the right
keys.
Press the
key.
The indication of load display section shows
END.
Press the
key.
After quitting from zero Span fine adjustment
mode, the load display section shows the present
load value.
34
525. Calibration procedure to apply registration again for zero point only
(1) Procedures by key operation
Warning
Procedures
Press the
key for about one second
The load display section shows FUNC.
The load display value continuously shows the
present load value.
Press the
key five times.
It makes the setting display section proceeded as
FUNCCCALLCALZERO
SPANTARE.
Here, set the initial load condition.
35
Procedures
Press the
key.
The TARE mode can be entered.
The display on the load display section shows
ZERO.
Press the
key.
The display of ZERO on the load display
section flashes on and off, and Tare weight
cancellation is entered.
Error code
Error code
Press the
key.
After quitting from the TARE mode, the load
display section shows the present load value.
36
During the execution of zero set, or Peak ON, compensation of symmetric property
mode cant be entered into(Display ER5).
The Compensation of symmetric property can be entered after the cancel of the
compensation data at Zero set(Execution of F98), and set the peak OFF.
When the changeover target of the calibration data is set to the changeover by
external control input(Setting of F80 00001 or 00011), execute the
calibration after the changeover of the calibration data changed by the external
control output(SEL.1 and SEL.2).
Procedures
Press the
key for about one second
The setting display section shows FUNC.
The load display value continuously shows the
present load value.
37
Procedures
Press the
key ten times.
It makes the setting display section proceeded as
FUNCCCALLCALZERO
SPANTARECHEKMONT
VCALVADJSYMM.
Here, set the maximum weight on the load cell,
which initial load condition.
Here, please give the load cell the maximum load
which can be applied to the load cell below the
maximum indicated value on a minus side.
Press the
key.
Enters to the symmetric property compensation
mode, and the display of load display section
blinks. At the same time, adjust the present load
value to be the same load applied on the load cell
with the right keys.
Press the
key.
The indication of load display section shows
END.
Press the
key.
After quitting from the compensation mode of
symmetric property, the load display section
shows the present load value.
38
Warning
The calibration accuracy obtained in this procedure is less than 1/1 000 or so. When
precise accuracy more than 1/1 000 is necessary, make calibration with actual load
according to the paragraph 531(2). Besides, the accuracy described here is a
combined accuracy of the instrument and the strain gage applied transducer
connected. If there may exist another factors of error such as mechanical elements
and so on, it will become out of warranty, so care is taken fully.
The rated output value for load cell applicable by the calculation is assumed as the
value described on the Inspection data individually.
For example, we will show the calibration procedures as follows, that is, 3 points of load cells
with 3 mV/V of rated output and 5 t of rated capacity.
Tare weight
Weighing capacity
Maximum display
1.5 t
5t
5 000
39
Calculate the output of load cell at maximum display from the above conditions. Check that
the calculated value is within the range from 0.4 mV/V to 3.1 mV/V. If the value is out of the
range, calibration cant be executed.
Output of load cell at maximum display
Weighing capacity
(No. of load cells)(Rated load)
5t
3 points5 t
1 mV/V
2
After making the load cell to the initial load condition (tare weight), execute the calibration
according to the paragraph 521. In this case, input 5000 in the step 6, and input 1.0000
in the step 8 individually.
If necessity requires, apply zero/span fine adjustment according the paragraph 523, and
524.
(2) When the both conditions of load and the output of load cell are clarified.
(In case that required accuracy is more than 1/1 000 or so.)
Warning
The accuracy obtained through the procedures of this calibration consists from
combined accuracy with the instrument and combined strain gage applied
transducer, the accuracy of weight used during the calibration, error factors on
mechanical and also error factors on calibration works, that is, the total accuracy of
these. If high accuracy is required, full considerations is made on each factor. If
neglected, there will be a case that desired accuracy may not be obtained, so care is
taken fully.
When high accuracy is required, actual load calibration by using the weight and so on are
required.
For example, well show the calibration procedures in the following conditions, that is, 3 points
of load cell with 3 mV/V of rated output and 5 t of rated capacity.
Tare weight
1.5 t
Weighing capacity
5t
Maximum display
5 000
5231. Calculate the output of load cell at the maximum display from the above conditions.
Check that the calculated value at this point is within the range from 0.4 mV/V to 3.1 mV/V.
If the value is out of the range, calibration cant be executed.
Output of load cell at maximum display
Weighing capacity
(No. of load cells)(Rated load)
5t
3 points5 t
1 mV/V
2
After making the load cell to the initial load condition (tare weight), execute the calibration
according to the paragraph 522. In this case, input 5000 in the step 6, and input the load
value applied on the load cell in the step 8 individually.
If necessity requires, apply zero/span fine adjustment according the paragraph 523, and
524.
40
(3) When the load condition is clarified but the output condition of load cell is not clarified.
In the case of using the existing load detecting section, and adopting the new digital indicator
only, it is necessary to execute calibration after checking the output of load cell when its
output is not clarified.
For example, followings are calibration procedures when weighing capacity is 5 t and the
others are not clarified.
1
Set the instrument in the monitor mode according to the paragraph 716. In this condition,
the output level of load cell connecting with the instrument can be monitored up to approx.
3.100 0 with the unit of mV/V.
After making the load cell section to the initial load condition (tare weight), record the display
value on load display. This value is the output of load cell at the time of initial load condition.
Record the display value on load display after applying 5 t load on the load cell section. This
value is the output of load cell with weighing capacity applied.
4. From the load cell output at the time of initial load application recorded at , and load cell
output recorded at at the time of application of weighing capacity, output of load cell at the
time of maximum display can be calculated according to the below formula.
Check that the calculated value is within the range from 0.4 mV/V to 3.1 mV/V. The
calibration cant be executed if the value is out of the range.
(Output of load cell at the time of maximum display)
(Output of load cell at weighing capacity)(Output of load cell at initial load application)
After making the load cell to the initial load condition (Tare weight), execute calibration
according to the paragraph 521. In this case, the accuracy is less than 1/1 000 or so.
At this moment, input each value, 5000 in the step 5 and another input is the value of
Output of load cell at the maximum display calculated from the in the step 8. If the
accuracy more than of 1/1 000 or so is required, execute calibration according to the paragraph
522. And at the same time, input 5000 in the step 6 and also input Load value going to
apply on load cell in the step 8 individually.
As necessity requires, make fine adjustment on Zero and Span according to the paragraph
523 and 524.
Warning
When the load at the section of load cell cant make it with initial load application due to
failure on the existing CSD819C, execute calibration by referring to the procedures as below.
However, in case that the initial load condition can be obtained, make calibration according to
the procedures of (1) and (2).
1
According to the paragraph 81, read out and write down the function F90 Increment
value, the F91 Maximum display value, the F93 Zero calibration value, and the F94
Span calibration value in the existing CSD819C.
41
According to the paragraph 4, replace the exiting CSD819C with a normal instrument and
make connections.
After turning ON the normal instrument, make calibration according to the paragraph
521. In case of this, make the weight on the load cell to the initial load condition and input
the Increment value recorded at in the step 4, the Maximum display value in the step 6
and input the value subtracted Zero calibration value from Span calibration value in the
step 9.
After setting the initial load (tare weight) on load cell section, execute calibration according to
the paragraph 525.
Warning
The accuracy obtained through the calibration procedures consists from combined
accuracy with the instrument and strain gage applied transducer, the accuracy of
weight used during the calibration, error factors on mechanical and also error
factors on calibration works, that is , total accuracy of these.
If high accuracy is required, full considerations is made on each factor.
If neglected, there will be a case that the desired accuracy is not obtained.
42
SEL.1
Open
Short
Open
Short
SEL.2
Open
Open
Short
Short
Warning
When the analog output is made against four kinds of calibration data, the function
setting by Display value at the minimum analog output(F21), Display value at
the maximum analog output (F22), or the execution of Fine adjustment of
Analog output is executed on each calibration data. If neglected, the correct output
may not be obtained.
The set content displayed in the function mode is displayed against the calibration
data which has been selected by External control input and Function F81.
When you execute the calibration, please execute it after setting the calibration
data by using the external control input or function F81.
SEL.1 and SEL.2 of the external control input signal are used combinedly with the
input signal of Comparator code changeover. When the both setting of function
F80 is selected to the target of External control input, Calibration data and
Comparator code changeover at the same time.
43
6. Operation procedure
Well show the operating procedures with keys located on the front panel.
Warning
61.
Key operation in Measurement mode can be effective by pressing it for about one
second or so.
key
62.
key
63.
key
44
key with the condition of displaying various kinds of set values, the
By pressing the
flashing digits for set value will carry up from 100, 101, 102, 103 to 104 in order.
(However, the range of carry differs depending on the number of digits of set values and yes/no
of polarity sign.)
(2) Change of function and so on.
Executes change of various kinds of functions in Function mode, and also change of function
during Check mode.
(3) Decrement at the time of fine adjustment.
64.
In the operation method of the paragraph 632(3), when the key is pressed for
more than about 1 second, each operation will be executed continuously at a
constant interval without ON/OFF operation of the key.
key
By pressing the
key, the comparison value selecting display will increase per one count
from 0, 1, 2, 3, 4 and 0 again in order, and then the comparison set value of selected number is
displayed.
key with the condition of displaying various kinds of set values, the set
By pressing the
value will increase per one count from 0, 1, 2, 3, 4, 5, 6, 7, 8, 9 and 0 again in order.
(2) Increment at the time of fine adjustment
65.
In the operation method of the paragraph 642(2), when the key is pressed for
more than about 1 second, each operation will be executed continuously at a
constant interval without ON/OFF operation of the key.
key
45
66.
key
key is pressed while entered in various kinds of modes, you can shift to the
When the
Measurement mode.
67.
key
68.
key
Pressing the
key makes to register the set values internally, then the condition of Possible to
set will be over.
46
Name
ZERO
HOLD
10
PEAK
/TRACK
11
12
RESET
SEL.1
13
SEL.2
14
COM.1
Operation
When the indicated value on load display section is within 10 %
against the maximum display value, zero set function will activate
by the operation and make the display 0 compulsively. (Same
key operation in the paragraph 62.) As for the operational
details, refer to the paragraph 79.
While inputting the signal, the target selected with Function
F10 among display, open collector output, analog output and
options will be frozen. As for the operational details, refer to the
paragraph 77.
Changeover of track/peak hold, bottom hold, peak/bottom hold,
the local maximum hold, the local minimum hold and inflection
point hold.
Open Track
ShortPeak hold, Bottom hold, Peak/bottom hold, The local
maximal value hold, The local minimal value hold, The inflection
point hold
During the various kinds of peak hold operation, reset condition is
made by short circuit.
Changeover of comparator code and calibration data by the
combination of SEL.1
SEL 1 and SEL.2.
SEL 2
(The target selected by the function F80 is changed.)
The common for the input signal (Terminal No.8 to 13)
Operation of input signal will be executed after shortening for more than 50 ms
approximately. (The changeover of level and pulse width of 1, 2, 5, 10 and 20 ms is
available. Related function F72)
As for the ZERO signal input, the operation of each calibration data which has
been selected is executed.
47
Terminal No.
Name
15
END
16
S0
17
18
19
20
S1
S2
S3
S4
21
COM.2
Operation
Output when the completion of various kinds of peak mode
measurement. (Outputs with END LED interlock.)
Operated with whichever condition as follows by the setting F33.
a) ON in the condition of Load display valueThe maximum
display value
b) ON when both open collector outputs S1 and S2 are OFF
c) ON when both open collector outputs S1 and S3 are OFF
d) ON when both open collector outputs S1 and S4 are OFF
e) ON when both open collector outputs S2 and S3 are OFF
f) ON when both open collector outputs S2 and S4 are OFF
g) ON when both open collector outputs S3 and S4 are OFF
h)Operation whichever Open collector ON at more than the set
value, or Open collector ON at less than the set value
i) Interlock with HOLD LED
j) Interlock with PEAK LED
k)Interlock with MEAS. LED
Open collector output for S1 comparator.
Open collector output for S2 comparator.
Open collector output for S3 comparator.
Open collector output for S4 comparator.
The common of open collector output(Terminal No.1520).
10 k
2.2 k
12 V
1 k
5 V
INPUT
3 300 pF
3.3 k
OUTPUT
COM.2
VCE=DC30 V, IC=30 mA MAX.
48
COM.1
72. Comparator
The instrument prepares comparators that consist of 4 kinds of set values S1, S2, S3 and S4 and
comparator S0 that can change the operation by the setting function F33. Additionally, this can
memorize four kinds of comparator code, and changeover and use them
721. ON/OFF for the Comparator S0, S1, S2, S3 and S4.
Operational selection of ON/OFF can be made for each comparator S0, S1, S2, S3 and S4. These
selection can be made with the function (Related function F30).
As for default, all of the S0, S1, S2, S3 and S4 are selected ON.
SEL.1 input
SEL.2 input
Open
Open
Short
Open
Open
Short
Short
Short
Code No.
00000
00001
00002
00003
When you change the comparator set value, change the comparator set value after
adjusting the changing code by the external control input or setting by function
F82.
SEL.1 and SEL.2 of external control input signal is used combinedly with the input
signal of Calibration data changeover. When the all setting of function F80 is
selected to the target of External control input, the changeover of Calibration
data and Comparator code is made at the same time.
49
Warning
When the set value for the comparator is set wrong, or set in the wrong procedures,
it may not obtain the correct results from the comparator, and it may cause
malfunctions in peripheral equipments and also cause a damage as well.
Procedures
Selects the code which wants to set by external
control input signal or function F82. In the
key is
measurement mode, when the
pressed, the comparison value selecting display
section blinks.
Selects the number which wants to change by
using the
key and the
key. The set
value corresponding to the number is displayed
in setting display section.
Press the
key. The minimum display
effective digit of setting display section blinks.
Set the comparator set value of the selected
number by using the right keys.
Press the
key upon completing the change.
The set value becomes effective and the
selecting display section of the comparative
value blinks. Return to step 2 to change the
other set value, or return to step 1 to set the
value of the other code.
Press the
mode.
Warning
Warning
Depending on the operational selection for comparator, ON/OFF condition for each
open collector output may differ. If wrong operation is selected, ON/OFF condition
for open collector output becomes inadequate and it may cause an unexpected
accident due to malfunctions on peripheral instruments, so care is taken fully.
When the load display is OL or OL, the display value for the comparison of
comparator is assumed as (infinity) and (infinity) individually.
Operation on judgement display section and open collector output will be shown as follows for
the S1 as a sample. S2, S3 and S4 are also in the same operation.
(1) When the operation of open collector ON at more than the set value is selected.
S1 judgement display, S1 open collector output ON at (S1 set value)(Display value)
Display (large)
Display (small)
S1 set value
ON
S1 judgement display,
S1 open collector output
OFF
(2) When the operation of open collector ON at less than the set value is selected.
S1 judgement display, S1 open collector output ON at (S1 set value)(Display value)
Display (large)
Display (small)
S1 set value
ON
S1 judgement display,
S1 open collector output
OFF
51
Warning
Operation on judgement display section each comparative target and the operation of open
collector output will be shown as follows when the operation of open collector ON at more
than the set value is selected by the S1, for an example. The same is the operation of S2, S3 and
S4.
(1) When the operation of PEAK is selected.
S1 judgement display, S1 open collector output ON at (S1 set value)(Display load)
Load display (small)
Load display (large)
S1 set value
ON
S1 judgement display,
S1 open collector output
OFF
OFF
52
Warning
As example, the operation of S0 judgement display and S0 open collector output at the time of
whichever is selected from the 00000 to 00010 with the function F33, are shown in the
following table.
Setting of F33
00000
00001
00002
00003
Operation
ON at (Load display value)(Maximum display value)
ON when both open collector output S1 and S2 are OFF.
ON when both open collector output S1 and S3 are OFF.
ON when both open collector output S1 and S4 are OFF.
00004
00005
00006
00007
00008
00009
00010
In the next, as for the sample, the operation at S0 judgement display and S0 open collector
output selected 00001 with the Function F33 will be shown as follows. The same operation
will be made when 00002 to 00006 are selected. The operation for S0 comparator when the
00007 is selected will be the same as the operation of S1, S2, S3 and S4 written in the
paragraph 724, and 725.
(1) When the both of S1 and S2 select more than with the Function F32.
S1 judgement display, S1 open collector output
ON at (S1 set value)(Display value)
S2 judgement display, S2 open collector output
ON at (S2 set value)(Display value)
S0 judgement display, S0 open collector output
ON at (S1 set value)(Display value) and (S2 set value)(Display value)
Display (large)
Display (small)
S1 set value S2 set value
ON
S2 judgement display,
S2 open collector output
OFF
ON
S1 judgement display,
S1 open collector output
OFF
ON
S0 judgement display,
S0 open collector output
OFF
53
(2) When the S1 selects less than and the S2 selects more than with the Function F32.
S1 judgement display, S1 open collector output
S2 judgement display, S2 open collector output
S0 judgement display, S0 open collector output
Display (small)
S1 set value
S2 judgement display,
S2 open collector output
OFF
ON
S1 judgement display,
S1 open collector output
OFF
ON
S0 judgement display,
S0 open collector output
OFF
Above figure indicates the case of (S1 set value)<(S2 set value).
In the case of (S1 set value)(S2 set value), the S0 judgement display and the S0
open collector output will be normally OFF.
(3) When the S1 selects more than, and the S2 selects less than at the function F32.
S1 judgement display, S1 open collector output
S2 judgement display, S2 open collector output
S0 judgement display, S0 open collector output
Display (small)
S1 set value
S2 set value
ON
S2 judgement display,
S2 open collector output
OFF
ON
S1 judgement display,
S1 open collector output
OFF
ON
S0 judgement display,
S0 open collector output
OFF
Above figure indicates the case of (S1 set value)(S2 set value).
In the case of (S1 set value)(S2 set value), the S0 judgement display and the S0
open collector output will ON in the condition of (S2 set value)(display
value)(S1 set value)
54
(4) When both of the S1 and S2 select less than at the function F32
S1 judgement display, S1 open collector output
ON at (S1 set value)(display value)
S2 judgement display, S2 open collector output
ON at (S2 set value)(display value)
S0 judgement display, S0 open collector output
ON at (S1 set value)(display value) and also (S2 set value)
(display value) at the same time.
Display (large)
Display (small)
S1 set value
S2 set value
ON
S2 judgement display,
S2 open collector output
OFF
ON
S1 judgement display,
S1 open collector output
OFF
ON
S0 judgement display,
S0 open collector output
OFF
55
Warning
As for the example of S1, the operation of judgement display section and open collector output
when the hysteresis on comparator is set, will be shown as follows
The same operation will be obtained in the case of S2, S3, S4 and Normal mode at S0.
(1) When the operation of open collector ON at more than the set value is selected at S1 and
also effective direction for hysteresis is set as On delay.
Display
Hysteresis
data width
S1 set value
Time
S1 judgement
ON
display
S1 open
OFF
collector output
(2) When the operation of open collector ON at more than the set value is selected at S1 and
also effective direction for hysteresis is set as Off delay.
Hysteresis time width
Display
S1 set value
Hysteresis
data width
Time
ON
S1 judgement display
S1 open collector output
OFF
56
(3) When the operation of open collector ON at less than the set value is selected at S1 and also
effective direction for hysteresis is set as On delay.
Display
Time
ON
S1 judgement display
S1 open collector output
OFF
(4) When the operation of open collector ON at less than the set value is selected at S1 and also
effective direction for hysteresis is set as Off delay.
Display
Hysteresis
data width
S1 set value
Time
ON
S1 judgement display
S1 open collector output
OFF
57
Warning
10 Hz
stable
Response speed
slow
100 Hz
1 kHz
rapid
quick
low
rapid
quick
high
stable
slow
The comparator comparison operation and the analog output of this unit have
synchronized with the A/D sampling. Therefore, please execute the change in the
A/D sampling rate when you change the conversion rate of the comparator and
analog output.
58
00000Peak hold
00001Bottom hold
00002Peak bottom hold
00003The local minimal value hold
00004The local maximal value hold
00005Inflection point hold
F61
F62
F63
F64
F65
0000000049
Unit0.1 times
9999999999
Unit1D
F66
0000000450
Unit1 ms
F67
0000000450
Unit1 ms
F68
0000009999
Unit1 ms
F69
9999999999
Unit1D
The table below shows the combination of various holding functions and related functions.
F60 F61 F62 F63 F64 F65 F66 F67 F68 F69
Peak hold
Bottom hold
Peak/bottom hold
Local minimal value hold
59
Load display
Time
RESET
zone
Detecting zone
Detecting
zone
key input 1
PEAK/TRACK
input 1
key or
RESET input
PEAK LED
2
MEAS. LED
2
1 Whichever
key input or PEAK/TRACK input becomes effective. At the time
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
2 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
60
Load
Load display
Time
Detecting zone
RESET
zone
Detecting
zone
key input 1
PEAK/TRACK
input 1
key or
RESET input
PEAK LED
2
MEAS. LED
2
1 Whichever
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
2 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
61
Load display
Load display0
RESET
zone
Detecting zone
Detecting
zone
key input 1
PEAK/TRACK
input 1
key or
RESET input
PEAK LED
2
MEAS. LED
2
1 Whichever
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
2 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
62
Load display
Time
Detecting
zone
Detecting
zone
zone
RESET
Holding zone
Holding zone
key input 1
PEAK/TRACK
input 1
key or
RESET input 2
PEAK LED
3
MEAS. LED
3
END LED and
END output 4
1 Whichever
key input or PEAK/TRACK input becomes effective. At the time
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
key.
Press the
RESET of the external control input signal (terminal No.11) and COM.1
(terminal No.14) are shorted.
The provided command/data is transmitted from the host (personal computer
and sequencer, etc.) by the RS232C interface or the RS422/485 interface.
3 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
4 The END output and END LED are turned on when the holding section.
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
63
Load display
Time
Detecting
zone
Holding zone
RESET
zone
Detecting
zone
Holding zone
key input 1
PEAK/TRACK
input 1
key or
RESET input 2
PEAK LED
3
MEAS. LED
3
END LED and
END output 4
1 Whichever
key input or PEAK/TRACK input becomes effective. At the time
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
key.
Press the
RESET of the external control input signal (terminal No.11) and COM.1
(terminal No.14) are shorted.
The provided command/data is transmitted from the host (personal computer
and sequencer, etc.) by the RS232C interface or the RS422/485 interface.
3 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
4 The END output and END LED are turned on when the holding section.
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
64
Load display
Time
Detecting
zone
RESET
Holding zone
zone
Detecting Holding
zone
zone
key input 1
PEAK/TRACK
input 1
key or
RESET input 2
PEAK LED
3
MEAS. LED
3
END LED and
END output 4
1 Whichever
key input or PEAK/TRACK input becomes effective. At the time
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
2 Proceed either of undermentioned operation when the inflection point held during
the PEAK/TRACK ON is reset, and the measuring is begun again.
The load display becomes 0 while inputting RESET.
Press the
key.
RESET of the external control input signal (terminal No.11) and COM.1
(terminal No.14) are shorted.
The provided command/data is transmitted from the host (personal computer
and sequencer, etc.) by the RS232C interface or the RS422/485 interface.
3 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
4 The END output and END LED are turned on when the holding section.
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
65
Load display
Time
Detecting
zone
Holding
zone
Detecting RESET
zone
zone
Detecting
zone
Holding
zone
key input 1
PEAK/TRACK
input 1
key or
RESET input
PEAK LED
2
MEAS. LED
2
1 Whichever
key input or PEAK/TRACK input becomes effective. At the time
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
2 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
3 END output and END LED are turned on during the holding zone.
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
66
Load display
Time
Detecting
zone
Holding Detecting
zone
zone
RESET
zone
Detecting Holding
zone
zone
key input 1
PEAK/TRACK
input 1
key or
RESET input
PEAK LED
2
MEAS. LED
2
1 Whichever
key input or PEAK/TRACK input becomes effective. At the time
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
2 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
3 END output and END LED are turned on during the holding zone.
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
67
Load
Load display
Detecting
Detecting
zone
Holding zone
zone
RESET
zone
Detecting Holding
zone
zone
key input 1
PEAK/TRACK
input 1
key or
RESET input
PEAK LED
2
MEAS. LED
2
1 Whichever
key input or PEAK/TRACK input becomes effective. At the time
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
2 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
3 END output and END LED are turned on during the holding zone.
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
68
Load display
Time
Detecting
zone
Holding zone
RESET Detecting
zone
zone
Holding zone
key input 1
PEAK/TRACK
input 1
key or
RESET input 2
PEAK LED
3
MEAS. LED
3
END LED and
END output 4
1 Whichever
key input or PEAK/TRACK input becomes effective. At the time
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
Press the
key.
RESET of the external control input signal (terminal No.11) and COM.1
(terminal No.14) are shorted.
The provided command/data is transmitted from the host (personal computer
and sequencer, etc.) by the RS232C interface or the RS422/485 interface.
3 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
4 The END output and END LED are turned on when the holding section.
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
69
Load display
Time
Detecting
zone
Detecting
zone
zone
RESET
Holding zone
Holding zone
key input 1
PEAK/TRACK
input 1
key or
RESET input 2
PEAK LED
3
MEAS. LED
3
END LED and
END output 4
1 Whichever
key input or PEAK/TRACK input becomes effective. At the time
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
Press the
key.
RESET of the external control input signal (terminal No.11) and COM.1
(terminal No.14) are shorted.
The provided command/data is transmitted from the host (personal computer
and sequencer, etc.) by the RS232C interface or the RS422/485 interface.
3 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
4 The END output and END LED are turned on when the holding section.
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
70
Load display
Time
Detecting
zone
RESET
Holding zone
zone
Detecting
zone
Holding zone
key input 1
PEAK/TRACK
input 1
key or
RESET input 2
PEAK LED
3
MEAS. LED
3
END LED and
END output 4
1 Whichever
key input or PEAK/TRACK input becomes effective. At the time
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
Press the
key.
RESET of the external control input signal (terminal No.11) and COM.1
(terminal No.14) are shorted.
The provided command/data is transmitted from the host (personal computer
and sequencer, etc.) by the RS232C interface or the RS422/485 interface.
3 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
4 The END output and END LED are turned on when the holding section.
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
71
Load display
Time
Detecting zone(F68)
Holding
zone
Detecting zone(F68)
Detecting zone
Holding
zone
key input 1
PEAK/TRACK
input 1
key or
RESET input
PEAK LED
2
MEAS. LED
2
1 Whichever
key input or PEAK/TRACK input becomes effective. At the time
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
2 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
3 END output and END LED are turned on during the holding zone.
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
72
Load display
Time
Holding
zone
Detecting RESET Detecting
zone
zone zone
Detecting zone(F68)
Detecting zone(F68)
Detecting zone
Holding
zone
key input 1
PEAK/TRACK
input 1
key or
RESET input
PEAK LED
2
MEAS. LED
2
END LED and
END output 3
1 Whichever
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
2 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
3 END output and END LED are turned on during the holding zone.
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
73
Load
Load display
Reference line
Time
Holding
zone
key input 1
PEAK/TRACK
input 1
key or
RESET input
PEAK LED
2
MEAS. LED
2
1 Whichever
key input or PEAK/TRACK input becomes effective. At the time
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
2 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
3 END output and END LED are turned on during the holding zone.
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
74
The minimal value of the load is detected and held during detection time set by the function
(F68) from point by which the PEAK/TRACK signal is input. (Related function F6000003,
F6100002, F630000099999, F640000000049 and F680000009999)
It is necessary to input the RESET signal to release holding. The load display becomes 0 against
the RESET input during detecting, and detected again by RESET input OFF.
As for the detecting condition, refer to the paragraph 756. (The set of the local maximal and
minimal point detecting condition).
Load
Load display
Time
Detecting time(F68)
Detecting
zone
RESET
zone
Detecting
zone
Detecting time(F68)
Detecting
zone
Holding
zone
key input 1
PEAK/TRACK
input 1
key or
RESET input
PEAK LED
2
MEAS. LED
2
1 Whichever
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
2 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
3 END output and END LED are turned on during the holding zone.
When the local maximal (minimal) value cannot be detected during the detection
time (set of function F68), the TRACK operation will be made.
key or
key during the various kinds of hold function is
The input of
effective only in the measurement mode.
75
Load display
Time
Detecting time(F68)
Detecting time(F68)
Detecting
zone
RESET
zone
Detecting
zone
Detecting
zone
Holding
zone
key input 1
PEAK/TRACK
input 1
key or
RESET input
PEAK LED
2
MEAS. LED
2
END LED and
END output 3
1 Whichever
key input or PEAK/TRACK input becomes effective. At the time
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
2 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
3 END output and END LED are turned on during the holding zone.
When the local maximal (minimal) value cannot be detected during the detection
time (set of function F68), the TRACK operation will be made.
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
76
Load display
Detecting time(F68)
Detecting
zone
RESET
zone
Detecting
zone
Detecting time(F68)
Detecting
zone
Time
Holding
zone
key input 1
PEAK/TRACK
input 1
key or
RESET input
PEAK LED
2
MEAS. LED
2
1 Whichever
key input or PEAK/TRACK input becomes effective. At the time
of short of PEAK/TRACK input, the peak hold condition will not change even if
the
2 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
3 END output and END LED are turned on during the holding zone.
When the inflection point value cannot be detected during the detection time (set of
function F68), the TRACK operation will be made.
key or
key during the various kinds of hold function is
The input of
effective only in the measurement mode.
77
Load display
Time
Detecting time(F68)
Detecting
zone
RESET
zone
Detecting
zone
Holding
zone
key or
RESET input
PEAK LED
1
MEAS. LED
1
1 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
2 END output and END LED are turned on during the holding zone.
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
78
Load display
Time
Automatic start level
Detecting time(F68)
Detecting
zone
RESET
zone
Detecting
zone
Holding
zone
key or
RESET input
PEAK LED
1
MEAS. LED
1
1 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
2 END output and END LED are turned on during the holding zone.
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
79
Load
0
Load display
Time
Detecting time(F68)
Detecting
zone
RESET
zone
Detecting
zone
Holding zone
key or
RESET input
PEAK LED
1
MEAS. LED
1
1 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
2 END output and END LED are turned on during the holding zone.
The input of
key or
key during the various kinds of hold function is
effective only in the measurement mode.
80
The local minimal value hold in the specified zone from automatic start time
The local minimal value of the load is detected and held during set time from the point by
which the load indicated value crossed automatic start level (F69).
(Related function F6000003, F6100004, F630000099999, F640000000049,
F680000009999 and F699999999999)
It is necessary to input the RESET signal to release holding. The load display becomes 0
against the RESET input during detecting, and detected again by RESET input OFF.
As for the detecting condition, refer to the paragraph 756 (The set of the local maximal and
minimal point detecting condition).
Load
Load display
Time
Detecting time(F68)
Detecting
zone
RESET
zone
Detecting
zone
Detecting time(F68)
Detecting
zone
Holding zone
key or
RESET input
PEAK LED
1
MEAS. LED
1
1 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
2 END output and END LED are turned on during the holding zone.
When the local maximal (minimal) value cannot be detected in the detection time
(set of function F68), TRACK operation is proceeded, and it detects again every
time the load change passes the automatic start level afterwards (Regardless of the
direction).
81
The local maximal value hold in the specified zone from automatic start time
The local maximal value of the load is detected and held during detection time set by the
function (F68) from the time when the load indicated value passed automatic start level
(F69). (Related function F6000004, F6100004, F630000099999, F6400000
00049, F680000009999 and F699999999999)
It is necessary to input the RESET signal to release holding. The load display becomes 0
against the RESET input during detecting, and detected again by RESET input OFF.
As for the detecting condition, refer to the paragraph 756 (The set of the local maximal and
minimal point detecting condition).
Load
Load display
Time
Detecting time(F68)
Detecting
zone
RESET
zone
Detecting time(F68)
Detecting
zone
Detecting
zone
Holding zone
key or
RESET input
PEAK LED
1
MEAS. LED
1
1 Interlocked to PEAK LED or MEAS. LED, open collector output from S0 terminal
is made. (by function F33)
2 END output and END LED are turned on during the holding zone.
When the local maximal (minimal) value cannot be detected in the detection time
(set of function F68), TRACK operation is proceeded, and it detects again every
time the load change passes the automatic start level afterwards (Regardless of the
direction).
82
Inflection point hold in the specified zone from automatic start time
The value just before a rapid change in the load is detected and held during detection time set
by the function (F68) from the time when the load indicated value passed automatic start
level (F69). (Related function F6000005, F6100003, F659999999999, F66
0000000450, F670000000450, F680000009999 and F699999999999)
It is necessary to input the RESET signal to release holding. The load display becomes 0
against the RESET input in the detecting, and detected again by RESET input OFF. As for the
detecting condition, refer to the paragraph 757 (The set of the inflecting point detecting
condition).
Load
Load display
Time
Detecting time(F68)
Detecting RESET
Detecting
zone
zone
zone
Detecting time(F68)
Detecting
zone
Holding zone
key or
RESET input
PEAK LED
1
MEAS. LED
1
When the inflecting point value cannot be detected in the detection time (set of
function F68), TRACK operation is proceeded, and it detects again every time the
load change passes the automatic start level afterwards (Regardless of the
direction).
83
756. Setting of detecting condition of the local maximal value and the local minimal value
As a peak holding function of this instrument, Local maximal value holding function by
which the first peak magnitude (prime maximum value) is held most for the load change and
The local mimimal value holding function by which the first bottom value (prime minimum
value) is held most after the first peak magnitude (prime maximum value) is passed most are
provided. In the The local maximal value holding function and The local mimimal value
holding function, the parameter to detect the local maximal value and the local minimal value
is set in the function mode. The width of data to judge the local maximal value and the local
minimal value by function F63 is set. Magnification a to detect the local maximal value and
the local minimal value by function F64 is set.
D Method of detecting the local maximal value and the local minimal value
A
X
B
In case of the load change like the abovementioned, make the first peak magnitude as A
point and the first bottom value as B point. Difference X between A point and B point is
calculated, and judge the local maximal value as A point and the the local minimal value as
B point when the value of this X is more than function F63 set value.
C
A
(YaXa0.14.9)
X
B
The value by which the difference X between A as the local maximal value and B as the
local minimal value judged, and set value a (0.14.9) of function F64 is multiplied
becomes level Y by which the local maximal value and the local minimal value are detected.
When the load change passes B point and exceeds over the C point(BY), the load
display section displays A point (B point) as the local maximal value (the local minimal
value), and becomes a hold status.
In the environment with load change by vibration and load change by exogenous
noise etc., when the width of the local maximal/minimal value judgement data (set
of F63) is too small, the load change might be detected as local maximal/minimal
value and a correct measurement result may not be obtained.
The detection standard of the local maximal/minimal value is different according to
the measured sample. Please adjust referring to the detection method to the
optimum value.
84
Z
Inflection point
YX=Z
X
a
A
X
B
When there is a load change like the abovementioned, the amount of the load change
during the time width A set by function F66 is assumed to be X. In addition, the load
change during the time width B set by function F67 is assumed to be Y.
When you assume the change amount of the inclination to have pulled X of the change
amount of time width A from Y of the change amount of time width B to be Z, and when
the value of change amount Z is more than the data width set value of function F65 (set
value of YXF65), a point is displayed in load display section as inflection point and
becomes a hold condition.
85
When the bridge power supply voltage is changed, make calibration again.
It is common to all of four kinds of calibration data and executed.
86
key makes zero set function operated and the display will show
the chapter 5.), pressing the
0 compulsively.
However, zero set will not be accepted when zero compensation for total 10 % is executed with
zero set and zero tracking until that time. (ERR0 display)
Also, the same operation can be made with the operation of ZERO at the input signal of external
control. Cancellation for data applied zero compensation by zero set can be executed with Function
F98.
10 digit,
10 digit
10 digit
10 digit
Moreover, when the key is locked , lock for the key will be cancelled only once after the
key is pressed together with the key for more than 3 seconds.
100 digit
1
3
4
When the
key is pressed in the Measurement mode, CHECK value equivalent to the set value
with the Function F11 will be ON. And at the same time when the CHECK on status display
lights up, the load value equivalent to the set value with Function F11 will be added to the load
display value. As for default, 0.3 mV/V has set.
By pressing the
as it is.
key again, the CHECK value will be OFF and returns to the former condition
When the setting of Function F11 is 00000, load display value will not vary
even if the CHECK lights up on the status display by pressing the
Because CHECK is 0.0 mV/V.)
It is common to all of four kinds of calibration data and executed.
87
key.
Warning
When the power supply is turned on with shorting the external HOLD signal, the
analog output will be made as follows:
When the target of HOLD by F10 is the analog output, the analog output will
become approx.0 V in voltage output, and approx.12 mA in current output..
The analog outputs for the instrument are 2 type of Voltage output (Standard)
and Current output(Optional).
The analog output of the instrument executes rewriting the outputs synchronous
with the display.
The analog output has possibility of the output variation when the power is turned
on. To take the stable condition, use the instrument about one hour after the power
has been turned on.
Analog output
The maximum 20 mA
10 V
value
110 % of the
maximum display
The minimum
value
4 mA
0V
Display
The maximum
display
110 % of the
maximum display
0 display
Approx.2.4 mA
Approx.11 V
88
F21 sets the display when the minimum value(standard voltage output0 V, optional current
output4 mA) is desired to output. F20 sets the display when the maximum value(standard
voltage output10 V, optional current output20 mA) is desired to output.
EX) F21Set as 1 000
F22Set as 5 000
When the display is 5 000, the maximum value outputs.
When the display is 1 000, the minimum value outputs.
Analog output
Approx.21.6 mA
Approx.11 V
The maximum value 20 mA
10 V
Warning
1 000
Approx.2.4 mA
Approx.11 V
5 000
Display
5 500
Take care that the setting on the F22 doesnt exceed the maximum display value
that has set in the Chapter 5. Meantime, please put the set value of F21 into the
condition of (the absolute value of F21 setting value) the set value of F22. If
neglected the correct scaling cant be obtained.
89
During the application on fine adjustment, if you want to suspend, press the
key. The data of the minimum value and the maximum value are kept as they were
before entering the fine adjustment, and the Measurement mode can be
reentered.
Make fine adjustment one (1) hour or so after feeding the power.
You can make fine adjustment with safer conditions.
Procedures
Press the
key for about one second.
The setting display section shows FUNC.
Load display section continuously displays a
present load value.
Press the
key 8 times.
The setting display section changes as FUNC
CCALLCALZEROSPAN
TARECHEKMONTVCAL.
Press the
key.
The load display section shows ALOW.
90
Procedures
Press the
key.
The load display section flashes on and off
showing ALOW. At the same time, the analog
output equivalent to the minimum value of
analog output will be obtained.
Adjust so the output will become the minimum
value with the right keys.
Voltage output
(Standard)
Minimum
value
0V
Current output
(Optional)
4 mA
Press the
key.
The load display section flashes display showing
A_HI.
Press the
key.
The load display section flashes on and off
showing A_HI.
At the same time, the analog output equivalent
to the maximum value of analog output will be
obtained.
Adjust so the output will become the maximum
value with the right keys.
Voltage output
(Standard)
Maximum
value
10 V
Current output
(Optional)
20 mA
91
Procedures
Press the
key.
The load display section shows END.
By pressing the
key again, the
Measurement mode can be returned through the
VCAL mode, then the present load is displayed.
At this moment, the result of fine adjustment on
the minimum/maximum output of analog output
can be renewed.
92
Warning
Before making the fine adjustment, be sure to make scaling for the analog output
by referring to the paragraph 7121. If neglected, deviation of output cant be
adjusted during the fine adjustment.
During the application on fine adjustment, if you want to suspend the fine
Procedures
Press the
key for about one second.
The setting display section shows FUNC.
Load display section continuously displays a
present load value.
Press the
key 9 times.
The setting display section changes as FUNC
CCALLCALZEROSPAN
TARECHEKMONTVCAL
VADJ.
Press the
key.
The load display section shows ALOW.
At the same time, set the weight equivalent to
the minimum output value(standard voltage
output0 V, optional current output4 mA) of
the analog output.
93
Procedures
Press the
key.
The load display section flashes on and off
showing the current load value.
At the same time, adjust the deviation with the
right keys so the analog output meets with the
actual weight.
key.
Press the
The load display section shows A_HI.
At the same time, set the weight equivalent to
the maximum output value(standard voltage
output10 V, optional current output20 mA)
of the analog output.
Press the
key.
The load display section shows the current load
value and flashes on and off.
At the same time, adjust the deviation of analog
output against the load with the right keys.
94
Procedures
Press the
key.
The load display section shows END.
By pressing the
key again, the
Measurement mode can be returned through the
VADJ mode, then the present load will be shown.
At this moment, the result of fine adjustment on
the minimum/maximum output of analog output
can be renewed.
95
The memory locations for the ZERO data can be changed to whichever the RAM
or the EEPROM with the setting Function F71.
96
The check on the BCD output can be operated only when the BCD output is
installed.
The instrument can return to the Measurement mode by pressing the
even in the halfway of the Check mode.
key
When the
key is pressed with the setting display section of FUNC, the
display will change as the following arrow marks indicate at every time the key is
Procedures
Press the
key for one second.
The setting display section shows FUNC.
Load display section continuously displays a
present load value.
Press the
key 6 times.
The setting display section changes as FUNC
CCALLCALZEROSPAN
TARECHEK.
97
Procedures
Check on the ROM version
Press the
key.
The Check mode can be entered, and the
display on the load display section shows
key operation.
ROM
OP
BV
IN
SOUT
AOUT
BCD
END
ROM
key
98
Procedures
Check on the options
Press the
key.
The load display section shows OP.
Check on bridge power supply voltage
Display
Installed options
07
Current output
15
BCD output
74
RS232C interface
76
RS422/485 interface
Press the
key.
The load display section shows BV.
99
Procedures
Check on the external control input
Press the
key.
The load display section shows IN.
MEAS. display
HOLD display
PEAK display
END display
SEL.1 display
SEL.2 display
ZERO input
HOLD input
PEAK/TRACK input
RESET input
SEL.1 input
SEL.2 input
Press the
key.
The load display section show SOUT.
S0
S1
S2
S3
S4
END
key
key
100
Procedures
Check on the analog output
Press the
key.
The load display section shows AOUT.
MID
HIGH
Display
Standard
Option
(Voltage output) (Current output)
LOW
0V
4 mA
MID
5V
12 mA
HIGH
10 V
20 mA
Press the
key.
The load display section shows BCD.
By pressing the
key again, the display shows
00000 and the digit of 100 flashes on and off.
At this moment, the same value as the display
outputs from the BCD output. When changing
the display with the right keys, the BCD output
changes corresponding to it.
101
Procedures
Press the
key.
The load display section shows END.
By pressing the
key again, it will over the
Check mode and returns to the Measurement
mode to show the load value.
10
102
Procedures
Press the
key for one second.
The setting display section will show FUNC.
The load display section continuously displays a
present load value.
Press the
key 7 times.
The setting display section changes as CCAL
LCALZEROSPANTARE
CHEKMONT.
103
Procedures
Press the
key.
The Monitor mode can be entered, and the
converted value into mV/V for the present input
value for the transducer will flash on and off on
the load display section.
Press the
key.
The load display section shows END.
Press the
key.
The Monitor mode can be over, and the present
load is shown on the load display section.
104
8. Function mode
Press the
key for one second.
The setting display section shows FUNC.
The load display section continuously displays a
present load value.
Press the
key. Function mode can be
entered, then the setting display section shows
F**, and the digit of 100 will flash on and off.
The last called Function No. is shown at **.
Suspend the setting of Function mode, then press
pressing the
key.
105
Procedures
Press the
key.
Content of setting Function that has selected is
displayed and the digit of 100 will flash on and off
in the load display section.
Change the setting with the right keys.
Press the
key.
The set contents are registered, then the load
display section returns to the registered Function
No., and the 100 digit will flash on and off.
Press the
key.
Setting another Function No. is desired, return
to step 3.
Press the
key.
Quitting the Function mode, the Measurement
mode can be returned.
106
Initial value00000
key
digit key
digit key
digit key
digit key
100 digit
101
102
103
104
Key lock cancellation is made by setting 0, and key lock is made by setting 1.
pressed together.
107
D F10
Setting of the target of HOLD
Initial value11111 100 digitLoad display
101 digitComparator S0 open collector output, LED display
102 digitComparator S1, S2, S3 and S4 open collector output,
LED display
3
10 digitAnalog output
104 digitOptional BCD output
Out of the target at the setting 0, and target of HOLD is available at the setting 1.
D F11
Setting the CHECK value
Initial value00003 Setting range0000000020
Unit0.1 mV/V
Approx. 1.5 mV/V CHECK value at the setting 00015.
It is common to all of four kinds of calibration data and executed.
D F12
Setting bridge power supply voltage
Initial value00000 0000010 V
000015 V
000022.5 V
It is common to all of four kinds of calibration data and executed.
D F20
Setting the target of analog output
Initial value00000 00000TRACK
00001PEAK
It is common to all of four kinds of calibration data and executed.
D F21
D F22
D F30
Setting comparator operation
Initial value11111 0OFF
1ON
100 digitComparator S0
101 digitComparator S1
102 digitComparator S2
103 digitComparator S3
104 digitComparator S4
It is common to all of four kinds of calibration data and executed.
108
D F31
Setting the target of comparator
Initial value00000 0TRACK
1Synchronous with display
100 digitComparator S0
101 digitComparator S1
102 digitComparator S2
103 digitComparator S3
104 digitComparator S4
It is common to all of four kinds of calibration data and executed.
D F32
Setting the direction of comparator
Initial value00000 0Greater or equal
1less or equal
100 digitComparator S0
101 digitComparator S1
102 digitComparator S2
103 digitComparator S3
104 digitComparator S4
It is common to all of four kinds of calibration data and executed.
D F33
Setting applicable condition for the comparator S0
Initial value00000 00000ON when comparator S0 is in the condition of
Load display value(The maximum display value)
00001ON when both of S1 and S2 open collector output are off.
00002ON when both of S1 and S3 open collector output are off.
00003ON when both of S1 and S4 open collector output are off.
00004ON when both of S2 and S3 open collector output are off.
00005ON when both of S2 and S4 open collector output are off.
00006ON when both of S3 and S4 open collector output are off.
00007Operate whichever Open collector ON more than the set
value or Open collector ON below the set value.
00008Interlock with HOLD LED
00008Interlock with PEAK LED
00008Interlock with MEAS. LED
It is common to all of four kinds of calibration data and executed.
D F34
Setting the condition of Hysteresis operation for comparator
Initial value00000 00000ON delay
00001OFF delay
It is common to all of four kinds of calibration data and executed.
D F35
Setting Hysteresis data for comparator
Initial value00000 00000Hysteresis data width OFF
Setting rage0000000099
Unit1D
Data width of 99D at the setting of 00099.
It is common to all of four kinds of calibration data and executed.
D F36
Setting Hysteresis time width for comparator
Initial value00000 00000Hysteresis time width OFF
Setting rage0000000099
Unit0.1 s
Data width of 9.99 s at the setting of 00999
It is common to all of four kinds of calibration data and executed.
109
D F38
Setting light ON/OFF of comparative value display section
Initial value00000 00000Light ON
00001Light OFF
D F40
Setting the target of BCD output(Effective when the option is installed.)
Initial value00000 00000TRACK
00001PEAK
D F41
Setting the logic of BCD output (Effective when the option is installed.)
Initial value00000 00000Negative logic
00001Positive logic
D F42
Setting the polarity of BCD output (Effective when the option is installed.)
Initial value00000 00000Negative logic
00001Positive logic
D F43
Setting the logic of BCD flag output (Effective when the option is installed.)
Initial value00000 00000Negative logic
00001Positive logic
D F44
Setting the logic of BCD P.C. output (Effective when the option is installed.)
Initial value00000 00000Negative logic
00001Positive logic
D F45
Setting the BCD P.C. width(Effective when the option is installed.)
Initial value00004 00000125 ms
0000125 ms
0000210 ms
000035 ms
000042.5 ms
D F46
Setting BCD output times(Effective when the option is installed.)
Initial value00004 000004 times/s
0000120 times/s
0000250 times/s
00003100 times/s
00004200 times/s
D F50
D F51
D F52
D F53
D F54
D F55
D F56
D F57
Setting the ID number of RS422/485(Effective when the option is installed.)
Initial value00000 Setting range0000000031
D F58
Changing RS422/485(Effective when the option is installed.)
Initial value00000 00000RS422
00001RS485
D F59
Setting the delay time of returning RS485
Initial value00005 Setting range0000000999
Unit
1 ms
The delay is 999 ms at the 00999 setting.
D F60
Setting the Peak, Bottom and Peak bottom hold
Initial value00000 00000Peak hold
00001Bottom hold
00002Peak bottom hold
00003Local minimal value hold
00004Local maximal value hold
00005Inflection point hold
D F61
Setting the kinds of detecting mode
Initial value00000 00000All zone specification
00001Zone specification
00002Time zone specification
00003Automatic start time zone specification
D F62
Setting referring point(Effective when peak/bottom holding condition)
Initial value00000 Setting range9999999999
D F63
111
D F64
D F65
D F66
D F67
D F68
D F69
D F71
Setting the storing area of ZERO data
Initial value00001 0RAM
1EEPROM
Selects whether the data at the time of ZERO is recorded at the EEPROM or
not. In case that the high frequency of use of ZERO, the durability times will be over,
so set 0. The durability times for the EEPROM will be approx. one million times.
It is common to all of four kinds of calibration data and executed.
D F72
Setting the effective time for external control input
Initial value00000 0000050 ms
0000120 ms
0000210 ms
000035 ms
000042 ms
000051 ms
D F75
Symmetric property compensation value(for reference)
The compensation value set when the symmetric property compensation is executed
can be referred.
A setting here cannot be changed.
The reference value here is a value to the calibration data which has been selected.
D F80
Setting to the changeover target of calibration data and comparator code
Initial value00000 0Changeover by the function(F81 or F82)
1Changeover by external control input
100 digitCalibration data
101 digitCode
112
D F81
Setting of the calibration data selection
Initial value00000 00000Calibration data 0
00001Calibration data 1
00002Calibration data 2
00003Calibration data 3
D F82
Setting of the comparator code selection
Initial value00000 00000Code 0
00001Code 1
00002Code 2
00003Code 3
D F90
Increment value (For reference)
The increment value set when the calibration is applied can be referred to.
The setting cant be changed in the function.
The reference value here is the value for the selecting calibration data.
D F91
The maximum display value (For reference)
The maximum display value set when the calibration is applied can be referred to.
The setting cant be changed in the function.
The reference value here is the value for the selecting calibration data.
D F92
The actual load value (For reference)
The actual load value set when the calibration is applied(LCAL) can be referred to.
When the calibration except LCAL is made, this value will not change.
The setting cant be changed in the function.
The reference value here is the value for the selecting calibration data.
D F93
Zero calibration value (For reference)
The input voltage value that has read as the initial load value at the time of executing
calibration can be referred to.
The setting cant be changed in the function.
The reference value here is the value for the selecting calibration data.
D F94
Span calibration value (For reference)
The input voltage value at the time of the maximum display can be referred to.
The setting cant be changed in the function.
The reference value here is the value for the selecting calibration data.
D F95
Internal calibration data value (for our maintenance)
The setting cant be changed in the function.
The reference value here is the value for the selecting calibration data.
Internal calibration data value (for our maintenance)
D F96
The setting cant be changed in the function.
The reference value here is the value for the selecting calibration data.
D F97
Prohibition of calibration
Initial value00000 00000Possible to calibrate
00001Prohibition from calibration
It is common to all of four kinds of calibration data and executed.
113
D F98
ZERO clear
Zero compensated data by zero set function can be cancelled.
key is pressed while ZCLR display lights on and off, F98 display can
When the
be returned. Now, ZERO clear has completed.
The selected each calibration data is executed.
D F99
Memory clear
Setting from F01 to F97 recorded at EEPROM will return to the default value.
key is pressed with the display of F99, then FCLR display can be
obtained. (At the same time, the display lights on and off.) At this point, press the
When the
key when suspending memory clear is desired. Measurement mode can be returned and
Memory clear will not be executed.
When the
key is pressed during FCLR load display lights on and off, and after
about 1 second, it will become FUNC display and the operation of Memory clear has
completed.
Warning
Never use the following functions because they may destroy the functions at
internal of the instrument.
F00
F07
F08
F09
F13
F14
F15
F16
F17
F18
F19
F23
F24
F25
F26
F27
F28
F29
F37
F39
F47
F48
F49
F70
F73
F74
F76
F77
F78
F79
F83
F84
F85
F86
F87
F88
F89
114
9. Options
The options for the instrument are as follows:
1
P/N.CSD819CP07
BCD output
P/N.CSD819CP15
RS232C interface
P/N.CSD819CP74
RS422/485 interface
P/N.CSD819CP76
For the options from to , there are some limitations among their combinations as follows
P07
P15
P74
P76
P07
P15
P74
P76
Possible, Impossible
Refer to the paragraph 435, for the connecting method, and refer to the
paragraph 712, for their applications.
F21
F22
CSD819CP07
(1) Output
Output
4 mA to 20 mA
260 or less
(3) Nonlinearity
0.025 %F.S.
(4) Resolution
115
Warning
When power is ON for the instrument with the external HOLD signal shorted, the
BCD output will be as follows:
1
Even when the Display is targeted for the HOLD with the F10, BCD outputs
00000 if the target for BCD output is set as Display.
When the BCD output is assumed to be the target of HOLD with the F10, BCD
output outputs 00000.
Other than the case above and , the present load value will output after
00000 has output.
In other than the Measurement mode, the BCD output will not be renewed. In due
course, the ERROR for the BCD output wont be ON in other than the mode of
the Measurement mode, so care is taken fully.
When
key is applied, pay attention to the following point. By the ON operation
of CHECK, the OL error display (BCD output is OVR.) might be shown.
TRACK, PEAK
F41
F42
F43
F44
F45
F46
key
Same as key
Same as key
Same as
COM.
1100
2100
4100
8100
13
14
15
16
17
8102
1103
2103
4103
8103
25
26
27
28
29
ERROR
P.C.
HOLD
N.C.
SEL.1
6
7
8
9
1101
2101
4101
8101
18
19
20
21
1104
COM.
2104
4104
30
31
32
33
SEL.2
ZERO
PEAK/TRACK
RESET
10
11
12
1102
2102
4102
22
23
24
8104
POL.
OVR.
34
35
36
N.C.
BCDENABLE
N.C.
430
2.2 k
Approx.12 V
0.022 F
INPUT
COM.
COM.
VCEDC30 VIc20 mA MAX.
117
Warning
In case of reading each output data of the BCD output through the sequencer and
so on, read them at the timing of The edge from ON to OFF for the P.C. (Print
command). Moreover, read the Input response delay time for the reading
instrument such as a sequencer and so on, with full considerations. If neglected,
there may have the possibility that correct reading of data wont be obtained.
(1) Normal
200 times/sApprox.5 ms
100 times/sApprox.10 ms
50 times/sApprox.20 ms
20 times/sApprox.50 ms
4 times/sApprox.250 ms
ON
DATA
ON
ON
ON
POL.
Changeable from approx.2.5 ms, 5 ms, 10 ms, 25 ms and 125 ms by function
ON
ON
ON
ON
P.C.
At the time of data output of each P.C., DATA and POL., output transistor will
become ON(Negative logic electrically).
(2) When the data is overranged
DATA
POL.
ON
ON
ON
ON
ON
ON
P.C.
ON
OVR.
At the time of OVR output, output transistor will at the OVR signal will become
ON(Negative logic electrically). Moreover, for all of the DATA, output transistor
will become OFF (Positive logic electrically) at the time of OVR output. (However,
for the POL., normal OFF at the OL, and normal ON at the OL.
(3) When ERROR is occurred
DATA
POL.
ON
ON
ON
ON
ON
ON
P.C.
ON
ERROR
At the time of ERROR output, output transistor at ERROR signal will become
ON(Negative logic electrically). Moreover, for each DATA, POL., all of the output
transistor will become OFF at the time of ERROR output(Positive logic
electrically).
118
At the time of HOLD signal input, output transistor for the P.C. will be OFF
condition. (Positive logic electrically.)
After inputting the HOLD signal, it takes the following response times to freeze the
DATA, POL or cancellation of HOLD is executed.
At 200 times/sApprox.5 ms at maximumInput response time
At 100 times/sApprox.10 ms at maximumInput response time
At 50 times/sApprox.20 ms at maximumInput response time
At 20 times/sApprox.50 ms at maximumInput response time
At 4 times/sApprox.250 ms at maximumInput response time
Output data
Condition of
transistor
Yes
ON
PinCOM level
at the time of voltage
supply externally.
L
No
OFF
Yes
OFF
No
ON
927. Selection of output logic for P.C.(Print command), and of its width
Selection of the P.C. logic for BCD output, and its width can be made by setting
function. (Related functionF44, F45)
Select the P.C. width to meet with the display rate set by F03, and execute the suitable
selection according to the following list.
Display
rate(F46)
P.C. width
Approx.125 ms Approx.25 ms Approx.10 ms
Approx.5 ms
Approx.2.5 ms
4 times/s
20 times/s
50 times/s
100 times/s
200 times/s
Warning
The selection of P.C. width is made adequately according to the display times set
with the F03. If neglected, the P.C. output will not operate correctly.
119
Warning
F51
F52
F53
F54
F55
F56
Setting of this function makes the setting activated just after setting.
Corresponds to RS232C
Data length
7 bit or 8 bit
Parity bit
Stop bit
1 bit or 2 bit
Terminator
CR or CRLF
Synchronous method
Transmission data
within 15 m
120
Command/Data
Data
HostCSD819C
CSD819CHost
The communication operation can be made in all of the modes. However, in the
Calibration mode, Fine adjustment mode and Setting mode, the Error command
will be sent.
The flow control is not executed in the CSD819C.
The CTS/RTS signal isnt applied.
The X flow control isnt performed.
The operating communication is a conversational dialogue type.
121
Signal Name
CD
TXD
RXD
N.C.
S.G.
N.C.
RTS
CTS
N.C.
The screws for the fixing base of plug at the connector of RS232C interface is inch
type thread.
An internal circuit and photocoupler are insulated.
(2) Example of connection at the RS232C interface
1
Example 1
Host(25 pin
CSD819C
1
CD
F.G.
TXD
TXD
RXD
RXD
N.C.
3
4
S.G.
CTS
N.C.
DSR
RTS
S.G.
CTS
DCD
N.C.
RTS
19
20
21
25
122
DTR
Example 2
Host(9 pins)
CSD819C
1
CD
DCD
TXD
RXD
3
4
RXD
TXD
N.C.
3
4
S.G.
S.G.
N.C.
DSR
RTS
RTS
CTS
CTS
N.C.
RI
DTR
4
0
10
12
14
Terminator
Sign of
load data
Command No.
Load data
2
@
10
12
O
123
12
O
14
3
12
10
6
9
10
0
4
0
2
@
2
@
12
Terminator
14
3
Terminator
14
Terminator
14
Terminator
4
0
6
2
Terminator
20
Command No.
21
22
Return(CSD819CHost)
2
4
6
@
Operation
Command No.
10
12
14
Terminator
Load data
2
@
10
0
10
12
O
124
12
O
14
3
12
10
6
2
4
0
2
@
2
@
12
Terminator
14
3
Terminator
14
Terminator
14
Terminator
6
0
Command No.
Operation
30
31
32
33
34
Terminator
Command No.
Return(CSD819CHost)
2
4
6
@
10
12
14
Command No.
Terminator
Sign
Set value
4
0
6
0
Command No.
Operation
40
Terminator
Command No.
Return(CSD819CHost)
2
4
@
6
a
8
b
10
d
Command No.
aSEL.1
bSEL.2
cCHECK
dHOLD
ePEAK
fMEAS.
gEND
LED display
LED display
LED display
LED display
LED display
LED display
LED display
12
f
14
Terminator
Space
Condition
1ON, 0OFF
1ON, 0OFF
1ON, 0OFF
1ON, 0OFF
1ON, 0OFF
1ON, 0OFF
1ON, 0OFF
125
4
0
Command No.
6
1
41
Terminator
Operation
Reading out the comparative
result
Command No.
Return(CSD819CHost)
2
4
6
@
S0
8
S1
S2
10
S3
12
S4
14
Terminator
Command No.
Space
Condition
S01ON, 0OFF
S11ON, 0OFF
S21ON, 0OFF
S31ON, 0OFF
S41ON, 0OFF
5
Change of condition(HostCSD819C)
2
4
6
@
Command No.
Terminator
50
Operation
Zero set
Command No.
51
52
PEAK/TRACK
RESET
Return(CSD819CHost)
2
4
6
@
Terminator
Command No.
4
0
10
12
Command No.
14
Terminator
Set value
Sign
Command No.
Return(CSD819CHost)
2
4
6
@
Command No.
Operation
60
61
62
63
64
10
12
14
Terminator
Set value
Sign
126
4
0
6
0
12
Command No.
Function No.
14
Terminator
Setting value
Sign
Operation
Setting of holding mode (Change contents of F60)
00000 Peak hold
00001 Bottom hold
00002 Peak/bottom hold
00003 Local minimal value hold
00004 Local maximal value hold
00005 Inflection point hold
Setting of kinds for detecting mode
(Change contents of F61)
00000 All zone specification
00001 Zone specification
00002 Time zone specification
00003 Automatic start time specification
Setting of standard point (Change contents of F62)
Setting range9999999999 Unit1D
Setting of local maximal/minimal data width
(Change contents of F63)
Setting range0000099999 Unit1D
Setting value
0000000005
64
0000000049
65
9999999999
66
0000000450
67
0000000450
68
0000009999
69
9999999999
Function No.
60
61
62
63
Return(CSD819CHost)
2
4
6
@
10
Command No.
Function No.
10
0000000003
9999999999
0000099999
Unit1D
12
14
Terminator
Sign
127
Setting value
4
0
6
0
81
82
14
Terminator
Setting value
Space
Operation
Setting of calibration data selection
00000Calibration data 0
00001Calibration data 1
00002Calibration data 2
00003Calibration data 3
Setting value
0000000003
0000000003
Return (CSD819CHost)
2
4
6
@
12
Command No.
Function No.
Function No.
10
10
12
Command No.
Function No.
14
Terminator
Setting value
Space
4
0
6
R
8
1
Terminator
Error command No.
Error
Command No.
01
02
10
11
12
13
14
Contents
Nonexecutable error
Additionally, error by
this unit convenience
Parity error
Framing error
Overrunning error
Data code and data
length error
No applicable command
Remarks
For the calibration mode, fine adjustment mode,
check mode and monitor mode.
When the reception command cannot be
executed.
At the parity detection error
At the stop bit detection error
At the reception command reading error
When neither the received data code nor data
length are corresponding
When reception command isnt corresponding
Error code is not replied when the completion code (terminator) cannot be
detected.
Please consider dealing on the host side when the communication error command
is replied from this unit.
128
Warning
The error code is sent against the command from the host during other than the
mode of Measurement mode, such as in the Calibration mode, Fine adjustment
mode, Check mode and Monitor mode.
When CHECK switch is ON status, be careful on the following points.
1
When CHECK switch will be ON status, the instrument will be out of the
Measurement mode, but RS422/485 interface will make response to the
command from the Host.
The sending terminal is low impedance for 1 ms after finishing sending in the
instrument. Therefore, to prevent from competing with other instruments, apply
the sending wire (SDA, SDB) at the intervals of 1ms or more.
F52
F53
F54
1 bit or 2 bit
F55
CR or CR+LF
F56
Non or Exist
F57
0 to 31
F58
Change of RS421/485
F59
0 to 999
every 1 ms (unit)
129
Based on RS422/485
7 bit or 8 bit
Parity bit
Stop bit
1 bit or 2 bit
Terminator
CR or CRLF
Synchronous method
Communication data
Address
00 to 31
Approx.1 km
Builtin
(Yes/No can be selectable by the connection of terminal blocks.)
With LED
(The layout is shown on the P.C. board at rear side of terminal block.)
Command/Data
Data
HostCSD819C
CSD819CHost
The communicating operation can be made in all of the modes. However, the error
command is transmitted in the Calibration mode, Fine adjustment mode, Check
mode and Monitor mode.
The flow control is not executed in the CSD819C.
The CTS/RTS signal isnt applied.
The X flow control isnt performed.
The communication operation is a conversational type.
130
Differential output
Differential output
RDA
RDB
TRM.
S.G.
Differential input
Differential input
Terminator
Signal ground
1 to 1
RS422
Host
CSD819C
RDA
RDB
SDA
SDB
SDA
SDB
RDA
RDB
RS485
CSD819C
Host
RDA
RDB
SDA
SDB
SDA
SDB
RDA
RDB
131
section.
1 to n
RDA
RDB
CSD819C
SDA
SDB
RDA
RDB
SDA
SDB
RDA
RDB
CSD819C
Host
Host
section
132
RDA
RDB
CSD819C
SDA
SDB
RDA
RDB
CSD819C
SDA
SDB
CSD819C
RDA
RDB
RDA
RDB
SDA
SDB
SDA
SDB
RDA
RDB
SDA
SDB
SDA
SDB
RS485
CSD819C
CSD819C
SDA
SDB
SDA
SDB
RDA
RDB
RS422
CSD819C
RDA
RDB
4
0
6
2
Terminator
Command No.
ID No.
0031
Return(CSD819CHost)
2
4
6
@
Operation
Command No.
20
21
22
10
12
14
ID No.
0031
Terminator
Load data
ID No.
0031 2
@
ID No.
0031
@
10
O
ID No.
0031
133
14
3
12
10
6
2
10
0
4
0
2
0
ID No.
0031 2
@
12
Terminator
14
3
Terminator
12
14
Terminator
12
14
Terminator
6
0
Operation
30
31
32
33
34
Terminator
Command No.
ID No.
0031
Return(CSD819CHost)
2
4
6
@
Command No.
10
12
14
ID No.
0031
Terminator
Sign
Command No.
Setting value
4
0
6
0
40
10
d
12
f
14
Terminator
Space
Condition
ID No.
0031
aSEL.1
bSEL.2
cCHECK
dHOLD
ePEAK
fMEAS.
gEND
Operation
Terminator
Command No.
ID No.
0031
Return(CSD819CHost)
2
4
6
8
@
Command No.
LED display
LED display
LED display
LED display
LED display
LED display
LED display
Command No.
1ON, 0OFF
1ON, 0OFF
1ON, 0OFF
1ON, 0OFF
1ON, 0OFF
1ON, 0OFF
1ON, 0OFF
134
Terminator
41
Command No.
ID No.
0031
Return(CSD819CHost)
2
4
6
8
@
S0
S1
S2
10
S3
Terminator
Space
Command No.
50
51
52
Terminator
Command No.
ID No.
0031
Return(CSD819CHost)
2
4
6
@
Sign
Command No.
ID No.
0031
14
Terminator
Return(CSD819CHost)
2
4
6
@
12
ID No.
0031
Operation
Zero set
PEAK/TRACK
RESET
Terminator
Command No.
ID No.
0031
6 Writing comparative data (HostCSD819C)
2
4
6
8
10
@
14
Condition
Change of status(HostCSD819C)
2
4
6
@
12
S4
ID No.
0031
Command No.
S01ON, 0OFF
S11ON, 0OFF
S21ON, 0OFF
S31ON, 0OFF
S41ON, 0OFF
5
Operation
Read out comparative result
Set value
Command No.
10
60
Operation
Writing S0 data
61
62
63
64
Writing S1 data
Writing S2 data
Writing S3 data
Writing S4 data
12
14
Terminator
Sign
Command No.
D The comparative data enters from the right end.
D The setting range is within 99 999 to 99 999.
D Dont add a decimal point.
135
Set value
6
0
10
12
ID No.
0031
Command No.
Function No.
14
Terminator
Set value
Sign
Operation
Setting hold mode (Change contents of F60)
00000Peak hold
00001Bottom hold
00002Peak/bottom hold
00003Local minimal value hold
00004Local maximal value hold
00005Inflection point hold
Setting the kind of detecting mode
(Change contents of F61)
00000All zone specification
00001Zone specification
00002Time zone specification
00003Automatic start time
Setting of standard point (Change contents of F62)
Setting range9999999999 Unit1D
Setting data width of local maximal/minimal value
(Change contents of F63)
Setting range0000099999 Unit1D
Setting value
0000000005
64
0000000049
65
9999999999
66
0000000450
67
0000000450
68
0000009999
Function No.
60
61
62
63
69
Return(CSD819CHost)
2
4
6
@
ID No.
0031
Command No.
Function No.
10
12
0000000003
9999999999
0000099999
9999999999
14
Terminator
Set value
Sign
136
4
0
6
0
10
12
14
Terminator
ID No.
0031
Command No.
Set value
Space
Function No.
Function No.
81
Operation
Setting selection of calibration data
00000Calibration data 0
00001Calibration data 1
00002Calibration data 2
00003Calibration data 3
Setting value
0000000003
82
0000000003
Return(CSD819CHost)
2
4
6
@
10
12
14
Terminator
ID No.
0031
Command No.
Space
Function No.
Set value
4
0
6
R
8
1
Terminator
ID No.
0031
Error
Command No.
01
02
10
11
12
13
14
Contents
Nonexecutable error
Additionally, error by
this unit convenience
Parity error
Framing error
Overrunning error
Data code and data
length error
No applicable command
Remarks
For the calibration mode, fine adjustment mode,
check mode and monitor mode.
When the reception command cannot be
executed.
At the parity detection error
At the stop bit detection error
At the reception command reading error
When neither the received data code nor data
length are corresponding
When reception command isnt corresponding
Error code is not replied when the completion code (terminator) cannot be
detected.
Please consider dealing on the host side when the communication error command
is replied from this unit.
137
Operation
NG
OK
Abnormal operation
Normal Operation
Execute trouble
shooting.
Start measurement
138
NO
YES
YES
Display is wrong.
NO
Operation of
comparator is wrong.
YES
NO
YES
Connecting method
is good.
YES
Key operation
doesnt work.
NO
YES
4
YES
Analog output
is wrong.
NO
Operation of
options is wrong.
NO
YES
Inform Minebea about the contents of
failure and situation at site in details.
Check the options.
139
NO
NO
YES
Load display
doesnt vary.
YES
NO
Display fluctuates
abnormally.
Displays
optional values.
YES
NO
NO
8
OL display
NO
YES
YES
7
NO
OL display
YES
Same situation
NO
YES
Start measurement.
Fuse is broken.
NO
140
YES
Replace fuse by
referring to the
paragraph 131.
NO
NO
YES
Operation of
comparator is the same as
its intention.
YES
YES
Contact output chatters.
NO
YES
Contact output isnt ON.
NO
NO
Connecting method is good.
YES
141
ZERO input
doesnt operate.
YES
NO
Displays ER0.
NO
PEAK/TRACK
input doesnt work.
10 % of the maximum
display value.
YES
NO
RESET input
doesnt work.
NO
HOLD input
doesnt work.
YES
Either the HOLD
of external input or BCD
output is used.
YES
YES
NO
NO
Connecting method
is good.
YES
142
NO
YES
NO
YES
HOLD of external
control input is used.
NO
143
Option of
current output
YES
NO
10
NO
Load resistance is
5 k or more.
YES
1
2
Set the connecting range to DCV range for the measuring instrument
3
NO
Varies to 0 V, 5 V
and 10 V.
YES
1
2
Put the connecting cable for the AOUT terminal where it was.
Check the setting related with voltage output.
F21 Display value when analog output is the minimum.
F22 Display value when analog output is the maximum.
(Refer to the paragraph 8.)
Setting is correct.
NO
Set correctly.
Refer to the chapter 8.
YES
YES
Set the HOLD input open.
NO
Inform Minebea about the
contents of failure and
situation at site in details.
144
1
2
Remove the connecting cable for strain gage applied transducer from terminal block.
Measure the voltage between the AC terminals on the terminal block.
Set the connecting range to DCV range for the measuring instrument such as
tester and so on.
NO
YES
1
Connect the connecting cable for strain gage applied transducer to the terminal
block again. (Refer to the chapter 4)
By checking the voltage between the terminal B and D on the terminal block, apply
load on the strain gage applied transducer.
Set the connecting range to DCmV range for the measuring instrument such as
tester and so on.
YES
NO
145
NO
Start Measurement.
Remove the connecting cable for strain gage applied transducer from the terminal block.
Measure the voltage between the AC terminals on the terminal block.
Set the connecting range to DCV for the measuring instrument such as tester and so on.
NO
YES
1
2
Connect the connecting cable for strain gage applied transducer to the terminal block again.
(Refer to the chapter 4.)
Set the load display section to be the monitoring condition for strain gage applied transducer
according to the paragraph 716.
Monitoring display
exceeds the range from 2.0 mV/V
to 2.0 mV/V.
YES
Short between BD on
the terminal block.
NO
Make recalibration
according to the procedures
of chapter 5.
Monitoring display
exceeds the range from 2.0 mV/V
to 2.0 mV/V.
YES
Same condition
YES
NO
Start measurement.
146
NO
1
2
Remove the connecting cable for strain gage applied transducer from the terminal block.
Measure the voltage between the AC terminals on the terminal block.
Set the connecting range to DCV for the measuring instrument such as tester and so
on.
NO
YES
1
2
NO
NO
Same condition
YES
Start measurement.
147
YES
NO
10
YES
NO
RS232C is wrong.
11
YES
NO
RS422 is wrong.
12
YES
NO
RS485 is wrong.
13
YES
NO
14
148
10
NO
Load resistance is
260 or less.
YES
1
2
Set the connecting range to DCmA range for the measuring instrument such as
3
NO
Varies to 4 mA, 12 mA
and 20 mA.
YES
1
2
Put the connecting cable for the current output terminal where it was.
Check the setting related with current output.
F20 Selection of target for the analog output.
F21 Display value at the time of the minimum analog output.
F22 Display value at the time of the maximum analog output.
(Refer to the paragraph 712)
NO
Setting is correct.
YES
External control
input or HOLD at BCD
output is applied.
YES
NO
149
11
Set correctly.
NO
YES
Adjust the setting related with BCD output to the
specifications for external connecting instruments.
F41 Setting the output logic for BCD data
Other than the BCD
is output.
YES
NO
YES
NO
YES
NO
150
12
Connecting is good.
NO
YES
NO
YES
Setting for
the command/data are
correct.
NO
YES
Flow control is
specified by the host.
YES
YES
NO
Intended value
is not transmitted in the
stream mode.
NO
151
13
Connected correctly.
NO
YES
NO
YES
NO
YES
YES
Flow control
is specified by the host.
YES
NO
Change of RS422/485
is set correctly.
NO
YES
152
14
Connected correctly.
NO
NO
YES
ID Nos. are set
correctly.
YES
NO
YES
Setting for the
command/data are correct.
NO
Use the command/data correctly by referring to
the paragraph 94.
YES
Flow control
is specified by the host.
YES
NO
Change of RS422/485
is set correctly.
NO
YES
There is 1 ms
or more of interval between
receiving the command and
sending for the
host.
NO
YES
Against the
response from the host,
the delay time setting for
response is adequate
or not.
NO
YES
Inform Minebea about the contents of
failure and situation at site in details.
153
Contents of error
Remedy
ER1
Setting mistake
Set correctly.
ER2
Set correctly.
ER4
ER5
ER6
HOLD
TEL
TEH
SPL
ER0
SPH
ERE
EEPROM error
ERR
EEPROM error
OL
OL
154
11. Specifications
111. Specifications for analog section
DC10 V0.5 V
Applicable transducers
Input range
Output range
Output times
Output resolution
2.0 mV/V
Nonlinearity
Display
Output
0.025 %F.S.
0.025 %F.S.
Temperature coefficient
Zero point
Sensitivity
within 60 mA
Input noise
Input filter
A/D sampling
2 000 times/s
(changeable to 100 times/s, 500 times/s or 1 000 times/s)
CHECK
Approx.0.3 mV/V
(Setting can be available at the approx. 0.1 mV/V interval within the
range from approx.0.1 mV/V to 2.0 mV/V.)
The extension cable is applied to Minebeas standard cable
CAB-502(4 cores) within the length of 30 m.
Not applicable when the zener barrier is used.
11 000 to 11 000
1 (changeable to 2, 5 or 10)
7 segment red LED, with 17 mm characters height
Comparator display
Display range
Display
Number of display
99 999 to 99 999
7 segment green LED, with 8 mm characters height
1 point(Selectable from S0, S1, S2, S3 and S4)
Status display
Judgement display
Display rate
ZERO
Same as the
key
Above is pulse input, and effective once at the pulse input and the pulse
width is 50 ms or more. (Pulse width is changeable to 1 ms, 2 ms, 5 ms,
10 ms or 20 ms.)
PEAK/TRACK
Change of Track and Peak hold, Bottom hold, Peak bottom hold, Local
maximal value hold, Local minimal value hold or Inflection point hold
(It can be changed by the function.)
Or control of holding zone in zone specification mode or time zone
specification mode
Open
Track
Short Peak hold, Bottom hold, Peak bottom hold, Local maximal value
hold, Local minimal value hold or Inflection point hold
(It can be changed by the function.)
HOLD
RESET
Same as the
SEL.1, SEL.2
12 V
12 V
100 k
100 k
330 pF
156
2.2 k
1k
INPUT
COM.1
99 999 to 99 999
Numbers of setting
0 to 99 digits
S0
COM.2
The set value of the comparator of S0, S1, S2, S3 and S4 can be
memorized up to four kinds, and do changeover of them by the
function or the external control input. (The changeover target of
Calibration data and Comparator code is set by the function)
AC100 V to AC240 V
(Permissible variation rangeAC85 V to AC264 V)
Power supply frequency 50/60 Hz
Power consumption
Approx. 8 VA(Without option, at AC100 V)
Approx. 17 VA at max. (With option, at AC100 V to AC240 V)
DC10 V
Span adjustment
Analog output
1110. Accessories
Instruction manual
1 piece
Timelug fuse
1 piece (1 A)
Unit seal
1 piece
2 pieces
1 piece
1111. Options
11111. Current output
P/N
Specifications
Output
Nonlinearity
Resolution
Over range
Output rate
CSD819C-P07
DC4 mA to 20 mA Load resistance 260 or less
0.025 %F.S.
As same as display resolution
OL display at approx.DC2.4 mA and OL display at approx.DC21.6 mA.
Changeable to 100 times/s, 500 times/s, 1 000 times/s and 2 000 times/s
(Synchronous with A/D sampling rate.)
Voltage output isnt available when this option is installed.
158
CSD819CP15
Specifications
Output
BCD
Input
ZERO
Same as the
key.
Above pulse input and pulse width is 50 ms or more is effective once.
(Pulse width is changeable to 1 ms, 2 ms, 5 ms, 10 ms and 20 ms.)
key
As same as the key
CSD819CP74
Specifications
Baud rate
159
CSD819CP76
Specifications
Baud rate
160
Front
Rear
Upper
Unitmm
161
12. Warranty
121. Warranty
D The instrument is covered by a warranty for a period of one year from the date of delivery.
D As for repairs and/or after service is required during the period of warranty, contact with
Minebeas sales office or sales agent from which you have purchased.
122. Repair
Before asking repairs, make checks once again that the connection, setting and adjustment for the
instrument have finished properly by referring to 10. Trouble shooting.
Especially, make checks whether the connections of sensors are disconnected or cut off.
After that, still there may be found some defects in the instrument, contact with Minebeas sales
office or sales agency from which you have purchased.
162
13. Appendix
131. Replacement of fuse
Warning
When installation method for the fuse is wrong and/or the capacity of installed fuse
is inadequate, it causes and unexpected faulty of the instrument.
Holding the rear panel assembly, draw out it slowly to the arrow marked direction.
Case
Rear panel assembly
163
Fuse
Fuse
Fuse holder
After replacing the fuse, install the rear panel assembly into the case.
Set the 2 pieces of setscrews on the rear panel. Check that the rear panel and the case is
attached closely.
Warning
When the rear panel is not attached closely, you cant feel the click touch and also
there may have the possibility that key operation is not made.
164
165
Initial value
F01
Customers setting
Function No.
Initial value
00000
F55
00001
F02
00003
F56
00000
F03
00001
F57
00000
F04
00055
F58
00000
F05
00002
F59
00005
F06
00000
F60
00000
F10
11111
F61
00000
F11
00003
F62
00000
F12
00000
F63
00200
F20
00000
F64
00015
F21
00000
F65
00100
F22
02000
F66
00100
F30
11111
F67
00100
F31
00000
F68
01000
F32
00000
F69
01000
F33
00000
F71
00000
F34
00000
F72
00000
F35
00000
F75
F36
00000
F80
00000
F38
00000
F81
00000
F40
00000
F82
00000
F41
00000
F90
F42
00000
F91
F43
00000
F92
F44
00000
F93
F45
00004
F94
F46
00004
F95
F50
00001
F96
F51
00000
F97
00000
F52
00003
F98
F53
00021
F99
F54
00000
Memo
166
Customers setting
0267322200 .0267311350
0466227152 .0466221701
KARUIZAWA PLANT 410673 Miyota, Miyotamachi, Kitasakugun, Naganoken 3890293, Japan
0267311309 .0267311350
HOMEPAGE ADDRESS http://www.minebeamcd.com