Soft Starters

A soft starter has Thyristor in its main circuit by which it adjusts motor voltage.
Motors that run typical industrial applications employing conveyors, pumps, blowers, and
compressors all have one common quality: They draw a large amount of current when they start
up, perhaps six times what they draw during normal operation. This level of current can stress
motor components and cause power quality issues on plant electrical systems, particularly for
larger motors of 1 hp or more. That is why motors of this size frequently employ soft starting.
The idea behind a soft start is to gradually allow the motor current to rise until the motor reaches
its steady state. This reduces start-up current but also reduces start-up motor torque. Soft starters
adjust motor voltage through use of back-to-back Thyristor or triacs in each ac supply line to the
motor. The Thyristor are actuated during the start-up phase such that their turn-on is successively
delayed less for each ac half cycle. The delayed switching effectively ramps up the average ac
voltage to the motor until the motor sees full line voltage. Once the motor hits its rated speed, the
Thyristor switching circuit may be bypassed. Larger motors employ either soft starters or they
are controlled by variable-frequency drives that incorporate a soft-start function.

A soft starter can be contrasted with a full-voltage starter (manual and magnetic), which applies
full voltage directly to motor terminals on start up. Full-voltage starters today generally are
confined to smaller motors where start-up current isnt an issue.
Some soft starters can also provide a soft-stop function in applications where an abrupt stop can
cause problems. Examples include pumps where a quick stop can bring on water hammering and
conveyor belts where material can get damaged if belts stop too quickly. The soft-stop sequence
uses the same power semiconductors employed for soft starting.

Thyristor in a soft starter let part of the voltage through at the beginning of the starting sequence
and gradually increase it according to the set ramp time. The Thyristor can also typically
implement a soft stop by reducing motor voltage according to a set ramp time.
A special kind of soft-start function called star-delta start is sometimes used on three-phase
motors. Basically it starts the motor with stator windings connected in a wye configuration and
switches them to a delta configuration when the motor hits its normal operating speed. Here, the
starter normally consists of a contactor for each of the three phases, an overload relay and a timer
that sets the duration of time in the star-position. The starting current is about 30% of that seen
during direct on-line start and the starting torque is about 25% of what would be available at a
direct on-line start. This starting method only works when there is a light motor load during the
start. Motors that are too heavily loaded wont have enough torque to accelerate up to speed
before being switched over to the delta position.
Soft starters are generally used with induction (asynchronous) motors. But they also may provide
benefits powering synchronous motors. The reason is that many synchronous motors behave like
induction motors initially when they start up. That is, there is a lag between the rotating electric
field and the rotor position. There is a delay before the motor comes into a synchronous
condition. As in the case of induction motors, synchronous motors can also draw large stator
currents during start-up of perhaps five to eight times the full load current in the absence of soft
starting.
In both induction and synchronous motors, high stator and rotor current at start-up leads to a low
power factor, typically about 0.2 lagging. Power factor and, thus, energy efficiency, rises as the
motor accelerates up to its running speed. In this regard, it should also be noted that some soft
starters could serve as voltage controllers or voltage regulators for the motor. Their back-to-back
thyristors or triacs make this possible because they can adjust motor voltage depending on the
load the motor sees, when paired with an appropriate controller. Thus, functioning this way, a
soft starter can double as an energy manager: A controller monitors the motor power factor,

which is a function of motor loading. On light loads, the power factor is low enough that the
controller reduces the motor voltage and, thus, the motor current.

Soft starter selection


Many of the applications to which soft starters are applied fall into general categories of pumps,
compressors, and conveyors. There are a few rules of thumb for each of these uses.
The start-up time for soft starters is user settable. The typical start-up time for most applications
ranges from 5 to 10 sec. The longer time periods tend to be found in pumping and compressor
applications where there is a high possibility of pressure waves building up in piping systems.

A typical soft starter reduces the motor torque and current during start-up. The star-delta starter
accomplishes the same thing but by means of switching motor windings from a star to a delta
connection at the appropriate time.
The initial start voltage is settable as well, but most applications use a start level that is 30% of
the line level. Screw compressors and conveyors sometimes start at higher levels (perhaps 40%)
depending on the load conveyors sometimes have material on them when they start up so they
may need a higher starting torque, and screw compressors have dont develop much pressure at
low speeds.
Soft starters typically have the same rating as the motors they power. The situation may be
different for start-up ramp times and initial voltage levels that are outside the norm. For heavyduty uses, a common practice is to use a soft starter having a power rating one size bigger than
the motor and to use an overload relay when ramp times grow long; ditto for applications with
frequent starts.